Beruflich Dokumente
Kultur Dokumente
Prepared by :
Mr. mayur a. agrawal (06dee020)
Mr. harshal j. chokshi (06dee022)
Mr. goldi g. makhija (07dee201)
Mr. akshay v. patel (08dee312)
Mr. pranay k. patel (08dee319)
Guided by :
Mr. dhiren k. rathod (assistant prof.)
[internal guide]
Industrial guide :
Certificate
This is to certify that;
Mr. Mayur Agrawal (06Dee020)
Mr. Harshal Chokshi (06Dee022)
Mr.Goldi Makhija (07Dee201)
Mr. Akshay Patel (08Dee312)
Mr. Pranay Patel (08Dee319)
Student of 6th & 8th Semester Diploma in
Electrical Engineering Institute of Diploma
Studies, Nirma University has successfully
completed their industrial training at Siemens
(India) at Vadodra.
Date of submission:
ACKNOWLEDGEMENT
We humbly like to thank to our respected
guide Mr. Dhiren K. Rathod, assistant professor in
Electrical Engineering Department, Nirma
University for his valuable time and constant
guidance given to us, from the concept stage to
the formation of our industrial training report.
We would also like to thank Prof. Hemang S.
Pandya, H.O.D., Electrical Engineering who was
always been prepared to offer us help at any time,
inspite of his busy schedule.
We would like to thank Mr. Kandarp.
Brahmbhatt sir (Electrical Head), Mr. Satyen
Dave (Executive engg.), Mr. Bhavesh Desai
(Project Manager), for providing us the
unforgettable training in their esteemed company
(Siemens India Ltd.)
We would also like to thank all the employees
of the SIEMENS for their co-operation and helping
us directly or indirectly during our training period.
Table of contents
Sr. No.
Topics
Pag
e
no.
M.C.C Panel
Synchronising Panel
10
A.V.R panel
11
GENERATOR PROTECTION
12
SIEMENS profile
Siemens has been associated with India since 1867. The Siemens Group in
India is a unique player in the field of electrical and electronics engineering
with a business volume aggregating about Rs 11,800 crores. Siemens is
present in over 190 countries. From power generation and distribution to the
efficient use of energy in industry, households and transportation to cuttingedge technologies for water management and pollution control.
INTRODUCTION TO SIEMENS
(BARODA PLANT):
The process of the project management has three steps which are
being carried out initially S.L.D is being designed, later L.A.S.C.P.T is
being designed then the N.G.R is being designed as per the project
requirement.
Training schedule
Week 1:
TG MCC/LAVT
CT Panel
Akshar Seth
GENERATOR
PROTECTION
Satyen Dave
GENERATOR
SYNCRONIZATI
ON
Parikshit Gupte
(22/02/2010
to
(27/02/2010)
Week 2:
(01/03/2010
to
(06/03/2010)
Week 3:
(08/03/2010
to
(13/03/2010)
Week 4:
(15/03/2010
to
(20/03/2010)
Week 5:
(22/02/2010
to
(27/03/2010)
Week 6 :
GENERATOR
AND AVR
Bhavesh Desai
Battery and
Charger DC
Starter Panel /
NGR
Pranjal Desai /
vaibhav Tharot
Basic
Instrumentation
control and
Power cable
Anjali Dhampuria /
Yogesh Solanki
(29/02/2010
to
(03/04/2010)
Week 7:
(05/04/2010
to
(10/04/2010)
Week 8:
(12/04/2010
to
(17/04/2010)
Siemens not only designs the small captive plants but it also
designs the large power plants the highest plant designed by
Siemens is of the 25 MW T-G set.
RANKINE CYCLE
Initially the coal is used as the main source of the energy. The
combustion of coal takes place, and by the calorific energy of
the coal the water is converted into the hot pressurised steam.
Now this turbine is coupled with the gear box and further
connected to the alternator and electricity is produced.
Synchronising panel.
[Note-All the panels are being interrelated to each other the relation between
each of them is being shown through the S.L.D as above].
In this panel the L.A as well as S.C are used for the
protection of the system from the voltage surge due to lightning
as well as due to the transient situation, while the C.T and P.T are
being used for the protection, metering, synchronising and A.V.R
purpose.
This panel is being used for the metering of each and every
components used in the system, through which the proper
controlling can be easily done. The output of all the transducers
and the sensors as well as the C.T and the P.T are connected to
the panel for the metering and relay purpose.
Synchronising panel:
D.C.S system:
(Discriminate control system)
[Note-The photos beside show the controlling as well as the visual indication
of the air flue gas and the fuel feeding system as well as the turbine
generator operating system]
Protection
Protection
Metering
A.V.R
Synchronising
Metering
Protection
A.V.R
In the panel the C.T and the P.T used has single primary
winding and three secondary winding.
Generally the two P.T with the three secondary are being
preferred. And even the three P.T with that of the two
secondary cores can also be preferred.
[Note-The selection criteria of the C.T, P.T, S.C and the L.A are explained
further in the report]
M.C.C PANEL:
(Motor Control Centre):
In the power station the power from the generator itself have
to be used for all the auxiliary running in the power station.
The M.C.C panel is being used for the control of the various
motors in the power station which are stated as follows:
o Boiler water pump
o Main oil pump
o Auxiliary oil pump motor which
o Condensed oil pump.
o Condenser extraction pump
o Circulating water pump
The M.C.C panel is being used for the control of the various
auxiliary supplies in various panels in the power station which are
stated as follows:
It menace that they cannot be used unless they have some other device
upstream.
We had learn that MCB are use for short circuit and overload protection, But
actually in industry MCB is use for switching and short-circuit Protection
Only, its overload protection is not that much effective, so not Use as Overload
Protection.
But the combination of MCB and overload relay seems to be somewhat costly.
Based on the type of application MCB are classified as B, C, and D curve type.
When range of operation is more than 80Amp then MCCB is used instead of
MPCB It is used in heavy commercial and heavy industrial application
Mostly MCCB are available as single module and used for 3pole and 4pole
current range for AC 50-60Hz is from 80Amp to 1600Amp
Overload relay is provided with adjustable switch with the help of which we
can set the current at which its contacts get operate as a result the coil of
contactor get de-energized and hence power to the motor is shutoff.
When motor get overload, so it will consumes more current and when this
current excides the current ratting set in overload relay for overload protection
then normally close contact will normally open.
This NC contact is usually connected in series with the relay coil of contactor,
so that when it opens the relay will automatically de-energize thereby shutting
off power to the motor by disconnecting the contactor .
MPCB compact design save size of a panel by having both functions of MCB
and overload protection.
MPCB are most suitable for switching and protection three phase induction
motor up to 45KW at 415V AC with thermal overload and magnetic short
circuit release an auxiliary switch is use together with MPCB is called ADDON. Add-on has NO/ NC contact and is connected with MPCB. Its main
purpose is that, when MPCB get trip, its contacts get as a result it makes a
some lamp or buzzer circuit which will indicate the tripping of MPCB It is
available in range 0.4 to 100Amp
In this circuit the 3 phase supply is directly given to the motor. As shown in the
figure the overload relays are being attached for the overload protection.
The indication lamps for each phase are kept so that we can know whether
each of the phases is healthy or not.
Now the further the supply is given to the MPCB and then given to the motor
contactors KM-1. The motor cannot directly be switched on
To start the motor the start push button is pressed by which the km-1 contact
gets energized and the motor can start.
In case of stopping the motor the Stop push button is pressed which deenergizes the KM-1 contact and the motor stops.
When the KM-1 gets energized then the lamp ON would be indicated and when
the KM-1 contacts get de-energized then the lamp OFF would be indicated and
in case of the tripping the TRIP lamp gets indicated.
ADVANTAGES OF M.C.C
Protects the system through over-load as relays are attached to it which can
trip the faulty part
Synchronising panel
TYPES OF SYNCHRONISATION
Auto-synchronization
Manual- synchronization
Synchronizing lamps:
Formerly, two bulbs are connected between the generator terminals
and the system terminals (or more generally, to the terminals of
instrument transformers connected to generator and system). As
the generator speed changes, the lights will rise and fall in intensity
at a rate proportional to the difference between generator
frequency and system frequency. When the voltage at the generator
is opposite to the system voltage (either ahead or behind in phase
the lamps will be bright. When the voltage at the generator matches
the system voltage, the lights will be glow. At that instant, the
circuit breaker connecting the generator to the system may be
closed and the generator will then stay in synchronism with the
system.
Synchroscope:
Synchronizing relays:
Synchronous operation:
When the generator is synchronized, the frequency of the system
will change depending on load and the average characteristics of all
the generating units connected to the grid. Large changes in system
frequency can cause the generator to fall out of synchronism with
the system. Protective devices on the generator will operate to
disconnect it automatically.
FREQUENCY
AMMETER
VOLTMETER
WATTMETER
TRI-VECTOR METER
PF METER
KVAR MATER
KVA METER
RPM METER
Tripping system:
Generally the contactors are in the normally closed (N.C) condition
or that of the normally open condition (N.O) if there is a fault
condition the N.O becomes N.C and the N.C becomes N.O. for the
passive source such as the generator the N.O is used for the healthy
condition and the N.C is used for the unhealthy condition. For the
active source such as the turbine the N.O is being kept for the
healthy condition and the N.C is being kept for the unhealthy
condition.
A.V.R panel
(Automatic voltage regulator)
For the A.V.R system excitation is one of the main thing there are
two types of the excitation systems:
Generator protection
Difficulty with the generator protection system is that unlike other equipments
opening a breaker to isolate the defective generator is not enough to prevent
further damage, since the generator will continue to supply power to its own
fault until its field excitation has been suppressed.
It is therefore, necessary to remove the field supply, shut-off the steam, water or
fuel supply to the prime-power, trip the boiler and shut-off all the auxiliaries of
the generator.
Further carbon dioxide is pumped into some large machines to extinguish any
burning of insulation which has been initiated by the rotor moment.
Unbalanced loading.
Field failure.
Overload
Over voltage
Failure of prime-mover.
Loss of synchronism
Over-speed.
Under frequency
Overheating.
Differential protection.
Overload protection.
Overvoltage protection.
Class A:
If a fault is of very serious nature and reflects to the generator,
generator-transformer, prime mover or boiler (fault is likely to
cause a direct and very serious damage to the unit even after
isolating the unit from the infinite bus), the protective scheme
that operates is known as class A protection.
Tie breaker between auxiliary station bus auxiliary unit bus are
closed.
Boiler trips.
Prime-mover trips.
Class -B:
Because of this tripping the generator will lose input and hence
the power output will gradually reduce. Because of this action
the generator does not speed up and stored kinetic energy is
utilized.
Boiler is tripped
Turbine is tripped.
Class-C:
Differential protection
Over-Voltage protection
Reverse Power-Protection
Differential protection
The voltage across the relay coil is zero in case of the external
faults and hence the relay does not operate.
Larger the KPV greater will be working range of the C.Ts and
higher will be the saturation flux density for this reason grain
oriented silicon steel have higher saturation level are used as
core material for the protective C.T.
Such faults are associated with very high local currents which
can cause damage to the generator core. The inter-turn fault
itself is not so dangerous but it leads to an earth fault which is
a dangerous fault.
For the faults without the access of the parallel winding the
arrangement in the above figure cannot be used the protection
scheme is based on the fact that voltage drops in the faulted
phase .the zero sequence component of the unbalanced
voltage so produced is detected across the open delta of the
P.T secondary the voltage operated watt-hour meter type relay
will then operate
The ground fault current will flow through this arc if this earth
fault current is high the arc energy will also be high resulting in
very high arc temperature. This high temperature can cause
failure of the insulation between laminations this will result in
increase of the eddy currents losses and damage to a large
portion of the stator core.
The stator ground faults are the very destructive faults; if the
ground fault current is large hence for the large generators the
ground fault current is usually limited to a very low value such
that the resultant arc is not very intense.
The arc temperature in this case will be very low and therefore
the damage to the stator core can be reduced to a minimum
as such no damage may occur during the time of the relay
operation and consequent tripping.
Ra=106/6fc
F = system frequency
The time for which the rotor can withstand this condition varies
inversely as the square of the negative sequence current i.e.
I2t=K where K is a constant which varies from 7 in a large
steam Turbo-generator to about 60 for a salient pole hydro
machines.
In the modern protective scheme the operation of an overvoltage relay initially causes the alarm to be sounded and thus
warns the operator. Should the automatic voltage regulator not
restore the voltage to normal within preset time the machine
has to be tripped completely as the over voltage, so produced
Reverse Power-Protection
The prime mover will act as a load on the motor this means
that flow of power is reversed. The reversal of Power is sensed
by a reverse power relay.
For the small turbines the relay are set to operate when
forward power reduces below 3% of the rated power. For large
turbines the sensitive setting of 0.5% of rated power is being
used. These relays are known as low-forward power relays
Over-speed protection
Vibration Protection
Auxiliary failure
Field Suppression
The figure shows how the field gets suppressed. When the field
breaker is opened due to operation of Class-A protection.
Lightning arrestors limit the crest value of an impulse voltage. When the
voltage reaches a pre-determined value it provides a discharge path to ground.
Surge Capacitors pick up where lightning arrestors leave off and protect you
against the smaller surges, which occur every day. Varying levels of current
occurring when appliances turn on and off, or when power to a local grid is
lost or regained brings on these surges.
Over time, the constant wear-and-tear of these surges will permanently damage
delicate electrical components. While surge capacitors are fully capable of
guarding against the smaller fluctuations in current and voltage, they are
unable to provide protection against large voltage spikes. This is why it is best
to have both a lightning arrestor and a surge capacitor installed.
If the surge capacitor is not being connected then it may even cause the line to
ground fault and even the surge may not be prevented.
Table
System Voltage
Capacitance in Mfd
per Phase
Impulse Voltage
3.3 kV
0.1 to 0.5
6 kV
60 kVP
Capacitor switching.
Estimates of the magnitude of these surges normally range from two to five times the
normal line-to-neutral crest voltage with rise times ranging from .1 u seconds
(microseconds) to 10 u seconds.
2.3
.6
2400
10
1.0
4160
16
1.6
4800
19
1.9
6600
25
2.5
6900
26
2.6
The table above indicates the maximum withstand voltages (VM) and rate rise for
Line Motors.
For applications where the values in the table above are exceeded, it is recommended
that a special insulation system with increased dielectric strength be used (turn-toturn and turn-to-ground) or that surge capacitors and / or lightning arrestors be
utilized. From an availability and economic standpoint the latter alternative should be
used.
momentarily absorbing some of the initial energy thereby slowing down or sloping the
steep wave front.
System
Voltage
Capacitor Rating
Arrestor Rating ( KV )
UFD
RMS
600
1.0
.6
.65
2400
.5
2.4
3.0
4160
.5
4.16
4.5
4800
.5
4.8
6.0
6600
.5
6.6
7.5
6900
.5
6.9
7.5
Current transformers:
It is necessary that the fault is cleared at the shortest possible
time in order to reduce the effect of the short circuit on the system.
While isolating the faulty section the healthy portion shall remain
uninterrupted this means there must be selectivity while clearing
the faults so that healthy sections are not affected.
Today there are fast operating relays and circuit breakers for
achieving the above. However it is necessary that the instrument
the instrument transformer feeding the relay shall be accurate in
order that the operation of relay is reliable. Therefore the reliable
performance of the current transformer for satisfactory operation of
system assumes great importance.
Performance of the C.T for a particular application depends on
the right choice whether needs the under-standing of the various
parameters which go into the design and manufacture as well as
different types of C.T available for the choice.
Instrument transformer is defined as transformer intended to
feed the measuring instruments, meters relays and other similar
apparatus .A current transformer is an instrument transformer in
which the secondary current ( in normal condition of use) is
substantially reduced proportional to the primary current and differs
in phase from it by an angle which is approximately zero for
appropriate direction of connections.
high voltage on the primary side. For this purpose CTs having a
ration of 5/5A are common. They are frequently used to measure
small currents at high voltage in the test labs.
Sometimes it may be necessary to give a feed back of actual
load to certain control devices for taking corrective actions ( in the
case of voltage regulators) the current transformers are used for
giving such feedback of load to the regulators/control equipments.
Two identical breakers are used many times for sharing the
current in case of medium voltage switch gear for high current
feeders. Due to slight difference in path resistance there may be
current imbalance in current can be corrected by providing suitable
cross connected by providing suitable cross connected current
transformers.
Following are the definitions of some of the main terms used
in the selection of the C.T and in specifying the
characteristics of the C.T:
Indoor
outdoor
Metering
Protection
Main C.T
Auxiliary C.T
Bar
Ring
Wound
Split Core
Linear
Cascade.
Dry type
Epoxy
Sf6
Tank type
Inverted type
Insulator type
Normally the C.T are used for the feeding the instruments,
relays , voltage regulations etc equipment being feed will impose a
specific requirement on the C.T.
C.T for the Metering purpose:
C.Ts feed for the metering instruments shall be able to
transform the current at an acceptable degree of the accuracy to
the secondary side from 10% to 120% of the rated current however
at the same time under fault condition secondary reflected current
should not be very high so as to damage the instrument
Normally the ISF of the 0.5 is specified it is found from
experience that the instrument are not damaged even if the current
of 10 times the rated current or more passes through them for a
short duration therefore the ISF of 5 is not always a must and can be
relaxed when there are design constraints the cost of the C.T
depends on the burden as well as the accuracy class. While
selecting C.T attention is to be paid towards the application.
C.T for the protection:
In this case the C.T shall have the desired accuracy between
the rated current up to the maximum desired reflected secondary
current under fault condition. Required by the type of the protection
C.T generally need not be accurate below the rated current .
Many times because of design limitations it will be difficult to
achieve the accuracy class of 5P. However for most of the protection
accuracy of 10P should be acceptable since under fault condition
accuracy of the 5P to 10P will not have any appreciable effect on
most of the relay characteristics.
Apart from the general protection class 5P 10P the
requirement for some of the specific type of relays are specified in
terms of the knee point voltage are known as PS class.
For protection CT international practice is to specify accuracy
class of 5P only the relays of most of the reputed manufacturers are
working satisfactorily with C.Ts of the above specifications
therefore under most of the circumstances CT of 5P/10P shall be
sufficient to feed the relays of most of the manufacturers.
0.1
0.2
0.5
5P10,5P20
SELECTION OF C.T
P=1.73*V*I*Cos
For understanding the way to select the C.T ratio let us assume
an practical example where we have to select the C.T ratio.
(Note: The values which are being used in the example are not
practical values but are only assumed)
P=1.73VICOS
P=45MW
V=11KV
COS =0.8
Therefore I =2952.3A
Burden is calculated for each and every C.T as per the formula
Potential Transformer
Potential transformer are used for the measurement and the
protection purpose accordingly they are of two types measuring
type or the protective type and they may be either single phase
or three phase units
There are two types of the construction:
Rated burden
Supplied frequency
Number of phases
Voltage factor:
The upper limit of the operating voltage is given by (Rated voltage * Voltage
factor) is specified for certain time e.g. 1.1 continuous 1.5 for 60 sec 1.9 for
30 sec
Phase displacement
(minutes)
(%)
0.1
+/-0.1
+/-5
0.2
+/-0.2
+/-10
0.5
+/-0.5
+/-20
1.0
+/-1.0
+/-40
3.0
+/-3.0
Not specified
Phase displacement
(%)
(%)
3P
+/-30
+/-120
6P
+/-60
+/-240
1.2
Time
Phase displacement
rating
continuous
1.2
continuous
1.5
30 s
1.2
continuous
1.9
30 s
1.2
continuous
1.9
8 hours
References:
By - B.A.OZA.
www.siemens.com
www.allinterview.com
CONCLUSION:
During our training period we came
much closer to the industrial environment
and their managing capabilities.
Due to this training our technical as
well as non-Technical skills have been
polished.
Due to this training we came to know
AN ENGINEERING WITHOUT TRAINING IS
JUST LIKE A SHIP WITHOUT RUDDER
Neutral Isolation is mandatory when you have a Mains Supply Source and a Standby Power Supply Source. This is necessary because if you do not have neutral
isolation and the neutrals of both the sources are linked, then when only one source
is feeding and the other source is OFF, during an earth fault, the potential of the OFF
Sources Neutral with respect to earth will increase, which might harm any
maintenance personnel working on the OFF source.
It is for this reason that PCC Incomers & Bus Couplers are normally 4-Pole. (Note
that only either the incomer or the bus coupler needs to be 4-pole and not both).
3pole or 4pole switches are used in changing over two independent sources, where
the neutral of one source and the neutral of another source should not mix.
The examples are electricity board power supply and standalone generator supply
etc. the neutral return current from one source should not mix with or return to
another source.
As a mandatory point the neutral of any transformer etc are to be earthed, similarly
the neutral of a generator also has to be earthed. While paralling (under uncontrolled
condition) the neutral current between the 2 sources will cross and create tripping of
anyone source breaker.
Also as per IEC standard the neutral of a distribution system shall not be earthed
more than once. Means earthing the neutral further downstream is not correct.
In India, at low voltage level (433V) you must do only Solid Earthing of the system
neutral. This is by IE Rules 1956, Rule No. 61 (1) (a).
Because, if you opt for impedance earthing, during an earth fault, there will be
appreciable voltage present between the faulted body & the neutral, the magnitude
of this voltage being determined by the fault current magnitude and the impedance
value.
In solid earthing, you do not have this problem, as at the instant of an earth fault, the
faulted phase goes to neutral potential and the high fault current would invariably
cause the Over current or short circuit protection device to operate in sufficiently
quick time before any harm could be done.
Providing a tertiary winding for a transformer may be a costly affair. However, there
are certain constraints in a system which calls for a tertiary transformer winding
especially in the case of considerable harmonic levels in the distribution system.
Tertiary winding is may be used for any of the following purposes:
1) To limit the fault level on the LV system by subdividing the in feed that is, double
secondary transformers.
(4) The transmission tower construction Middle arm is longer than the upper and
lower arm
To prevent a broken upper line from falling on one or more of the phase lines below.
(5) What is the difference between Insulating, Isolating, and Shielded Winding
transformers?
These terms are used to describe the separation of the primary and secondary
windings.
A shielded transformer includes a metallic shield between the primary and secondary
windings to attenuate (lessen) transient noise.
Neutral is connected to earth at some point, thus it has some value as a return path
in the event of say and equipment earth being faulty. Its a bit like asking why dont
we break the Earth connection
It was stupid and dangerous, as it was possible for the neutral fuse to blow; giving
the appearance of no power when in fact the equipment was still live.
The acceptable meg-ohm value = motor KV rating value + 1 (For LV and MV Motor).
Example, for a 5 KV motor, the minimum phase to ground (motor body) insulation is
5 + 1 = 6 meg-ohm.
Minimum
Insulation
Resistance
TEST SPECIMEN
For most windings made before about 1970, all field windings,
R1 min = kV+1 R1
and others not described below For most dc armature and ac
min = 100
windings built after about 1970 (form wound coils)
R1 min = 5
For most machines with random -wound stator coils and formwound coils rated below 1kV
(8) What method is used for Protection of Lighting in Transmission Line and
Building?
The transmission line towers would normally be higher than a substation structure,
unless you have a multi-storey structure at your substation.
Earth Mats are essential in all substation areas, along with driven earth electrodes
(unless in a dry sandy desert site).
It is likewise normal to run catenary (aerial earth conductors) for at least 1kM out
from all substation structures. Those earth wires to be properly electrically to each
supporting transmission tower, and bonded back to the substation earth system.
It is important to have the catenary earth conductors above the power conductor
lines, at a sufficient distance and position that a lightning strike will not hit the power
conductors.
In some cases it is thus an advantage to have two catenary earth conductors, one
each side of the transmission tower as they protect the power lines below in a better
manner.
In lightning-prone areas it is often necessary to have catenary earthing along the full
distance of the transmission line.
Without specifics, (and you could not presently give tower pictures in a Post because
of a CR4 Server graphics upload problem), specifics would include:
In some older outdoor substation structures, air-break isolator switches are often at a
very high point in the structure, and in those cases small structure extension towers
are installed, with electrodes at the tapered peak of those extension towers.
The extension towers are normally 600mm square approximately until the extension
tower changes shape at the tapered peak and in some cases project upwards from
the general structure 2 to 6 meters, with the electrode some 2 to 3 meters projecting
upwards from the top of the extension tower.
The substation normally has a Lightning Counter which registers a strike on the
structure or connected catenary earth conductors, and the gathering of that
information (Lightning Days, number per Day/Month/Year, Amperage of each strike)
gives the Engineering Staff good statistics for future substation design.
1. Location
2. Country
3. Site soil type and resistivity
4. Number of Lightning Days
5. Expected Voltage + Current of a local lightning strike
6. Other Advise please.
(9) What is service factor?
Service factor is the load that may be applied to a motor without exceeding allowed
ratings. For example, if a 10-hp motor has a 1.25 service factor; it will successfully
deliver 12.5 hp (10 x 1.25) without exceeding specified temperature rise. Note that
when being driven above its rated load in this manner, the motor must be supplied
with rated voltage and frequency.
Keep in mind, however, that a 10-hp motor with a 1.25 service factor is not a 12.5-hp
motor. If the 10-hp motor is operated continuously at 12.5 hp, its insulation life could
be decreased by as much as two-thirds of normal. If you need a 12.5-hp motor, buy
one; service factor should only be used for short-term overload conditions.
Protects from fire which cause due to oil spillage from transformer and also protects
from wild habitat.
The earthing must have minimum resistance. yes for small trans. if neutral is directly
earthed then the same earthing point can be used for body earthing too, but in case
of big size trans. where neutral is grounded through impedance or resistance, the
length of body earthing increases that time, so better to use separate earthing pit
which will provide minimum resistance path for body,
You can also ensure that the resistance between two different earthing pits in your
company is having almost negligible resistance, so both are redundant.
In India It is mandatory as per IE rules that u have 2 neutral earth pits exclusively
which can also be connected to the earth grid .Body earthing needs separate pits.
Earthing does not receive as much attention as one would desire. It may never be in
use in its life time. But if and when a fault occurs it should be in condition.
(12) Why the up to dia 70mm live conductors, the earth cable must be same size?
Above dia 70mm live conductors the earth conductor need to be only dia 70mm?
(a) The external earth loop impedance of the installation (i.e. beyond the supply
terminals)
Now when the active conductor (b) is small, its impedance is much more than (a), so
the earth (c) cable is sized to match.
As the active conductor gets bigger, its impedance drops significantly below that of
the external earth loop impedance (a); when quite large (here in 70mm 2) its
impedance can be ignored. At this point there is no merit in increasing the earth
cable size
NEUTRAL is the origin of all current flow. In a poly-phase system, as its phase
relationship with all the three phases is the same, (i.e.) as it is not biased towards
any one phase, thus remaining neutral, thats why it is called neutral.
Whereas, GROUND is the EARTH on which we stand. It was perceived to utilize this
vast, omnipresent conductor of electricity, in case of fault, so that the fault current
returns to the source neutral through this conductor given by nature which is
available free of cost. If earth is not used for this purpose, then one has to lay a long.
Long metallic conductor for the purpose, thus increasing the cost.
Ground should never be used as neutral. The protection devices (e.g. ELCB, RCD
etc) work basically on principle that the phase currents are balanced with neutral
current. In case you use ground wire as the neutral, these are bound to trip if they
are there and they must be there. At least at substations. And these are kept very
sensitive i.e. even minute currents are supposed to trip these.
One aspect is safety when someone touches a neutral, you do not want him to be
electrocuted.
Usually if the switches at home are on the phase and not neutral (except at the MCB
stage). Any one assumes the once the switch is off, it is safe (the safety is taken care
of in 3 wire system, but again most of the fixtures are on 2 wire) he will be shocked
at the accidental touching of wire in case the floating neutral is floating too much.
(14)
It means the ratio of the voltage (that if you applied it to one side of the transformer
while the other side of the transformer is short circuited, a full load current shall flow
in the the short circuited side), to the full load current.
More the %Z of transformer, more copper used for winding, increasing cost of the
unit. But short circuit levels will reduce; mechanical damages to windings during
short circuit shall also reduce. However, cost increases significantly with increase in
%Z.
Lower %Z means economical designs. But short circuit fault levels shall increase
tremendously, damaging the winding & core.
The high value of %Z helps to reduce short circuit current but it causes more voltage
dip for motor starting and more voltage regulation (% change of voltage variation)
from no load to full load.
(1) Short the secondary side of the transformer with current measuring devices
(Ammeter)
(2) Apply low voltage in primary side and increase the voltage so that the secondary
current is the rated secondary current of the transformer. Measure the primary
voltage (V1).
(3) Divide the V1 by the rated primary voltage of the transformer and multiply by 100.
This value is the percentage impedance of the transformer.
When we divide the primary voltage V1 with the full load voltage we will get the short
circuit impedance of the transformer with refereed to primary or Z01. For getting the
percentage impedance we need to use the formula = Z01*Transformer MVA /
(Square of Primary line voltage).
An electrical system consisting of more than two low voltage Diesel Generator sets
intended for parallel operation shall meet the following conditions:
(i) Neutral of only one generator needs to be earthed to avoid the flow of zero
sequence current.
(ii) During independent operation, neutrals of both generators are required in low
voltage switchboard to obtain three phases, 4 wire system including phase to neutral
voltage.
(iii) required to achieve restricted earth fault protection (REF) for both the generators
whilst in operation.
Solution:
Neutral contactors shall be interlocked in such a way that only one contactor shall
remain closed during parallel operation of generators. During independent operation
of any generator its neutral contactor shall be closed.
(16) Calculate the size the CT on the neutral point of the secondary side of 11/0.415
kV Transformer
1.
2.
3.
4.
5.
For high impedance relays (differential or restricted earth fault relays), Class X
current transformers are recommended to be used.
Please note that both CTs (neutral & phase) shall have the same characteristics. The
following is an example to size the CT:
Input data:
cross section and length of pilot wires can have a significant effect on the required knee
voltage of the CT and therefore the size and cost of the CT. When the relay is located some
distance from the CT, the burden is increased by the resistance of the pilot wires.
1.
2.
The Vkp of the CT should be higher than the setting of relay stability voltage (Vs), to
ensure stability of the protection during max.
Through fault current. To calculate the stability voltage, you should follow the related
formula given by the relay manufacturer, as each relay manufacturer has its own
formula.
You may calculate the Vkp as above using a CT with secondary current of 5 A, and
you will notice the difference in the Vkp.
In section 1.4.2, IEEE Std 142-1991 (Green Book) states: Numerous advantages
are attributed to grounded systems, including greater safety, freedom from excessive
system overvoltage that can occur on ungrounded systems during arcing, resonant
or near-resonant ground faults, and easier detection and location of ground faults
when they do occur.
If you effectively ground the neutral, you have just replaced the hazards associated
with ungrounded systems with new hazards in the form of arc flash / blast hazards,
which are associated with solidly grounded systems.
In section 7.2.4, IEEE Std 141-1993 (Red Book) states: A safety hazard exists for
solidly grounded systems from the severe flash, arc burning, and blast hazard from
any phase-to-ground fault. For this reason, IEEE Std 142-1991 (Green Book), in
section 1.4.3, states the benefits of resistance grounding: The reasons for limiting
the current by resistance grounding may be one or more of the following:
(1) To reduce burning and melting effects in faulted electric equipment, such as
switchgear, transformers, cables, and rotating machines.
(2) To reduce mechanical stresses in circuits and apparatus carrying fault currents.
(4) To reduce the arc blast or flash hazard to personnel who may have accidentally
caused or who happen to be in close proximity to the ground fault.
(5) To reduce the momentary line-voltage dip occasioned by the clearing of a ground
fault.
(6) To secure control of transient overvoltage while at the same time avoiding the
shutdown of a faulty circuit on the occurrence of the first ground fault (highresistance grounding).
Its best to not only ground the neutral, but also to ground through high-resistance
(typically 5A) for all systems less than 600V and most systems from 600V to 5kV.
For systems more than 5kV, low-resistance grounding (typically 200A or 400A) is
used.
(18) What are the results of if we do not ground a 480/277V, 3-phase, 4-wire diesel
generator set? Take into consideration the two options of switching or not
switching the neutral.
significantly higher than 3-phase faults. In section 1.8.1, the IEEE Green Book
states: Unlike a transformer a generator will usually have higher initial groundfault current than 3-phase fault current if the generator has a solidly grounded
neutral. According to NEMA, the generator is required to withstand only the 3-phase
current level unless it is otherwise specified
This is due to very low zero-sequence impedance within the generator, which causes
very high earth fault currents. For generators 600V or below, this may not be an
issue. However, it is almost always an issue as the voltage class increases.
The resistor also significantly reduces any circulating currents, which are typically
triple harmonics, leading to reduced overheating in the generator windings.
Circulating currents are caused by different pitch windings in generators.
For solidly grounded systems, neutral switching is a viable option. According to the
NEC, when the service falls under the requirements of 230.95, you should ground
the neutral at each source and switch it where the Code requires ground-fault
detection coordination.
When the service rating equals or exceeds 1,000A (833kVA), 230.95 requires
ground-fault protection on the service disconnect. Along with this, if you have an
alternate power supply, you must switch the neutral. If you have a service larger than
1,000A, the NEC requires ground-fault protection at the main service disconnect.
If the generator neutral grounding runs via a solid connection to the main service
neutral and the generator experiences a ground fault while feeding the load, the
main service disconnect will open. This will not disconnect the arc fault from the
generator, and coordination will be lost.
Furthermore, if the neutrals of the two sources are separately grounded, you must
switch the load neutral conductor to the source feeding the load, as per 230.95(C)
FPN No. 3. Ground-fault current will return only to the source from which it
originates, providing for coordination of the ground-fault protection scheme. Its not
always necessary to separately ground the generator neutral conductor. However, if
you do, you may need to switch a load neutral along with its phase conductors when
transferring loads between power sources, particularly when you use ground-fault
protection. The NEC requires ground-fault protection for 480/277V, 3-phase, 4-wire,
wye-connected services rated 1,000A or more, but its optional in other
configurations that dont include ground-fault protection. However, where a branch
circuit neutral conductor transfers between sources, the switching means should
assure the neutral conductor switching contact does not interrupt current.
(19) If one lamp connects between two phases it will glow or not?
If the voltage between the two phases is equal to the lamp voltage then the lamp will
glow.
When the voltage difference is big it will damage the lamp and when the difference is
smaller the lamp will glow depending on the type of lamp. On the type of lamp.
(20) Why transmission line 11Kv OR 33KV, 66Kv not in 10kv 20kv?
The form factor of an alternating current waveform (signal) is the ratio of the RMS
(Root Mean Square) value to the average value (mathematical mean of absolute
values of all points on the waveform). In case of a sinusoidal wave, the form factor is
approximately 1.11.
The reason is something historical. In olden days when the electricity becomes
popular, the people had a misconception that in the transmission line there would be
a voltage loss of around 10%. So in order to get 100 at the load point they started
sending 110 from supply side.
Nowadays that thought has changed and we are using 400 V instead of 440 V, or
230 V instead of 220 V.
Also alternators are now available with terminal voltages from 10.5 kV to 15.5 kV so
generation in multiples of 11 does not arise.
(21) When should We use Molded Case Circuit Breakers and Mini Circuit Breakers?
First of all MCB is Miniature Circuit Breaker, since it is miniature it has limitation for
Short Circuit Current and Amp Rating Both.
MCB:
Usually Current range for A.C. 50-60 HZ, is from 0.5 Amp 63 Amp. Also available
80A, 100A, and 125 Amp.
SC are limited 10 KA
Tripping Curve: (1) B Resistive and lighting load, (2) C Motor Load, (3) D Highly
inductive load.
MCCB:
Usually Current range for A.C., 50-60 HZ, are from 3.2 /6.3/12.5/25/50/100/125/ 160
Amp. SC 25/35/65 KA.
Over load rated current 0.4 1.0 in steps of o.1 of in trip time at 600 % Ir (sec)
0.2.0.5,1, 1.5 , 2 ,3
Short Circuit :-2 10 in steps of 1 lr , short time delay (sec) 0.02.0.05,0.1, 0.2 ,0.3
MCB (Miniature Circuit Breaker) Trip characteristics normally not adjustable, factory
set but in case of MCCB (Moulded Case Circuit Breaker)Trip current field
adjustable.
A multi meter is good enough. A shorted C will clearly show very low resistance. An
open C will not show any movement on ohmmeter.
A good capacitor will show low resistance initially, and resistance gradually
increases. This shows that C is not bad. By shorting the two ends of C (charged by
ohmmeter) momentarily can give a weak spark.
(23) How to identify the winding starting and ending leads in a motor which is
having 6 leads in the
terminal box
Use IR tester to identify 3 windings and their 6 leads. Then connect any two leads of
two winding and apply small voltage across it and measure the current.
Then again connect alternate windings of same two windings and apply small
amount of voltage (same as before) and measure current.
Check in which mode you get the max current and then mark it as a1-a2 & b1-b2.
You get max current when a2-b1 will be connected and voltage applied between a1b2.
Follow the same process to identify a1-a2, b1-b2, c1-c2.now you will be able to
connect it in delta or star.
Connecting a capacitor across a generator always improves power factor, but it will
help depends up on the engine capacity of the alternator, otherwise the alternator will
be over loaded due to the extra watts consumed due to the improvement on pf.
Secondly, do not connect a capacitor across an alternator while it is picking up or
without any other load.
Providing a tertiary winding for a transformer may be a costly affair. However, there
are certain constraints in a system which calls for a tertiary transformer winding
especially in the case of considerable harmonic levels in the distribution system.
Tertiary winding is may be used for any of the following purposes:
o (1) To limit the fault level on the LV system by subdividing the in feed that is
double secondary T.C.
o (2) The interconnection of several power systems operating at different supply
voltages.
o (3) The regulation of system voltage and of reactive power by means of a
synchronous capacitor connected to the terminals of one winding.
o It is desirable that a three-phase transformer should have one set of threephase windings connected in delta thus providing a low-impedance path for
third-harmonic currents. The presence of a delta connected winding also
allows current to circulate around the delta in the event of unbalance in the
loading between phases, so that this unbalance is reduced and not so greatly
fed back through the system.
200/230=0.8696 A
100/230=0.4348 A
60/230=0.2609 A respectively
Now, when in series, current flowing in all bulbs will be same. The energy released
will be I2R
Thus, light output will be highest where resistance is highest. Thus, 60 watt bulb will
be brightest.
The 60W lamp as it has highest resistance & minimum current requirement.
Highest voltage drop across it X I [which is common for all lamps] =s highest power.
Note to remember:
And highest resistance will drop highest voltage drop across it in a Series circuit
And highest resistance in a parallel circuit will pass minimum current through it. So
minimum power dissipated across it as min current X equal Voltage across =s min
power dissipation.
(27) Difference between Restricted Earth Fault & Unrestricted Earth Fault
protections?
Restricted earth fault is normally given to on star connected end of power equipment
like generators, transformers etc. mostly on low voltage side. For REF protection 4
nos CTs are using one each on phase and one in neutral. It is working on the
principle of balanced currents between phases and neutral.
For Differential Protection CTs using on both side HT & LV side each phase, and
comparing the unbalance current for this protection also PX class CTs are using.
o The magnetization of any given point on the sheet varies, so the extension
and contraction is not uniform. A transformer core is made from many sheets
of special steel to reduce losses and moderate the ensuing heating effect.
o The extensions and contractions are taking place erratically all over a sheet
and each sheet is behaving erratically with respect to its neighbor, so you can
see what a moving, writhing construction it is when excited. These extensions
are miniscule proportionally and therefore not normally visible to the naked
eye.
o However, they are sufficient to cause a vibration, and consequently noise.
Applying voltage to a transformer produces a magnetic flux, or magnetic lines
of force in the core. The degree of flux determines the amount of
magnetostriction and hence, the noise level.
o Why not reduce the noise in the core by reducing the amount of flux?
Transformer voltages are fixed by system requirements.
o The ratio of these voltages to the number of turns in the winding determines
the amount of magnetization. This ratio of voltage to turns is determined
mainly for economical soundness. Therefore the amount of flux at the normal
voltage is fixed. This also fixes the level of noise and vibration. Also,
increasing (or decreasing) magnetization does not affect the magnetostriction
equivalently. In technical terms the relationship is not linear.
(29) What are the advantages and disadvantages of Low Resistance Grounding
(LRG) systems compared to High Resistance Grounding (HRG) systems? Also, what
ratings of resistance (in ohms) are considered low and high resistance?
The first parameter is voltage. By choosing HRG on systems 600V or below, you
reduce ground-fault currents to less than 25A. For systems between 600V and 5kV,
we can use either HRG or LRG arrangements.
In either case, the resistance chosen must be such that the desired let-through
ground-fault current is above the system capacitive charging current. On systems
above 5kV, LRG is the typical choice in that it reduces ground-fault currents to
between 25A and 1,200A. (Most people use a value of 200A or less.)
The next parameter is system capacitive charging current. Every system has a
capacitance value, mostly due to the systems cables and surge arresters/capacitors.
The general rule of thumb for estimating this charging current is to use 1A per
1,000kVA. If necessary, you can perform a more detailed calculation based on
system components.
desired resistor current (IR) must be greater than the system capacitive charging
current to avoid transient overvoltage. You determine the neutral grounding
resistance by using the following equation: R = VL-N IR
For systems less than 600V, the system capacitive charging current is typically 1A to
3A. Therefore, most people use 5A neutral current as a standard. Because this is
less than 10A, all 600V systems are high-resistance grounded.
For systems between 600V and 5kV, you can use either HRG or LRG. The decision
is typically based on system capacitive charging current, which can vary from 1A to
10A. This value then determines whether to use HRG or LRG. For systems above
5kV, the system capacitive charging current may be greater than 25A, so LRG is
almost always used.
On systems with grounding resistor let-through currents higher than 10A or for
systems of voltage ratings greater than 5kV the faulted feeder should be tripped
and the fault isolated. These are generally called LRG systems.
(30) What are the advantages and disadvantages of the various grounding
methods for medium- voltage systems in power plants?
You can broadly classify medium-voltage (MV) grounding systems into four
categories: solidly grounded, low-resistance grounded (LRG), high-resistance
grounded (HRG), and insulated neutral (ungrounded) systems. A good reference is
ANSI/IEEE Std. 242 (Buff Book), Protection and Coordination of Industrial and
Commercial Power Systems.
The neutral point of the system is grounded without any resistance. If the ground
fault occurs, high ground current passes through the fault. Its use is very common in
low voltage system, where line to neutral voltage is used for single phase loads.
With the solidly grounded system, there is no intentional impedance in the neutral-toearth path. Instead, the neutral is solidly connected to earth. This is why the term
earthing is sometimes used in place of grounding.
The phase-to-ground voltage remains constant during a ground fault, and there are
very high fault current flows, which can result in extensive damage. The protective
device closest to the fault must trip and isolate the circuit as fast as possible.
If the fault is in a rotating machine, then there is a high possibility of core damage
and replacement costs. The cost associated with the downtime also can be
significant.
This is used for limiting the ground fault current to minimize the impact of the fault
current to the system. In this case, the system trips for the ground fault. In this
system, the use of line to neutral (single phase) is prohibited. The ground fault
current is limited to in the rage from 25A to 600A
With LRG systems, the ground-fault current is controlled and normally limited to
between 25A and 1,000A. The voltage to ground on the un-faulted phases can
increase up to the phase-to-phase voltage level, so you must use adequately rated
insulation systems and surge suppression devices.
You also must detect and isolate the ground fault. Since the ground-fault current is
smaller and controlled, ground-fault relaying still has the requirement of fast tripping.
However, you can achieve better time current coordination with this type of
grounding system. Damage at the fault point is also reduced; therefore, maintenance
and repair costs are reduced.
The neutral grounding resistor needs to be short time rated (usually 10 seconds), as
the fault will be cleared by the protective relay closest to the fault.
(2) Derive a neutral on the paralleling bus via a zigzag transformer, and then add
resistance grounding on the derived neutral.
It is used where service continuity is vital, such as process plant motors. With HRG,
the neutral is grounded through a high resistance so that very small current flows to
the ground if ground fault occurs. In the case of ground fault of one phase, the faulty
phase goes to the ground potential but the system doesnt trip.
This system must have a ground fault monitoring system. The use of line to neutral
(single phase) is prohibited (NEC, 250.36(3)) in HRG system, however, phase to
neutral is used with using the additional transformer having its neutral grounded.
When ground fault occurs in HRG system, the monitoring systems gives alarm and
the plant operators start the standby motor and stop the faulty one for the
maintenance. This way, the process plant is not interrupted. The ground fault current
is limited to 10A or less.
There are other two types such as Corner Grounding (for Delta system) and
ungrounded system but they are not commonly used.
With an HRG system, the ground-fault current is in the 10A range. The intention
here is to allow the system to operate without tripping, even with a phase-to-ground
fault on one phase.
When a ground fault does occur, only an alarm is raised. This permits time to locate
the fault while power continuity is maintained. This also allows repairs to be done at
a scheduled shutdown of the faulty equipment. Maintenance costs should be less
than that for a low-resistance grounding system. Damage at the fault location also
should be small.
If the fault is in a rotating machine, there usually is no iron damage in the stator. The
system, with one phase faulted to earth, operates with the un-faulted phases now
raised from earth to the full phase-to-phase voltage for an extended period.
As such, the insulation system needs to be rated for phase-to-phase voltage. For
phase-to-ground voltages to remain at the phase-to-phase level and not
increased beyond that level the net capacitive charging current at the fault must
be less than that from the controlled resistive ground-fault current fed from the
neutral grounding. The grounding resistor also needs to be continuously rated
because it will carry the let-through current in the event of a fault for an extended
period of time.
(2) Derive a neutral on the paralleling bus via a zigzag transformer, and then
add resistance grounding on the derived neutral.
Be careful here in that you cannot use this neutral for any loads or connect it to
anything except the resistor. There are advantages/disadvantages for each option.
By having a resistor on each source, the total ground-fault current is dependent upon
the total number of sources in operation. However, the system is always grounded. If
the resistor is on the paralleling bus, the ground-fault current is always the same
value however, the system is only grounded if the paralleling bus in operation. Most
people choose option 2 and have a resistor on the paralleling bus
When a ground fault occurs, the fault current is contributed by the system
capacitance to earth on the un-faulted phases. This is usually small, and the system
can be operated without tripping.
Because the system is floating, if the ground fault is of the arcing or intermittent type,
then there is the possibility of substantial transient overvoltage, which can be six to
eight times the phase voltage.
These transients often cause a subsequent failure elsewhere, thus raising the
possibility of a phase-to-earth-to-phase fault, and leading to high fault current and
extensive damage. Coordinated tripping is often difficult, and extensive damage is
seen at the two faulted locations. Maintenance costs are typically the highest among
the four types of grounding systems now at least two pieces of equipment need
repair.
These transients often cause a subsequent failure elsewhere, thus raising the
possibility of a phase-to-earth-to-phase fault.
The standards and best practices in various countries generally follow ANSI or IEC
standards. The technical literature supports these practices. In power plant
applications, MV systems occur in two places: generation and station service. In
practice, both station service and generators are low- or high-resistance grounded.
For station service at distribution voltages of less than 15kV, power continuity is very
important. Here, we would size the neutral grounding resistor so that the let-through
ground-fault current is higher than the net current from the distributed capacitance. If
the let-through ground-fault current is less than 10A, then this would be highresistance grounding. If this current were more than 10A, then it would be lowresistance grounding.
Although its rare to have station service voltage that is higher than 15kV, if the
voltage is higher than this, then the same rule as noted above would apply, except
the fault should be detected and isolated by tripping the faulted feeder at the closest
protective device.
For generators, the ground-fault current is almost always controlled, and we can
employ resistance grounding. The resistor let-through current will be dependent on
the size of the generator and generation voltage. Typically, 5A to 400A let-through
current grounding is used.
More recently, hybrid grounding has been proposed. Here, two resistors in parallel
are used: one of low resistance; the other of high resistance (5A).
In the event of an internal earth fault in the stator winding of the generator, a fastacting generator ground differential relay opens the low-resistance grounding path,
thus allowing the high resistance (5A let-through resistor) to control and lower the
fault current and reducing the stator damage caused by the internal ground fault after
the generator has been isolated (while it is slowing down).
Without this reduction of current, the generator would continue to feed energy into
the fault while it is coming to a stop. The result would be extensive stator iron
damage at the ground-fault location.
For CTs either we use for 3 phases or 2 phase or even if you use only 1 CTs for the
Over current Protection or for the Earth Faults Protection, their neutral point is
always shorted to earth. This is NOT as what you explain as above but actually it is
for the safety of the CTs when the current is passing throuw the CTs.
In generally, tripping of Earth faults and Over current Protection has nothing to do
with the earthing the neutral of the CTs. Even these CTs are not Grounded or
Earthed, these over current and the Earth Faults Protection Relay still can operated.
Operating of the Over current Protection and the Earth Faults Relays are by the
Kirchhoff Law Principle where the total current flowing into the points is equal to the
total of current flowing out from the point.
Therefore, for the earth faults protection relays operating, it is that, if the total current
flowing in to the CTs is NOT equal total current flowing back out of the CTs then
with the differences of the leakage current, the Earth Faults Relays will operated.
The following points need to check before going for Neutral Grounding Resistance.
(2) Capacity of transformer to sustain ground fault current, w.r.t winding, core
burning. Manufacturer shall be able to give this data.
(4) Standard practice of limiting earth fault current. In case no data or calculation is
possible, go for limiting E/F current to 300A or 500A, depending on senility of relay.
No comments:
Post a Comment
About Me
Bhavik Panchal
View my complete profile
Blog Archive
2012 (4)
o
July (4)
Electrical Q&A
Electrical Funda
Referring Fig. 2 the three current transformers and relay coils connected in star and the star
point is earthed. When short circuit occurs in the protected zone the secondary current of CT's
increase. The current flows through coiler and the relay pick-up. The relay close, thereby the trip
circuit is closed and the circuit breaker operates.
The over-current protection scheme with three over-current relays (Fig. 2) responds to phase
faults and earth faults including single phase to earth fault. Therefor such schemes are used with
solidly earthed system where phase to phase and phase to earth faults are likely occurs.
In Fig. 2 the polarities of CT's are indicated by dots. For proper functioning of over-current and
earth fault protection, the choice of CT's and polarity connections should be correct.
Fig. 3 illustrates the modified circuit with additional auxiliary relays and a definite time relay.
Definite time relay can be set to get desired delay. Auxiliary relays is used to close trip circuit.
In the scheme discussed here the earth fault at any location near or away from the location of
CT's can cause the residual current flow. Hence the protection zone is not definite. Such protection is
called unrestricted earth fault protection. For selectivity directional earth fault protection is necessary.
OC = over-current
; EF = earth fault
can
not
transformer/generator
be
accurately
winding
alone.
defined.
The
The
relay
protected
sense
the
area
earth
is
not
faults
restricted
to
beyond
the
transformer/generator winding. Hence such protection is called unrestricted earth fault protection.
Fig. 6 Earth fault protection by earth fault relay connected in neutral to earth circuit
The earth fault protection by relay in neutral to earth circuit depends upon the type of neutral
earthing.. In case of large generators, voltage transformer is connected between neutral to earth.
The earth fault relay is connected to secondary of VT.
7. Combined earth fault and phase fault protection
It is convenient to incorporate phase fault relays and earth fault relay in a combined phase fault
and earth fault protection (Fig. 7). The increase in current of phase causes corresponding increase in
respective secondary currents. The secondary current flows through respective relay units.Very often
only toe phase relays are provided instead of three, because in cause of phase faults current in any
at least tow phase must increase. Hence tow relay units are enough. The earth fault relay is
residually connected as explained earlier.
8. Earth fault protection with core balance current transformer (Zero sequence ct)
In this type of protection Fig. 8(a) a single ring shaped core of magnetic material, encircles the
conductors of all the three phases. A secondary coil is connected to a relay unit. The cross section of
ring core is ample, so that saturation is not a problem. During no earth fault condition, the component
of fluxes due to the fields of three conductors are balanced and the secondary current is negligible.
During earth faults, such a balance is disturbed and current is inducted in the secondary. Core
balance protection can be conveniently used for protection of low voltage and medium voltage
system. The burden of relay and exciting current are deciding factors. Very large cross section of
core are necessary for sensitivity less than 1A. Thus form of protection is likely to be more popular
with static relay due to the less burden of the latter. Instantaneous relay unit is generally used with
core balance shcemes.
Theory of core balance CT. Let a, b and c be the three line currents and a, b and c be
corresponding components of magnetic flux in the core. Assuming linearity, we get resultant
magnetic flux r as,
r = k(a + b + c)
Where k is constant r= k Ia. Referring to theory of symmetrical components
a + b + c = 3c = n
Where, Io is zero sequence current and In is current in neutral to ground circuit.
During normal condition, when earth fault is absent,
a + b + c = 0
Hence r= 0 and relay does not operate
During earth fault the earth fault current flows through return neutral path. For example for single line
ground fault.
If = 3Ia0 = In
Hence the zero sequence current component of Io produces the resultant in the core. Hence
core balance current transformer is also called as zero sequence current transformer (ZSCT)
Application for core balance CT's with cable termination joints
The termination of a three core cable into three separate lines or bus-bars is through cable
terminal box. Ref. Fig. 8 (b), the core balance protection is used along with the cable box and should
be installed before making the cable joint.
The induced current flowing through cable sheath of normal healthy cable need particular
attention with respect to the core balance protection.
The sheath current (Ish) flow through the sheath to the cover cable box and then to earth
through the earthing connection between cable box. For eliminating the error due to sheath current
(Ish) the earthing lead between the cable box and the earth should be taken through the core of the
core balance protection. Thereby the error due to sheath current is eliminated. The cable box should
be insulated from earth.
9. Frame leakage protection
The meta-clad switchgear can be provided with frame leakage protection. The switchgear is
lightly insulated from the earth. The metal frame work or enclosure of the switchgear is earthed with
a primary of a CT in between Fig. (9).
The concrete foundation of the switchgear and the cable boxes and other conduits are slightly
insulated from earth, the resistance to earth being about 12 ohms. In the event of an earth fault
within the switchgear, the earth fault current finds the path through the neutral connection. While
doing so, it is sensed by the earth fault relay.
Circulating current differential protection also responds to earth faults within its protected
zone .
Summary
Earth fault protection can be achieved by following methods :
- Residually connected relay.
- Relay connected in neutral to ground circuit.
- Core balance scheme.
- Frame leakage arranged for detecting earth faults on line.
- Circulating current differential protection.
10. Directional over-current protection
The over-current protection can be given directional feature by adding directional element in the
protection system. Directional over-current protection responds to overcurrents for a particular
direction flow. If power flow is in the opposite direction, the Directional over-current protection
remains un- operative.
Directional over-current protection comprises over-current relay and power directional relay in a
single relay casing. The powers directional does not measure the power but is arranged to respond
to the direction of power flow.
Directional operation of relay is used where the selectivity can be achieved by directional
relaying. The directional relay recognizes the direction in which fault occurs, relative to the location of
the relay. It is such that it actuates for faults occurring in one direction only. It does not act for faults
occurring in the other direction. Consider a feeder XY (Fig. 10.) passing through subsection A. The
circuit breaker in feeder AY is provided with a directional relay 'R' which will trip the breaker CBy, if
fault power flow in direction A, alone, therefor for faults in feeder AX, the circuit breaker CBy does not
trip unnecessarily. However for faults in feeder Ay the circuit breaker CBy trips because its protective
relaying in set with a directional feature to act in direction Ay.
Fig. 12
Fig. 14
Summary
Over-current protection responds to increase above the pick-up value over-currents are caused
by overloads and short circuits. The over-current relays are connected the secondary of current
transformer. The characteristic of over-current relays includes inverse time characteristic, definite
time characteristic.
Earth fault protection responds to single line to ground faults and double line to ground faults.
The current coil of earth fault relays is connected either in neutral to ground circuit or in residually
connected secondary CT circuit.
Core balance CTs are used for earth fault protection.
Frame leakage protection can be used for metal-clad switchgear.
Directional over-current relay and directional earth fault relay responds to fault in which power
flow is in the set direction from the CT and PT locations. Such directional relays are used when
power can flow both directions to the fault point.