Beruflich Dokumente
Kultur Dokumente
INTRODUCTION
At present, the Double-Fed Induction Generator (DFIG) has
a large proportion in variable speed and constant frequency
wind power generation System, with the increasing of the
single-unit capacity and installed capacity of the DFIG unit, the
reaction between the generator and grid becomes more and
more important [1]. According to the new requirement of grid
regulation, when power failure occurs such as voltage dip (in a
certain range), the wind turbine shall remain to be connected
with the Main-Grid, therefore Low Voltage Ride
Through(LVRT) of DFIG has become one of the domestic and
foreign scholars hot research subjects. The leading country of
the wind power generation technology has issued the quota
standard about through fault in succession.
The voltage dip is referred to the sudden voltage drop by
10% -90% in a single point and lasts for a half cycle to 1
minute. The voltage dip is classified in three categories
according to the reason which it forms: voltage dip caused by
power failure, voltage dip caused by large-scaled generators
start-up, voltage dip caused by generators reacceleration. As to
the voltage dip caused by the power failure, the time of the
voltage dip and voltage recovery is comparatively short, so it is
a usual form of voltage tip. In order to reduce the harm to the
DFIG caused by power failure, ascertain the related method of
passing through fault on low voltage and protective measure,
so it is very important to make clear the dynamic respond of
the DFIG during Grid voltage dip and the reason which it
produced. Literature [5] has established the precise model for
DFIG in the stator winding dynamics process, and the voltage
dip fault response simulation is implemented on the basis of
improved vector control strategy. Literature [6], the response of
DFIG during symmetrical grid faults is simulated by time
I.
L dI
Vs = Rs I s + m mo + j1 s
dt
Lr dI r L2 m dI mo
Vr = Rr I r +
+
+ js r
dt
Ls dt
(1)
s = Ls I s + Lm I r = Lm I mo
2
= L m I mo + L I
r r
r
Ls
is:
[ ]
[ ]
P = 1.5 Re Vs I s *
*
Q = 1.5 Im Vs I s
L2 m
Ls I s
In the formula: I mo =
= 1
Vs
Lm + Lr
Lr Ls
Vr are respectively the stator and rotor voltage vector; I s
I r are respectively the stator and rotor current vector; s
r are respectively the stator and rotor flux linkage vector;
Rs Rr are respectively the stator and rotor resistance;
u s = Rs i s +
d s
dt
+ sP
+ sN
=
s = sDC
5
U sN
s usP
U s U sP
u
e +
+ sN
j j
j
j j
Where s is the space vector of the generator stator flux
is the space vector of the
linkage after the fault and sDC
generator stator flux linkage transient DC component after the
and sN are the space vector of generator stator
fault, sP
flux positive and negative sequence components after the fault;
U s is the space vector of the generator stator voltage before
and U sN
are the space vector of the generator stator
fault; U sP
voltage of positive and negative sequence components after the
fault; is the stator angular frequency; s is the attenuation
time constant of stator flux transient DC component; u sP and
usN are the space vector of the positive and negative sequence
components of generator stator voltage after the fault.
When DFIG-side three-phase symmetrical short-circuit
fault occurs, due to the exhausted function of stator resistance,
the stator flux DC component will gradually decrease, and the
attenuation rate depends on the motor stator resistance and
leakage. Since the generator rotor rotates with high speed
during the voltage dip, the stator magnetic DC component with
angular speed r rotate against rotor winding, at the same
time rotated frequency current component can be induced in
the rotor winding (relative to the rotor), and then rotor flux
transient DC component (relative to the stator) can be
generated. Rotor flux DC component and stator flux DC
component phase offset to maintain the rotor flux conservation
during the fault. After the fault, under the effects of the stator
resistance, the stator flux DC component will gradually
attenuate, and the corresponding rotor speed frequency current
component will attenuate, the attenuation rate depends on
generator parameters. Because the momentary rotor transient
magnetic components can only cross the stator winding
magnetic leakage, when the stator flux DC component is large,
the rotor winding induces a large current that produces enough
magnetic flux which balances the stator flux linkage. This will
lead to the rotor flow.
After the removal of the fault, generator stator voltage
returns to be normal, the generator transient process is similar
to the moment of fault, the stator flux still appears transient DC
component, and this will also lead to the rotor flow.
As to the asymmetric grid fault, the stator flux linkage not
only contains DC component but also contains negative
sequence component. As the wind turbine speed is usually
higher than the thermal power units, the speed of the stator flux
leakage with a great rated slip that is relative to the DC
component and negative sequence component causes the
increasing of rotor circuit voltage and current significantly.
III.
A.
ref
Te*
Ls
L m
udr*
udr
idr*
s
Qref
uqr*
uqr
iqr*
ua*1
dq u
abc u
*
b1
*
c1
idr , iqr
ids , iqs
IV.
dq
abc
uds , uqs
dq
abc
A.
Figure 2. Diagram of Generator Side Rectifier Control
id*
v*d
dq
u *dc
*
q
abc
v*q
e L
ud
u abc
e L
id
iq
dq
abc
iabc
dq
abc
b) Rotor Speed
c) DC Voltage
d) Rotor Current
b) Rotor Speed
c) DC Voltage
d) Rotor Current
REFERENCES
[1]
[2]
[3]
[4]
f) The Active and Reactive Power of the Stator
Figure 5. Dynamic Response of DFIG during 80%0.25s Voltage Dip
[5]
TABLE I.
Stator voltage
Electromagnetic torque
Active power of generator
Reactive power of stator side
rev
Rotor current active component
Rotor current reactive component
Voltage on DC side
Change
trend
reduction
reduction
reduction
reduction
acceleration
augment
augment
augment
CONCLUSION
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
BIOGRAPHIES
Kao-she ZHANG, (1965- ), male, Qianese county in Shaanxi
Province, associate professor, doctor, mainly engaged in the study
of the power system stability control and electrical market.
Ping Su (1985- ), male, PingLiangnese in GanSu province, master
graduated student, mainly engaged in the study of power system
analysis and wind power.