Beruflich Dokumente
Kultur Dokumente
The given U-values were not in accordance with the TEK10 14, therefore it was necessary
to change the values before the thermal calculation has been made. The following U-values
are advisable following the standards of TEK10:
As a consequence of the standards the U-values of the windows and doors, roof and floor
(was not given!) have to be improved significantly. In other words, the materials of the roof
have to be changed to ones that have a smaller U-value. The higher the U-value is, the
higher the energy losses are through e.g. the roof.
The following U-values I finally used for the thermal calculations:
Calculations:
Transmission calculation:
Storage:
Area
East wall:
North wall:
West wall:
South wall:
length [m]
21,92
19,51
13,57
19,51
height [m]
3
3
3
3
minus
1,785
result [m]
65,76
58,53
40,71
56,745
Losses
Loss [W]
Object
Walls:
1363,73
Roof:
2279,42
Doors:
1320,28
Floor:
2630,1
Lobby:
Area
length 1 [m]
East wall:
Northwest:
North wall:
South wall:
3,91
5,091
9,4767
1,8977
length 1 [m]
2,321
Windows:
Floor:
Object
Part 1
Part 2
Part 3
Part 4
Part 5
Part 6
Sum
height [m]
3
3
3,59
3
3
length 2
[m]
9,312
length 3
[m]
1,741
0,85
Doors:
Roof:
length 2
[m]
1,265
Area [m]
27,355
6,241
52,901
12,158
33,602
4,541
minus
result [m]
1,785
15,525
13,488
28,4301
16,4631
height [m]
result [m]
40,122
2,1
1,785
result [m]
136,798
136,798
Losses
Loss [W]
Object
Walls:
454,53
2061,82
Roof:
729,13
Floor
841,31
Offices
Area
Windows/Doors
length 1 [m]
North:
South:
West:
18,28
18,28
4,189+4,190
length 1 [m]
North wall:
South wall:
West wall:
23,1733
23,07
14,7
length 1 [m]
Roof:
Floor:
height 1
[m]
1,4
1,4
2,5
length 2
[m]
3,1988
3,19
2*0,91
height 2[m]
result [m]
2,5
2,5
1,1
33,589
33,567
22,95
length 2
[m]
height [m]
minus
result [m]
3
3
3
33,589
33,567
22,95
35,9309
36,879
21,15
length 2 breadth2[m]
[m]
3,8
0,412
result [m]
0,412
breadth
[m]
23,173 14,7-0,412
332,666
332,666
Losses
Windows/D = 0,12 W/mK * (33,589+33,567+22,95) * (21C-(-20C)) =
4433,22
Walls:
577,85
Roof:
1773,11
Floor:
2045,9
20510,4
Q total
Ventilation calculation:
Volumes
Offices:
Storage:
Lobby:
Volume total
Losses:
Vent total
Loss [W]
15448,42
Infiltration calculation:
Volume
Offices:
Storage:
Lobby:
area [m]
height [m]
332,666
427,66
136,798
volume [m]
3
997,998
3
1282,98
3
410,394
Volume total
2691,372
Loss [W]
Losses
Infiltration
11586,35
Total losses
Thermal Ventilation Infiltration
20510,4
15448,42
11586,35
Total
47545,17
2) Ventilation concept
Desired characteristics of the Ventilation System:
For the connection between each BACnet controller and the KNX
system a gateway will be needed, but there should be no problem to
find one, because both systems are common
Valve type should be a valve with two blades that are independently
controllable by the system
room. As soon as the CO2 sensor detects the need of fresh air, it would send a telegram to
the heating for turning on or higher and then with a short delay the valve blade opens for
more fresh air. And this leads us to the next point, the controlling of the heating.
The heating should be regulated, as well as the lighting, by a movement sensor, mounted at
a reasonable point to the ceiling. It has proved ones worth to regulate the heating with four
modes: frost protection, comfort, night and stand-by. Using a movement sensor for
regulating the heating assures that not only the heating but the entire microsystem in the
office stays in comfort mode as long as the sensor detects a person in the room, especially
in the evenings this can be important to people, who work longer. In addition to the
movement sensor I would recommend window contacts to save energy, when a window is
open. There should be a priority for the modes on the one hand to maintain a comfortable
indoor climate and on the other hand to save energy. In other words, a window is open and
the window contact has detected that, the heating should switch into frost protection mode
to save heating energy. The heating stays in this mode until the window is closed again. The
priorities should be the following with connected actions and time:
1
2
3
4
The above chosen time schedule is of course depending on the working hours of the
specific company, they are just examples. In addition to that the following temperatures are
advisable for the different modes:
Frost protection: 7C
Comfort: summer 19C, winter 21C
Night: summer 15C, winter 17C
Stand-by: summer 17C, winter 19C
the needed temperature in this only room, if there is no mode setting in the controller. In
this case the main line would go down to Night mode and the air temperature, which is
needed in this only room could be provided by the local radiator this saves a lot of energy.
The proposed ideas can be applied to the normal offices as well as to the meeting rooms.
10
5. Variables
Temperature
Frost protection mode
Comfort mode
Night mode
Stand-by mode
Actual setpoint
CO2
Valve blade 1 sup
Valve blade 2 sup
Valve blade 1 exh
Valve blade 2 exh
Emergency
Occupancy
Switch
Dimming
Light intensity
Window contacts
CB1
GT
SF1
EF1
FID 1:1
FID 1:2
AHU1-FD1:1
AHU1-FD1:2
3) Lighting concept
1. All three areas:
To achieve a system that integrates each part, it is reasonable to also chose the
KNX bus for the lighting system
The DALI dimming concepts are quite cheap so far and dimming is one of the
most expensive points in building automation, therefore it would be
recommendable to equip each light with a DALI ballast. As far as I know it works
for the Avion 3*49W as well as for the Glamox Zapp360 22W
As a consequence of very high prices for DALI gateways to the KNX bus (400) I
would propose to put several lights, e.g. all offices on the north side, on one
gateway wires are cheaper. This should work well, because one DALI gateway
can handle 64 actuators at the same time. Separation see different areas
11
Each device connected to the gateway can still be controlled separately and all at the same
time, unconsidered the time delay caused by wires and a lot of telegrams. The light should
be controlled by the movement sensor, which is installed in each office and the meeting
rooms. A built in daylight sensor, not in the meeting room 129, will adjust the needed
artificial light and dim the lights up or down. There are several kinds of movement sensors
with built-in daylight sensor, but it is advisable to select one that either can differ between
artificial light and daylight or is oriented only to the area of the window to assure a real
control by daylight. In addition, a switch should provide manual adjustments of the
dimming percentage and an on/off control. This function would be integrated by one
rocker in the above mentioned room thermostat. To integrate the manual functions
properly into the automation functions it is necessary to think about how the system gets
back again into the automation mode. This could be realised by switching back to the
automation mode as soon as the person leaves the room. To turn on the manual mode
again, the light needs to be dimmed or turned on/off at the switch. Furthermore there
should be the possibility to check all the lights for their status, working hours and damage
from one point in the system (overall control unit).
For the meeting rooms it is reasonable to integrate different light scenes, which e.g. provide
the right light during a presentation. In the meeting room 129 could it be handled like that:
For a presentation only the light near to the door would be on and dimmed to e.g. 50%, the
other lights are in a different group and are turned off. Furthermore there could be a group
with only the two lights aligned to the long side of the room and the two others in another
group. Considering the limit of group numbers it would still work, because in the corridor
there would be only six groups, so ten are left. Another group should consist of all four
lights and turn on in case the movement sensor detects occupancy. The other light scenes
can only be controlled by a controlling panel, e.g. the Jung KNX Smart-Control.
12
Considering the fact that there is no light coming in through windows, the lights in the
corridor could always be dimmed to 20-30% and only turn to 100% when somebody
enters. This can be handled dependent on the use of the corridor. As well as in the offices I
would also recommend here to only integrate one DALI gateway and save costs. For
controlling the lights I would select movement sensors, which are adjustable in a very
precise way that the establishing of the different zones can be done well. The lights are also
available with a built-in movement sensor, but in my opinion it is better to have six
different zones with one sensor, it is easier to control and to maintain. Besides that the
lights should be controllable by switches at e.g. four spots. There are already two switches
in the north and south side of the corridor, integrated in the room thermostat and there
should be two more in the east and west part and one in the vestibule to the technical
room. The switches can control the specific parts of the corridor and the one in the west
part of the corridor can control a new group consisting of the north west part and the south
west part. The limit of the groups is still not exceeded. In the corridor could also apply
different modes, e.g. like that:
The given lights are also available with an emergency battery, which could be a good
addition to the entire system for providing a safe environment in the corridor in an
emergency case. Another mode, same as for the ventilation, could be set to fully turn every
light on in this situation. To save some more electricity it would be reasonable to think
about controlling the lights in the entrance area of the corridor by a daylight sensor,
depending on how much light comes in through the glass wall.
13
dimmed down to 20-30% like in the corridor to at least provide a bit light. For the case,
that people are working in the reception the specific area could be controlled by a separate
switch integrated in the room thermostat, which is already mounted to the wall at a
reasonable spot to be controlled from a working place in the rear area of the reception. The
layout for the different light groups is already chosen in a way that provides a single area
with one movement sensor for a working place in the rear area of the reception. Assuming
that the most used way leads to the offices it is a compromise between nicely designed
daylight control and energy saving to take the one light at the corner of the three groups to
the upper group. The two lights next to the corridor entrance on the south side are not
really belonging to either group, but I would prefer to add them to the main group.
Furthermore there should be a switch to control the three other groups.
14
Next step will be to compare these functions with the automation functions needed e.g. in
class A or B. Starting with class B, we will explore how high the energy efficiency in this
project is. Note, there is no information given about blinds and cooling.
Integrated
Individual room
control with
communication
between controllers
Indoor temperature
control of
distribution air
temperature
Partial interlock
between heating
and cooling control
(dependent on
HVAC system)
Better integrated
Not integrated
Lighting
Heating
Ventilation
Class B
Manual daylight
control
Automatic
occupancy detection
manual on / auto off
Automatic
occupancy detection
manual on /
dimmed
Automatic
occupancy detection
auto on / auto off
Automatic
occupancy detection
auto on / dimmed
Not considered
15
Integrated
Individual room
control with
communication
between controllers
Indoor temperature
control of
distribution air
temperature
Total interlock
between heating
and cooling control
Weather station for
blind control
Frost protection
Better integrated
Not integrated
Lighting
Demand or
presence dependent
air flow control at
room level
Variable set point
with load
dependant
compensation of
supply temperature
control
Room or exhaust or
supply air quality
control
Air exchange
scheduling
Heating
Ventilation
Class A
Automatic daylight
control
Automatic
occupancy detection
manual on / auto off
Automatic
occupancy detection
manual on /
dimmed
Automatic
occupancy detection
auto on / auto off
Automatic
occupancy detection
auto on / dimmed
Maintenance
Not considered
To sum up all these factors shown above, it is obvious that in the class B comparison there
are several functions that are better integrated than actually needed to fulfil the
requirements. Focussing on the comparison with functions needed to be entitled to class A
there are three points, which are not fulfilled or controversial. One point is the needed air
exchange scheduling. In the considered office building is only integrated a CO2 sensor, but
no scheduling based on outside temperature and the consequential temperature gradient.
Therefore it is depending on how exactly the standards need to be fulfilled and if there is a
tolerance. However, if an air exchange scheduling would be strictly needed it would be easy
to integrate that in the existing system. Furthermore the points total interlock between
heating and cooling control and weather station for blind control is not exactly defined in
the description of this office building. As a consequence, it is not possible to judge these
features for the considered project.
In conclusion, we explored that a lot of automation functions are integrated in the system
for this particular office building to be considered at least better than class B. To finally
decide which class would be appropriate for this project, it is necessary to know how the
tolerances are. Nevertheless, I would entitle the considered office building to the lower end
of class A.
16
Appendix
BAS3900-4_Office_lighting.jpg
BAS3900-4_Corridor_lighting.jpg
BAS3900-4_Reception_lighting.jpg
BAS3900_Office_ventilation.pdf
BAS3900_Corridor_ventilation.pdf
BAS3900_Reception_ventilation.pdf
17