Data Sheet CT/VT Interface 560CVT10

CT/VT Interface 560CVT10

The fault current is measured up to 20 times


nominal current. Therefore the current inputs
withstand 50 times nominal current for 1 s.
The CT/VT interface is equipped with one binary
output which can be used to indicate e.g. alarm
for over current.
All CT/VT interfaces are mounted in the RTU cabinet. Current and voltage inputs are connected via
transformer only (see Figure 1).
The CT/VT interfaces are designed for mounting
on DIN rails 35 mm.

Meter Operation
Application

The following metered parameters are available:

The Current/Voltage Transducer Interface


(CT/VT interface) is used for measuring analog AC input signals from three independent
phases with 3 or 4 wire connections. For
each phase voltage, current and power are
measured directly, and a number of other parameters derived from these in software. The
results are transmitted to the RTU560.

Instantaneous Meter Values


Measured by true RMS conversion and transmission to the RTU560 of following values:
Phase - Neutral Voltage 1N, 2N, 3N, Average
Phase -Phase Voltage 1-2, 2-3, 3-1, Average
Current Phase 1, 2, 3

There are several versions available:

Fault Current Phase 1, 2, 3, N

Auxiliary Voltage (LO):


3 current-, 3 voltage inputs (In 1A)
3 current-, 3 voltage inputs (In 5A)
4 current-, 4 voltage inputs (In 1A)
4 current-, 4 voltage inputs (In 5A)

Active Power, Phase 1, 2, 3, Total

Auxiliary Voltage (HI):


4 current-, 4 voltage inputs (In 1A)
4 current-, 4 voltage inputs (In 5A)

Frequency,

Reactive Power, Phase 1, 2, 3, Total


Apparent Power, Phase 1, 2, 3, Total
Power Factor, Phase 1, 2, 3, Average

Phase Rotation
Voltage / Current Harmonic Distortion (THD,

Characteristics
The CT/VT interface is a microprocessorbased Intelligent Electronic Device (IED) intended for current, voltage, power and energy measurement.
Distorted input waveforms with harmonics to
the 15th are therefore detected accurately.
Additional functionality to provide functions
as fault current detection, minimum and
maximum logging and analog high and low
limit supervision is available.

Doc-No.: 1KGT 150 623 V001 1

current and voltage phase 1,2 and 3)

Derived Meter Values


calculation of Active, Apparent and Reactive
Energy accumulated values (intermediate and
end of period readings, delivery and consumption)
calculation of Ampere Hours accumulated
values (intermediate and end of period readings, delivery and consumption)
Neutral current (with 3 wire connection)

RTU560
Data Sheet CT/VT Interface 560CVT10

Functionalities
With a powerful diagnostic tool the operator
is able to fulfil below described tasks. As option the related date can be transferred over
the communication link to the RTU and the
control system.

Harmonic analysis for power quality analysis


(up to 15th harmonic):

Communications over RS485 port with


Modbus RTU Protocol
User Mapping to speed up communication
Logging of Minimum and Maximum Values

Relay output for configurable alarm


Configurable alarms for over voltage, over
frequency, over current and so on
Fault current detection (Option)
- configurable flexcurve for overcurrent
alarm (in the same as IEC, ANSI curves)
Event Logging
Trend logging (option)
Waveform Capturing and phaser
analysis:

Doc.-No.: 1KGT 150 623 V001 1

RTU560
Data Sheet CT/VT Interface 560CVT10

Wiring

Fig. 1: 3 phase with 3 wire connection

Doc-No.: 1KGT 150 623 V001 1

Fig. 2: 3 phase with 4 wire connection

RTU560
Data Sheet CT/VT Interface 560CVT10

Technical Data
In addition to the RTU560 general data, the following applies:

Stability
Stability

max. 100ppm/C
(Temperature range
-10 to +50C)

Input Channels
Voltage
U1, U2, U3, U4

Current
I1, I2, I3, I4

Range:
10 ... 300V AC
3 Phase, 3 or 4 Wire
Load : <0.15 VA at 300V
Un:
- R001x:
3 voltages (U1, U2, U3)
- R002x, R004x:
4 voltages (U1, U2, U3, U4)

Serial Ports
Modbus RTU protocol

RS485

Diagnostic Port

RS232

Baud Rate

1.2k, 2.4k, 4.8k, 9.6k,


19.2k bps

R00x5: 5A, max. 6A


R00x1: 1A, max. 1.2A
Fault current: 20 x In
Load: <0.2VA per phase

Test Voltage

Overload withstand:
-2 x In continuous
-25 x In 2 s
-50 x In 1 s

Dielectric Strength
IEC 255-5

2kV AC rms,
1 minute

In:
- R001x: 3 current (I1, I2, I3)
- R002x, R004x:
4 current (I1, I2, I3, I4)
Frequency

40 ... 70Hz

Samples

32 samples per cycle

Accuracy
Phase I

0.2 %

Neutral I

0.5 %

Phase I, fault current

1%

Phase U

0.2%

Ph-Ph U

0.2%

Watts

0.5 %

VA

0.5 %

Vars

0.5 %

PF

0.5 %

Frequency

0.05 % rd

AD converting

12 bit + sign bit

Immunity Test
ANSI / IEEE
C37.90.1-1989

3 kV SWC

IEC 61000-4-12

Class III SWC

Fast Transient /
Burst IEC 61000-4-4

Class IV SWC

Surge Immunity Test


IEC 61000-4-5

Class IV Impulse

Auxiliary voltage
Auxiliary Voltage
(LO)

24/ 48 V DC 15%

Auxiliary Voltage
(HI)

80 260 V AC
80 330 V DC

Doc.-No.: 1KGT 150 623 V001 1

RTU560
Data Sheet CT/VT Interface 560CVT10

Mechanical Layout

Ordering information

Width

134.8 mm

Height

70.3 mm

560CVT10 R00011
In = 1A, 3 voltage, 3
current, Version LO

1KGT 018900
R0011

Depth

149.5 mm

Height

70.3 mm

560CVT10 R00015
In = 5A, 3 voltage, 3
current, Version LO

1KGT 018900
R0015

Enclosure

for DIN Rail 35 mm

560 CVT10 R0021


In = 1A, 4 voltage, 4
current, Version LO

1KGT 018900
R0021

560 CVT10 R0025


In = 5A, 4 voltage, 4
current, Version LO

1KGT 018900
R0025

560 CVT10 R0041


In = 1A, 4 voltage, 4
current, Version HI

1KGT 018900
R0041

560 CVT10 R0045


In = 5A, 4 voltage, 4
current, Version HI

1KGT 018900
R0045

Environmental Conditions
Operating
ture

Tempera-

-25 to +60 C

Storage Temperature

-40 to +80 C

Relative
humidity

10 95 %
non condensing

Doc-No.: 1KGT 150 623 V001 1

RTU560
Data Sheet CT/VT Interface 560CVT10

Note:
We reserve the right to make technical changes or modify
the con-tents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail.
ABB AG does not accept any responsibility whatsoever for
potential errors or possible lack of information in this document.
We reserve all rights in this document and in the subject
matter and illustrations contained therein. Any reproduction,
disclosure to third parties or utilization of its contents - in
whole or in parts - is forbidden without prior written consent
of ABB AG.
Copyright 2011 ABB
All rights reserved

Doc.-No.: 1KGT 150 623 V001 1