Beruflich Dokumente
Kultur Dokumente
On
STATIC SYNCHRONOUS COMPENSATOR (STATCOM)
Supervised by
Dr. G.K. Joshi
Head
Submitted by
Dimpal Soni
Enroll. No. : - 12/22526
Roll No. :B.Tech (Electrical Eng.)
Page | 1
ACKNOWLEDGEMENT
By the blessings of Lord Shiva, the academic outcome in the form of a
seminar
work
on
STATIC
SYNCHRONOUS
COMPENSATOR
Page | 2
CERTIFICATE
This is to certify that Miss Dimpal Soni, B.tech. Scholar in Electrical
engineering bearing Roll no. 111103365 & Enroll. No. 12/22526 has carried out
her seminar on STATIC SYNCHRONOUS COMPENSATOR (STATCOM)
under my supervision.
The work presented in this seminar has not been submitted elsewhere for
award of any other degree or diploma.
Dr. G. K. Joshi
Supervisor
Head
Deptt. Of Electrical Eng.
J.N.V. University, Jodhpur
Counter Signed by
Prof. Manoj Kumar Bhaskar
Deptt. Of Electrical Engineering
J.N.V. University, Jodhpur
Page | 3
LIST OF TABLES
Table No.
Particulars
Page No.
33
Page | 4
LIST OF FIGURES
Fig. No.
Particulars
Page No.
1.1
1.2
1.3
1.4
SVC Outlook
1.5
1.6
1.7
2.1
10
2.2
11
2.3
11
2.4
12
2.5
14
2.6
15
2.7
15
2.8
17
2.9
18
2.10
19
Page | 5
2.11
6 Pulses STATCOM
20
2.12
21
2.13
21
3.1
23
3.2
24
3.3
25
3.4
26
3.5
27
4.1
30
Page | 6
Chapter 1 INTRODUCTION
1-8
1.1 INTRODUCTION
1
2
4
4
4
6
7
9-21
2.1 INTRODUCTION
10
10
11
12
13
15
18
18
22-28
Page | 7
22
3.2 TCSC
3.2.1 Advantages
22
23
23
24
26
26
29-33
29
31
31
34
34
35
References36
Page | 8
CHAPTER: 1
INTRODUCTION
1.1 INTRODUCTION:Flexible AC transmission system (FACTS) controllers are power electronics based controllers.
With the applications of FACTS technology, bus voltage magnitude and power flow along the
transmission lines can be more flexibly controlled. Among the FACTS controllers, the most
advanced type is the controller that employs Voltage Sourced Converter (VSC) as synchronous
sources. Representative of the VSC type FACTS controllers are the Static Synchronous
Compensator (STATCOM), which is a shunt type controller, the Static Series Compensator
(SSSC), which is a series type controller and the Unified Power Flow Controller (UPFC), a
combined series-shunt type controller. Of all the VSC the most widely used is the STATCOM. It
can provide bus voltage magnitude control. Computation and control of power flow for power
systems embedded with STATCOM appear to be fundamental for power system analysis and
planning purposes. Power flow studies incorporating STATCOM requires accurate model in
solution algorithms.
There are mainly two models of STATCOM which have well tested in power systems. There are
the Current Injection Model (CIM) and the Power Injection Model (PIM). The CIM STATCOM
has a current source connected in shunt the bus for voltage magnitude control. The PIM models
the STATCOM as shunt voltage source behind an equivalent reactance or impedance, which is
also referred to as voltage source model (VSM). This steady state power injection model of
STATCOM has proved reliable when incorporated in power systems and is well documented.
The use of this STATCOM in power system simulators has therefore increased over the last one
decade and is therefore adopted implementation in this work with the voltage expressed in
rectangular coordinate.
1.2 FACTS DEVICES:Flexible AC Transmission Systems, called FACTS, got in the recent years a well known term
for higher controllability in power systems by means of power electronic devices. Several
FACTS-devices have been introduced for various applications worldwide. A number of new
types of devices are in the stage of being introduced in practice.
In most of the applications the controllability is used to avoid cost intensive or landscape
requiring extensions of power systems, for instance like upgrades or additions of substations
and power lines. FACTS-devices provide a better adaptation to varying operational conditions
and improve the usage of existing installations. The basic applications of FACTS-devices are:
Power flow control,
Increase of transmission capability,
Page | 9
Voltage control,
Reactive power compensation,
Stability improvement,
Power quality improvement,
Power conditioning,
Flicker mitigation,
Interconnection of renewable and distributed generation and storages.
1.2.1 FACTS FOR TRANSMISSION SYSTEM:Figure 1.1 shows the basic idea of FACTS for transmission systems. The usage of lines for
active power transmission should be ideally up to the thermal limits. Voltage and stability
limits shall be shifted with the means of the several different FACTS devices. It can be seen
that with growing line length, the opportunity for FACTS devices gets more and more
important.
The influence of FACTS-devices is achieved through switched or controlled shunt
compensation, series compensation or phase shift control. The devices work electrically as fast
current, voltage or impedance controllers. The power electronic allows very short reaction
times down to far below one second.
Page | 10
1.3 MAJOR FACTS DEVICES:The development of FACTS-devices has started with the growing capabilities of power
electronic components. Devices for high power levels have been made available in converters
for high and even highest voltage levels. The overall starting points are network elements
influencing the reactive power or the impedance of a part of the power system. Figure 1.2
shows a number of basic devices separated into the conventional ones and the FACTS-devices.
For the FACTS side the taxonomy in terms of 'dynamic' and 'static' needs some explanation.
The term 'dynamic' is used to express the fast controllability of FACTS-devices provided by the
power electronics. This is one of the main differentiation factors from the conventional devices.
The term 'static' means that the devices have no moving parts like mechanical switches to
perform the dynamic controllability. Therefore most of the FACTS-devices can equally be
static and dynamic.
Page | 11
The left column in Figure 1.2 contains the conventional devices build out of fixed or
mechanically switch able components like resistance, inductance or capacitance together with
transformers. The FACTS-devices contain these elements as well but use additional power
electronic valves or converters to switch the elements in smaller steps or with switching
patterns within a cycle of the alternating current. The left column of FACTS-devices uses
Thyristor valves or converters. These valves or converters are well known since several years.
They have low losses because of their low switching frequency of once a cycle in the
converters or the usage of the Thyristors to simply bridge impedances in the valves.
The right column of FACTS-devices contains more advanced technology of voltage source
converters based today mainly on Insulated Gate Bipolar Transistors (IGBT) or Insulated Gate
Commutated Thyristors (IGCT). Voltage Source Converters provide a free controllable voltage
in magnitude and phase due to a pulse width modulation of the IGBTs or IGCTs. High
modulation frequencies allow to get low harmonics in the output signal and even to compensate
disturbances coming from the network. The disadvantage is that with an increasing switching
frequency, the losses are increasing as well. Therefore special designs of the converters are
required to compensate this.
Reduction of unwanted reactive power flows and therefore reduced network losses.
Keeping of contractual power exchanges with balanced reactive power.
Compensation of consumers and improvement of power quality especially with huge demand
fluctuations like industrial machines, metal melting plants, railway or underground train
systems.
Compensation of Thyristor converters e.g. in conventional HVDC lines.
Improvement of static or transient stability.
Almost half of the SVC and more than half of the STATCOMs are used for industrial
applications. Industry as well as commercial and domestic groups of users require power
quality. Flickering lamps are no longer accepted, nor are interruptions of industrial processes
due to insufficient power quality. Railway or underground systems with huge load variations
require SVCs or STATCOMs.
1.4.2 SVC:
Electrical loads both generate and absorb reactive power. Since the transmitted load varies
considerably from one hour to another, the reactive power balance in a grid varies as well. The
result can be unacceptable voltage amplitude variations or even a voltage depression, at the
extreme a voltage collapse.
A rapidly operating Static Var Compensator (SVC) can continuously provide the reactive
power required to control dynamic voltage oscillations under various system conditions and
thereby improve the power system transmission and distribution stability.
Applications of the SVC systems in transmission systems:
a. To increase active power transfer capacity and transient stability margin
b. To damp power oscillations
c. To achieve effective voltage control
In addition, SVCs are also used
1. in transmission systems
a. To reduce temporary over voltages
b. To damp sub synchronous resonances
c. To damp power oscillations in interconnected power systems
Page | 13
2. in traction systems
a. To balance loads
b. To improve power factor
c. To improve voltage regulation
3. In HVDC systems
a. To provide reactive power to acdc converters
4. In arc furnaces
a. To reduce voltage variations and associated light flicker
Installing an SVC at one or more suitable points in the network can increase transfer capability
and reduce losses while maintaining a smooth voltage profile under different network
conditions. In addition an SVC can mitigate active power oscillations through voltage
amplitude modulation.
SVC installations consist of a number of building blocks. The most important is the Thyristor
valve, i.e. stack assemblies of series connected anti-parallel Thyristors to provide
controllability. Air core reactors and high voltage AC capacitors are the reactive power
elements used together with the Thyristor valves. The step up connection of this equipment to
the transmission voltage is achieved through a power transformer.
Page | 14
The main disadvantage of this configuration is the significant harmonics that will be generated
because of the partial conduction of the large reactor under normal sinusoidal steady-state
operating condition when the SVC is absorbing zero MVAr. These harmonics are filtered in the
following manner. Triplex harmonics are canceled by arranging the TCR and the secondary
windings of the step-down transformer in delta connection. The capacitor banks with the help
of series reactors are tuned to filter fifth, seventh, and other higher-order harmonics as a highpass filter. Further losses are high due to the circulating current between the reactor and
capacitor banks.
1.6 SVC USING A TCR AND TSC:This compensator overcomes two major shortcomings of the earlier compensators by
reducing losses under operating conditions and better performance under large system
disturbances. In view of the smaller rating of each capacitor bank, the rating of the reactor bank
will be 1/n times the maximum output of the SVC, thus reducing the harmonics generated by
the reactor. In those situations where harmonics have to be reduced further, a small amount of
FCs tuned as filters may be connected in parallel with the TCR.
Page | 16
CHAPTER: 2
STATIC SYNCHRONOUS COMPENSATOR (STATCOM)
2.1 INTRODUCTION:The STATCOM is a solid-state-based power converter version of the SVC. Operating as a
shunt-connected SVC, its capacitive or inductive output currents can be controlled
independently from its terminal AC bus voltage. Because of the fast-switching characteristic of
power converters, STATCOM provides much faster response as compared to the SVC. In
Page | 17
addition, in the event of a rapid change in system voltage, the capacitor voltage does not change
instantaneously; therefore, STATCOM effectively reacts for the desired responses. For
example, if the system voltage drops for any reason, there is a tendency for STATCOM to
inject capacitive power to support the dipped voltages.
STATCOM is capable of high dynamic performance and its compensation does not depend on
the common coupling voltage. Therefore, STATCOM is very effective during the power
system disturbances.
Moreover, much research confirms several advantages of STATCOM. These advantages
compared to other shunt compensators include:
Size, weight, and cost reduction
Equality of lagging and leading output
Precise and continuous reactive power control with fast response
Possible active harmonic filter capability
This chapter describes the structure, basic operating principle and characteristics of
STATCOM. In addition, the concept of voltage source converters and the corresponding
control techniques are illustrated.
2.2 STRUCTURE OF STATCOM:Basically, STATCOM is comprised of three main parts (as seen from Figure below): a voltage
source converter (VSC), a step-up coupling transformer, and a controller. In a very-highvoltage system, the leakage inductances of the step-up power transformers can function as
coupling reactors. The main purpose of the coupling inductors is to filter out the current
harmonic components that are generated mainly by the pulsating output voltage of the power
converters.
Page | 18
Page | 19
.
Fig. 2.2 STATCOM operating in inductive or capacitive modes
In other words, looking at the phasor diagrams on the right of Figure 3.4, when1I, the reactive
current component of the STATCOM, leads (THVE1) by 90, it is in inductive mode and
when it lags by 90, it is in capacitive mode.
This dual mode capability enables the STATCOM to provide inductive compensation as well
as capacitive compensation to a system. Inductive compensation of the STATCOM makes it
unique. This inductive compensation is to provide inductive reactance when overcompensation
due to capacitors banks occurs. This happens during the night, when a typical inductive load is
about 20% of the full load, and the capacitor banks along the transmission line provide with
excessive capacitive reactance due to the lower load. Basically the control system for a
STATCOM consists of a current control and a voltage control.
2.3.2 Current Controlled STATCOM
Page | 20
Figure above shows the reactive current control block diagram of the STATCOM. An
instantaneous three-phase set of line voltages, vl, at BUS 1 is used to calculate the reference
angle, , which is phase-locked to the phase a of the line voltage, vla . An instantaneous threephase set of measured converter currents, il, is decomposed into its real or direct component,
I1d, and reactive or quadrature component, I1q, respectively. The quadrature component is
compared with the desired reference value, I1q* and the error is passed through an error
amplifier which produces a relative angle, , of the converter voltage with respect to the
transmission line voltage. The phase angle, 1, of the converter voltage is calculated by adding
the relative angle, , of the converter voltage and the phase lock-loop angle, . The reference
quadrature component, I1q*, of the converter current is defined to be either positive if the
STATCOM is emulating an inductive reactance or negative if it is emulating a capacitive
reactance. The DC capacitor voltage, vDC, is dynamically adjusted in relation with the converter
voltage. The control scheme described above shows the implementation of the inner current
control loop which regulates the reactive current flow through the STATCOM regardless of the
line voltage.
2.3.3 Voltage Controlled STATCOM
In regulating the line voltage, an outer voltage control loop must be implemented. The outer
voltage control loop would automatically determine the reference reactive current for the inner
current control loop which, in turn, will regulate the line voltage.
The real power (P) and reactive power (Q) are given by:
E is the line voltage of transmission line. V is the generated voltage of VSC. X is the equivalent
reactance of interconnection transformer and filters and is the phase angle of E with respect to
V.
In steady state operation, the voltage V generated by the VSC is in phase with E (=0), so that
only reactive power is flowing (P=0). If V is lower than E, Q is flowing from E to V
(STATCOM is absorbing reactive power). On the reverse, if V is higher than E, Q is flowing
from V to E (STATCOM is generating reactive power).
Since we are using here a VSC based on SPWM inverters hence modulation index is varied for
controlling the reactive power injection to the transmission line. A capacitor is connected on the
DC side of the VSC acts as a DC voltage source. In steady state the voltage V has to be phase
shifted slightly behind E in order to compensate for transformer and VSC losses and to keep the
capacitor charged.
Page | 23
By equaling right-hand terms of the above formulas, a formula for the current I1 is obtained as
Where UR is the STATCOM terminal voltage if the STATCOM is out of operation, i.e. when Iq
= 0. The fact that Iq is shifted by 90 with regard to UR can be used to express Iq as
Applying the sine law to the diagram in Figure below the following two equations result
Page | 25
To dispose of the term UR the cosine law is applied to the diagram in Figure above Therefore,
Page | 26
2.6 STATCOM V-I CHARACTERISTIC:A V-I characteristic of a STATCOM is depicted in Fig.2.9 . As can be seen, the STATCOM can
supply both the capacitive and the inductive compensation and is able to independently control
its output current over the rated maximum capacitive or inductive range irrespective of the
amount of ac-system voltage. That is, the STATCOM
can provide full capacitive-reactive power at any system voltage even as low as 0.15 pu. The
characteristic of a STATCOM reveals strength of this technology: that it is capable of yielding
the full output of capacitive generation almost independently of the system voltage (constantcurrent output at lower voltages). This capability is particularly useful for situations in which the
STATCOM is needed to support the system voltage during and after faults where voltage
collapse would otherwise be a limiting factor.
2.7 FUNCTIONAL REQUIREMENTS OF STATCOM:The main functional requirements of the STATCOM in this thesis are to provide shunt
compensation, operating in capacitive mode only, in terms of the following;
Voltage stability control in a power system, as to compensate the loss voltage along
transmission. This compensation of voltage has to be in synchronism with the AC system
regardless of disturbances or change of load.
Transient stability during disturbances in a system or a change of load.
Page | 27
Direct voltage support to maintain sufficient line voltage for facilitating increased reactive
power flow under heavy loads and for preventing voltage instability
Reactive power injection by STATCOM into the system
The design phase and implementation phase (as presented in the next chapter) would refer to
the theoretical background of STATCOM in providing the requirements
In 1999 the first SVC with Voltage Source Converter called STATCOM (STATic
COMpensator) went into operation. The STATCOM has a characteristic similar to the
synchronous condenser, but as an electronic device it has no inertia and is superior to the
synchronous condenser in several ways, such as better dynamics, a lower investment cost and
lower operating and maintenance costs. A STATCOM is build with Thyristors with turn-off
capability like GTO or today IGCT or with more and more IGBTs. The static line between the
current limitations has a certain steepness determining the control characteristic for the voltage.
The advantage of a STATCOM is that the reactive power provision is independent from the
actual voltage on the connection point. This can be seen in the diagram for the maximum
currents being independent of the voltage in comparison to the SVC. This means, that even
during most severe contingencies, the STATCOM keeps its full capability.
In the distributed energy sector the usage of Voltage Source Converters for grid interconnection
is common practice today. The next step in STATCOM development is the combination with
energy storages on the DC-side. The performance for power quality and balanced network
operation can be improved much more with the combination of active and reactive power.
Page | 28
STATCOMs are based on Voltage Sourced Converter (VSC) topology and utilize either GateTurn-off Thyristors (GTO) or Isolated Gate Bipolar Transistors (IGBT) devices.
The STATCOM is a very fast acting, electronic equivalent of a synchronous condenser. If the
STATCOM voltage, Vs, (which is proportional to the dc bus voltage Vc) is larger than bus
voltage, Es, then leading or capacitive VARS are produced. If Vs is smaller then Es then
lagging or inductive VARS are produced.
Page | 29
CHAPTER: 3
OTHER SERIES AND SHUNT DEVICES
3.1 SERIES DEVICES:Series devices have been further developed from fixed or mechanically switched
compensations to the Thyristor Controlled Series Compensation (TCSC) or even Voltage
Source Converter based devices.
The main applications are:
Reduction of series voltage decline in magnitude and angle over a power line,
Reduction of voltage fluctuations within defined limits during changing power transmissions,
Improvement of system damping resp. damping of oscillations,
Limitation of short circuit currents in networks or substations,
Avoidance of loop flows resp. power flow adjustments.
3.2 TCSC:Thyristor Controlled Series Capacitors (TCSC) address specific dynamical problems in
transmission systems. Firstly it increases damping when large electrical systems are
interconnected. Secondly it can overcome the problem of Sub Synchronous Resonance (SSR), a
phenomenon that involves an interaction between large thermal generating units and series
compensated transmission systems.
The TCSC's high speed switching capability provides a mechanism for controlling line power
flow, which permits increased loading of existing transmission lines, and allows for rapid
readjustment of line power flow in response to various contingencies. The TCSC also can
regulate steady-state power flow within its rating limits.
From a principal technology point of view, the TCSC resembles the conventional series
capacitor. All the power equipment is located on an isolated steel platform, including the
Thyristor valve that is used to control the behavior of the main capacitor bank. Likewise the
control and protection is located on ground potential together with other auxiliary systems.
Figure shows the principle setup of a TCSC and its operational diagram. The firing angle and
the thermal limits of the Thyristors determine the boundaries of the operational diagram.
Page | 31
Local mitigation of sub synchronous resonance (SSR). This permits higher levels of
compensation in networks where interactions with turbine-generator torsional vibrations or
with other control or measuring systems are of concern.
Damping of electromechanical (0.5-2 Hz) power oscillations which often arise between
areas in a large interconnected power network. These oscillations are due to the dynamics of
inter area power transfer and often exhibit poor damping when the aggregate power tranfer over
a corridor is high relative to the transmission strength.
3.3 DYNAMIC POWER FLOW CONTROLLER:A new device in the area of power flow control is the Dynamic Power Flow Controller (DFC).
The DFC is a hybrid device between a Phase Shifting Transformer (PST) and switched series
compensation.
A functional single line diagram of the Dynamic Flow Controller is shown in Figure 3.2. The
Dynamic Flow Controller consists of the following components:
A standard phase shifting transformer with tap-changer (PST)
Series-connected Thyristor Switched Capacitors and Reactors
Page | 32
quite different characteristics. The steady state control range for loadings up to rated current is
illustrated in Figure 3.3 , where the x-axis corresponds to the throughput current and the y-axis
corresponds to the injected series voltage.
Page | 34
3.4 UNIFIED POWER FLOW CONTROLLER:The UPFC is a combination of a static compensator and static series compensation. It acts as a
shunt compensating and a phase shifting device simultaneously.
Page | 35
Automatic Voltage Control Mode: The shunt inverter reactive current is automatically
regulated to maintain the transmission line voltage at the point of connection to a reference
value. For this mode of control, voltage feedback signals are obtained from the sending end bus
feeding the shunt coupling transformer.
The series inverter controls the magnitude and angle of the voltage injected in series with the
line to influence the power flow on the line. The actual value of the injected voltage can be
obtained in several ways.
Direct Voltage Injection Mode: The reference inputs are directly the magnitude and phase
angle of the series voltage. Phase Angle Shifter Emulation mode: The reference input is phase
displacement between the sending end voltage and the receiving end voltage. Line Impedance
Emulation mode: The reference input is an impedance value to insert in series with the line
impedance. Automatic Power Flow Control Mode: The reference inputs are values of P and Q
to maintain on the transmission line despite system changes.
Page | 37
CHAPTER: 4
STATIC SYNCHRONOUS COMPENSATOR POWER FLOW MODEL
(2)
where
In these expressions, Vk represents bus k voltage and Vstc represents the voltage source inverter.
IN is the Nortons current while Istc is the inverters current. Also, Z SC and Y SC are the
transformers impedance and short-circuit admittance respectively.
The STATCOM voltage injection V STC bound constraints is as follows:
(3)
Where VSTC min and VSTC max are the STATCOMs minimum and maximum voltages.
The current expression in (2) is transformed into a power expression by the VSC and power
injected into bus k as shown in equations (4) and (5) respectively.
(4)
(5)
Page | 38
Fig. 4.1 Thevenin Equivalent Circuit Diagram of STATCOM: (a) STATCOM Schematic
Diagram; (b) STATCOM Equivalent Circuit
Using the rectangular coordinate representation,
Where V STC and STC are the STATCOM voltage magnitude and angle respectively. e k and f k
are the real and imaginary parts of the bus voltage respectively.
e STC and f STC are the real and imaginary parts of the STATCOM voltage respectively. The
active and reactive powers for the STATCOM and node k respectively are:
(6)
(7)
Page | 39
And
(8)
(9)
The Jacobian elements in equation (10) are given in table 4.1 ahead.
4.3 NEWTON-RAPHSON-ALGORITHM
1. We assume a suitable solution for all the buses except the slack bus. We assume a flat voltage
profile i.e. Vp=1.0+j0.0 for p=1,2,,n, ps, Vs=a+j0.0.
2. We then set a convergence criterion = i.e. if the largest of absolute of the residues exceeds ,
the process is repeated, or else its terminated.
3. Set the iteration count K=0.
4. Set the bus count p=1.
5. Check if a bus is a slack bus. If that is the case, skip to step 10.
Page | 40
6. Calculate the real and reactive powers Pp and Qp respectively, using the equations derived for
the same earlier.
7. Evaluate
8. Check if the bus p is a generator bus. If that is the case, compare Qkp with the limits. If it
exceeds the limits, fix the reactive power generation to the corresponding limit and treat the bus
as a load bus for that iteration and go to the next step. If lower limit is violated, set Q sp=Qp min. If
the limit is not violated evaluate the voltage residue.
9. Evaluate
10. Increment the bus count by 1, i.e. p = p+1 and finally check if all the buses have been taken
into consideration. Or else, go back to step 5.
11. Determine the largest value among the absolute value of residue.
12. If the largest of the absolute value of the residue is less than , go to step 17.
13. Evaluate the Jacobian matrix elements.
14. Calculate the voltage increments
15. Calculate the new bus voltage
of all voltages.
Page | 41
TABLE 1
Page | 42
CHAPTER: 5
APPLICATIONS, CONCLUSION AND FUTURE WORK
Due to the excessive number of semiconductor devices and passive components, a fault
protection scheme to enhance the ride-though capability in various faults scenarios remains as an
important challenge
Page | 43
investigate the possibility of charging ES to a higher extent and the related issues such as
protection issues.
Research on the CMC based topology with ESS can be implemented for real and reactive
power compensation in wind farms with FSIGs or Double Fed Induction Generator
5.3 CONCLUSION
Among FACTS controllers, the shunt controller STATCOM have shown feasibility in terms of
cost effectiveness in a wide range of problem-solving abilities from transmission to distribution
levels. A comparison between the STATCOM and the SVC is made and based on several aspects
it is concluded that a STATCOM is more preferred when compared to SVC and other
compensation devices. Instead of directly deriving reactive power from the energy storage
components, the STATCOM basically circulates power with the connected network. Therefore,
the reactive components used in the STATCOM are much smaller than those in the SVC.
The location of the shunt FACTS device depends on the application for which it is installed.
Shunt compensation FACTS devices are installed at the end points of transmission lines (buses)
when used for applications, such as bus voltage regulation and improving HVDC link
performance, etc. However, from simulation results it is observed that for increasing the power
transfer capability of long transmission lines (tie lines connecting two major grids), midpoint of
the lines is the best location for shunt connected multi pulse STATCOM device. When
connected at the midpoint the real power is improved and the load ability margin. The midpoint
sitting of STATCOM also facilitates the independent control of reactive power at both the ends
of the transmission line. For a given voltage limit, the midpoint sitting controls a larger reactive
power because each side of the STATCOM device addresses only half the line impedance and
not the full line impedance as in the case of the transmission line receiving end sitting and
sending end sitting. The simulation study shows that a STATCOM with real power capability
can improve the real power and enhance load stability margin, damp the power system
oscillations ore effectively and stabilize the system faster if the STATCOM-SMES controller is
located at the midpoint. Various concepts regarding the FACTS technology and the important
features of some of the FACTS devices have been presented. The Newton raphson method has
been presented to solve the power flow problem in the power system with static synchronous
compensator (STATCOM).
The study of the basic principles of the STATCOM is carried out as well as the basics of reactive
power compensation using a STATCOM. A power flow model of the STATCOM is attempted
and it is seen that the modified load flow equations help the system in better performance. The
bus system shows improved plots and the thus we can conclude that the addition of a STATCOM
controls the output of a bus in a robust manner.
Hence our objective to maintain voltage stability has been successfully achieved with the
incorporation of Static Synchronous Compensator (STATCOM).
Page | 44
REFERENCES:[1]. How FACTS controllers benefits AC transmission systems: John J. Paserba, Fellow IEEE.
[2]. How FACTS improve the performance of electrical grid: Rolf Grunbaum, Ake Petersson,
Bjom Thorvaldsson (ABB Review 3/2002)
[3] Gyugyi L, Schauer C.D., Williams S.L., Rietman T.R., Torgerson D.R., Edris A., (1995),
The Unified Power Flow Controller: A New Approach to Power Transmission Control, IEEE
Transactions on Power Delivery, vol. 2, pp. 1085-1097.
[4] Edris A, Mehraban A.S., Rahman M, Gyugyi L, Arabi S, Reitman T., (1998),Controlling
The Flow of real and reactive power, IEEE Computer Applications in power, 20-5.
[5] Haque M.H., Yam C.M., (2003), A simple method of solving the controlled load flow
problem of a power system in the presence of UPFC, Electric Power Systems Research 65(1),
pp. 55-62.
[6] Hingorani N.G. and Gyugyi, L. (2000), Understanding FACTS, The Institute of Electrical
and Electronics Engineers, New York.
[7] Sen, K.K., (1999), STATCOM-static synchronous compensator theory, modelling and
applications, IEEE PES Winter Meeting 2, pp.1177-1183.
[8] Chun, L., Qirong, J., Xiaorong, X. and Zhonghong, W. (1998), Rule-based control for
STATCOM to increase power system stability, Power System Technology, Proceedings 1998
International Conference on POWERCON, pp. 372376.
[9] Rahim, A. H. M. A., Al-Baiyat, S. A. and Al-Maghrabi, H. M.: 2002, Robust damping
controller design for a static compensator, IEE Proceedings on Generation, Transmission and
Distribution 149, 491496.
[10] Haque, M. H.: (2004), Improvement of first swing stability limit by utilizing full benefit of
shunt FACTS devices, IEEE Transactions on Power Systems 19(4), 18941902.
[11] Acha, E., Fuerte-Esquivel, C.R., Ambriz-Perez, H. and Angeles-Camacho, C. (2004),
FACTS Modelling and Simulation in Power Networks, John Wiley & Sons, Chichester.
[12] Wei, X., Chow, J.H., Fardanesh, B. and Edris, A.A. (2004), A Common modelling
framework of voltage sourced converters for power flow, sensitivity, and dispatch analysis,
IEEE Transactions Power on System, vol.19, pp. 934-941.
[13] Zhang, X. P., Rehtanz, C. and Pal, B. (2006) Flexible AC Transmission Systems:
Modelling and Control, Springer-Verlag Berlin Heidelberg, Germany.
[14] Milano, F. (2005), An Open Source Power System Analysis Toolbox, IEEE Transactions
on Power Systems, vol.20, no.3, pp.11991206.
Page | 45