in cross-bonded
underground transmission lines
Antoine NAUD (RTE)
Gatan GUTIERREZ (RTE)
Wilfried FRELIN (EDF R&D)
Minh NGUYEN TUAN (EDF R&D)
Content
Introduction
Case study: modelling of a 90 kV cross-bonded link with EMTP-RV
Switching surge
Lightning stroke
Conclusion & perspectives
Introduction
For long UGL, sectionalised cross-bonding is common practice.
Until recently, SVL were installed at each cross-bonding point.
Terminations
Sectionalizing joints
Earthing joints
Minor section
Major section
The availability of reliable tools for transient studies allows the optimization of
the design of cross-bonded links.
SUBSTATION B
OHL
Case study
Cables: 3 x single-core 1200 mm Al
90 kV
Cross-bonded, 2 major sections
SVL: 12 kV, star connection with
grounded neutral
Withstand
levels
X1
R2
X2
Rf
Zc
Switching surges
Re-closing
1.5
x 10
PLOT
gauche_a1@vn@1
source_gauche/VwZ1a@vb@1
0.5
-0.5
-1
Network voltage
-1.5
280
290
300
310
320
330
t (ms)
340
350
360
370
380
This is also true in the worst case of re-closing of a charged cable on voltage of
opposite polarity.
This is also true when performing a sensitivity analysis on re-closing time,
length of minor sections, length of bonding leads, earthing resistances, cable
cross-section, number of major sections.
Lightning stroke
!
OHL/UGL transition
120
100
Second towers
80
60
40
20
0
P0
P1
P2
P3
P4
P5
P6
10
OHL/UGL transition
Peak Voltage(kVc)
Second towers
6
5
4
3
2
1
0
P1
P2
P4
P5
Cross-bonding point
Influence of skywires
Mid-span
2nd tower
Oversheath
Screen
interruption
according to Cigr TB 63
Lightning current
(kA)
Probability
Thank you
for your attention.