Touch Panel Display

VT3 Series
PLC Connection Manual
Mitsubishi Electric Corporation Servo
Amplifier Connection
Whats External Equipment Connection?
Precautions on External Equipment Connection
Checks to Perform before Making Connections
System Configuration
Connection to VT3 Series
Unit Settings
Communication Conditions and Available Devices
List of Communication Errors
Connection with Converters

Refer to PLC Connection Manual for


other chapters and the appendix.

Target PLC
MELSERVO series
96017E-754

1024-28

26-1

External Equipment Connection

Whats External Equipment Connection?


In VT3, VT3 can be connected directly to external equipments from various manufacturers with communication
functions.
One communication port of VT3 can be connected to 31 external equipments. If MultiTalk function is used, up to 62 (2
ports*1 x31 units) can be connected to 1 VT3*2.
VT3 Series

26
EXTERNAL EQUIPMENT CONNECTION

PORT2/3/4*2*3

: Communications cable KPEV-SB (1P)


Communications cable length 1,000m or less

External equipment
VT No. 1
(terminator ON)

External equipment
VT No. 2

External equipment
VT No. 7

External equipment
VT No. 30
(terminator ON)

External equipments from various manufacturers (Max. 31 units)


*1
*2
*3

RS232C-RS485 is required when connecting external devices with PORT2/PORT3,VT-TI of VT3 series in 1:N mode.
If external equipments are selected between PLC-A.PLC-B in the case of MultiTalk, PLC cannot be connected.
When VT3 handy Series uses MultiTalk function, RS-232C/422A/485/Ethernet connecting cable (OP-87191/87192/
87193), or relay terminal block (VT-T1) + cable with removable connector (OP-87194/87195/87196) is required
In addition, MultiTalk function cannot be used in VT3-V7R/W4T(A)/W4M(A)/W4G(A).

Point

26-2

When external equipments are connected to VT3. Handy Series/VT3-V7R, be sure to connect
to one terminal of the communication cable, and set the terminator ON.

- VT3 Series and DT Series PLC Connection Manual -

26-1 External Equipment Connection

Precautions on External Equipment Connection


Internal special device
When external equipments are connected, the connection state of external equipments shall be notified in the
following internal devices.
Device No.

Description

1(ON)

0(OFF)

MB00D00

PLC_A VT No. 0 connection state

Being connected to VT3

Not being connected to VT3

MB00D01

PLC_A VT No. 1 connection state

Being connected to VT3

Not being connected to VT3

PLC_A VT No. 1 connection state

Being connected to VT3

Not being connected to VT3

MB00D20

PLC_A VT No. 16 connection state

Being connected to VT3

Not being connected to VT3

MB00D2F

PLC_A VT No. 31 connection state

Being connected to VT3

Not being connected to VT3

MB00D80

PLC_B VT No. 0 connection state

Being connected to VT3

Not being connected to VT3

MB00D8F

PLC_B VT No.15 connection state

Being connected to VT3

Not being connected to VT3

MB00DA0

PLC_B VT No.16 connection state

Being connected to VT3

Not being connected to VT3

MB00DAF

PLC_B VT No. 31 connection state

Being connected to VT3

26

Not being connected to VT3

When external equipments are connected, the connection state of external equipments can be set in the following
internal devices.
Device No.
MB00D10
MB00D11

Contents
PLC_A VT No.0 connection setting
PLC_A VT No.1 connection setting

MB00D1F
MB00D30

MB00D9F
MB00DB0

PLC_B VT No.15 connection setting


PLC_B VT No.16 connection setting

MB00DBF

Not connected to VT3


Not connected to VT3

PLC_A VT No. 31 connection setting Connected to VT3


PLC_B VT No. 0 connection setting
Connected to VT3

0(OFF)
Not connected to VT3
Not connected to VT3

PLC_A VT No.15 connection setting Connected to VT3


PLC_A VT No. 16 connection setting Connected to VT3

MB00D3F
MB00D90

1(ON)
Connected to VT3
Connected to VT3

Not connected to VT3


Not connected to VT3

Connected to VT3
Connected to VT3

Not connected to VT3


Not connected to VT3

PLC_B VT No. 31 connection setting Connected to VT3

Not connected to VT3

"Chapter 6 Prior to Parts Setting", VT3 Series Reference Manual

Operations for "cut off/reset station No. in communication error"


Communication with the station No. in communication error is cut off when the "cutoff/reset station No. in
communication error" checkbox is selected. And this No. is regularly monitored and communication is started again
once the error is removed.
Operations in case of a communication error are as follows:

No operation is taken even if a timeout error occurs.


The device value of the station No. in communication error is as follows.
In communication before cut-off
Hold value
When updating
0
During write operation
Disabled
- VT3 Series and DT Series PLC Connection Manual -

26-3

EXTERNAL EQUIPMENT CONNECTION

MB00D0F

26-6

Connection to Servo Amplifiers from MITSUBISHI ELECTRIC

This section describes how to connect the servo amplifiers from MITSUBISHI ELECTRIC to VT3.

Checks to Perform before Making Connections


Here, make sure the necessary items used for connecting VT3 to inverters from MITSUBISHI ELECTRIC.
(1) Make sure that VT3 can be connected to servo amplifiers.
(2) Make sure if servo amplifier setting is necessary.
(3) Confirm the target PLC.

26

Be sure to check the above three points before connecting the PLC to the VT3/DT.

EXTERNAL EQUIPMENT CONNECTION

Series Name

26-52

Servo amplifiers

MR-J2S series

MR-J2S-A

MR-J3 series

MR-J3-A

I/F
RS-422A

Unit Setting
*

P.26-59

Communication through equivalent RS-485 is made possible by means of wiring.

- VT3 Series and DT Series PLC Connection Manual -

Target PLC
MELSERVO series

26-6 Connection to Servo Amplifiers from MITSUBISHI ELECTRIC

System Configuration
Connection to servo amplifiers from MITSUBISHI ELECTRIC

MR-J2S series
VT3(PORT4)/VT-T1: Wiring diagram 1
RS-422RS-485 equivalent

VT3-V6H(G)/Q5H(G)Wiring diagram H40


VT3-W4TA/W4MA/W4GA : Wiring diagram W40

26

VT3-V7R : Wiring diagram R1


RS-422
(RS-485 equivalent)

VT3(PORT3)*

(Wiring diagram 3)

EXTERNAL EQUIPMENT CONNECTION

VT3(PORT2)/VT-T1*
VT3 Series

VT3-V6H(G)/Q5H(G)*
I/Flevel converter
N-48
*

External equipment
MR-J2S-A

VT3-V7R*

For the connection between converters and VT3, refer to


"26-11 Connection with Converters".

MR-J3 series

RS-422(RS-485 equivalent)

VT3(PORT4)/VT-T1: Wiring diagram 2


VT3-V6H(G)/Q5H(G)Wiring diagram H41
VT3-W4TA/W4MA/W4GA: Wiring diagram W41
VT3-V7R: Wiring diagram R2

RS-422
(RS-485 equivalent)

VT3(PORT2)/VT-T1*
VT3(PORT3)*

(Wiring diagram4)

VT3-V6H(G)/Q5H(G)*
I/Flevel converter
N-48
*

VT3 Series

VT3-V7R*

For the connection between converters and VT3, refer to


"26-11 Connection with Converters".

External equipment
MR-J3-A

- VT3 Series and DT Series PLC Connection Manual -

26-53

26-6 Connection to Servo Amplifiers from MITSUBISHI ELECTRIC

Connection to VT3 Series


The following describes wiring of connector cables.
The wiring diagrams recommended by MITSUBISHI ELECTRIC may differ from those presented in this manual.
There will, however, be no problems if wiring is performed according to the wiring diagrams in this manual.

Wiring diagram 1 (RS-422A: 4-wire)


*2

VT3
PORT4

26

Servo amplifier
(CN3)
Shielded

Servo amplifier
(CN3)
Shielded

SD

SD

EXTERNAL EQUIPMENT CONNECTION

SDP

SDP

RDP
SDN

RDP
SDN

SG

RDN

RDN

TRE
LG
LG

TRE
LG
LG

*1

*1 Make short-circuit of RDN-TRE for servo amplifier at one end of communication cable.
*2 Terminal resistor not allowed at VT3 side.

Wiring diagram 2 (RS-422A: 4-wire)


*2

VT3 *1
PORT4

A
B

SG

*1
*2

Reference

Distributor

Servo amplifier
(CN3)

5
3
4
6
1
7

SDP
RDP
SDN
RDN
LG
LG

Terminator
(150 1/4W)

Terminator
(150 1/4W)

Terminal resistor not allowed at VT3 side.


Add terminal resistance into inverters at one end of communication cable(150 1/4W).

The following diagram shall be referenced when CN3 ports of MR-J3 series servo amplifiers are
connected to VT3.

(2)

(2)

(2)
CN3

VT3 Series

CN3

(3)

(3)

Distributor

Distributor

(1)

(1)

Point

26-54

CN3

(1)

(3)
Distributor

(1)

Item

Model

Manufacturer

Remarks

Cable

Cables (10BASE-T cable, etc) compliant with EIA 568

(2)

Cable

(3)

Distributor

BMJ-8

Hachiko Electric

Cables (10BASE-T cable, etc) compliant with EIA 568


Without terminator

Be sure to configure VT3 at the termination.


Cut down the branch line (cable of (2)) as short as possible.
Add terminal resistor 150W (1/4W) at the terminal distributor. If commuincation is unstable,
remove the teminal resistor.
The maximum length of trunk line (total of (1)) is 15m.

- VT3 Series and DT Series PLC Connection Manual -

26-6 Connection to Servo Amplifiers from MITSUBISHI ELECTRIC

Wiring diagram 3 (RS-422A:4-wire)


Servo amplifier
(CN3)

Converter*1
Shielded

Servo amplifier
(CN3)
Shielded

SD

SD

SDP

SDP

RDP

RDP

SDN
RDN

SDN
RDN

TRE

TRE

SG

LG

LG

24V

LG

LG

*2

26

0V

EXTERNAL EQUIPMENT CONNECTION

*1 Set the terminator switch ON even if the converter is at one end of communication cable.
*2 Make short-circuit of RDN-TRE for servo amplifier at one end of communication cable.

Wiring diagram 4 (RS-422A:4-wire)


*2

*1

5
3
4
6
1
7

+
SG
24V
0V
*1
*2

Reference

Servo amplifier
(CN3)
Terminator
(150 1/4W)
SDP
RDP
SDN
RDN
Terminator
LG
(150 1/4W)
LG

Distributor

Converter

Set the terminator OFF.


Add terminal resistance into inverters at one end of communication cable.
(150 1/4W)

The following diagram shall be referenced when CN3 ports of MR-J3 series servo amplifiers are
connected to VT3.
(2)

(2)

(2)
CN3

VT3 Series

(3)

(3)

Distributor

(1)
N-48
Converter

CN3

(3)

Distributor

Point

CN3

Distributor

(1)

(1)

Item

Model No.

Manufacturer

(1)

Cables

(2)

Cables

(3)

Distributor

BMJ-8

Hachiko Electric

Remarks
Reference to EIA 568
cables(10BASE-T cable, etc)
Reference to EIA 568
cables(10BASE-T cable, etc)
With terminal resistor

Be sure to configure VT3 into the terminal.


Please cut down the branch line (cable of (2)) as short as possible.
Please add terminal resistor 150W (1/4W) at the terminal distributor.
If the commuincation is unstable, remove the teminal resistor.
The maximum length of trunk line (sum of (1)) is 15m.

- VT3 Series and DT Series PLC Connection Manual -

26-55

26-6 Connection to Servo Amplifiers from MITSUBISHI ELECTRIC

Connection with VT3 Handy Series


Point

For the use of unit connecting cable (OP-87191/87192/87193), please always read
"Precautions on Connection", on Page A-13.

Wiring diagram H40 (RS-485: 4-wire)


OP-87191: 3m, OP-87192: 5m, OP-87193: 10m
VT3 (CN1)

26
EXTERNAL EQUIPMENT CONNECTION

RS-422 RS-485 *1
TMCTMR
ON

Servo amplifier
(CN3)

SD
SDP
RDP
SDN
RDN
TRE
LG
LG

SD
SDP
RDP
SDN
RDN
TRE
LG
LG

Pink (dot: red 1)


A
Pink (dot: red 2)
B
Pink (dot: red 3)
SG

OFF
1

Servo amplifier
(CN3)

Shielded

*2

Shielded

*1 Set the terminator to OFF.


*2 Make short-circuit of RDN-TRE for servo amplifier at one end of
communication cable.

Wiring diagram H41 (RS-422A: 4-wire)


OP-87191: 3m, OP-87192: 5m, OP-87193: 10m
VT3 (CN1)

A
B
SG

Distributor

Pink (dot: red 1)


Pink (dot: red 2)
Pink (dot: red 3)

5
3
4
6
1
7

Servo amplifier *2
(CN3)
Terminal resistor
(150 1/4W)
SDP
RDP
SDN
RDN
Terminal resistor
LG
(150 1/4W)
LG

*1 Set the terminator to OFF.


*2 The Inverter at communication cable end should be equipped with a
terminal resistor

Reference

When the CN3 port on MR-J3 Series servo amplifier is connected to VT3, please use the following
wiring diagram.
(2)

(2)

(2)
CN3

VT3 Series

(3)
Distributor

Point

26-56

CN3

(3)

(3)

Distributor

(1)
N-48
Converter

(1)

CN3

Distributor

(1)

(1)

Item

Model

Manufacturer

Remarks

Cable

Cables (10BASE-T cable etc.) compliant with EIA568

(2)

Cable

(3)

Distributor

BMJ-8

Hachiko Electric

Cables (10BASE-T cable etc.) compliant with EIA568


Without terminator

Be sure to connect VT3 at the termination.


Cut down the branch line (cable of (2)) as short as possible.
A terminator 150W (1/4W) needs to be connected for the terminal distributor. If
commuincation is unstable, remove the teminator.
Max. trunk line length (total for (1)) is 15m.
- VT3 Series and DT Series PLC Connection Manual -

26-6 Connection to Servo Amplifiers from MITSUBISHI ELECTRIC

Connection to VT3-W4TA/W4MA/W4GA
The following describes wiring of connector cables.
The wiring diagram in this manual may be different from that recommended by Yaskawa Electric. But it can still be
used for proper operation of the system.

Wiring diagram W40 (RS-422A: 4-wire)


VT3-W4T/W4M/W4G *1
PORT2(terminal block)

Servo amplifier
(CN3)

Shielded

TXDA

Servo amplifier
(CN3)
Shielded

SD

26

SD

SDP

TXDB

SDP

RDP

RDP

RXDB
SG

SDN

SDN

RDN

RDN

RTSA
RTSB

TRE
LG

TRE
LG

CTSA

LG

LG

EXTERNAL EQUIPMENT CONNECTION

RXDA

*2

CTSB
*1 RDN-TRE is short-circuited on the servo amplifier at the end of communication line.
*2 Set the terminator switch (TERM.) of VT3 to OFF.

Wiring diagram W41 (RS-422A: 4-wire)


*2

*1

VT3-W4T/W4M/W4G
PORT2(terminal block)

Distributor

Servo amplifier
(CN3)

5
3
4
6
1
7

SDP
RDP
SDN
RDN
LG
LG

TXDA
TXDB
RXDA
RXDB
SG
RTSA
RTSB
CTSA
CTSB

Terminator
(150 1/4W)

Terminator
(150 1/4W)

*1 Set the terminator switch (TERM.) of VT3 to OFF.


*2 Add a terminator (150 1/4W) to the inverter at the end of the communication line.

Reference

When the CN3 port on MR-J3 Series servo amplifier is connected to VT3, please use the following
wiring diagram.
(2)

(2)

(2)
CN3

VT3 Series

CN3

(3)

(3)

distributor

(1)

Point

(3)

distributor

(1)

CN3

distributor

(1)

(1)

Item

Model

Manufacturer

Remarks

Cable

Cables (10BASE-T cable etc.) compliant with EIA568

(2)

Cable

(3)

Distributor

BMJ-8

Hachiko Electric

Cables (10BASE-T cable etc.) compliant with EIA568


Without terminator

Be sure to connect VT3 at the termination.


Cut down the branch line (cable of (2)) as short as possible.
A terminator 150W (1/4W) needs to be connected for the terminal distributor. If
commuincation is unstable, remove the teminator.
Max. trunk line length (total for (1)) is 15m.

- VT3 Series and DT Series PLC Connection Manual -

26-57

26-6 Connection to Servo Amplifiers from MITSUBISHI ELECTRIC

Connection to VT3-V7R
Point

When using the connecting cable of the unit (VT-C5K1/C5K2/C5R1/C5R2/C15R2/C5A/C5F/OP75039), be sure to read
"Connection Precautions", page A-13.

Wiring diagram R1 (RS-485: 4-wire)


Servo amplifier
(CN3)

VT3-V7R
(CN2)

26

RS-422A

RS-485*1

TMC TMR

ON

EXTERNAL EQUIPMENT CONNECTION

B
SG

OFF
1

Servo amplifier
(CN3)

Gray/black

White/black
8
Light blue
9

SD

SD

SDP

SDP

RDP

RDP

SDN

SDN

RDN
TRE

RDN
TRE

LG

LG

LG

LG

Shielded

*2

Shielded

*1 Set the terminator OFF.


*2 Make short-circuit of RDN-TRE for servo amplifier at one end
of communication cable.

Wiring diagram R2 (RS-422A: 4-wire)


VT3-V7R
(CN2)

A
B

7
8

*1

Reference

Servo amplifier
(CN3)

5
3
4
6
1
7

SDP
RDP
SDN
RDN
LG
LG

Gray/black
White/black
Light blue

SG 9

*1
*2

Distributor

Terminator
(150 1/4W)

The following diagram shall be referenced when CN3 ports of MR-J3 series servo amplifiers are
connected to VT3.
(2)

(2)
CN3

VT3 Series

CN3

(3)
Distributor

(1)

Item
(1)

Cable

(2)

Cable

(3)

Distributor

CN3

(3)

Distributor

26-58

Terminator
(150 1/4W)

Set the terminator OFF.


Add terminal resistance into inverters at one end of communication cable.
(150 1/4W)

(2)

Point

*2

(1)

(3)
Distributor

(1)

Model

Manufacturer

Remarks

Cables (10BASE-T cable, etc) compliant with EIA 568


Cables (10BASE-T cable, etc) compliant with EIA 568

BMJ-8

Hachiko Electric

Without terminator

Be sure to configure VT3 at the termination.


Cut down the branch line (cable of (2)) as short as possible.
Add terminator 150W (1/4W) at the terminal distributor. If commuincation is unstable,
remove the teminator.
The maximum length of trunk line (total of (1)) is 15m.

- VT3 Series and DT Series PLC Connection Manual -

26-6 Connection to Servo Amplifiers from MITSUBISHI ELECTRIC

Unit Settings
The following describes the settings of the Link Unit matched to the default communications conditions.

Point

Be sure to turn power on again after the settings of parameters. Otherwise, communication is
impossible in the case of any change of communication-related parameters.

Communication settings of MR-J2S

26

For the setting methods, refer to operating instructions of various equipment.


Item
No.

Setting Range

PRM15

0 to 31

PRM16

1100
1101
1102
1103

Default
0

Communication speed,
communication
selection,
communication

:9600bit/s, RS-422, Enabled


:19200bit/s, RS-422, Enabled
:38400bit/s, RS-422, Enabled
:57600bit/s, RS-422, Enabled

0000*1

response delay
*1

Be sure to set PRM16 within the range of 1100 to 1103.Communication with V32 is impossible in the case of settings
other than this range.

Communication settings of MR-J3


For the setting methods, refer to operating instructions of various devices.
Item
Communication station
No.

Parameter No.
PC20

0 to 31

PC21

0100
0110
0120
0130
0140

Baud rate,
communication
response delay
*1

Setting Range

Default
0

:9600bit/s, Enabled
:19200bit/s, Enabled
:38400bit/s, Enabled
:57600bit/s, Enabled
:115200bit/s, Enabled

0000*1

Be sure to set PC21 as either one of 0100, 0110, 0120, 0130 and 0140. Communication with V32 is impossible in the
case of settings other than this range.

- VT3 Series and DT Series PLC Connection Manual -

26-59

EXTERNAL EQUIPMENT CONNECTION

Communication station

Parameter No.

26-6 Connection to Servo Amplifiers from MITSUBISHI ELECTRIC

Communication Conditions and Available Devices


Communication Conditions Setting Ranges and Defaults
MELSERVO series
Item

Setting Range
RS-232C(PORT2,PORT3)*1, RS-485(PORT4)*2

PLC I/F(Port no.)

26

Default
RS-485(PORT4)

EXTERNAL EQUIPMENT CONNECTION

Communication protocols

Start/stop synchro-half duplex mode(ASCII format)

Baud rate

9600,19200,38400,57600,115200*3 bit/s

9600 bit/s

Data bit

8 bits

8 bits

Stop bit

1 bit

1 bit

Parity

Even

Even

Flow Control

ER control

--

ER control

CheckSum

--

--

CR

--

--

LF

--

--

*1
*2
*3

Be sure to use I/F level converter(N-48) when RS-232C is selected.


Serial I/F of servo amplifier is RS-422A. Communication through equivalent RS-485 is made possible by means of
wiring.
Dont select when MR-J2S A series are connected.

Available devices
The following describes available devices and device range of various servo amplifiers.

MR-J2S series
For the details of devices, refer to operating instructions of various equipment.
Type

Device Name
Special functions*1

Bit Devices

SP0 to SP6

Status

ST00 to ST16

Parameter(RAM)
Word Devices

PRM00 to PRM90

Parameter(EEP-ROM)

PRM00 to PRM90

Alarm

AL000 to AL235*2

Input Status

DI0 to DI2

Output Status
*1
*2

DO0 to DO1

Write special devices.


Please use alarms in the following device ranges. Some errors may occur in VT3 if devices other than this range are
used.
Device No.

26-60

Device Range

Function

AL000

Current alarm No.

AL001

Current detailed alarm data

AL011 to AL025

Details in the case of occurrence of alarm

AL200 to AL205

Log alarm No.

AL210 to AL215

Time of occurrence of log alarm

AL230 to AL235

Detailed data of log alarm

- VT3 Series and DT Series PLC Connection Manual -

26-6 Connection to Servo Amplifiers from MITSUBISHI ELECTRIC

MR-J3 series
For the details of devices, see the manuals.
Type

Device Name
Special functions*1

Bit Devices

SP0 to SP6

Status

Word Devices

ST00 to ST16

Basic setting parameters(RAM)

PA01 to PA19

Gains filter parameters(RAM)

PB01 to PB45

Extended setting parameters(RAM)

PC01 to PC50

I/O setting parameters(RAM)

PD01 to PD30

Basic setting parameters(EEP-ROM)

PA01 to PA19

Gains filter parameters(EEP-ROM)

PB01 to PB45

Extended setting parameters(EEP-ROM)

PC01 to PC50

26

PD01 to PD30
AL000 to AL235*2

Alarm
Input Status

DI0 to DI2

Output Status

DO0 to DO1

Write special devices.


Please use alarms in the following device ranges. Some errors may occur in VT3 if devices other than this range are
used.
Device No.

Function

AL000

Current alarm No.

AL001

Current detailed alarm data

AL011 to AL025

Details in the case of occurrence of alarm

AL200 to AL205

Log alarm No.

AL210 to AL215

Time of occurrence of log alarm

AL230 to AL235

Detailed data of log alarm

Specifying Devices
Device No.

ST12_05_A
Device type

Device type

Station No.

PLC type

: specify in device range.

Device No.

: specify in device range.

Station No.

: specify in the range of 0-31.

PLC type

: specify PLC-A/PLC-B when MultiTalk function is used. Not described when MultiTalk function isn't used.

- VT3 Series and DT Series PLC Connection Manual -

26-61

EXTERNAL EQUIPMENT CONNECTION

I/O setting parameters(EEP-ROM)

*1
*2

Device Range

26-6 Connection to Servo Amplifiers from MITSUBISHI ELECTRIC

List of Communication Errors


When a communication error occurs, it will be displayed on the left bottom on the screen of the VT3 main unit.
The error messages are shown as follows.
Display message
COM ERROR
[ERR*(++)]

26

Causes
The device that is set is outside the range of the
device setting range.
A nonexistent device has been set.

EXTERNAL EQUIPMENT CONNECTION

COM ERROR
[SUM(++)]

For the error code[*], see "Connected


Servo amplifier User's Manual".

Cable is not connected correctly.

Please check again whether the cable is


connected correctly.

Power of the Servo amplifier is OFF.

Turn the Servo amplifier ON.

Communication setting error.

Verify whether there is a noise source. If


there is a noise source, then it must be
separated from the main unit.

Checksum is not correct. The calculation method for


checksum is wrong.

Please check the checksum calculation


method.

Connection status of the connection cables is not


good.

Verify whether there is wire break or bad


contact.
Keep the communication settings
consistent between Servo amplifier and
VT3.

Communication setting error.

A parity error occurred during communicating with


Servo amplifier.
Connection status of the connection cables is not good.
Communication setting error.

Affected by noise.
The receive buffer of VT3 overrun.

Over Run Error

26-62

Keep the communication settings


consistent between Servo amplifier and
VT3.
Verify whether there is a noise source. If
there is a noise source, then it must be
separated from the main unit.
Please decrease the communication
speed (baud rate).

Affected by noise.

Verify whether there is a noise source. If


there is a noise source, then it must be
separated from the main unit.

Communication protocol setting error.

Affected by noise.

Verify whether there is wire break or bad


contact.

Verify whether there is wire break or bad


contact. Keep the communication settings
consistent between Servo amplifier and
VT3.

Connection status of the connection cables is not good.

COM ERROR
[RecvData(++)]

Verify whether there is a noise source. If


there is a noise source, then it must be
separated from the main unit.

Connection status of the connection cables is not


good. Communication setting error.

The stop bit cannot be detected during communicating


with Servo amplifier.

Framing Error

Please clear the error or fault on the


Servo amplifier side.
Keep the communication settings
consistent between Servo amplifier and
VT3.

Affected by noise.

Affected by noise.

Parity Error

Please set it again within the device


setting range.

[*]: Error code of Servo amplifier

The Servo amplifier side is in error or fault status.


COM ERROR
[Timeout(++)]

How to handle

Multiple communication errors occurred.

Verify whether there is wire break or bad


contact.
Keep the communication protocol
consistent between Servo amplifier and
VT3.
Verify whether there is a noise source. If
there is a noise source, then it must be
separated from the main unit.
Please refer to the handling methods
mentioned above.

"(++)" indicates the station No. for which an error has occurred.
When MultiTalk function is used, in order to determine the connected equipment on which an error occurs, "A:" or "B:"
will be added in front of the above error messages.

- VT3 Series and DT Series PLC Connection Manual -

26-11

Connection with Converters

When external equipments are connected to VT3 by 1:N in the RS-485, they're generally connected to PORT4. But,
when PORT4 is used for Megabyte link or KL communication, serial I/F level converters are used to connect external
equipments to PORT2/PORT3 by 1:N.

Connection Methods
When external equipments are connected to VT3 series (by 1:N)
VT3 Shielded

26

Serial I/F
level converter
VT3(PORT2)/VT-T1: Wiring diagram 1

EXTERNAL EQUIPMENT CONNECTION

VT3(PORT3): Wiring diagram2


VT3-V6H(G)/Q5H(G): Wiring diagramH20
VT3-V7R:Wiring diagramR1

N-48
Communications cable KPEV-SB (1P) lead
Communications cable length 1,000m or less

External equipment VT No 1
(terminator ON)

External equipment
VT No 2

External equipment
VT No 7

External equipment VT No 31
(terminator ON)

Connection of VT3 to Converters


Point

When the connection cable of the unit (VT-C5K1/C5K2/C5R1/C5R2/C15R2/C5A/C5F/OP-75039)


is used for connection, please read
"Connection Precautions", page A-13

Wiring diagram 1 (OP-24027)


VT3 PORT2 (20-pin)
(1)

(10)
Front view

(20)
(2)
(1)
Rear view

(11)

TXD
RXD
(11)
(10) GND
(9)
CTS
RTS
(12) (19)(20)

20-pin connector

2
3
7
5
4

Red
Red/white
black
Green/white
Green

Converter (9-pin)
2
3
5
7
8

RD(RXD) (1)
(6)
SD(TXD)
GND(SG)
Front
RS(RTS)
(5)
(9)
CS(CTS)
D-Sub9pin
Connectors
Female mould

* The signal name at converter side is the signal name of output target.

26-106

- VT3 Series and DT Series PLC Connection Manual -

26-11 Connection with Converters

Wiring diagram 2 (OP-26486+OP-24025(5m), OP-24045(1m))


VT3PORT3(9-pin)

Converter (9-pin)

TXD

2 RD(RXD)

RXD

3 SD(TXD)

Front view GND

5 GND(SG)

CTS
RTS

7
8

7 RS(RTS)
8 CS(CTS)

(1)

(6)

(5)

(9)

D-Sub9 pin
Connectors
Female mould

(1)

(6)
Front view

(5)

(9)

D-Sub9 pin
Connectors
Female mould

* The signal name at converter side is the signal name of output target.

26

Wiring diagram H20 (RS-232C)


VT3 (CN2A)
RS-422A RS-485
TMCTMR
ON
OFF
1

TXD
RXD
SG
RTS
CTS

EXTERNAL EQUIPMENT CONNECTION

OP-87191: 3m, OP-87192: 5m, OP-87193: 10m


Converter (9-Pin)

Orange (dot: black 1


Orange (dot: black 3
Orange (no dot)
Orange (dot: red 1
Orange (dot: red 3

2
3
5
7
8

RD(RXD)
SD(TXD)
GND(SG)
RS(RTS)
CS(CTS)

Shielded
* Signal name of the inverter is changed to signal name of
the output destination.

Wiring diagram R1 (RS-232C:VT-C5R1)


VT3-V7R (CN2)
RS-422A

RS-485

TMC TMR
ON
OFF
1

TXD
RXD
SG
DSR
CTS
RTS

1
2
9
5
4
3

Converter (9-pin)

Red

2 RD(RXD)
3 SD(TXD)
5 GND(SG)

Red/white
Light blue
Yellow
Green/white
Green

7 RS(RTS)
8 CS(CTS)
Shielded

Reference

For the pin No. of connectors at one side of VT3/DT series, refer to the chapters in the Appendix.

- VT3 Series and DT Series PLC Connection Manual -

26-107