Beruflich Dokumente
Kultur Dokumente
Identifying
Mechanical
Deformations
User-friendly
transformer testing
Sunday C. Palabrica
Application
29
measurement?
transformer diagnostics?
decisions.
results ourselves.
FRAnalyzer
The FRAnalyzer (Frequency Response Analyzer) was developed
Key features
>> Extremely small and compact device (< 1.8 kg/4 lbs)
30 Application
rating are around 25 years old and were operated for extended periods of
time under full load conditions. The high-voltage motors of the boiler feed
pumps are an important component in the steam circuit. "The key here is to
ments gathered over a long period of time, the energy supplier has deter-
mined threshold values which the service teams can now use as a guide to
assess the operating condition of the motors. The results of essentially three
tests are compiled to create a priority list, based on which the motors are
ultimately maintained. The three main measured factors are the polarization
index (PI), the dissipation factor (Tan Delta) and the partial discharge (PD)
level.
Decision-making matrix based on three measurements
The decision-making matrix was developed to summarize the three tests
to allow management to understand the priorities. The colors red, yellow,
blue and green were used to highlight priority motors. How the colors are
selected from the detailed tests is summarized below.
Polarization index
(PI)
Dissipation factor
(Tan Delta)
Partial discharges
(in nC at 11 kV)
Motor
red
white
blue
red
white
blue
red
white
blue
3-EFP-1
11.5
12.8
12.2
0.82
0.83
0.81
120
20
250
1-EFP-3
10.4
9.7
10.0
1.37
0.79
0.80
27
17
14
3-IDF-1
5.2
5.5
5.4
0.28
0.27
0.28
Application
Decision-making matrix
Rating
Polarization
Dissipation fac-
Partial dischar-
index (PI)
Critical
>10
>0.65
>40
Poor
>7.5 <10
>0.5 <0.65
>20 <40
Adequate
>6 <7.5
>0.4 <0.5
>10 <20
Good
<6
<0.4
<10
assessment, we decided to use the value calculated from the difference between the two measured results," comments Rob Saggers.
"As long as this difference value (Delta Tan Delta) is less than 0.5,
we consider the condition of the motor to be adequate (blue color).
However, we class any value greater than 0.65 as critical (red color)."
Polarization index and partial discharges
Similar considerations were also applied when assessing the measurement results of the polarization index and the partial discharges.
"We developed the decision-making criteria based on our own experience and together with external experts," Rob Saggers comments.
In the concept employed at Loy Yang Power, a polarization index of
less than 7.5 is still considered acceptable, but any value higher than
10 is classed as critical. A Partial Discharge level of up to 20 nanocoulombs (nC) is considered okay, but a level higher than 40 nC is
classed as critical.
Proven system
Some 34 motors were tested and assessed in the first cycle. Based
on the results, Rob Saggers drafted a priority list from the detailed test report for management. The highest priority motor was
replaced with the existing spare motor, inspected and overhauled.
The inspection of this motor brought to light both missing and
broken slot wedges, as well as insulation that had been damaged
due to the age and operation conditions of the motor. "Boiler feed
Rob Saggers
been upgraded from 500 MW to 580 MW, which has also resulted
in the boiler feed pump motors running near or over their nameplate
rating," explains Rob Saggers. Failure of the boiler feed pump motor
was prevented and saved Loy Yang Power an estimated lost revenue
devices.
Versatile
Loy Yang Power also employs the same devices to test its transform-
ers and generators. Rob Saggers is delighted with the results here:
the system which not so long ago would only have been possible
hemisphere.
31
www.loyyangpower.com.au