RTU7 IEC 60870-5-101/104 Interoperability list

Physical layer
1. IEC 60870-5-101
Baud rate: 9600 bps, even parity, one stop bit in both directions (control and monitor).
2. IEC 60870-5-104
Ethernet 802.3
GPRS

Link layer
Link layer settings are valid only for IEC 60870-5-101.
Link transmission procedure
Balanced transmission
X

Unbalanced transmission

Address field of the link


Not present (balanced transmission only)
X

One octet

Two octets
Structured

Unstructured

Frame length
255 Maximum length of frame

All ASDUs are assigned to class 2. Class 1 is not used.

Application layer
Transmission mode for application data
Common address of ASDU
One octet
X

Two octets

Information object address


One octet
Two octets
X

Three octets

Structured
Unstructured

Cause of transmission
One octet
X

Two octet s (with originator address) Originator address is set to zero if not used

Length of APDU
253 Maximum length of APDU per system

Selection of standard ASDUs


Used ASDUs are market by X.
Process information in monitor direction
X

Single-point information

M_SP_NA_1

Single-point information with time tag

M_SP_TA_1

Double-point information

M_DP_NA_1

Double-point information with time tag

M_DP_TA_1

Step position information

M_ST_NA_1

Step position information with time tag

M_ST_TA_1

Bitstring of 32 bit

M_BO_NA_1

Bitstring of 32 bit with time tag

M_BO_TA_1

Measured value, normalized value

M_ME_NA_1

10

Measured value, normalized value with time tag

M_ME_TA_1

11

Measured value, scaled value

M_ME_NB_1

12

Measured value, scaled value with time tag

M_ME_TB_1

13

Measured value, short floating point value

M_ME_NC_1

14

Measured value, short floating point value with time tag

M_ME_TC_1

15

Integrated totals

M_IT_NA_1

16

Integrated totals with time tag

M_IT_TA_1

17

Event of protection equipment with time tag

M_EP_TA_1

18

Packet start events of protection equipment with time tag

M_EP_TB_1

19

Packed output circuit information of protection equipment with time tag

M_EP_TC_1

20

Packed single-point information with status change detection

M_SP_NA_1

21

Measured value, normalized value without quality descriptor

M_ME_ND_1

30

Single-point information with time tag CP56Time2a

M_SP_TB_1

31

Double-point information with time tag CP56Time2a

M_DP_TB_1

32

Step position information with time tag CP56Time2a

M_ST_TB_1

33

Bitstring of 32 bit with time tag CP56Time2a

M_BO_TB_1

34

Measured value, normalized value with time tag CP56Time2a

M_ME_TD_1

35

Measured value, scaled value with time tag CP56Time2a

M_ME_TE_1

36

Measured value, short floating point value with time tag CP56Time2a

M_ME_TF_1

37

Integrated totals with time tag CP56Time2a

M_IT_TB_1

38

Event of protection equipment with time tag CP56Time2a

M_EP_TD_1

39

Packet start events of protection equipment with time tag CP56Time2a

M_EP_TE_1

40

Packed output circuit information of protection equipment with time tag CP56Time2a M_EP_TF_1

System information in control direction


X

45

Single command

C_SC_NA_1

46

Double command

C_DC_NA_1

47

Regulating step command

C_RC_NA_1

48

Set point command, normalized value

C_SE_NA_1

49

Set point command, scaled value

C_SE_NB_1

50

Set point command, short floating point value

C_SE_NC_1

51

Bitstring of 32 bit

C_BO_NA_1

58

Single command with time tag CP56Time2a

C_SC_TA_1

59

Double command with time tag CP56Time2a

C_DC_TA_1

60

Regulating step command l with time tag CP56Time2a

C_RC_TA_1

61

Set point command , normalized value with time tag CP56Time2a

C_SE_TA_1

62

Set point command, scaled value with time tag CP56Time2a

C_SE_TB_1

63

Set point command short floating point value s asem CP56Time2a

C_SE_TC_1

64

Bitstring of 32 bit with time tag CP56Time2a

C_BO_TA_1

System information in monitor direction


X

70

End of initialization

M_EI_NA_1

System information in control direction


X

100 Interrogation command

C_IC_NA_1

101 Counter interrogation command

C_CI_NA_1

102 Read command

C_RD_NA_1

103 Clock synchronization

C_CS_NA_1

104 Test command

C_TS_NA_1

105 Reset process command

C_RP_NA_1

106 Delay acquisition command

C_CD_NA_1

107 Test command with time tag CP56Time2a

C_TS_TA_1

Parameter in control direction


110 Parameter of measured value, normalized value

P_ME_NA_1

111 Parameter of measured value, scaled valued

P_ME_NB_1

112 Parameter of measured value, short floating point value

P_ME_NC_1

113 Parameter activation

P_AC_NA_1

File transfer
120 File ready

F_FR_NA_1

121 Section ready

F_SR_NA_1

122 Call directory, select file, call file, call section

F_SC_NA_1

123 Last section, last segment

F_LS_NA_1

124 Ack file, ack section

F_AF_NA_1

125 Segment

F_SG_NA_1

126 Directory {blank or X, only available in monitor (standard) direction}

F_DR_TA_1

Basic application function


Station initialization
Remote initialization

Cyclic data transfer


Cyclic data transfer

Read procedure
Read procedure

Spontaneous transmission
X

Spontaneous transmission

Double transmission of information objects with cause of transmission spontaneous


Not used.
Station interrogation
X

Global
Group1 to 16

Clock synchronization
X

Clock synchronization

Day of week used


RES1, GEN (time tag substituted/not substituted) used

SU-bit (summer time) used

Command transmission
X

Direct command transmission

Direct set point command transmission

Select and execute command


Select and execute set point command

C_SE_ACTTERM used

No additional definition

Short-pulse duration

Long-pulse duration

Persistent output

Transmission of integrated totals


Not used.

Parameter loading
Not used.
Parameter activation
Not used.
Test procedure
X

Test procedure

File transfer
Not used.
Background scan
Not used.
Acquisition of transmission delay
Not used.
Port number
It is valid only for IEC 60870-5-104.
2404 Port number

Definitions of time outs


It is valid only for IEC 60870-5-104.
Parameter

Default
value

t0

30 s

Time-out of connection establishment

30 s

t1

15 s

Time-out of send or test APDUs

30 s

t2

10 s

Time-out for acknowledges in case of no data messages t2 < t1

10 s

t3

20 s

Time-out for sending test frames in case of long idle state

30 s

Remarks

Selected
value

Maximum number of outstanding I format APDUs k and the latest acknowledge (w)
It is valid only for IEC 60870-5-104.
Parameter

Default
value

12 APDUs

Maximum difference receive sequence number to send state

12 APDUs

8 APDUs

Latest acknowledge after receiving w I format APDUs

8 APDUs

Remarks

Selected
value