Air System Sizing Summary for UMA-14 Ok

Project Name: NOGALES MARCO


Prepared by:

01/03/2015
10:17p.m.

Air System Information


Air System Name ....................................... UMA-14 Ok
Equipment Class ............................................ CW AHU
Air System Type ................................................ SZCAV

Number of zones ............................................................. 1


Floor Area ............................................................... 5388.0 ft
Location ................................................ Nogales, Mexico

Sizing Calculation Information


Calculation Months ..................................... Jan to Dec
Sizing Data .................................................. Calculated

Zone CFM Sizing ................. Sum of space airflow rates


Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load .......................................................... 41.9
Total coil load ........................................................ 503.0
Sensible coil load ................................................. 272.4
Coil CFM at Jul 1400 ............................................. 8791
Max block CFM ..................................................... 8791
Sum of peak zone CFM ........................................ 8791
Sensible heat ratio ............................................... 0.542
ft/Ton ................................................................... 128.5
BTU/(hr-ft) ............................................................. 93.4
Water flow @ 10.0 F rise .................................. 100.66

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at ..................................................... Jul 1400


OA DB / WB ...................................................... 98.0 / 78.7
Entering DB / WB ............................................. 91.5 / 74.9
Leaving DB / WB .............................................. 58.6 / 57.4
Coil ADP ..................................................................... 55.0
Bypass Factor .......................................................... 0.100
Resulting RH ................................................................. 56
Design supply temp. ................................................... 58.0
Zone T-stat Check .................................................... 1 of 1
Max zone temperature deviation .................................. 0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load ........................................................ 186.5
Coil CFM at Des Htg ............................................. 8791
Max coil CFM ........................................................ 8791
Water flow @ 20.0 F drop ................................... 18.66

MBH
CFM
CFM
gpm

Load occurs at ..................................................... Des Htg


BTU/(hr-ft) ................................................................. 34.6
Ent. DB / Lvg DB .............................................. 47.5 / 70.0 F

Supply Fan Sizing Data


Actual max CFM .................................................... 8791 CFM
Standard CFM ....................................................... 7687 CFM
Actual max CFM/ft ................................................. 1.63 CFM/ft

Outdoor Ventilation Air Data

Fan motor BHP ........................................................... 0.00 BHP


Fan motor kW .............................................................. 0.00 kW
Fan static ..................................................................... 0.00 in wg
CFM/person .............................................................. 80.13 CFM/person

Design airflow CFM ............................................... 6170 CFM


CFM/ft ................................................................... 1.15 CFM/ft

Hourly Analysis Program v4.80

Page 1 of 7

Zone Sizing Summary for UMA-14 Ok


Project Name: NOGALES MARCO
Prepared by: IPD

01/03/2015
10:17p.m.

Air System Information


Air System Name ....................................... UMA-14 Ok
Equipment Class ............................................ CW AHU
Air System Type ................................................ SZCAV

Number of zones ............................................................. 1


Floor Area ............................................................... 5388.0 ft
Location ................................................ Nogales, Mexico

Sizing Calculation Information


Calculation Months ..................................... Jan to Dec
Sizing Data .................................................. Calculated

Zone CFM Sizing ................. Sum of space airflow rates


Space CFM Sizing ............. Individual peak space loads

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
141.1

Design
Minimum
Airflow
Airflow
(CFM)
(CFM)
8791
8791

Maximum
Heating
Time of
Load
Peak Load
(MBH)
Jan 2300
0.0

Zone
Floor
Area
(ft)
5388.0

Zone
CFM/ft
1.63

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows
Zone Name /
Space Name
Zone 1
UMA-14 Lab Clinico

Hourly Analysis Program v4.80

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

141.1

Jan 2300

8791

0.0

5388.0

1.63

Page 2 of 7

Ventilation Sizing Summary for UMA-14 Ok


Project Name: NOGALES MARCO
Prepared by: IPD

01/03/2015
10:17p.m.

1. Summary
Ventilation Sizing Method ...................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................... 6170 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
UMA-14 Lab Clinico
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.80

Mult.

Floor
Area
(ft)

Maximum
Occupants

5388.0

77.0

Maximum
Required
Supply Air Outdoor Air
(CFM) (CFM/person)
8790.7
8790.7

0.00

Required
Outdoor Air
(CFM/ft)
0.00

Required
Required
Outdoor Air Outdoor Air
(CFM) (% of supply)
6170.0

0.0

Uncorrected
Outdoor Air
(CFM)
6170.0
6170.0

Page 3 of 7

Air System Design Load Summary for UMA-14 Ok


Project Name: NOGALES MARCO
Prepared by: IPD

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Central Heating Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.80

01/03/2015
10:17p.m.

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1400
HEATING DATA AT DES HTG
COOLING OA DB / WB 98.0 F / 78.7 F
HEATING OA DB / WB 38.0 F / 31.7 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
0 ft
0
0 ft
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
12123 W
41363
0
0
5000 W
17060
0
0
17000 W
58004
0
0
77
22715
35035
0
0
0
0
0
0
0
2000
0
0
0
0% / 0%
0
0
0%
0
0
141141
35035
0
0
144399
35035
0
0
0%
0
0
0
0%
0
0
0
0%
0
0
0
8791 CFM
0
8791 CFM
0
6170 CFM
128020
195560
6170 CFM
186474
0
8791 CFM
0
8791 CFM
0
0
0
0%
0
0%
0
272419
230595
186474
0
272419
230606
0
0
0
186474
272419
230606
186474
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 4 of 7

System Psychrometrics for UMA-14 Ok


Project Name: NOGALES MARCO
Prepared by: IPD

01/03/2015
10:17p.m.

July DESIGN COOLING DAY, 1400


TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
98.0
91.5
58.6
58.6
58.6
58.6
76.0
76.0

Specific
Humidity
(lb/lb)
0.01983
0.01755
0.01123
0.01123
0.01123
0.01123
0.01219
0.01219

Airflow
(CFM)
6170
8791
8791
8791
8791
8791
8791
8791

CO2 Level
(ppm)
400
477
477
477
477
477
658
658

Sensible
Heat
(BTU/hr)
128020
272419
0
0
144399
0

Latent
Heat
(BTU/hr)
195560
230606
35035
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.944 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4150.9 BTU/(hr-CFM)
Site Altitude = 3664.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
141141

Zone
T-stat
Cond
Mode (BTU/hr)
Cooling
144399

Zone
Temp
(F)
76.0

Zone
Airflow
(CFM)
8791

CO2
Level
(ppm)
658

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 5 of 7

System Psychrometrics for UMA-14 Ok


Project Name: NOGALES MARCO
Prepared by: IPD

01/03/2015
10:17p.m.

WINTER DESIGN HEATING


TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
38.0
47.5
47.5
70.0
70.0
70.0
70.0
70.0

Specific
Humidity
(lb/lb)
0.00284
0.00284
0.00284
0.00284
0.00284
0.00284
0.00284
0.00284

Airflow
(CFM)
6170
8791
8791
8791
8791
8791
8791
8791

CO2 Level
(ppm)
400
403
403
403
403
403
411
411

Sensible
Heat
(BTU/hr)
-186474
0
186474
0
0
0

Latent
Heat
(BTU/hr)
0
0
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.944 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4150.9 BTU/(hr-CFM)
Site Altitude = 3664.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
0

Zone
T-stat
Cond
Mode (BTU/hr)
Deadband
0

Zone
Temp
(F)
70.0

Zone
Airflow
(CFM)
8791

CO2
Level
(ppm)
411

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 6 of 7

Psychrometric Analysis for UMA-14 Ok


Project Name: NOGALES MARCO
Prepared by: IPD

01/03/2015
10:17p.m.

Location: Nogales, Mexico


Altitude: 3664.0 ft.
Data for: July DESIGN COOLING DAY, 1400
1
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Room Air

0.020

0.018
0.016

S p e c i f i c H u m i d i t y ( l b /l b )

0.014
5

0.012

34

0.010
0.008
0.006
0.004
0.002
0.000
30

Hourly Analysis Program v4.80

40

50

60
70
Temperature ( F )

80

90

100

Page 7 of 7