Sie sind auf Seite 1von 45

TRANSFORMASI LAPLACE

[f(t)] F(s)

f(t).e
0

A. Fungsi Step
F(t) = 0 untuk t < 0
= A untuk t > 0
A
0

A
F(s) A.e st .dt e st |
0
s
0
=

A
(0 1)
s

A
s

B. Fungsi Pulse
F(t) = 0 untuk t < 0 & t >T
= A untuk 0 t T
A
0

F(s) f(t).e st .dt


0

st

.dt

A.e st .dt
0
A
.e st | T
0
s
A
(e st 1)
s
A
(1 e st )
s
Fungsi Unit Step : f(t) = 1 (t) F(s) = 1/s
C. Fungsi Impulse

f(t)

A
lim
to 0 to

=0

F(s)

untuk 0 < t < to


untuk t < 0 & to < t

st
A
o)
lim
(1 e
t
s
t 0
0

d
[A(1 e sto )]
lim dto
d
to 0
(tos)
dto
A
s
s
=A
Fungsi Unit-Impulse : f(t) = (t)
F(s) = 1
D. Fungsi Ramp

F(t) = 0 untuk t < 0


= At untuk t 0
A
0

F(s) A.t.e st .dt


0

A t.e- st .dt
0
e st A.e st
A.t.
|
dt
s 0 0 s
A st

.dt
e
s 0
A

s2
E. Fungsi Eksponensiil
F(t) = o untuk t < 0
= A e t untuk t 0

F(s)

A.e t .e st .dt
0
( s)t
Ae
.dt
0
A (s )t

e
|
0
s
A

(0 1)
s
A

F. Fungsi Sinus
f(t) = A sin t


F(s) A.sin.si st .dt
0
e jt e jt
A.
.e st dt
2j
0
A jt st
jt st

e
.e
)dt
(e .e
2j 0
A (j s)t
(j s)t

e
)dt
(e
2j 0
A 1
1
(j s)t
(j s)t
[
e

e
]
0
2j j s
j s
A 1
1
[

]
2j s j s j
A s j s j
.
2j
s 2 2

A. 2
s 2
G. Fungsi Cosinus
f(t) = A cos t
F(s) = A.

s
s 2
2

DEFINISI SPESIFIKASI RESPONS TRANSIENT


1. Delay time (td)
2. Rise time (tr)
3. Peak time (tp)
4. Maximum overshoot (Mp)
5. Settling time (ts)

KURVA RESPONS UNIT STEP


Delay time (td)

: waktu yang diperlukan untuk mencapai setengah dari nilai akhir pada waktu pertama
kali

Rise time (tr)

: waktu yang diperlukan untuk naik dari 10 90%, 5 55%, atau 0 100% dari nilai
akhirnya.
Untuk sistem underdamped : 0 100%
Untuk sistem overdamped : 10 90%

Peak time (tp)

: waktu yang diperlukan untuk mencapai peak pertama dari overshoot.

Maximum overshoot (Mp,%) : nilai puncak (peak) maksimum dari kurva respons yang diukur dari satu.
Maximum per cent overshoot = c(tp) c(~)
c(~)
Settling time

x 100%

: waktu yang diperlukan untuk mencapai dan tetap di dalam sebuah range nilai akhir
yang ditetapkan oleh persentase absolut dari nilai akhir (biasanya 5% atau 2%).

Diinginkan respons transient :

- cukup cepat

- cukup memiliki redaman


(aplikasi : osilasi tidak dapat ditoleransi)

Respons transient yang diinginkan dari sistem orde kedua :


faktor redaman : antara 0,4 dan 0,8

Mendapatkan nilai dari tr, tp, Mp, dan ts


A.

RISE TIME (tr) :


sin d t)

c(t) = 1 e -n t( cosdt +

1 2
t = tr c(tr) = 1, maka:
c(tr) = 1 e -n tr( cosdtr +

sin d tr)

1 2
karena e -n tr 0 maka :
cos d tr +

sin d tr = 0

1 2

atau
tan d tr = -

1 2

DEFINISI SUDUT :

atau
tan d tr

Jadi,
tr =

1

tan 1 ( d )

d
d

= _

POLE-POLE KOMPLEKS :

GARIS-GARIS FAKTOR REDAMAN KONSTAN


= cos

B.

PEAK TIME (tp) :


= (sin d tp)

dc

e-n tp = 0

1-

dt t = tp

sin d tp = 0
d tp = 0, , 2, 3,
d tp =
tp =
d

C.

MAXIMUM OVERSHOOT (Mp) :


Mp = c(tp) 1
= - e-n( / d) (cos +

sin )
1 2

-( / d)

e-(/

1-2 )

Maximum Overshoot (%) = e-( / d) x 100%


D.

SETTLING TIME :
e-nt
c(t) = 1 1-

sin (dt + tan-1 1 - 2 )

Kurva-kurva 1 ( e-nt /

(t 0)

1 - 2 ) :

Menutupi kurva respons transient untuk sebuah input unit-step.


Time constant (T) dari kurva-kurva tersebut adalah

1
n

KURVA SETTLING TIME ts vs

untuk 0 < < 0,9 : ts = 4T = 4 =


4

n
ts = 3T = 3 =
3
n

(band toleransi 2%)


(band toleransi 5%)

untuk nilai lebih besar, ts meningkat hampir linier; dan nilai min = 0,76 ( un-tuk 2%)
atau min = 0,68 (untuk 5%)

Nilai biasanya ditentukan dari syarat maksimum overshoot yang diijinkan. Sedangkan
settling time (ts) ditentukan terutama oleh undamped natural frequency (n).

Hal ini berarti, durasi periode transient dapat tanpa mengubah overshoot maksi-mum, yaitu
dengan mengatur n.

Untuk mendapatkan respons yang cepat : n harus besar. Untuk membatasi overshoot
maksimum (Mp) dan membuat ts kecil : seharusnya tidak terlalu kecil.

Faktor redaman di antara 0,4 dan 0,8, maka overshoot maksimum (%) untuk step respons
adalah di antara 25% dan 2,5%.

Kurva Mp versus :
2
n
s(s2 )
n

Contoh :
R(s)

E(s)

C(s)

Sistem orde ke dua memiliki harga : = o,6 dan n = 5 rad/sec


Apabila sistem diberikan input unit step, carilah rise time (t r), peak time (tp), maksimum overshoot (Mp),
dan settling time (ts) !
Penyelesaian :
d

1 2

5 1 (0,6)2
=4

= . n = 0,6 . 5 = 3

Rise time (tr)

= tan -1

= tan-1 (4 / 3)

= 0,93 rad
tr =

3,14 0,93
4

= 0,55 sec
Peak Time (tp) =

3,14
= 4 0,785 sec
d

Maximum Overshoot (Mp) =

(/ )
d

(3/4)x3,14

= 0,095
= 0,095 x 100%
= 95 %
Setting time (Ts) =

4 4
1,33 sec (u/ kriteria 2%)
3

3 3
1 sec (untuk kriteria 5%)
3

Example 5.1.1 A simple analogy of a control system


In the process example shown (Figure 5.1.1), the operator manually varies the flow of water by opening or closing an
inlet valve to ensure that:

The water level is not too high; or it will run to waste via the overflow.
The water level is not too low; or it will not cover the bottom of the tank.

The outcome of this is that the water runs out of the tank at a rate within a required range. If the water runs out at too
high or too low a rate, the process it is feeding cannot operate properly.
At an initial stage, the outlet valve in the discharge pipe is fixed at a certain position.
The operator has marked three lines on the side of the tank to enable him to manipulate the water supply via the inlet
valve. The 3 levels represent:
1.
2.

The lowest allowable water level to ensure the bottom of the tank is covered.
The highest allowable water level to ensure there is no discharge through the overflow.

3.

The ideal level between 1 and 2.

The Example (Figure 5.1.1) demonstrates that:


1. The operator is aiming to maintain the water in the vessel between levels 1 and 2. The water level is called
the Controlled condition.
2. The controlled condition is achieved by controlling the flow of water through the valve in the inlet pipe. The
flow is known as the Manipulated Variable, and the valve is referred to as the Controlled Device.
3.

The water itself is known as the Control Agent.

4.

By controlling the flow of water into the tank, the level of water in the tank is altered. The change in water
level is known as the Controlled Variable.

5.

Once the water is in the tank it is known as the Controlled Medium.

6.

The level of water trying to be maintained on the visual indicator is known as the Set Value (also known as
the Set Point).

7.

The water level can be maintained at any point between 1 and 2 on the visual indicator and still meet the
control parameters such that the bottom of the tank is covered and there is no overflow. Any value within this
range is known as the Desired Value.

8.

Assume the level is strictly maintained at any point between 1 and 2. This is the water level at steady state
conditions, referred to as the Control Value or Actual Value.
Note: With reference to (7) and (8) above, the ideal level of water to be maintained was at point 3. But if the
actual level is at any point between 1 and 2, then that is still satisfactory. The difference between the Set
Point and the Actual Value is known as Deviation.

9.

If the inlet valve is closed to a new position, the water level will drop and the deviation will change. A
sustained deviation is known as Offset.

It is worth repeating these points in a slightly different way to reinforce Example 5.1.2:
In simple terms the operator's aim in Example 5.1.1 is to hold the water within the tank at a pre-defined level.
Level 3 can be considered to be his target or Set Point.
The operator physically manipulates the level by adjusting the inlet valve (the control device). Within this
operation it is necessary to take the operator's competence and concentration into account. Because of this, it is
unlikely that the water level will be exactly at Level 3 at all times. Generally, it will be at a point above or below
Level 3. The position or level at any particular moment is termed the Control Value or Actual Value.
The amount of error or difference between the Set Point and the Actual Value is termed deviation. When a
deviation is constant, or steady state, it is termed Sustained Deviation or Offset.

Summary of terminology

Basic Controller
The Basic Controller for an application can be visualized as

The controller consists of

a measuring unit with an appropriate instrument to measure the state of process, a


temperature transmitter, pressure transmitter or similar.
a input set point device to set the desired value.

a comparator for comparing the measured value with the set point, calculating the
difference or error between the two.

a control unit to calculate the output magnitude and direction to compensate the
deviation from the desired value.

a output unit converting the output from the controller to physical action, a control valve,
a motor or similar.

Modes of control
An automatic temperature control might consist of a valve, actuator, controller and sensor detecting the space
temperature in a room. The control system is said to be 'in balance' when the space temperature sensor does not
register more or less temperature than that required by the control system. What happens to the control valve when
the space sensor registers a change in temperature (a temperature deviation) depends on the type of control system
used. The relationship between the movement of the valve and the change of temperature in the controlled medium
is known as the mode of control or control action.
There are two basic modes of control:

On/Off - The valve is either fully open or fully closed, with no intermediate state.
Continuous - The valve can move between fully open or fully closed, or be held at any intermediate position.

Variations of both these modes exist, which will now be examined in greater detail.

On/off control
Occasionally known as two-step or two-position control, this is the most basic control mode. Considering the tank of
water shown in Figure 5.2.1, the objective is to heat the water in the tank using the energy given off a simple steam
coil. In the flow pipe to the coil, a two port valve and actuator is fitted, complete with a thermostat, placed in the water
in the tank.

Fig. 5.2.1 On/off


temperature control of water in a tank
The thermostat is set to 60C, which is the required temperature of the water in the tank. Logic dictates that if the
switching point were actually at 60C the system would never operate properly, because the valve would not know
whether to be open or closed at 60C. From then on it could open and shut rapidly, causing wear.
For this reason, the thermostat would have an upper and lower switching point. This is essential to prevent over-rapid
cycling. In this case the upper switching point might be 61C (the point at which the thermostat tells the valve to shut)
and the lower switching point might be 59C (the point when the valve is told to open). Thus there is an in-built
switching difference in the thermostat of 1C about the 60C set point.
This 2C (1C) is known as the switching differential. (This will vary between thermostats). A diagram of the
switching action of the thermostat would look like the graph shown in Figure 5.2.2. The temperature of the tank
contents will fall to 59C before the valve is asked to open and will rise to 61C before the valve is instructed to close.

Fig. 5.2.2 On/off switching action of the


thermostat
Figure 5.2.2 shows straight switching lines but the effect on heat transfer from coil to water will not be immediate. It
will take time for the steam in the coil to affect the temperature of the water in the tank. Not only that, but the water in
the tank will rise above the 61C upper limit and fall below the 59C lower limit. This can be explained by cross
referencing Figures 5.2.2 and 5.2.3. First however it is necessary to describe what is happening.
At point A (59C, Figure 5.2.3) the thermostat switches on, directing the valve wide open. It takes time for the transfer
of heat from the coil to affect the water temperature, as shown by the graph of the water temperature in Figure 5.2.3.
At point B (61C) the thermostat switches off and allows the valve to shut. However the coil is still full of steam, which
continues to condense and give up its heat. Hence the water temperature continues to rise above the upper switching
temperature, and 'overshoots' at C, before eventually falling.

Fig. 5.2.3 Tank temperature


versus time
From this point onwards, the water temperature in the tank continues to fall until, at point D (59C), the thermostat
tells the valve to open. Steam is admitted through the coil but again, it takes time to have an effect and the water
temperature continues to fall for a while, reaching its trough of undershoot at point E.
The difference between the peak and the trough is known as the operating differential. The switching differential of
the thermostat depends on the type of thermostat used. The operating differential depends on the characteristics of
the application such as the tank, its contents, the heat transfer characteristics of the coil, the rate at which heat is
transferred to the thermostat, and so on.
Essentially, with on/off control, there are upper and lower switching limits, and the valve is either fully open or fully
closed - there is no intermediate state.
However, controllers are available that provide a proportioning time control, in which it is possible to alter the ratio of
the 'on' time to the 'off' time to control the controlled condition. This proportioning action occurs within a selected
bandwidth around the set point; the set point being the bandwidth mid point.
If the controlled condition is outside the bandwidth, the output signal from the controller is either fully on or fully off,
acting as an on/off device. If the controlled condition is within the bandwidth, the controller output is turned on and off
relative to the deviation between the value of the controlled condition and the set point.
With the controlled condition being at set point, the ratio of 'on' time to 'off' time is 1:1, that is, the 'on' time equals the
'off' time. If the controlled condition is below the set point, the 'on' time will be longer than the 'off' time, whilst if above
the set point, the 'off' time will be longer, relative to the deviation within the bandwidth.
The main advantages of on/off control are that it is simple and very low cost. This is why it is frequently found on
domestic type applications such as central heating boilers and heater fans.
Its major disadvantage is that the operating differential might fall outside the control tolerance required by the
process. For example, on a food production line, where the taste and repeatability of taste is determined by precise
temperature control, on/off control could well be unsuitable.
By contrast, in the case of space heating there are often large storage capacities (a large area to heat or cool that will
respond to temperature change slowly) and slight variation in the desired value is acceptable. In many cases on/off
control is quite appropriate for this type of application.
If on/off control is unsuitable because more accurate temperature control is required, the next option is continuous
control.

1. AKSI KONTROL ON-OFF / 2 POSISI

Untuk mencegah terlalu banyaknya operasi mekanis on-off.


Aplikasi : Sistem kontrol level cairan

Continuous control
Continuous control is often called modulating control. It means that the valve is capable of moving continually to
change the degree of valve opening or closing. It does not just move to either fully open or fully closed, as with on-off
control.
There are three basic control actions that are often applied to continuous control:

Proportional (P)

Integral (I)

Derivative (D)

It is also necessary to consider these in combination such as P + I, P + D, P + I + D. Although it is possible to


combine the different actions, and all help to produce the required response, it is important to remember that both the
integral and derivative actions are usually corrective functions of a basic proportional control action.
The three control actions are considered below.

Proportional Controller (P-Controller)


This is the most basic of the continuous control modes and is usually referred to by use of the letter 'P'. The principle
aim of proportional control is to control the process as the conditions change.

One of the most used controllers is the Proportional Controller (P-Controller) who produce an
output action that is proportional to the deviation between the set point and the measured
process value.
OP = -kP Er

(1)

where
OP = output proportional controller
kP = proportional gain or action factor of the controller
Er = error or deviation between the set point value and the measured value
The gain or action factor - kP

influence on the output with a magnitude of kP


determines how fast the system responds. If the value is too large the system will be in
danger to oscillate and/or become unstable. If the value is too small the system error or
deviation from set point will be very large.
can be regarded linear only for very small variations.

The gain kP can be expressed as


kP = 100 / P

(1b)

where
P = proportional band
The proportional band P, express the value necessary for 100% controller output. If P = 0, the
gain or action factor kP would be infinity - the control action would be ON/OFF.
Note! A proportional controller will have the effect of reducing the rise time and will reduce, but
never eliminate, the steady-state error.

This section shows that:

The larger the proportional band, the more stable the control, but the greater the offset.
The narrower the proportional band, the less stable the process, but the smaller the offset.

The aim, therefore, should be to introduce the smallest acceptable proportional band that will always keep the
process stable with the minimum offset.
In explaining proportional control, several new terms must be introduced.
To define these, a simple analogy can be considered - a cold water tank is supplied with water via a float operated
control valve and with a globe valve on the outlet pipe valve 'V', as shown in Figure 5.2.4. Both valves are the same
size and have the same flow capacity and flow characteristic. The desired water level in the tank is at point B
(equivalent to the set point of a level controller).
It can be assumed that, with valve 'V' half open, (50% load) there is just the right flowrate of water entering via the
float operated valve to provide the desired flow out through the discharge pipe, and to maintain the water level in the
tank at point at B.
The questions these people ask about steam are markedly different.

Fig. 5.2.4 Valve 50%


open
The system can be said to be in balance (the flowrate of water entering and leaving the tank is the same); under
control, in a stable condition (the level is not varying) and at precisely the desired water level (B ); giving the required
outflow.
With the valve 'V' closed, the level of water in the tank rises to point A and the float operated valve cuts off the water
supply (see Figure 5.2.5 below).
The system is still under control and stable but control is above level B. The difference between level B and the actual
controlled level, A, is related to the proportional band of the control system.
Once again, if valve 'V' is half opened to give 50% load, the water level in the tank will return to the desired level,
point B.

Fig. 5.2.5 Valve closed


This means the system is simpler and less expensive than, for example, a high temperature hot water system. The
high efficiency of steam plant means it is compact and makes maximum use of space, something which is often at a
premium within plant.
Furthermore, upgrading an existing steam system with the latest boilers and controls typically represents 50% of the
cost of removing it and replacing it with a decentralised gas fired system.

Why Not Use A Proportional Controller?


Of all the controllers you can choose to control a system, the proportional
controller is the simplest of them all.

If you want to implement a proportional control system, it's usually the


easiest to implement.
In an analog system, a proportional control system amplifies the error signal
to generatethe control signal. If the error signal is a voltage, and the
control signal is also a voltage, then a proportional controller is just an
amplifier.I
In a digital control system, a proportional control system computes the error
from measured output and user input to a program, and multiplies the error
by a proportional constant, then generates an output/control signal from
that multiplication.

Goals For This Lesson


Proportional control is a simple and widely used method of control for many
kinds of systems. When you are done with this lesson you will need to be able to
use proportional control with some understanding. Your goals are as follows:
Given a system you want to control with a proportional controller,

Identify the system components and their function, including the comparator,
controller, plant and sensor.
Be able to predict how the system will respond using a proportional controller including speed of response, accuracy (SSE) and relative stability.
Be able to use the root locus to make
those predictons.
Be able to use frequency response analysis to make those predictions.

Properties Of Proportional Controllers


Proportional controllers have these properties:

The controller amplifies the error as shown in the block diagram below.
So, the actuating signal (the input to G(s)) is proportional to the error.

In the material that follows, we will examine some of the features of


proportional control using a proportional controller.
In a proportional controller, steady state error tends to depend inversely upon
the proportional gain, so if the gain is made larger the error goes down.
In this system, SSE is given by the expression
SSE = 1/(1 + KpG(0))

As the proportional gain, Kp, is made larger, the SSE becomes smaller. As the
DC loop gain, KpG(0), becomes large, the error approaches becoming inversely
proportional to the proportional gain, Kp. That's true for most of the cases of
interest, that is those with small SSE.

Proportional control has a tendency to make a system faster.

If we think about the root locus for a system with proportional control we can
note the following:

The proportional gain, Kp, is either the root locus gain, or the root locus gain
is proportional to Kp.
The root locus for a first order system will have the form shown below.

There's one pole.


The root locus moves to the left from that pole.

As the pole moves to the left, the time constant becomes smaller.

Higher order systems will not behave in the same way, but there may be
tendencies to speed up the system, at least for some gain values. Here is
the root locus for a second order system.

Persamaan matematis :
u(t) = KP . e(t)
dimana KP : konstanta proporsional
dalam Laplace
U(s)/E(s) = KP
Diagram Blok
Dikenal juga sebagai : gain/penguatan
Pengaruh pada sistem :
Menambah atau mengurangi kestabilan
Dapat memperbaiki respon transien khususnya : rise
time, settling time
Mengurangi (bukan menghilangkan) Error steady state
Catatan : untuk menghilangkan Ess, dibutuhkan KP
besar, yang akan membuat sistem lebih tidak
stabil
Kontroler Proporsional memberi pengaruh langsung
(sebanding) pada error
Semakin besar error, semakin besar sinyal kendali yang
dihasilkan kontroler
Grafik (di Ogata)

2. AKSI KONTROL PROPORTIONAL


m(t) = Kp . e(t)

M(s)
Kp ; Kp = sensitivitas proportional ( gain )
E(s)

Kontroler proportional mempunyai sebuah daerah respons linier.


Proportional band : perubahan dalam error ( persentase dari full-scale error ) yang akan
menyebabkan output untuk pergi dari full-off menuju full-on

Kp

1
proportional band

Q. What does using steam say about the company ?


The use of steam is environmentally responsible. Companies continue to choose steam because it is generated with
high levels of fuel efficiency. Environmental controls are increasingly stringent, even to the extent that organisations
have to consider the costs and methods of disposing of plant before it is installed. All these issues are considered
during the design and manufacture of steam plant.

Fig. 5.2.6 Valve open


The system is under control and stable, but there is an offset; the deviation in level between points B and C. Figure
5.2.7 combines the three conditions used in this example.
The difference in levels between points A and C is known as the Proportional Band or P-band, since this is the
change in level (or temperature in the case of a temperature control) for the control valve to move from fully open to
fully closed.
One recognised symbol for Proportional Band is Xp.
The analogy illustrates several basic and important points relating to proportional control:

The control valve is moved in proportion to the error in the water level (or the temperature deviation, in the
case of a temperature control) from the set point.
The set point can only be maintained for one specific load condition.
Whilst stable control will be achieved between points A and C, any load causing a difference in level to that
of B will always provide an offset.

Fig. 5.2.7 Proportional band


Note: By altering the fulcrum position, the system Proportional Band changes. Nearer the float gives a narrower Pband, whilst nearer the valve gives a wider P-band. Figure 5.2.8 illustrates why this is so. Different fulcrum positions
require different changes in water level to move the valve from fully open to fully closed. In both cases, It can be seen
that level B represents the 50% load level, A represents the 0% load level, and C represents the 100% load level. It
can also be seen how the offset is greater at any same load with the wider proportional band.

Fig.
5.2.8 Demonstrating the relationship between P-band and offset
The examples depicted in Figures 5.2.4 through to 5.2.8 describe proportional band as the level (or perhaps
temperature or pressure etc.) change required to move the valve from fully open to fully closed. This is convenient for
mechanical systems, but a more general (and more correct) definition of proportional band is the percentage change
in measured value required to give a 100% change in output. It is therefore usually expressed in percentage terms
rather than in engineering units such as degrees centigrade.
For electrical and pneumatic controllers, the set value is at the middle of the proportional band. The effect of changing
the P-band for an electrical or pneumatic system can be described with a slightly different example, by using a
temperature control.
The space temperature of a building is controlled by a water (radiator type) heating system using a proportional
action control by a valve driven with an electrical actuator, and an electronic controller and room temperature sensor.
The control selected has a proportional band (P-band or Xp) of 6% of the controller input span of 0 - 100C, and the
desired internal space temperature is 18C. Under certain load conditions, the valve is 50% open and the required
internal temperature is correct at 18C.
A fall in outside temperature occurs, resulting in an increase in the rate of heat loss from the building. Consequently,
the internal temperature will decrease. This will be detected by the room temperature sensor, which will signal the
valve to move to a more open position allowing hotter water to pass through the room radiators.
The valve is instructed to open by an amount proportional to the drop in room temperature. In simplistic terms, if the
room temperature falls by 1C, the valve may open by 10%; if the room temperature falls by 2C, the valve will open
by 20%.

In due course, the outside temperature stabilises and the inside temperature stops falling. In order to provide the
additional heat required for the lower outside temperature, the valve will stabilise in a more open position; but the
actual inside temperature will be slightly lower than 18C.
Example 5.2.1 and Figure 5.2.9 explain this further, using a P-band of 6C.

Example 5.2.1 Consider a space heating application with the following characteristics:
1.
2.

The required temperature in the building is 18C.


The room temperature is currently 18C, and the valve is 50% open.

3.

The proportional band is set at 6% of 100C = 6C, which gives 3C either side of the 18C set point.

Figure 5.2.9 shows the room temperature and valve relationship:

Fig. 5.2.9 Room temperature


and valve relationship - 6C proportional band
As an example, consider the room temperature falling to 16C. From the chart it can be seen that the new valve
opening will be approximately 83%.
With proportional control, if the load changes, so too will the offset:

A load of less than 50% will cause the room temperature to be above the set value.
A load of more than 50% will cause the room temperature to be below the set value.

The deviation between the set temperature on the controller (the set point) and the actual room temperature is called
the 'proportional offset'.
In Example 5.2.1, as long as the load conditions remain the same, the control will remain steady at a valve opening of
83.3%; this is called 'sustained offset'.

The effect of adjusting the P-band


In electronic and pneumatic controllers, the P-band is adjustable. This enables the user to find a setting suitable for
the individual application.
Increasing the P-band - For example, if the previous application had been programmed with a 12% proportional
band equivalent to 12C, the results can be seen in Figure 5.2.10. Note that the wider P-band results in a less steep
'gain' line. For the same change in room temperature the valve movement will be smaller. The term 'gain' is discussed
in a following section.

In this instance, the 2C fall in room temperature would give a valve opening of about 68% from the chart in Figure
5.2.10.

Fig. 5.2.10 Room temperature


and valve relationship - 12C Proportional band
Reducing the P-band - Conversely, if the P-band is reduced, the valve movement per temperature increment is
increased. However, reducing the P-band to zero gives an on/off control. The ideal P-band is as narrow as possible
without producing a noticeable oscillation in the actual room temperature.

Example 5.2.2
Let the input span of a controller be 100C.
If the controller is set so that full change in output occurs over a proportional band of 20% the controller gain is:

Gain
The term 'gain' is often used with controllers and is simply the reciprocal of proportional band.
The larger the controller gain, the more the controller output will change for a given error. For instance for a gain of 1,
an error of 10% of scale will change the controller output by 10% of scale, for a gain of 5, an error of 10% will change
the controller output by 50% of scale, whilst for a gain of 10, an error of 10% will change the output by 100% of scale.
The proportional band in 'degree terms' will depend on the controller input scale. For instance, for a controller with a
200C input scale:
An Xp of 20% = 20% of 200C = 40C
An Xp of 10% = 10% of 200C = 20C

Example 5.2.2
Let the input span of a controller be 100C.
If the controller is set so that full change in output occurs over a proportional band of 20% the controller gain is:

Equally it could be said that the proportional band is 20% of 100C = 20C and the gain is:

Therefore the relationship between P-band and Gain is:

As a reminder:

A wide proportional band (small gain) will provide a less sensitive response, but a greater stability.
A narrow proportional band (large gain) will provide a more sensitive response, but there is a practical limit
to how narrow the Xp can be set.

Too narrow a proportional band (too much gain) will result in oscillation and unstable control.

For any controller for various P-bands, gain lines can be determined as shown in Figure 5.2.11, where the controller
input span is 100C.

Fig.
5.2.11 Proportional band and gain

Reverse or direct acting control signal


A closer look at the figures used so far to describe the effect of proportional control shows that the output is assumed
to be reverse acting. In other words, a rise in process temperature causes the control signal to fall and the valve to
close. This is usually the situation on heating controls. This configuration would not work on a cooling control; here

the valve must open with a rise in temperature. This is termed a direct acting control signal. Figures 5.2.12 and 5.2.13
depict the difference between reverse and direct acting control signals for the same valve action.

Fig. 5.2.12 Reverse acting signal

Fig. 5.2.13 Direct acting signal


On mechanical controllers (such as a pneumatic controller) it is usual to be able to invert the output signal of the
controller by rotating the proportional control dial. Thus, the magnitude of the proportional band and the direction of
the control action can be determined from the same dial.
On electronic controllers, reverse acting (RA) or direct acting (DA) is selected through the keypad.

Gain line offset or proportional effect


From the explanation of proportional control, it should be clear that there is a control offset or a deviation of the actual
value from the set value whenever the load varies from 50%.
To further illustrate this, consider Example 5.2.1 with a 12C P-band, where an offset of 2C was expected. If the
offset cannot be tolerated by the application, then it must be eliminated.
This could be achieved by relocating (or resetting) the set point to a higher value. This provides the same valve
opening after manual reset but at a room temperature of 18C not 16C.

Fig. 5.2.14 Gain line offset

Manual reset
The offset can be removed either manually or automatically. The effect of manual reset can be seen in Figure 5.2.14,
and the value is adjusted manually by applying an offset to the set point of 2C.
It should be clear from Figure 5.2.14 and the above text that the effect is the same as increasing the set value by 2C.
The same valve opening of 66.7% now coincides with the room temperature at 18C.
The effects of manual reset are demonstrated in Figure 5.2.15.

Fig.
5.2.15 Effect of manual reset

Integral control - automatic reset action


'Manual reset' is usually unsatisfactory in process plant where each load change will require a reset action. It is also
quite common for an operator to be confused by the differences between:

Set value - What is on the dial.


Actual value - What the process value is.

Required value - The perfect process condition.

Such problems are overcome by the reset action being contained within the mechanism of an automatic controller.
Such a controller is primarily a proportional controller. It then has a reset function added, which is called 'integral
action'. Automatic reset uses an electronic or pneumatic integration routine to perform the reset function. The most
commonly used term for automatic reset is integral action, which is given the letter I.
The function of integral action is to eliminate offset by continuously and automatically modifying the controller output
in accordance with the control deviation integrated over time. The Integral Action Time (IAT) is defined as the time
taken for the controller output to change due to the integral action to equal the output change due to the proportional
action. Integral action gives a steadily increasing corrective action as long as an error continues to exist. Such
corrective action will increase with time and must therefore, at some time, be sufficient to eliminate the steady state
error altogether, providing sufficient time elapses before another change occurs. The controller allows the integral
time to be adjusted to suit the plant dynamic behaviour.
Proportional plus integral (P + I) becomes the terminology for a controller incorporating these features.
The integral action on a controller is often restricted to within the proportional band. A typical P + I response is shown
in Figure 5.2.16, for a step change in load.

Fig. 5.2.16 P+I


Function after a step change in load
The IAT is adjustable within the controller:

If it is too short, over-reaction and instability will result.


If it is too long, reset action will be very slow to take effect.

IAT is represented in time units. On some controllers the adjustable parameter for the integral action is termed
'repeats per minute', which is the number of times per minute that the integral action output changes by the
proportional output change.

Repeats per minute = 1/(IAT in minutes)


IAT = Infinity - Means no integral action

IAT = 0 - Means infinite integral action

It is important to check the controller manual to see how integral action is designated.

Overshoot and 'wind up'


With P+ I controllers (and with P controllers), overshoot is likely to occur when there are time lags on the system.
A typical example of this is after a sudden change in load. Consider a process application where a process heat
exchanger is designed to maintain water at a fixed temperature.
The set point is 80C, the P-band is set at 5C (2.5C), and the load suddenly changes such that the returning
water temperature falls almost instantaneously to 60C.
Figure 5.2.16 shows the effect of this sudden (step change) in load on the actual water temperature. The measured
value changes almost instantaneously from a steady 80C to a value of 60C.
By the nature of the integration process, the generation of integral control action must lag behind the proportional
control action, introducing a delay and more dead time to the response. This could have serious consequences in
practice, because it means that the initial control response, which in a proportional system would be instantaneous
and fast acting, is now subjected to a delay and responds slowly. This may cause the actual value to run out of
control and the system to oscillate. These oscillations may increase or decrease depending on the relative values of
the controller gain and the integral action. If applying integral action it is important to make sure, that it is necessary
and if so, that the correct amount of integral action is applied.
Integral control can also aggravate other situations. If the error is large for a long period, for example after a large
step change or the system being shut down, the value of the integral can become excessively large and cause
overshoot or undershoot that takes a long time to recover. To avoid this problem, which is often called 'integral windup', sophisticated controllers will inhibit integral action until the system gets fairly close to equilibrium.
To remedy these situations it is useful to measure the rate at which the actual temperature is changing; in other
words, to measure the rate of change of the signal. Another type of control mode is used to measure how fast the
measured value changes, and this is termed Rate Action or Derivative Action.

Integral Controller (I-Controller)


With integral action, the controller output is proportional to the amount of time the error is
present. Integral action eliminates offset.
OI = - kI (Er dt)

(2)

where
OI = output integrating controller
kI = integrating gain or action factor of the controller
dt = time sample
The integral controller produce an output proportional with the summarized deviation between
the set point and measured value and integrating gain or action factor.
Integral controllers tend to respond slowly at first, but over a long period of time they tend to
eliminate errors.

The integral controller eliminates the steady-state error, but may make the transient response
worse. The controller may be unstable.
The integral regulator may also cause problems during shutdowns and start up as a result of the
integral saturation or wind up effect. An integrating regulator with over time deviation (typical
during plant shut downs) will summarize the output to +/- 100%. During start up the output is set
to 100%m which may be catastrophic.
Integral action (Figure 5.5.3)
With too short an integral time, temperature (curve A) will cross the set point and some oscillation will occur.
An excessive integral time will result in the temperature taking too long to return to set point (curve B).
Curve C shows a correct integral time setting where the temperature returns to set point as rapidly as possible
without any overshoot or oscillation.

Fig. 5.5.3 Integral time


reaction to change in load

3. AKSI KONTROL INTEGRAL

dm(t)
Ki . e(t)
dt
atau

m(t) Ki e(t) dt
0

M(s) Ki
s
E(s)

Pengaruh pada sistem :


Menghilangkan Error Steady State
Respon lebih lambat (dibanding P)
Dapat menimbulkan ketidakstabilan (karena
menambah orde sistem)
Perubahan sinyal kontrol sebanding dengan perubahan
error

Semakin besar error, semakin cepat sinyal


kontrol bertambah/berubah
Grafik (lihat Ogata)

Derivative control - rate action


A Derivative action (referred to by the letter D) measures and responds to the rate of change of process signal, and
adjusts the output of the controller to minimise overshoot.
If applied properly on systems with time lags, derivative action will minimise the deviation from the set point when
there is a change in the process condition. It is interesting to note that derivative action will only apply itself when
there is a change in process signal. If the value is steady, whatever the offset, then derivative action does not occur.
One useful function of the derivative function is that overshoot can be minimised especially on fast changes in load.
However, derivative action is not easy to apply properly; if not enough is used, little benefit is achieved, and applying
too much can cause more problems than it solves.
D action is again adjustable within the controller, and referred to as TD in time units:
T D = 0 - Means no D action.
T D = Infinity - Means infinite D action.
P + D controllers can be obtained, but proportional offset will probably be experienced. It is worth remembering that
the main disadvantage with a P control is the presence of offset. To overcome and remove offset, 'I' action is
introduced. The frequent existence of time lags in the control loop explains the need for the third action D. The result
is a P + I + D controller which, if properly tuned, can in most processes give a rapid and stable response, with no
offset and without overshoot.

Derivative action (Figure 5.5.4)


An excessive derivative time will cause an over-rapid change in temperature, overshoot and oscillation (curve B).
Too short a derivative time allows the temperature to deviate from the set point for too long (curve A).
The optimum setting returns the temperature to the set point as quickly as possible and is consistent with good
stability (curve C).

Fig. 5.5.4 Derivative time reaction to


change in load

With derivative action, the controller output is proportional to the rate of change of the
measurement or error. The controller output is calculated by the rate of change of the deviation
or error with time.
OD = - kD dEr / dt

(3)

where
OD = output derivative controller
kD = derivative gain or action factor of the controller
dEr = deviation change over time sample dt
dt = time sample
The derivative or differential controller is never used alone. With sudden changes in the system
the derivative controller will compensate the output fast. The long term effects the controller
allow huge steady state errors.
A derivative controller will in general have the effect of increasing the stability of the system,
reducing the overshoot, and improving the transient response.

PID controllers
P and I and D are referred to as 'terms' and thus a P + I + D controller is often referred to as a three term controller.

Proportional, Integral, Derivative Controller (PID-Controller)

The functions of the individual proportional, integral and derivative controllers complements
each other. If they are combined its possible to make a system that responds quickly to changes
(derivative), tracks required positions (proportional), and reduces steady state errors (integral).
Note that these correlations may not be exactly accurate, because P, I and D are dependent of
each other. Changing one of these variables can change the effect of the other two.

Controller
Response

Rise Time

Overshoot

Settling Time

Steady State
Error

Decrease

Increase

Small Change

Decrease

Decrease

Increase

Increase

Eliminate

Small Change

Decrease

Decrease

Small Change

The transfer function of the PID controller looks like the following:
Kp = Proportional gain
KI = Integral gain
Kd = Derivative gain

First, let's take a look at how the PID controller works in a closed-loop system using the schematic
shown above. The variable (e) represents the tracking error, the difference between the desired input
value (R) and the actual output (Y). This error signal (e) will be sent to the PID controller, and the
controller computes both the derivative and the integral of this error signal. The signal (u) just past
the controller is now equal to the proportional gain (Kp) times the magnitude of the error plus the
integral gain (Ki) times the integral of the error plus the derivative gain (Kd) times the derivative of
the error.

This signal (u) will be sent to the plant, and the new output (Y) will be obtained. This new output (Y)
will be sent back to the sensor again to find the new error signal (e). The controller takes this new
error signal and computes its derivative and its integral again. This process goes on and on.

The characteristics of P, I, and D controllers


A proportional controller (Kp) will have
the effect of reducing the rise time and will
reduce ,but never eliminate, the steadystate error. An integral control (Ki) will
have the effect of eliminating the steadystate error, but it may make the transient
response worse. A derivative control (Kd)
will have the effect of increasing the
stability of the system, reducing the
overshoot, and improving the transient
response. Effects of each of controllers Kp,
Kd, and Ki on a closed-loop system are
summarized in the table shown below. CL
RESPONSE

RISE
TIME

OVERS
HOOT

SETTLIN
G TIME

Kp

Decrease

Increase

Ki

Decrease
Small
Change

Increase

Small
Change
Increase

Decrease

Decrease

Kd

S-S
ERROR

Decrease
Eliminate
Small
Change

Summary of modes of control


A three-term controller contains three modes of control:

Proportional (P) action with adjustable gain to obtain stability.


Reset (Integral) (I) action to compensate for offset due to load changes.

Rate (Derivative) (D) action to speed up valve movement when rapid load changes take place.

The various characteristics can be summarised, as shown in Figure 5.2.17.

Fig.
5.2.17 Summary of control modes and responses
Finally, the controls engineer must try to avoid the danger of using unnecessarily complicated controls for a specific
application. The least complicated control action, which will provide the degree of control required, should always be
selected.
Top

Further terminology
Time constant

This is defined as: 'The time taken for a controller output to change by 63.2% of its total due to a step (or sudden)
change in process load'.
In reality, the explanation is more involved because the time constant is really the time taken for a signal or output to
achieve its final value from its initial value, had the original rate of increase been maintained. This concept is depicted
in Figure 5.12.18.

Fig. 5.2.18 Time constant

Example 5.2.2 A practical appreciation of the time constant


Consider two tanks of water, tank A at a temperature of 25C, and tank B at 75C. A sensor is placed in tank A and
allowed to reach equilibrium temperature. It is then quickly transferred to tank B. The temperature difference between
the two tanks is 50C, and 63.2% of this temperature span can be calculated as shown below:
63.2% of 50C = 31.6C
The initial datum temperature was 25C, consequently the time constant for this simple example is the time required
for the sensor to reach 56.6C, as shown below:
25C + 31.6C = 56.6C

Hunting
Often referred to as instability, cycling or oscillation. Hunting produces a continuously changing deviation from the
normal operating point. This can be caused by:

Hunting
The proportional band being too narrow.
The integral time being too short.

The derivative time being too long.

A combination of these.

Long time constants or dead times in the control system or the process itself.

In Figure 5.2.19 the heat exchanger is oversized for the application. Accurate temperature control will be difficult to
achieve and may result in a large proportional band in an attempt to achieve stability.
If the system load suddenly increases, the two port valve will open wider, filling the heat exchanger with high
temperature steam. The heat transfer rate increases extremely quickly causing the water system temperature to
overshoot. The rapid increase in water temperature is picked up by the sensor and directs the two port valve to close
quickly. This causes the water temperature to fall, and the two port valve to open again. This cycle is repeated, the
cycling only ceasing when the PID terms are adjusted. The following example (Example 5.2.3) gives an idea of the
effects of a hunting steam system.

Fig.
5.2.19 Hunting

Example 5.2.3 The effect of hunting on the system in Figure 5.2.19


Consider the steam to water heat exchanger system in Figure 5.2.19. Under minimum load conditions, the size of the
heat exchanger is such that it heats the constant flowrate secondary water from 60C to 65C with a steam
temperature of 70C. The controller has a set point of 65C and a P-band of 10C.
Consider a sudden increase in the secondary load, such that the returning water temperature almost immediately
drops by 40C. The temperature of the water flowing out of the heat exchanger will also drop by 40C to 25C. The
sensor detects this and, as this temperature is below the P-band, it directs the pneumatically actuated steam valve to
open
fully.
The steam temperature is observed to increase from 70C to 140C almost instantaneously. What is the effect on the
secondary water temperature and the stability of the control system?
As demonstrated in Tutorial 13.2 (The heat load, heat exchanger and steam load relationship), the heat exchanger
temperature design constant, TDC, can be calculated from the observed operating conditions and Equation 13.2.2:

Equation 13.2.2
Where:
TDC = Temperature Design Constant
T s = Steam temperature
T 1 = Secondary fluid inlet temperature
T 2 = Secondary fluid outlet temperature
In this example, the observed conditions (at minimum load) are as follows:

When the steam temperature rises to 140C, it is possible to predict the outlet temperature from Equation 13.2.5:

Equation 13.2.5
Where:
T s = 140C
T 1 = 60C - 40C = 20C temperature
TDC = 2

The heat exchanger outlet temperature is 80C, which is now above the P-band, and the sensor now signals the
controller to shut down the steam valve.
The steam temperature falls rapidly, causing the outlet water temperature to fall; and the steam valve opens yet
again. The system cycles around these temperatures until the control parameters are changed. These symptoms are
referred to as 'hunting'. The control valve and its controller are hunting to find a stable condition. In practice, other
factors will add to the uncertainty of the situation, such as the system size and reaction to temperature change and
the position of the sensor.
Hunting of this type can cause premature wear of system components, in particular valves and actuators, and gives
poor control.
Example 5.2.3 is not typical of a practical application. In reality, correct design and sizing of the control system and
steam heated heat exchanger would not be a problem.

Lag
Lag is a delay in response and will exist in both the control system and in the process or system under control.
Consider a small room warmed by a heater, which is controlled by a room space thermostat. A large window is
opened admitting large amounts of cold air. The room temperature will fall but there will be a delay while the mass of

the sensor cools down to the new temperature - this is known as control lag. The delay time is also referred to as
dead time.
Having then asked for more heat from the room heater, it will be some time before this takes effect and warms up the
room to the point where the thermostat is satisfied. This is known as system lag or thermal lag.

Rangeability
This relates to the control valve and is the ratio between the maximum controllable flow and the minimum controllable
flow, between which the characteristics of the valve (linear, equal percentage, quick opening) will be maintained. With
most control valves, at some point before the fully closed position is reached, there is no longer a defined control over
flow in accordance with the valve characteristics. Reputable manufacturers will provide rangeability figures for their
valves.

Turndown ratio
Turndown ratio is the ratio between the maximum flow and the minimum controllable flow. It will be substantially less
than the valve's rangeability if the valve is oversized.
Although the definition relates only to the valve, it is a function of the complete control system.

Das könnte Ihnen auch gefallen