PO# : 10-1283LVC
WARNING : The current system set points for alarms and shut down conditions are based on
our general testing process. Process set points must be adjusted according with specific
customer process environment and required system performance.
(0) P&ID
(1)SYSTEM DESCRIPTION
The compressor system will include the following main components :
Compressor
Compressor Motor
Separator
Heat Exchanger
Seal Pots.
The intent is to obtain an operating discharge pressure of 10 psig.
(2) INITIAL COMPRESSOR START
The liquid-ring compressor requires a prime of water such that the liquid level in the casing is at shaft center-line.
This prime of liquid sets up the liquid-ring seal through centrifugal action in the machine, so that compression can
occur. Upon start-up of a dry system, the compressor casing must first be filled with water to the shaft centerline.
(3) SUCTION LINE
The suction line consists of a check valve, low pressure switch, and a pressure gauge with isolation valve. The
check valve prevents water from back filling the upstream components if an upset condition exists. A low pressure
switch is used to monitor the pressure level of the inlet. If vacuum is accidentally drawn by the compressor, the
switch will trip and the by-pass modulated valve is opening . This will protect the equipment upstream of the
compressor from seeing large vacuum pressure levels. A pressure gauge is used to monitor the inlet pressure
level during operation. A manual isolation valve is used to allow maintenance of the pressure gauge during
operation.
(4) DISCHARGE SEPARATOR TANK
(a) General:
The separator tank is of the 2-phase design. The two phases consist of: 1.) Process Gas, 2.) Liquid Water.
Separation is achieved through baffling, and centrifugal action.
PERFORMANCE DATA:
Requirements:
Application:
Reactors
3.66
Carbon Dioxide:
61.97
wt%
Hydrogen Sulfide:
34.37
wt%
18.37
Barometric Pressure:
14.1
PSIA
Site Elevation:
350
M.A.S.L.
Suction Pressure:
20
mm H 2 0
Suction Temperature:
45.94
Calculated Capacity:
320
ACFM
Discharge Pressure:
PSIG
Service Liquid:
Water
@ 8C
Cooling Liquid:
Water
@ 4C
Compressor Performance:
Model:
60520
Capacity:
320
ACFM
Suction Pressure:
20
mm H 2 0
Suction Temperature:
45.9
10
PSIG
40
HP
Pump Speed:
1750
RPM
BHP: 28
Cooling Liquid Rate:
30
USGPM
0.5
USGPM
END OF DOCUMENT