Sie sind auf Seite 1von 2

Slection

Contactors
Contactors for the North American market
conforming to standards UL and CSA, 20 to 120 A

Standard power ratings


Taille
of motors 50/60 Hz
Size
Single-phase 3-phase
1
3
115 V 230 V 200 V 230 V 460 V 575 V
240 V 208 V 240 V 480 V 600 V
HP
HP
HP
HP
HP
HP

AssoContinuous Type of contactor required


ciated
current
(Basic reference.
cable
Complete with code indicating
Type
control circuit voltage)
75 C-Cu

0.5

7.5

00

AWG10

20

LC1, LP1-D09

7.5

10

AWG10

25

LC1, LP1-D12

10

15

AWG8

32

LC1, LP1-D18

7.5

15

20

AWG8

40

LC1, LP1-D25

7.5

10

20

30

AWG6

50

LC1, LP1-D32

10

10

30

30

AWG3

60

LC1, LP1-D40

7.5

7.5

15

15

40

40

AWG3

70

LC1, LP1-D50

7.5

10

20

20

50

50

AWG3

80

LC1, LP1-D65

7.5

15

20

25

60

60

AWG2

110

LC1, LP1-D80

7.5

15

20

25

60

60

AWG2

120

LC1-D95

LC1-D0901pp

LC1-D2510pp

Application example
For 15 HP-230 V motor

Select a contactor type LC1-D50 or LP1-D50.


Information : the contactor rating selected corresponds to size 2, the
associated cable is type AWG3 75 C-Cu.

Note : auxiliary contact blocks and modules : see pages 24013/2 to 24013/11.
For LC1 or LP1-D09 to D32 : clip-on mounting on 35 mm 6 rail AM1-DP.
For LC1 or LP1-D40 to D95 : clip-on mounting on 35 or 75 mm 6 rail AM1-DL.
Power terminals : LC1 or LP1-D09 to D95 protected against direct finger contact and ready-to-tighten terminals.

LC1-D9511pp

Selection guide :
pages 24003/2 to 24007/3
4050 Ver4.00-EN.fm/2

Characteristics :
pages 24008/2 to 24008/9

Dimensions, schemes :
pages 24014/2 to 24014/7
Schneider Electric

References

Contactors
Contactors for the North American market
conforming to standards UL and CSA, 175 to 1000 A

LC1-F225

Standard power ratings


of motors 50/60 Hz
3-phase
3
200 V 230 V 460 V 575 V
208 V 240 V 480 V 600 V
HP
HP
HP
HP

Taille
Size

Associated
cable
Type
75 C-Cu at
I continuous

Continuous
current
at 600 V max.

Type of contactor required


(Basic reference.
Complete with code indicating
control circuit voltage)
(1), (2)

50

60

125

150

AWG 3/0

200

LC1-F185 pp

60

75

150

150

300 MCM

250

LC1-F225 pp

60

75

150

200

300 MCM

285

LC1-F265 pp

75

100

200

250

600 MCM

370

LC1-F330 pp

100

125

250

300

600 MCM

420

LC1-F400 pp

150

200

400

500

2 x 500 MCM

700

LC1-F500 pp

250

300

600

800

3 x 400 MCM

1000

LC1-F630 pp

400

900

3 x 600 MCM

1000

LC1-F800 pp

450

900

2 x 3 x 600 MCM

1350

LC1-F780 pp

LC1-F630
Application example
For a 60 HP-230 V motor

Select a contactor type LC1-F185.


Information : the contactor rating selected corresponds to size 4, the
associated cable is type AWG 3/0 75 C-Cu.
(1) Auxiliary contact blocks and modules : see pages 25010/2 to 25010/7.
Power terminals can be protected by the addition of shrouds, to be ordered separately. See page 25010/6.
(2) Standard control circuit voltages (for other voltages, please consult your Regional Sales Office).
Volts a
LC1-F185 and F225
50 Hz (coil LX1)
60 Hz (coil LX1)
40400 Hz (coil LX9)
Volts a
LC1-F265F780
40400 Hz (coil LX1)

24

48

110

120

208

220

240

380

415

440

B5

E5
E6
E7

F5
F6
F7

G6
G7

L6
L7

M5
M6
M7

U5
U6
U7

Q5
Q6
Q7

N5

N7

R6
R7

48

110

120

208

220

240

380

415

E7 (3)

F7

G7 (4) L7

M7

U7

Q7

N7

125
GD

250
UD

440
RD

Volts c
24
48
110
LC1-F185F780
BD (5) ED (6) FD
(3) For contactors LC1-F265 to F630 .
(4) F7 for LC1-F630 and F780.
(5) For contactors LC1-F185 to LC1-F330.
(6) For contactors LC1-F265 to F630.

Selection guide :
pages 24003/2 to 24007/3
Schneider Electric

Characteristics :
pages 25007/2 to 25007/7

220
MD

Dimensions, schemes :
pages 25011/2 to 25011/7
24050 Ver4.00-EN.fm/

Das könnte Ihnen auch gefallen