Owner
Project:
Compiled by
Contents
Sl.No Descriptiion
Page No
Executive Summary
Reference Documents
Device Details
11
12
24
32
57
10
89
11
102
12
109
kV HT Switch Board
Executive Summary
Introduction
Project:
Owner:
ElectricalDistribution System
Protection Coordination
Conclusion
The short circuit currents at various busbars are calculated based on the above
assumptions. Calculated Short circuit currents are shown in the SLD.
Selectivity of relays and circuit breakers were worked out based on the cable
size and flow of short circuit currents.
Time current characterstic curves are generated for every path and verified .
Settings for each device,short circuit currents at every busbars,detailed
calculations for the settings are given in the following pages. While doing this
exercise certain discrepencies were noticed and these are brought out
seperately under heading 'Comments and Observations'.
Reference Documents/Drawings
Sl.No
1
2
3
4
5
6
7
8
9
10
11
12
13
14
File name
JCLSLD.DWG
RELAYS IN JCL.DOCX
2600KW HT motor test report.pdf
211218 ID fan 1000KW.jpg
803448 AHF -1 315KW.jpg
2000KVA transformer.pdf
20 MVA TR 1.jpg
1250 kVA TR 1.jpg
1600 kVA TR 1.jpg
1000 kVA TR 1.jpg
3.5 TG 1.jpg
16 TG 1.jpg
15 MVA TR 1.jpg
750 kVA TR 1.jpg
GRID
KPCTL
TG2
GEN
LINE_CB
TG1
GEN
50
51
TR_CB
50
51
50
51
125
TG_CABLE
110 kV BUS
126
GCB
50
51
TRAF01_20MVA
11 kV HT LCSS-1 UA IC1
BC
50
51
50
51
11 kV HT LCSS-1 UA IC2
50
51
11 kV HT LCSS-1 UA_RH
11 kV HT LCSS-1 UA_LH
KILN1&2
50
51
50
51
50
51
INT.PANEL
50
51
CAB:AFBC2
DG1
RMP3 TR
AFBC FEEDER 2
50
51
CAB_SWTP
GEN
TRAF02_2MVA
STP
50
51
CAB_KILN 3
KILN3&4
50
51
CAB_RMP3
TRAF01_2MVA
50
51
CAB_LCSS_FDR2
CAB_LCSS1_FDR1
141
138
RMP3
LCSS1_FDR2
50
51
50
51
CAB_PELLET
CAB_ET
ET
AFBC FEEDER
LCSS1_FDR1
50
51
CAB_KILN1
135
134
PELLET PLANT 1
50
51
11kV HT LCSS-1 UA BC
LCSS1_ET
133
STP PLANT1
50
51
AFBC TR2
KILN 3 TR
TRAF02_0.75 MVA
415V LCSS1 CPP IC2
kiln 3
KILN 3
6.6kV_LBSS1_IC2
6.6kV_LBSS1_IC1
50
51
50
51
1F1:HT MOTOR
2F1:LCSS2
50
51
5F1:LBDS2
4F1:LBDS1
3F1:LCSS3
50
51
50
51
50
51
6F1:SPARE
50
51
16F1:SPARE
17F1:HTMOTOR
50
51
50
51
TRAFO1_LCSS4
CAB_ORE GRINDING
TRAF03_LCSS3
50
51
CAB_SWBD_TRAFO1
TRAF2_LCSS2
15F1:LCSS2
50
51
CAB_SWBD_TRAFO
TRAFO1_LCSS3
14F1:LCSS3
50
51
50
51
2600kW
TRAFO1_LCSS2
13F1:LBDS2
12F1:LBDS2
105
103
91
50
51
6.6kV_LBSS1_RH
6.6kV_LBSS1_BC
6.6kV_LBSS1_LH
AH04
AH03
50
51
50
51
154
AH17
50
51
50
51
210
219
AH01 BC
50
51
AH6
AH8
50
51
50
51
AH10
AH12
AH14
AH16
AH18
AH20
50
51
50
51
50
51
50
51
50
51
50
51
293
AH07
50
51
283
AH09
50
51
170
AH 11
50
51
183
AH13
50
51
174
AH15
50
51
184
106
AH19
234
50
51
224
AH23
50
51
215
AH21
162
196
176
270
172
285
233
178
272
179
290
230
240
220
239
211
238
236
192
IDFAN_1000kW
226
217
205
AH FAN1_315kW
SC MCC TR
295
208
191
AH FAN2_315kW
287
SC.BLDG.MCC LHS
SC.BLDG.MCC RHS
TG MCC1
BALLING MCC1
P_MIXING MCC2
BALLING MCC2
TG MCC2
P_MIXING MCC1
REV. DATE
ECO#
DESCRIPTION
DWN APP
DRAWN BY/DATE:
DWG. No.
DWG No.:
ENG. APP./DATE:
MFG. APP./DATE:
SCALE:
PART No.:
DWG SIZE:
REV.
GRID
KPCTL
Ik" : 13145.13A
Vp: 110000 V
TG2
GEN
LINE_CB
TG1
GEN
50
51
TR_CB
50
51
50
51
125
TG_CABLE
110 kV BUS
Ik" : 13144.79A
Vp: 110000 V
126
GCB
50
51
TRAF01_20MVA
11 kV HT LCSS-1 UA IC1
BC
50
51
50
11 kV HT LCSS-1 UA_LH
51
Ik" : 9966.52A
Vp: 11000 V
LCSS1_FDR1
50
51
50
51
50
51
50
51
INT.PANEL
RMP3 TR
50
51
50
51
CAB:AFBC2
DG1
TRAF02_2MVA
50
51
11 kV HT LCSS-1 UA_RH
Ik" : 9965.19A
Vp: 11000 V
AFBC FEEDER 2
CAB_SWTP
GEN
50
51
STP
CAB_KILN 3
50
51
KILN3&4
CAB_RMP3
TRAF01_2MVA
138
RMP3
LCSS1_FDR2
CAB_LCSS_FDR2
ET
Ik" : 9864.91A
Vp: 11000 V 141
134
AFBC FEEDER
CAB_LCSS1_FDR1
CAB_KILN1
PELLET PLANT 1
CAB_PELLET
50
51
135
50
51
CAB_ET
50
51
KILN1&2
11kV HT LCSS-1 UA BC
LCSS1_ET
133
11 kV HT LCSS-1 UA IC2
50
51
STP PLANT1
50
51
AFBC TR2
KILN 3 TR
TRAF02_0.75 MVA
KILN
kiln 3 3
Ik" : 44146.08A
Vp: 415 V
415V LCSS1
IC2 CPP RH
415VCPP
LCSS1
Ik" : 39642.44A
Vp: 433 V
6.6kV_LBSS1_IC2
6.6kV_LBSS1_IC1
50
51
2F1:LCSS2
50
51
5F1:LBDS2
4F1:LBDS1
3F1:LCSS3
50
51
50
51
50
51
6F1:SPARE
50
51
17F1:HTMOTOR
50
51
50
51
TRAFO1_LCSS4
CAB_LBDS2
16F1:SPARE
CAB_ORE GRINDING
TRAF03_LCSS3
50
51
CAB_SWBD_TRAFO1
TRAF2_LCSS2
15F1:LCSS2
50
51
CAB_SWBD_TRAFO
TRAFO1_LCSS3
14F1:LCSS3
50
51
50
51
2600kW
Ik" : 7735.31A
Vp: 6600 V
TRAFO1_LCSS2
13F1:LBDS2
12F1:LBDS2
105
103
91
50
51
50
51
6.6kV_LBSS1_RH
Ik" : 7734.19A
Vp: 6600 V
6.6kV_LBSS1_BC
1F1:HT MOTOR
6.6kV_LBSS1_LH
Ik" : 7735.55A
Vp: 6600 V
50
51
AH17
50
51
154
Ik" : 7650.15A
Vp: 6600 V
50
51
210
219
AH01 BC
50
51
AH6
AH8
50
51
50
51
AH10
AH12
AH14
AH16
AH18
AH20
50
51
50
51
50
51
50
51
50
51
50
51
293
AH07
50
51
283
AH09
50
51
170
AH 11
50
51
183
AH13
50
51
50
51
162
Ik" : 7661.83A
Vp: 6600 V
174
AH15
50
51
184
106
AH19
234
50
51
AH04
AH03
224
AH23
50
51
215
AH21
196
176
270
172
285
BALLING MCC1
Ik" : 28456.18A
Vp: 433 V
P_MIXING MCC1
Ik" : 23433.37A
Vp: 433 V
178
233
SC.BLDG.MCC LHS
Ik" : 23433.37A
Vp: 433 V
SC.BLDG.MCC RHS
Ik" : 23441.38A
Vp: 433 V
272
P_MIXING MCC2
Ik" : 23441.38A
Vp: 433 V
179
BALLING MCC2
Ik" : 23441.38A
Vp: 433 V
290
230
240
220
239
211
238
236
TG MCC1
Ik" : 28456.18A
Vp: 433 V
I
226
192
IDFAN_1000kW
Ik" : 7577.09A
Vp: 6600 V
217
205
AH FAN1_315kW
Ik" : 7564.94A
Vp: 6600 V
SC MCC TR
295
208
191
AH FAN2_315kW
Ik" : 7588.28A
Vp: 6600 V
287
TG MCC2
Ik" : 23441.38A
Vp: 433 V
REV. DATE
ECO#
DESCRIPTION
DWN APP
DWG. No.
DWG No.:
ENG. APP./DATE:
MFG. APP./DATE:
SCALE:
PART No.:
DWG SIZE:
REV.
GRID
KPCTL
Ik" : 26266.72A
Vp: 110000 V
TG2
GEN
LINE_CB
TG1
GEN
50
51
TR_CB
50
51
50
51
125
TG_CABLE
110 kV BUS
Ik" : 26265.38A
Vp: 110000 V
126
GCB
50
51
TRAF01_20MVA
11 kV HT LCSS-1 UA IC1
BC
50
51
50
11 kV HT LCSS-1 UA_LH
51
Ik" : 10338.33A
Vp: 11000 V
LCSS1_FDR1
50
51
50
51
50
51
50
51
INT.PANEL
RMP3 TR
50
51
50
51
CAB:AFBC2
DG1
TRAF02_2MVA
50
51
11 kV HT LCSS-1 UA_RH
Ik" : 10336.89A
Vp: 11000 V
AFBC FEEDER 2
CAB_SWTP
GEN
50
51
STP
CAB_KILN 3
50
51
KILN3&4
CAB_RMP3
TRAF01_2MVA
138
RMP3
LCSS1_FDR2
CAB_LCSS_FDR2
ET
Ik" : 10228.38A
Vp: 11000 V 141
134
AFBC FEEDER
CAB_LCSS1_FDR1
CAB_KILN1
PELLET PLANT 1
CAB_PELLET
50
51
135
50
51
CAB_ET
50
51
KILN1&2
11kV HT LCSS-1 UA BC
LCSS1_ET
133
11 kV HT LCSS-1 UA IC2
50
51
STP PLANT1
50
51
AFBC TR2
KILN 3 TR
TRAF02_0.75 MVA
415V LCSS1 CPP IC2
kiln 3
KILN 3
415 V LCSS-7 STP IC2 Ik" : 44412.14A
Vp: 415 V
TRAF01_15 MVA
CAB_TRAFO_SWBD
6.6kV_LBSS1_IC2
6.6kV_LBSS1_IC1
50
51
2F1:LCSS2
50
51
5F1:LBDS2
4F1:LBDS1
3F1:LCSS3
50
51
50
51
50
51
6F1:SPARE
50
51
17F1:HTMOTOR
50
51
50
51
TRAFO1_LCSS4
CAB_LBDS2
16F1:SPARE
CAB_ORE GRINDING
TRAF03_LCSS3
50
51
CAB_SWBD_TRAFO1
TRAF2_LCSS2
15F1:LCSS2
50
51
CAB_SWBD_TRAFO
TRAFO1_LCSS3
14F1:LCSS3
50
51
50
51
2600kW
Ik" : 7857.85A
Vp: 6600 V
TRAFO1_LCSS2
13F1:LBDS2
12F1:LBDS2
105
103
91
50
51
50
51
6.6kV_LBSS1_RH
Ik" : 7856.7A
Vp: 6600 V
6.6kV_LBSS1_BC
1F1:HT MOTOR
6.6kV_LBSS1_LH
Ik" : 7858.11A
Vp: 6600 V
50
51
AH17
50
51
154
Ik" : 7769.84A
Vp: 6600 V
50
51
210
219
AH01 BC
50
51
AH6
AH8
50
51
50
51
AH10
AH12
AH14
AH16
AH18
AH20
50
51
50
51
50
51
50
51
50
51
50
51
293
AH07
50
51
283
AH09
50
51
170
AH 11
50
51
183
AH13
50
51
50
51
162
Ik" : 7781.73A
Vp: 6600 V
174
AH15
50
51
184
106
AH19
234
50
51
AH04
AH03
224
AH23
50
51
215
AH21
196
176
270
172
285
BALLING MCC1
Ik" : 28555.3A
Vp: 433 V
P_MIXING MCC1
Ik" : 23500.59A
Vp: 433 V
178
233
SC.BLDG.MCC LHS
Ik" : 23500.59A
Vp: 433 V
SC.BLDG.MCC RHS
Ik" : 23508.66A
Vp: 433 V
272
P_MIXING MCC2
Ik" : 23508.66A
Vp: 433 V
179
BALLING MCC2
Ik" : 23508.66A
Vp: 433 V
290
230
240
220
239
211
238
236
TG MCC1
Ik" : 28555.3A
Vp: 433 V
I
226
192
IDFAN_1000kW
Ik" : 7694.37A
Vp: 6600 V
217
205
AH FAN1_315kW
Ik" : 7681.84A
Vp: 6600 V
SC MCC TR
295
208
191
AH FAN2_315kW
Ik" : 7705.74A
Vp: 6600 V
287
TG MCC2
Ik" : 23508.66A
Vp: 433 V
REV. DATE
ECO#
DESCRIPTION
DWN APP
DWG. No.
DWG No.:
ENG. APP./DATE:
MFG. APP./DATE:
SCALE:
PART No.:
DWG SIZE:
REV.
Details of Devices
Transformers
To
From
11 kV Switch Board
GRID
110000
FDR 07 LBSS-1 6.6 kV LBSS-1 SWBD
FDR 4 11 kV SWBD
11000
Screening MCC LHS
AH11 HV distribution
6600
Screening MCC RHS
AH10 HV distribution
6600
TG MCC RHS
AH16 HV distribution
6600
TG MCC LHS
AH17 HV distribution
6600
BALLING SYSTEM LHS
AH15 HV distribution
6600
BALLING SYSTEM RHS
AH14 HV distribution
6600
PROPORTION & MIXING MCC LHS
AH13 HV distribution
6600
PROPORTION & MIXING MCC RHS
AH12 HV distribution
6600
ORE CRUSHING GRINDING SYSTEM LHS LCSS-2 FDR 02 6.6 kV LBBSS-1 SWBD
6600
ORE CRUSHING GRINDING SYSTEM RHS LCSS-1 FDR 15 6.6 kV LBBSS-1 SWBD
6600
CPP LCSS-1
FDR 5 11 kV SWBD
11000
CPP LCSS-1
FDR12 11 kV SWBD
11000
KILN 1&2
FDR 3 11 kV SWBD
11000
AFBC FEEDER LHS
FDR 6 11 kV SWBD
11000
AFBC FEEDER RHS
FDR 16 11 kV SWBD
11000
RMP3
FDR 13 11 kV SWBD
11000
KILN 3,4&5
FDR 14 11 kV SWBD
11000
STP FEEDER
FDR 15 11 kV SWBD
11000
11000
6900
433
433
433
433
433
433
433
433
433
433
433
433
433
433
433
433
433
433
20000
15000
1000
1000
1600
1600
1600
1600
1000
1000
1250
1250
2000
2000
1250
750
750
1000
2500
750
HV
STAR
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
LV
DELTA
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
HV
LV RATED
RATED
CURRENT
CURRENT
10 ONAN/ONAF 104.98 1049.76
8.35 ONAN/ONAF 787.32 1255.15
5 ONAN
87.48 1333.38
5 ONAN
87.48 1333.38
5 ONAN
139.96
2133
5 ONAN
139.96
2133
5 ONAN
139.96
2133
5 ONAN
139.96
2133
5 ONAN
87.48 1333.38
5 ONAN
87.48 1333.38
5 ONAN
109.35 1666.76
5 ONAN
109.35 1666.76
6.25 ONAN
104.98 2666.82
6.25 ONAN
104.98 2666.82
5 ONAN
65.61 1666.76
5 ONAN
39.37 1000.06
5 ONAN
39.37 1000.06
5.16 ONAN
52.49 1333.38
6.5 ONAN
131.22 3333.53
5 ONAN
39.37 1000.06
Vector
Z in %
Group
YNd1
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Type of
Cooling
SETTING CALCULATIONS
FOR
FOR TRANSFORMERS
TRANSFORMERS
DG SETS
433 V
11
3200
125/1
2000 kVA
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side ACB CT details
Percentage Impedance of Transformer
Through Fault current at 0.415 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current
PT
Vp
Vs
2000
kVA
11
kV
0.433
kV
125/1
CTRP 125
3200
Z
6.25%
33337
Amps
104.98
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 104.98/0.95
121.55
Isfl
0.97
1
1
Curve
Extreme Inverse
2666.82
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x 2666.82/0.95
3087.90
=3087.90/3200
33337.00
1312.27
11
10.50
13.00
6
433 V
Amps
Amps
Amps
Amps
433 V
11
1600 A
75/
1000 kVA
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side ACB Rating
Percentage Impedance of Transformer
Through Fault current at 0.415 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current
PT
Vp
Vs
1000
kVA
11
kV
0.433
kV
75/1
CTRP 75
1600
Z
5.16%
23208.00
Amps
52.49
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 52.49/0.95
60.78
Isfl
0.81
0.8
0.8
Curve
Extremel Inverse
1333.41
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x1333.41/0.95
1543.95
=1543.95/1600
23208.00
913.55
0.96496875
12.18
14.00
6.00
Amps
Amps
Amps
Amps
11
433 V
4000 A
800/1
2500 kVA
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side ACB Rating
Percentage Impedance of Transformer
Through Fault current at 0.415 kV Bus as per report
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current
PT
Vp
Vs
2500
kVA
11
kV
0.433
kV
150/1
CTRP 150
4000
Z
6.50%
36209
Amps
131.22
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 131.22/0.95
151.94
Isfl
1.01
1
1
Curve
Extreme Inverse
3333.53
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x 3333.53/0.95
3859.88
=3859.88/4000
36209.00
1425.32
9.50
12.00
6
Amps
Amps
Amps
Amps
433 V
11
2000 A
75/
1250 kVA
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side ACB Rating
Percentage Impedance of Transformer
Fault current at 0.415 kV Bus as per report
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current
PT
Vp
Vs
1250
kVA
11
kV
0.433
kV
100/1
CTRP 100
2000
Z
5.00%
25029.00
Amps
65.61
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x65.61/0.95
75.97
Isfl
0.76
0.75
0.75
Curve
Extreme l Inverse
1666.76
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x1666.76/0.95
1929.93
=1929.93/2000
25029.00
985.23
0.964615
9.85
12.00
6
Amps
Amps
Amps
Amps
433 V
11
1250 A
100/1
750 kVA
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side ACB Rating
Percentage Impedance of Transformer
Through Fault current at 0.433 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current
PT
Vp
Vs
750
kVA
11
kV
0.433
kV
100/1
CTRP 100
1250
Z
5.00%
18303.00
Amps
39.37
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x39.37/0.95
45.59
Isfl
0.46
0.5
0.5
Curve
Extreme Inverse
1000.06
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x1000.06/0.95
1157.96
=1157/1250
0.95
18303.00
720.47
6.6kV
0.925616
7.20
9.00
6
433 V
Amps
Amps
Amps
Amps
433 V
6.6kV
150/5
1000 kVA
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side ACB Rating
Percentage Impedance of Transformer
Through Fault current at 0.415 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current
1600 A
PT
Vp
Vs
1000
kVA
6.6
kV
0.433
kV
150/5
CTRP 30
1600
Z
5.00%
23208
Amps
87.48
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 87.48/0.95
101.29
Isfl
3.38
Amps
0.675283281
0.7
Curve
Extremel Inverse
1333.41
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x1333.41/0.95
1543.95
=1543.95/1600
23208.00
1522.59
6.6kV
0.96496875
50.75
60 (12)
6.00
433 V
Amps
Amps
Amps
Amps
433 V
6.6kV
1600 A
300/5
1000 kVA
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side ACB Rating
Percentage Impedance of Transformer
Through Fault current at 0.415 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current
PT
Vp
Vs
1000
kVA
6.6
kV
0.433
kV
300/5
CTRP 60
1600
Z
5.00%
21210
Amps
87.48
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 87.48/0.95
101.29
Isfl
1.69
Amps
0.337641641
0.35
Curve
Extremel Inverse
1333.41
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x1333.41/0.95
1543.95
=1543.95/1600
21210.00
1391.50
6.6kV
0.96496875
23.19
28(5.5)
6.00
433 V
Amps
Amps
Amps
Amps
Setting Calculation for Transformers 1.6 MVA Feeding TG/BALLING SYSTEM MCC
433 V
6.6kV
200/5
1600 kVA
2500 A
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side ACB Rating
Percentage Impedance of Transformer
Through Fault current at 0.415 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current
PT
Vp
Vs
1600
kVA
6.6
kV
0.433
kV
200/5
CTRP 40
2500
Z
5.00%
25244.00
Amps
139.97
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x139.97/0.95
162.07
Isfl
4.05
Amps
0.810339938
0.85
Curve
Extremel Inverse
2133.46
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x2133.46/0.95
2470.32
=2470/2500
25244.00
1656.16
6.6kV
0.988128146
41.40
50(10)
6.00
433 V
Amps
Amps
Amps
Amps
Setting Calculation for Transformers 1.25 MVA Feeding ORE C.SYSTEM MCC
433 V
6.6kV
200/5
1250 kVA
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side ACB Rating
Percentage Impedance of Transformer
Through Fault current at 0.415 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current
2000 A
PT
Vp
Vs
1250
kVA
6.6
kV
0.433
kV
125/1
CTRP 125
2500
Z
5.00%
28226.00
Amps
109.35
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x109.35/0.95
126.62
Isfl
1.01
Amps
1
1
Curve
Extremel Inverse
1666.76
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x1666.76/0.95
1929.94
=1929/2500
0.8
28226.00
1851.80
0.771975114
14.81
17.00
4.00
Amps
Amps
Amps
Amps
11
6.9kV
800/1
15000 kVA
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
TransformerLV side CT details CTLV
Turns Ratio
Percentage Impedance of Transformer
Fault current at 6.6 kV Bus as per report
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current
1500/1
PT
Vp
Vs
15000
kVA
11
kV
6.9
kV
800/1
CTRP 800
1500/1
1500
Z
8.35%
4915.00
Amps
787.32
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 787.32/0.95
911.63
Isfl
1.14
1.15
1.15
Curve
Normal Inverse
1255.15
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x1255.15/0.95
1453.33
=1453/1500
Curve
Normal Inverse
0.968884708
Amps
Amps
Amps
110 kV
11 kV
125/1
20000 kVA
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
TransformerLV side CT details CTLV
Turns Ratio
Percentage Impedance of Transformer
Fault current at 11 kV Bus as per report
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current
1250/1
PT
Vp
Vs
20000
kVA
110
kV
11
kV
125/1
CTRP 125
1250/1
1250
Z
10.00%
9996
Amps
104.98
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x104.98/0.95
121.55
Isfl
0.97
1
1
Curve
Normal Inverse
1049.76
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x1049.76/0.95
1212.04
=1212.04/1250
Curve
Normal Inverse
9996.00
999.60
0.969632
8.00
10.00
3
Amps
Amps
Amps
Range
50, 60
Setting
50Hz
Prime
Enabled, Disabled
Enabled
Range
Setting
Prime
CT rated primary
CT rated secondary
10..50000 A
1A/5A
150A
1A
PT rated primary
PT rated Secondary
0~132000 V
110230
11000 V
110
Range
Enabled, Disabled
Enabled, Disabled
Setting
Enabled
Enabled
Prime
Range
Enabled, Disabled
Setting
Enabled
Prime
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL Overcurrent element
is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent element is
enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time
150
Range
Enabled, Disabled
Setting
Enabled
1.05
Prime
1500
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault
element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
51N-1 Time Mult (IEC/ANSI) (TEp)
Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
5.2 50N-1
Description
50N-1 Element
Selects whether the DTL derived Earth fault element is
enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time
6 Directional Current Protection :67
Range
Enabled, Disabled
Setting
Enabled
0.05..4.00 A STEP
0.125
0.01
Normal Inverse ,Very Normal Inverse
Inverse ,Extremely
Inverse ,Long Inverse
0.05..3.20 s, oo
0.5
Range
Enabled, Disabled
Setting
Enabled
0.05..25.00 A STEP
0.01
0.00..60.00 s
1.1
6.1 67-1
Description
Range
Setting
67 Element
Enabled, Disabled
Enabled
67 Setting
Pickup level
67 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
18.75
Prime
165
1.45
Prime
-45
Prime
105
6.2 67N-1
Description
67N-1 Element
Selects whether the DTL derived Earth fault element is
Range
Setting
Enabled, Disabled
Enabled
67N-1 Setting
0.05, 0.06 ... 49.5, 50 0.06X In
Pickup level
Gn 67N-1 Delay
0, 0.01 ... 14300, 144000.65
Sets operate delay time
Characteristic Angle
-179.180 deg
-45
7 Breaker failure Protection -CB Fail Supervision : 50LBB
Setting name
Range
Setting
50BF Element
Diasabled/Enabled
Enabled
50BF Setting
0.05..2
0.2 x In
50BF-1 delay
20..60000
100ms
50BF-2 delay
20..60000
250 ms
8 Distance Protection setting 21
Value (Range)
Parameter
Settings
Unom PRIMARY
1.0 .. 1200.0 kV
110
Unom Secondary
80..125
110
CT Primary
10~5000
150
CT Secondary
1A/5A
1
SystemStarpoint
Solid Earthed
Solid Earthed
Peterson-Coil
Isolated
Uph / Udelta
0.10
.. 9.99
1.73
Rated Frequency
50/60 Hz
50 Hz
Phase Seq
L1 L2 L3L1 L3 L2
L1 L2 L3
Distance Unit
km/Miles
km
Full scale volt
1.0~1200
110
Full scale Current
10~5000
150
Line Angle
10~89 deg
67.38
P,Q sign
Not reversedReversed not reversed
R1 Conductor in ohms per km @ 85 deg C
0.16
X1 Conductor in ohms per km
0.0050~9.5
0.39
c'
0.0~100
0.01
Z1 Moose conductor in ohms per km @ 85 deg C
0.42
0.31
R0 Zero seq.Moose conductor in ohms per km @ 85 deg C
0.0050~9.5
1.30
X0 zero seq.Moose conductor in ohms per km
1.34
Z0 Moose conductor in ohms per km @ 85 deg C
Line length
0.1~1000
5
Adj short line
5.22
Adj Long line
16.23
2.10
Line Positive Sequence impedance (mag)
Prime
9
30
Unit
kV
V
A
A
kV
A
deg
ohms/km
ohms/km
mfd / km
ohms/km
ohms/km
ohms/km
ohms/km
km
km
km
Ohms
67.38 deg
0.0050~9.5
0.0050~9.5
Range
Setting
Y/DELT
Y
1Ph / 3Ph
3Ph
2...22 (EXIT)
6
U N = 100 V: 5...100 80
V U N = 230 V:
12...230 V U N = 400
V: 20...400 V
0.32
6.70
76.60
1.01
1.68
67.38
0.25
67.38
0
0.15
1.10
67.38
0.16
67.38
6.83
79.46
1.02
79.46
0.5
1
0.31
0.79
0.73
0.54
0.59
0.70
0.23
0.79
0.44
1.12
1.24
0.05
0.12
Ohms
deg
Ohms
deg
Ohms
deg
sec
Ohms
deg
Ohms
deg
Ohms
deg
Ohms
deg
sec
sec
Units
deg
V
Range
50, 60
Setting
50Hz
Prime
Enabled, Disabled
Enabled
Range
Setting
Prime
CT rated primary
CT rated secondary
10..50000 A
1A/5A
125A
1A
PT rated primary
PT rated Secondary
0~132000 V
110230
11000 V
110
Range
Enabled, Disabled
Enabled, Disabled
Setting
Enabled
Enabled
Prime
Range
Enabled, Disabled
Setting
Enabled
Prime
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL Overcurrent element
is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent element is
enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time
125
Range
Enabled, Disabled
Setting
Enabled
0.9
Prime
1250
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault
element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
51N-1 Time Mult (IEC/ANSI) (TEp)
Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
5.2 50N-1
Description
50N-1 Element
Selects whether the DTL derived Earth fault element is
enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time
6 Differential Protection: 87
Description
Diff.Prot
Pick up value of differential current I-diff>
T I-diff> time delay T I-diff>
Pick up value of High set trip I-diff>>
T I-diff> time delay T I-diff>>
Slope 1 of tripping charecterstic Slope 1
Base point for slope1 of charecterstic Base point 1
Slope 2 of tripping charecterstic Slope 2
Base point for slope2 of charecterstic Base point 2
Pick up for add on stablisation I Add on stab
Duration for add on stablisation T Add on stab
7 RESTRICTED EARTH FAULT PROTECTION 64
Setting name
64R Element
64R Setting
64R-1 delay
8 RESTRICTED EARTH FAULT PROTECTION 51G
Setting name
51G Element
51G Setting
51G-1 delay
Range
Enabled, Disabled
Setting
Enabled
Prime
0.05..4.00 A STEP
0.125
0.01
Normal Inverse ,Very Normal Inverse
Inverse ,Extremely
Inverse ,Long Inverse
0.05..3.20 s, oo
0.5
Range
Enabled, Disabled
Setting
Enabled
0.05..25.00 A STEP
0.01
0.00..60.00 s
1.1
Range
Setting
Range
Diasabled/Enabled
0.05..2
20..60000
Setting
Enabled
0.1 x In
100ms
Range
Diasabled/Enabled
0.05..2
20..60000
Setting
Enabled
0.15 x In
500ms
ON/OFF
0.05..2 I/InO
0.00..60.00 s
0.5..35 I/InO
0.00..60.00 s
0.1..0.5
0.00..2 I/InO
0.25..0.95
0.00..10 I/InO
2..15 I/InO
2..250 Cycles
15.625
Prime
137.5
1.3
ON
0.2
0
8
0
0.3
0
0.7
2.5
4
15
Prime
12.5
18.75
Description
Diff.Prot
Pick up value of differential current I-diff>
T I-diff> time delay T I-diff>
Pick up value of High set trip I-diff>>
T I-diff> time delay T I-diff>>
Slope 1 of tripping charecterstic Slope 1
Base point for slope1 of charecterstic Base point 1
Slope 2 of tripping charecterstic Slope 2
Base point for slope2 of charecterstic Base point 2
Pick up for add on stablisation I Add on stab
Duration for add on stablisation T Add on stab
Range
ON/OFF
0.05..2 I/InO
0.00..60.00 s
0.5..35 I/InO
0.00..60.00 s
0.1..0.5
0.00..2 I/InO
0.25..0.95
0.00..10 I/InO
2..15 I/InO
2..250 Cycles
Setting
50Hz
Prime
Enabled
Setting
Prime
10..50000 A
1A/5A
10..50000 A
1A/5A
10..50000 A
1A/5A
125A
1A
1250A
1A
1250A
1A
0~132000 V
110230
11000 V
110
Setting
Prime
ON
0.2
0
8
0
0.3
0
0.7
2.5
4
15
Range
50, 60
Setting
50Hz
Enabled, Disabled
Enabled
Range
Setting
Prime
CT rated primary
CT rated secondary
10..50000 A
1A/5A
1250A
1A
PT rated primary
PT rated Secondary
0~132000 V
110230
11000 V
110
Range
Enabled, Disabled
Enabled, Disabled
Setting
Enabled
Enabled
Prime
Range
Enabled, Disabled
Setting
Enabled
Prime
Normal InverseIEC
Description
50-1 Element
Selects whether the INST/DTL Overcurrent
element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time
Range
Enabled, Disabled
Setting
Enabled
0.00..60.00 s
0.75
Setting Dependencies
When enabled only active settings are
displayed and all others hidden
2 CT/VT CONFIG
Description
CTs
Prime
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
1250
0.9
Prime
8750
5 DERIVED E/F
5.1 51N-1
Description
Range
Setting
51N-1 Element
Selects whether the 51N-1 IDMTL derived
Earth Fault element is enabled
Enabled, Disabled
Enabled
0.1
Normal Inverse
Range
Enabled, Disabled
Setting
Enabled
0.00..60.00 s
1.15s
Range
Setting
o/v
o/v
5.2 50N-1
Description
50N-1 Element
Selects whether the DTL derived Earth
fault element is enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time
6 Over Voltage Protection :59
Setting name
6.1 59-1 Element 1
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
6.2 59 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All
Prime
125
0.4
Prime
1250
Prim Value
120
3
12000
5
Any
126
1.5
10
Any
12600
Range
Setting
u/v
u/v
8.1 67-1
Description
Range
Setting
67 Element
Enabled, Disabled
Enabled
67 Setting
Pickup level
67 Char
Selects characteristic curve to be IEC or
ANSI
IDMTL
DTL
67
Time
Multor(IEC/ANSI)
Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)
0.9
IEC-NI
Characteristic Angle
-179.180 deg
-45
V Hysteresis
V Block Threshold
V O/P Phases
7.2 27 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
8 Directional Current Protection :67
Prim Value
99
1
9900
3
Any
93.5
1.5
9350
10
Any
0.12
Prime
1125
8.2 67N-1
Description
67N-1 Element
Selects whether the DTL derived Earth fault
element is enabled
Range
Enabled, Disabled
67N-1 Setting
0.05, 0.06 ... 49.5, 50
Pickup level
Gn 67N-1 Delay
0, 0.01 ... 14300, 14400
Sets operate delay time
Characteristic Angle
-179.180 deg
9 Breaker failure Protection -CB Fail Supervision : 50LBB
Setting name
Range
50BF Element
Diasabled/Enabled
50BF Setting
0.05..2
50BF-1 delay
20..60000
50BF-2 delay
20..60000
Setting
Enabled
0.08X In
Prime
187.5
0.5
-45
Setting
Enabled
0.2 x In
100ms
250 ms
250
Range
50, 60
Enabled, Disabled
Setting
50Hz
Enabled
Prime
Range
Setting
Prime
CT rated primary
CT rated secondary
10..50000 A
1A/5A
1250A
1A
PT rated primary
PT rated Secondary
0~132000 V
110230
11000 V
110
Range
Enabled, Disabled
Enabled, Disabled
Setting
Enabled
Enabled
Prime
Range
Enabled, Disabled
0.1..4.00 A STEP 0.1
Normal Inverse ,Very Inverse
,Extremelys,Inverse
,Long
0.05..3.20
oo
Setting
Enabled
0.95
Normal InverseIEC
0.18
Prime
Range
Enabled, Disabled
0.1..25.00 A STEP 0.1
0.00..60.00 s
Setting
Enabled
4
0.7
Prime
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects
whether
51-1
Setting
(Ip)the 51-1 IDMTL
Pickup
level
51-1
Char
Selects
characteristic
curve to
be IEC or
51-1
Time
Mult (IEC/ANSI)
(Tp)
Time
multiplier (applicable to IEC and
4.2 50-1
Description
50-1 Element
Selects
whether
the INST/DTL Overcurrent
50-1 Setting
(I>>)
Pickup
level(T-I>>)
50-1
Delay
Sets operate delay time
1187.5
5000
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
SelectsSetting
whether(IEp)
the 51N-1 IDMTL derived
51N-1
Pickup Char
level
51N-1
Selects
characteristic
curve to(TEp)
be IEC or
51N-1 Time
Mult (IEC/ANSI)
Time50N-1
multiplier (applicable to IEC and
5.2
Description
50N-1 Element
SelectsSetting
whether(IE>>)
the DTL derived Earth
50N-1
Pickup Delay
level (TE>>)
50N-1
Sets
operate
delay
time :59
6
Over
Voltage
Protection
Setting name
6.1 59-1 Element 1
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
6.2 59 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
7 Under Voltage Protection:27
Setting name
7.1 27-1 Element 1
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
Range
Enabled, Disabled
0.05..4.00 A STEP 0.01
Normal Inverse ,Very Inverse
,Extremely
,Long
0.05..3.20 s,Inverse
oo
Setting
Enabled
0.08
direct
1.8
Prime
Range
Enabled, Disabled
0.05..25.00 A STEP 0.01
0.00..60.00 s
Setting
Enabled
1.8
0.01
Prime
Range
Setting
Prim Value
o/v
o/v
Range
Setting
u/v
100
2250
120
3
5
12000
126
1.5
10
12600
Any
Any
Prim Value
99
3
5
Any
9900
7.2 27 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
8 Directional Current Protection :67
8.1 67-1
Description
67 Element
Selects
whether the 51-1 IDMTL Overcurrent
67 Setting
Pickup
67
Charlevel
Selects
curve to be IEC or
67
Timecharacteristic
Mult (IEC/ANSI)
Time multiplierAngle
(applicable to IEC and
Characteristic
8.2 67N-1
Description
67N-1 Element
Selects
whether the DTL derived Earth fault
67N-1 Setting
u/v
Range
Setting
Enabled, Disabled
0.05, 0.06 ... 2.49, 2.5
DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI,
ANSI-EI
0.025,
0.05 ...ANSI-VI,
1.575, 1.6
-179.180 deg
Range
Enabled, Disabled
0.05, 0.06 ... 49.5, 50
Pickup
level
Gn
67N-1
Delay
0, 0.01 ... 14300, 14400
Sets operate delay
Characteristic
Angletime
-179.180 deg
9 Breaker failure Protection -CB Fail Supervision : 50LBB
Setting name
Range
50BF Element
Diasabled/Enabled
50BF Setting
0.05..2
50BF-1 delay
20..60000
50BF-2 delay
20..60000
93.5
1.5
10
9350
Any
Enabled
0.9
IEC-NI
0.12
-45
Setting
Enabled
0.08
0.5
-45
Setting
Enabled
0.2 x In
100ms
250 ms
Prime
1125
Prime
187.5
250
Range
50, 60
Enabled, Disabled
Setting
50Hz
Enabled
Prime
Range
Setting
Prime
CT rated primary
CT rated secondary
10..50000 A
1A/5A
300A
1A
PT rated primary
PT rated Secondary
0~132000 V
110230
11000 V
110
Range
Enabled, Disabled
Enabled, Disabled
Setting
Enabled
Enabled
Prime
Range
Enabled, Disabled
0.1..4.00 A STEP 0.1
Normal Inverse ,Very Inverse
,Extremelys,Inverse
,Long
0.05..3.20
oo
Setting
Enabled
0.9
Normal InverseIEC
0.18
Prime
Range
Enabled, Disabled
0.1..25.00 A STEP 0.1
0.00..60.00 s
Setting
Enabled
4
0.7
Prime
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects
whether
51-1
Setting
(Ip)the 51-1 IDMTL
Pickup
level
51-1
Char
Selects
characteristic
curve to
be IEC or
51-1
Time
Mult (IEC/ANSI)
(Tp)
Time
multiplier (applicable to IEC and
4.2 50-1
Description
50-1 Element
Selects
whether
the INST/DTL Overcurrent
50-1 Setting
(I>>)
Pickup
level(T-I>>)
50-1
Delay
Sets operate delay time
270
1200
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
SelectsSetting
whether(IEp)
the 51N-1 IDMTL derived
51N-1
Pickup Char
level
51N-1
Selects
characteristic
curve to(TEp)
be IEC or
51N-1 Time
Mult (IEC/ANSI)
Time50N-1
multiplier (applicable to IEC and
5.2
Description
50N-1 Element
SelectsSetting
whether(IE>>)
the DTL derived Earth
50N-1
Pickup Delay
level (TE>>)
50N-1
Sets
operate
delay
time :59
6
Over
Voltage
Protection
Setting name
6.1 59-1 Element 1
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
6.2 59 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
7 Under Voltage Protection:27
Setting name
7.1 27-1 Element 1
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
Range
Enabled, Disabled
0.05..4.00 A STEP 0.01
Normal Inverse ,Very Inverse
,Extremely
,Long
0.05..3.20 s,Inverse
oo
Setting
Enabled
0.08
Direct
1.8
Prime
Range
Enabled, Disabled
0.05..25.00 A STEP 0.01
0.00..60.00 s
Setting
Enabled
3.5
0.01
Prime
Range
Setting
Prim Value
o/v
o/v
Range
Setting
u/v
100
4375
120
3
5
12000
126
1.5
10
12600
Any
Any
Prim Value
99
3
5
Any
9900
7.2 27 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
8 Directional Current Protection :67
8.1 67-1
Description
67 Element
Selects
whether the 51-1 IDMTL Overcurrent
67 Setting
Pickup
67
Charlevel
Selects
curve to be IEC or
67
Timecharacteristic
Mult (IEC/ANSI)
Time multiplierAngle
(applicable to IEC and
Characteristic
8.2 67N-1
Description
67N-1 Element
Selects
whether the DTL derived Earth fault
67N-1 Setting
u/v
Range
Setting
Enabled, Disabled
0.05, 0.06 ... 2.49, 2.5
DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI,
ANSI-EI
0.025,
0.05 ...ANSI-VI,
1.575, 1.6
-179.180 deg
Range
Enabled, Disabled
0.05, 0.06 ... 49.5, 50
Pickup
level
Gn
67N-1
Delay
0, 0.01 ... 14300, 14400
Sets operate delay
Characteristic
Angletime
-179.180 deg
9 Breaker failure Protection -CB Fail Supervision : 50LBB
Setting name
Range
50BF Element
Diasabled/Enabled
50BF Setting
0.05..2
50BF-1 delay
20..60000
50BF-2 delay
20..60000
93.5
1.5
10
9350
Any
Enabled
0.9
IEC-NI
0.12
-45
Setting
Enabled
0.08
0.5
-45
Setting
Enabled
0.2 x In
100ms
250 ms
Prime
270
Prime
45
60
Transformer Feeder 750 kVA STP & AFBC FDR 1 & 2 Panel Nos 5, 14&15
Relay type Siemens Reyrolle 7SJ600
1 SYSTEM CONFIG
Description
Range
System Frequency
50, 60
Selects the Power System Frequency from
50 or 60 Hz
Setting Dependencies
When enabled only active settings are
displayed and all others hidden
2 CT/VT CONFIG
Description
CTs
Setting
50Hz
Prime
Enabled, Disabled
Enabled
Range
Setting
Prime
CT rated primary
CT rated secondary
10..50000 A
1A/5A
100A
1A
PT rated primary
PT rated Secondary
0~132000 V
110230
11000 V
110
Range
Enabled, Disabled
Enabled, Disabled
Setting
Enabled
Enabled
Prime
Range
Enabled, Disabled
Setting
Enabled
Prime
0.5
Extremely
Inverse-IEC
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)
4.2 50-1
Description
Range
50-1 Element
Enabled, Disabled
Selects whether the INST/DTL Overcurrent
element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time
50
Setting
Enabled
10
0.00..60.00 s
0.05
Prime
1000
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived
Earth Fault element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
Range
Enabled, Disabled
Setting
Enabled
0.1
Normal Inverse
0.05..3.20 s, oo
0.1
Range
Enabled, Disabled
Setting
Enabled
0.00..60.00 s
0.25s
Prime
10
Prime
100
Transformer Feeder LCSS 1 2000 kVA FDR 1 & 2 Panel Nos 4 & 11
Relay type Siemens Reyrolle 7SJ600
1 SYSTEM CONFIG
Description
Range
System Frequency
50, 60
Selects the Power System Frequency from
50 or 60 Hz
Setting Dependencies
When enabled only active settings are
displayed and all others hidden
2 CT/VT CONFIG
Description
CTs
Setting
50Hz
Prime
Enabled, Disabled
Enabled
Range
Setting
Prime
CT rated primary
CT rated secondary
10..50000 A
1A/5A
125A
1A
PT rated primary
PT rated Secondary
0~132000 V
110230
11000 V
110
Range
Enabled, Disabled
Enabled, Disabled
Setting
Enabled
Enabled
Prime
Range
Enabled, Disabled
Setting
Enabled
Prime
Extremely
Inverse-IEC
Range
Enabled, Disabled
Setting
Enabled
13
0.00..60.00 s
0.05
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent
element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time
125
Prime
1625
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived
Earth Fault element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
Range
Enabled, Disabled
Setting
Enabled
0.1
Normal Inverse
0.05..3.20 s, oo
0.3
Range
Enabled, Disabled
Setting
Enabled
0.8
0.00..60.00 s
0.25s
Prime
12.5
Prime
100
Panel Nos
Range
50, 60
Setting
50Hz
Prime
Enabled, Disabled
Enabled
Range
Setting
Prime
CT rated primary
CT rated secondary
10..50000 A
1A/5A
100A
1A
PT rated primary
PT rated Secondary
0~132000 V
110230
11000 V
110
Range
Enabled, Disabled
Enabled, Disabled
Setting
Enabled
Enabled
Prime
Range
Enabled, Disabled
Setting
Enabled
Prime
0.6
Extremely
Inverse-IEC
Range
Enabled, Disabled
Setting
Enabled
10.5
0.00..60.00 s
0.05
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent
element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time
60
Prime
1050
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived
Earth Fault element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
Range
Enabled, Disabled
Setting
Enabled
0.08
Normal Inverse
0.05..3.20 s, oo
0.3
Range
Enabled, Disabled
Setting
Enabled
0.6
0.00..60.00 s
0.25s
Prime
Prime
60
Range
50, 60
Setting
50Hz
Prime
Enabled, Disabled
Enabled
Range
Setting
Prime
CT rated primary
CT rated secondary
10..50000 A
1A/5A
100A
1A
PT rated primary
PT rated Secondary
0~132000 V
110230
11000 V
110
Range
Enabled, Disabled
Enabled, Disabled
Setting
Enabled
Enabled
Prime
Range
Enabled, Disabled
Setting
Enabled
Prime
0.75
Extremely
Inverse-IEC
Range
Enabled, Disabled
Setting
Enabled
12
0.00..60.00 s
0.05
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent
element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time
75
Prime
1200
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived
Earth Fault element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
Range
Enabled, Disabled
Setting
Enabled
0.08
Normal Inverse
0.05..3.20 s, oo
0.3
Range
Enabled, Disabled
Setting
Enabled
0.8
0.00..60.00 s
0.25s
Prime
Prime
80
Range
50, 60
Setting
50Hz
Prime
Enabled, Disabled
Enabled
Range
Setting
Prime
CT rated primary
CT rated secondary
10..50000 A
1A/5A
800A
1A
PT rated primary
PT rated Secondary
0~132000 V
110230
11000 V
110
Range
Enabled, Disabled
Enabled, Disabled
Setting
Enabled
Enabled
Prime
Range
Enabled, Disabled
Setting
Enabled
Prime
1.15
Normal InverseIEC
Range
Enabled, Disabled
Setting
Enabled
0.00..60.00 s
0.6
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent
element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time
920
0.8
Prime
5600
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived
Earth Fault element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
Range
Enabled, Disabled
Setting
Enabled
0.125
Normal Inverse
0.05..3.20 s, oo
0.4
Range
Enabled, Disabled
Setting
Enabled
0.00..60.00 s
Prime
12.5
Prime
800
Range
50, 60
Setting
50Hz
Prime
Enabled, Disabled
Enabled
Range
Setting
Prime
CT rated primary
CT rated secondary
10..50000 A
1A/5A
150A
1A
PT rated primary
PT rated Secondary
0~132000 V
110230
11000 V
110
Range
Enabled, Disabled
Enabled, Disabled
Setting
Enabled
Enabled
Prime
Range
Enabled, Disabled
Setting
Enabled
Prime
Extremely
Inverse-IEC
Range
Enabled, Disabled
Setting
Enabled
12
0.00..60.00 s
0.05
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent
element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time
150
Prime
1800
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived
Earth Fault element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
Range
Enabled, Disabled
Setting
Enabled
0.125
Normal Inverse
0.05..3.20 s, oo
0.3
Range
Enabled, Disabled
Setting
Enabled
0.9
0.00..60.00 s
0.25s
Prime
18.75
Prime
135
Prime
Enabled, Disabled
Enabled
Range
Setting
Prime
CT rated primary
CT rated secondary
10..50000 A
1A/5A
800A
1A
PT rated primary
PT rated Secondary
0~132000 V
110230
11000 V
110
Range
Enabled, Disabled
Enabled, Disabled
Setting
Enabled
Enabled
Prime
Range
Enabled, Disabled
Setting
Enabled
Prime
1.15
Extremely
Inverse-IEC
Range
Enabled, Disabled
Setting
Enabled
0.00..60.00 s
0.52
Range
Enabled, Disabled
Setting
Enabled
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent
element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived
Earth Fault element is enabled
920
0.65
Prime
4800
Prime
0.11
Normal Inverse
0.05..3.20 s, oo
0.35
Range
Enabled, Disabled
Setting
Enabled
0.95
0.00..60.00 s
0.9s
Description
Range
Setting
0.00..2 I/InO
5.2 50N-1
Description
50N-1 Element
Selects whether the DTL derived Earth
fault element is enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time
88
Prime
760
6 Differential Protection: 87
Diff.Prot
Pick up value of differential current I-diff>
T I-diff> time delay T I-diff>
Pick up value of High set trip I-diff>>
T I-diff> time delay T I-diff>>
Slope 1 of tripping charecterstic Slope 1
ON/OFF
0.05..2 I/InO
0.00..60.00 s
0.5..35 I/InO
0.00..60.00 s
0.1..0.5
0.25..0.95
ON
0.2
0
8
0
0.3
0
0.7
2.5
4
15
Prime
Setting
50Hz
Prime
Enabled, Disabled
Enabled
Range
Setting
Prime
CT rated primary
CT rated secondary
10..50000 A
1A/5A
600A
1A
PT rated primary
PT rated Secondary
0~132000 V
110230
6600 V
110
Range
Enabled, Disabled
Enabled, Disabled
Setting
Enabled
Enabled
Prime
Range
Enabled, Disabled
Setting
Enabled
Prime
0.9
Normal InverseIEC
Range
Enabled, Disabled
Setting
Enabled
0.00..60.00 s
0.15
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC
and ANSI curves but not DTL
selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL
Overcurrent element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time
540
0.7
Prime
4800
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL
derived Earth Fault element is
enabled
51N-1
Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL
Range
Enabled, Disabled
Setting
Enabled
0.1
Normal Inverse
0.05..3.20 s, oo
0.2
Description
Range
Setting
50N-1 Element
Selects whether the DTL derived
Earth fault element is enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time
6 Over Voltage Protection :59
Setting name
6.1 59-1 Element 1
V Operation
V Setting (Ph-N) Gn V Setting (PhPh)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
6.2 59 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (PhPh)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
7 Under Voltage Protection:27
Setting name
7.1 27-1 Element 1
V Operation
V Setting (Ph-N) Gn V Setting (PhPh)
V Delay
Enabled, Disabled
Enabled
0.8
0.00..60.00 s
0.4
Range
Setting
o/v
o/v
Range
Setting
u/v
V Hysteresis
V Block Threshold
V O/P Phases
Prime
60
Prime
480
Prim Value
120
3
5
7200
126
1.5
10
7560
Any
Any
Prim Value
99
1
3
Any
5940
7.2 27 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (PhPh)
V Delay
u/v
93.5
1.5
5610
10
Any
Setting
Enabled
0.2 x In
100ms
250 ms
250
Buscoupler panel
Relay type ABB REF610
1 SYSTEM CONFIG
Description
System Frequency
Selects the Power System
Frequency from 50 or 60 Hz
Setting Dependencies
When enabled only active settings
are displayed and all others hidden
2 CT/VT CONFIG
Description
CTs
Range
50, 60
Setting
50Hz
Prime
Enabled, Disabled
Enabled
Range
Setting
Prime
CT rated primary
CT rated secondary
10..50000 A
1A/5A
600A
1A
PT rated primary
PT rated Secondary
0~132000 V
110230
6600 V
110
Range
Enabled, Disabled
Enabled, Disabled
Setting
Enabled
Enabled
Prime
Range
Enabled, Disabled
Setting
Enabled
Prime
0.9
Normal InverseIEC
Range
Enabled, Disabled
Setting
Enabled
0.00..60.00 s
0.15
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC
and ANSI curves but not DTL
selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL
Overcurrent element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time
540
0.7
Prime
4800
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL
derived Earth Fault element is
enabled
51N-1
Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL
Range
Enabled, Disabled
Setting
Enabled
0.1
Normal Inverse
0.05..3.20 s, oo
0.2
Description
50N-1 Element
Selects whether the DTL derived
Earth fault element is enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time
Range
Enabled, Disabled
Setting
Enabled
0.8
0.00..60.00 s
0.4
Prime
60
Prime
480
Setting
50Hz
Prime
Enabled, Disabled
Enabled
Range
Setting
Prime
CT rated primary
CT rated secondary
10..50000 A
1A/5A
200A
5A
PT rated primary
PT rated Secondary
0~132000 V
110230
6600 V
110
Range
Enabled, Disabled
Enabled, Disabled
Setting
Enabled
Enabled
Prime
Range
Enabled, Disabled
Setting
Enabled
Prime
0.85
Extremely
Inverse-IEC
Range
Enabled, Disabled
Setting
Enabled
10
0.00..60.00 s
0.05
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC
and ANSI curves but not DTL
selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL
Overcurrent element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time
170
Prime
2000
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL
derived Earth Fault element is
enabled
51N-1
Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL
Range
Enabled, Disabled
Setting
Enabled
0.08
Normal Inverse
0.05..3.20 s, oo
0.1
Description
50N-1 Element
Selects whether the DTL derived
Earth fault element is enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time
Range
Enabled, Disabled
Setting
Enabled
0.8
0.00..60.00 s
0.25s
Prime
16
Prime
160
Transformer Feeder 1600 kVA BALLING SYSTEM FDR1 &2 Panels No__& __
Relay type ABB REF 610
1 SYSTEM CONFIG
Description
Range
Setting
System Frequency
50, 60
50Hz
Selects the Power System
Frequency from 50 or 60 Hz
Setting Dependencies
When enabled only active settings
are displayed and all others hidden
2 CT/VT CONFIG
Description
CTs
Prime
Enabled, Disabled
Enabled
Range
Setting
Prime
CT rated primary
CT rated secondary
10..50000 A
1A/5A
200A
5A
PT rated primary
PT rated Secondary
0~132000 V
110230
6600 V
110
Range
Enabled, Disabled
Enabled, Disabled
Setting
Enabled
Enabled
Prime
Range
Enabled, Disabled
Setting
Enabled
Prime
0.85
Extremely
Inverse-IEC
Range
Enabled, Disabled
Setting
Enabled
10
0.00..60.00 s
0.05
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC
and ANSI curves but not DTL
selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL
Overcurrent element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time
170
Prime
2000
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL
derived Earth Fault element is
enabled
51N-1
Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL
Range
Enabled, Disabled
Setting
Enabled
0.08
Normal Inverse
0.05..3.20 s, oo
0.1
Description
50N-1 Element
Selects whether the DTL derived
Earth fault element is enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time
Range
Enabled, Disabled
Setting
Enabled
0.8
0.00..60.00 s
0.25s
Prime
16
Prime
160
Transformer Feeder 1000 kVA SCREENING MCC FDR 1 &2 Panels No__& __
Relay type ABB REF 610
1 SYSTEM CONFIG
Description
Range
Setting
System Frequency
50, 60
50Hz
Selects the Power System
Frequency from 50 or 60 Hz
Setting Dependencies
When enabled only active settings
are displayed and all others hidden
2 CT/VT CONFIG
Description
CTs
Prime
Enabled, Disabled
Enabled
Range
Setting
Prime
CT rated primary
CT rated secondary
10..50000 A
1A/5A
150A
5A
PT rated primary
PT rated Secondary
0~132000 V
110230
6600 V
110
Range
Enabled, Disabled
Enabled, Disabled
Setting
Enabled
Enabled
Prime
Range
Enabled, Disabled
Setting
Enabled
Prime
0.7
Extremely
Inverse-IEC
Range
Enabled, Disabled
Setting
Enabled
12
0.00..60.00 s
0.05
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC
and ANSI curves but not DTL
selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL
Overcurrent element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time
105
Prime
1800
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL
derived Earth Fault element is
enabled
51N-1
Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL
Range
Enabled, Disabled
Setting
Enabled
0.1
Normal Inverse
0.05..3.20 s, oo
0.1
Description
50N-1 Element
Selects whether the DTL derived
Earth fault element is enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time
Range
Enabled, Disabled
Setting
Enabled
0.9
0.00..60.00 s
0.25s
Prime
15
Prime
135
Transformer Feeder 1000 kVA PROPORTION & MIXING MCC FDR1 &2 Panels No__& __
Relay type ABB REF 610
1 SYSTEM CONFIG
Description
Range
Setting
Prime
System Frequency
50, 60
50Hz
Selects the Power System
Frequency from 50 or 60 Hz
Setting Dependencies
When enabled only active settings
are displayed and all others hidden
2 CT/VT CONFIG
Description
CTs
Enabled, Disabled
Enabled
Range
Setting
Prime
CT rated primary
CT rated secondary
10..50000 A
1A/5A
300A
5A
PT rated primary
PT rated Secondary
0~132000 V
110230
6600 V
110
Range
Enabled, Disabled
Enabled, Disabled
Setting
Enabled
Enabled
Prime
Range
Enabled, Disabled
Setting
Enabled
Prime
0.35
Extremely
Inverse-IEC
Range
Enabled, Disabled
Setting
Enabled
0.00..60.00 s
0.05
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC
and ANSI curves but not DTL
selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL
Overcurrent element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time
105
Prime
1800
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL
derived Earth Fault element is
enabled
51N-1
Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL
Range
Enabled, Disabled
Setting
Enabled
0.05
Normal Inverse
0.05..3.20 s, oo
0.1
Description
50N-1 Element
Selects whether the DTL derived
Earth fault element is enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time
Range
Enabled, Disabled
Setting
Enabled
0.45
0.00..60.00 s
0.25s
Prime
15
Prime
135
Setting
50Hz
Enabled
Prime
Setting
Prime
10..50000 A
1A/5A
150A
5A
0~132000 V
110230
6600 V
110
Setting
Enabled
Enabled
Prime
Setting
Enabled
0.4
Normal Inverse
0.2
Prime
Setting
Enabled
12
0.05
Prime
60
1800
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects
whether(IEp)
the 51N-1 IDMTL
51N-1 Setting
Pickup Char
level
51N-1
SelectsTime
characteristic
curve to(TEp)
be
51N-1
Mult (IEC/ANSI)
Time50N-1
multiplier (applicable to IEC
5.2
Description
50N-1 Element
SelectsSetting
whether(IE>>)
the DTL derived
50N-1
Pickup Delay
level (TE>>)
50N-1
Sets
operate
delay time
6 OVER
VOLTAGE
PROTECTION :59
Setting name
6.1 59-1 Element 1
V Operation
V Setting (Ph-N) Gn V Setting (PhPh)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
6.2 59 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (PhPh)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
Range
Enabled, Disabled
0.05..4.00 A STEP 0.01
Normal Inverse ,Very Inverse
,Extremelys,Inverse
,Long
0.05..3.20
oo
Setting
Enabled
0.05
Normal Inverse
0.2
Prime
Range
Enabled, Disabled
0.05..25.00 A STEP 0.01
0.00..60.00 s
Setting
Enabled
0.5
0.25s
Prime
Range
Setting
Prim Value
o/v
o/v
7.5
75
126.5
1
5
7590
132
0.5
10
7920
Any
Any
7 UNBALANCE PROTECTION : 46
Parameter
Value (Range)
Set Value
Set Units
0.1 xIn
1s
0.2 xIn
1
10 Volts
1 sec
Motor Feeders 315kW Panel Nos 1 &17 Relay: ABB REM 615
ANTI HEAT FAN 1 &2
1. Available motor data
Size
Value
Power
Rated voltage
Motor rated current IA
Max. starting current (at 100 % Vn)
Starting time (at 100% Vn
Starting time (at 80% Vn
Heating time constant
Cooling time constant at standstill
Max. continuous thermal rating current
Max. blocked rotor time HOT
Max. blocked rotor time COLD
Locked rotor Current
Permissible max.accelerating time (WITH LOAD )
General power system data
Parameter
315
6.6
32.87
6X IA
1.7
3.2
45
240
34.5135
10
20
197.22
1.7
units
kW
kV
A
sec
sec
min
min
A
sec
sec
A
sec
Value
Unit
100
1
50
1
A
A
A
A
0.01
Set Value
0.35
Step
1.00%
1.00%
0.1
Step
0.01
0.01
80%
70%
2
Set Value
0.1
0.05
Step
1
0.1
0.1
0.1
Step
Set Value
2.7
0.05
0.4
2.7
IEC-VI
0.01
0.1
0.01
0.1
Set Value
0.1
1
0.2
1
1
0.1
Set Value
15
1
1
1
5
1
1
Set Value
3
2
60
20
20
0.01
1
2
4
Step
Step
Motor Feeders 1000kW Panel Nos 1 &17 Relay: ABB REM 615
ID FAN 1
1. Available motor data
Size
Value
Power
Rated voltage
Motor rated current IA
Max. starting current (at 100 % Vn)
Starting time (at 100% Vn
Starting time (at 80% Vn
Heating time constant
Cooling time constant at standstill
Max. continuous thermal rating current
Max. blocked rotor time HOT
Max. blocked rotor time COLD
Locked rotor Current
Permissible max.accelerating time (WITH LOAD )
General power system data
Parameter
1000
6.6
105.39
6X IA
1.7
3.2
45
240
110.6595
10
20
632.34
1.7
units
kW
kV
A
sec
sec
min
min
A
sec
sec
A
sec
Value
Unit
150
1
50
1
A
A
A
A
0.01
Set Value
0.75
Step
1.00%
1.00%
0.1
Step
0.01
0.01
80%
70%
2
Set Value
0.1
0.05
Parameter
Value (Range)
Current set I>>
0.5 to 40
Time delay t>>
0-150
Current set I>
0.1 to 25
Time delay t> ( tms)
0.1 -3.2
Curve
IEC-NI,IEC-EI,IEC-VI
Unbalance Protection ( ANSI 46)
Parameter
Value (Range)
Current Set I2>
0.04 to 0.8 In
Time delay
0.02 to 99.9
Current Set I2>>
0.04 to 0.8 In
Time Multiple setting ( TMS) I2>>
0.2 to 2
Ph:AS (Load Assymetry) (ANSi 47)
Parameter
Value (Range)
Current set
15 to 50%
Time delay
0.02 to 99.9
Number of permitted starts (ANSI 66)
Parameter
Value (Range)
Number of Cold Starts
0-5
Number of Hot Starts
0-5
T reference
10-120 mins
Restart Inhibition time
1-120 mins
Time between 2 Start ups
1-120 mins
Locked Rotor Protection ( ANSI 51LR/50s)
Current set
0.5 to 5 In
Time Delay for prolonged start:
1 to 60 s
Step
1
0.1
0.1
0.1
Step
Set Value
5.5
0.05
0.77
3
IEC-VI
0.01
0.1
0.01
0.1
Set Value
0.1
1
0.2
1
1
0.1
Set Value
15
1
1
1
5
1
1
Set Value
3
2
60
20
20
0.01
1
4.5
4
Step
Step
Range
50, 60
Setting
50Hz
Prime
Range
Setting
Prime
1500A
1A
6600 V
110
Range
Setting
Enabled, Disabled Enabled
Prime
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL Overcurrent element
is enabled
0.1..4.00 A STEP
0.1
Normal Inverse
,Very Inverse
,Extremely
Inverse ,Long
Inverse
0.05..3.20 s, oo
0.5
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent element is
enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time
Range
Setting
Enabled, Disabled Enabled
Prime
1500
Normal
Inverse-IEC
Range
Setting
Enabled, Disabled Enabled
Prime
6750
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault
element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
V Hysteresis
V Block Threshold
V O/P Phases
6.2 59 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
Range
Setting
Enabled, Disabled Enabled
Prime
120
0.35
Range
Setting
Enabled, Disabled Enabled
0.05..25.00 A
STEP 0.01
0.00..60.00 s
0.8
Range
Setting
Prime
1200
0.7
Prim Value
120
3
7200
126
1.5
10
7560
V Hysteresis
V Block Threshold
V O/P Phases
7.2 27 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
Range
Setting
Prim Value
99
1
5940
Any
5610
250
150
15
Transformer Feeder 1250 kVA LCSS1 ,LCSS3& Spare Panels No 2,3,6,14 &15
Relay type Siemens Reyrolle 7SJ600
1 SYSTEM CONFIG
Description
Range
Setting
System Frequency
Selects the Power System Frequency from 50 or 60 Hz
Setting Dependencies
When enabled only active settings are displayed and
all others hidden
50, 60
2 CT/VT CONFIG
Description
CTs
Range
Prime
50Hz
Setting
Prime
125A
1A
6600 V
110
Range
Setting
Enabled, Disabled Enabled
Enabled, Disabled Enabled
Prime
Range
Setting
Enabled, Disabled Enabled
Prime
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL Overcurrent element
is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent element is
enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time
0.1..4.00 A STEP
0.1
Normal Inverse
,Very Inverse
,Extremely
Inverse ,Long
Inverse
0.05..3.20 s, oo
125
Extremely
Inverse-IEC
Range
Setting
Enabled, Disabled Enabled
0.1..25.00 A STEP 17
0.1
0.00..60.00 s
0.05
Prime
2550
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault
element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
51N-1 Time Mult (IEC/ANSI) (TEp)
Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
5.2 50N-1
Description
50N-1 Element
Selects whether the DTL derived Earth fault element is
enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time
Range
Setting
Enabled, Disabled Enabled
Range
Setting
Enabled, Disabled Enabled
0.05..25.00 A
STEP 0.01
0.00..60.00 s
1
0.25s
Prime
12.5
Prime
125
Range
50, 60
Setting
50Hz
Prime
Range
Setting
Prime
600A
1A
6600 V
110
Range
Setting
Enabled, Disabled Enabled
Enabled, Disabled Enabled
Prime
Range
Setting
Enabled, Disabled Enabled
Prime
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL Overcurrent element
is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent element is
enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time
0.1..4.00 A STEP
0.1
Normal Inverse
,Very Inverse
,Extremely
Inverse ,Long
Inverse
0.05..3.20 s, oo
600
Extremely
Inverse-IEC
0.7
Range
Setting
Enabled, Disabled Enabled
0.1..25.00 A STEP 10
0.1
0.00..60.00 s
0.3
Prime
6000
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault
element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
51N-1 Time Mult (IEC/ANSI) (TEp)
Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
5.2 50N-1
Description
50N-1 Element
Selects whether the DTL derived Earth fault element is
enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time
Range
Setting
Enabled, Disabled Enabled
Prime
Range
Setting
Enabled, Disabled Enabled
0.05..25.00 A
STEP 0.01
0.00..60.00 s
0.9
0.55s
75
Prime
540
Range
50, 60
Setting
50Hz
Prime
Range
Setting
Prime
750 A
1A
6600 V
110
Range
Setting
Enabled, Disabled Enabled
Enabled, Disabled Enabled
Prime
Range
Setting
Enabled, Disabled Enabled
Prime
PTs
3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL Overcurrent element
is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent element is
enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time
0.1..4.00 A STEP
0.1
Normal Inverse
,Very Inverse
,Extremely
Inverse ,Long
Inverse s, oo
0.05..3.20
750
Extremely
Inverse-IEC
0.6
Range
Setting
Enabled, Disabled Enabled
0.1..25.00 A STEP 8
0.1
0.00..60.00 s
0.3
Prime
6000
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault
element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
51N-1 Time Mult (IEC/ANSI) (TEp)
Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
5.2 50N-1
Range
Setting
Enabled, Disabled Enabled
Prime
Description
Range
50N-1 Element
Selects whether the DTL derived Earth fault element is
enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time
0.05..25.00 A
STEP 0.01
0.00..60.00 s
Setting
0.8
0.55
60
Prime
600
Size
Power
Rated voltage
Motor rated current IA
Max. starting current (at 100 % Vn)
Starting time (at 100% Vn
Starting time (at 80% Vn
Heating time constant
Cooling time constant at standstill
Max. continuous thermal rating current
Max. blocked rotor time HOT
Max. blocked rotor time COLD
Locked rotor Current
Permissible max.accelerating time (WITH LOAD )
General power system data
Value
Parameter
2600
6.6
294
6X IA
1.7
3.2
45
240
308.7
10
20
1764
1.7
units
kW
kV
A
sec
sec
min
min
A
sec
sec
A
sec
Value
Unit
400
1
50
1
A
A
A
A
0.01
Set Value
0.77
Step
1.00%
1.00%
0.1
Step
0.01
0.01
80%
70%
2
Set Value
0.1
0.05
Value (Range)
Step
0.5 to 40
0-150
0.1 to 25
0.1 -3.2
IEC-NI,IEC-EI,IEC-VI
Value (Range)
0.04 to 0.8 In
0.02 to 99.9
0.04 to 0.8 In
0.2 to 2
Step
Value (Range)
15 to 50%
0.02 to 99.9
Step
Value (Range)
0-5
0-5
10-120 mins
1-120 mins
1-120 mins
Step
0.5 to 5 In
1 to 60 s
1
0.1
0.1
0.1
Set Value
5.8
0.05
0.8
2
IEC-VI
0.01
0.1
0.01
0.1
Set Value
0.1
1
0.2
1
1
0.1
Set Value
15
1
1
1
5
1
1
Set Value
3
2
60
20
20
0.01
1
4.4
4
Location of
Device
device
description
and release
Sevice ID
Breaker Set
Current In
SETTING
RANGE
IR=In X
Long time
Pick up
Current
setting (I1)
Primary
Current
Setting
range for
time-lag
class tR at
I2t
Setting
range
Isd =
Short time
Pick up
Current
Settint (Isd)
Primary
Current
Setting
range for
delay time
tsd in ms
Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms
Primary
Current
Ground-fault protection
Setting
range of
the
operating
current Ig
Operating
current
setting Ig
Primary
Current
Setting
range of
the delay
time tg in
ms
Delay time
tg in ms
In ...
1F1
3200A
INCOMER 1
ACB,ETU45
3F1
3200A
INCOMER 2
ACB,ETU45
2F1
3200A
BUSCOUPLER
ACB,ETU45
2500 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
2500 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
2500 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
2500 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
5000 100-200300-400
100 1.5-2.2-34-6-8-1012
15000 A-B-C-D-E
100-200300-400500
100
2500 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
5000 100-200300-400
100 1.5-2.2-34-6-8-1012
15000 A-B-C-D-E
100-200300-400500
100
0.8
2000 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
1.25
3125 100-200300-400
100 1.5-2.2-34-6-8-1012
10000 A-B-C-D-E
100-200300-400500
100
Location of
Device
device
description
and release
Sevice ID
Breaker Set
Current In
OVERLOAD PROTECTION
SETTING
RANGE
IR=In X
Long time
Pick up
Current
setting (I1)
Primary
Current
Setting
range for
time-lag
class tR at
I2t
Setting
range
Isd =
Short time
Pick up
Current
Settint (Isd)
Primary
Current
Setting
range for
delay time
tsd in ms
Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms
Primary
Current
Ground-fault protection
Setting
range of
the
operating
current Ig
Operating
current
setting Ig
Primary
Current
Setting
range of
the delay
time tg in
ms
Delay time
tg in ms
In ...
1F1
1600A
INCOMER 1
ACB,ETU45
3F1
1600A
INCOMER 2
ACB,ETU45
2F1
1600A
BUSCOUPLER
ACB,ETU45
1600 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1600 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1600 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1600 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
3200 100-200300-400
100 1.5-2.2-34-6-8-1012
9600 A-B-C-D-E
100-200300-400500
100
1600 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
3200 100-200300-400
100 1.5-2.2-34-6-8-1012
9600 A-B-C-D-E
100-200300-400500
100
0.65
1040 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
1.25
2000 100-200300-400
100 1.5-2.2-34-6-8-1012
6400 A-B-C-D-E
100-200300-400500
100
Location of
Device
device
description
and release
Sevice ID
Breaker Set
Current In
OVERLOAD PROTECTION
SETTING
RANGE
IR=In X
Long time
Pick up
Current
setting (I1)
Primary
Current
Setting
range for
time-lag
class tR at
I2t
Setting
range
Isd =
Short time
Pick up
Current
Settint (Isd)
Primary
Current
Setting
range for
delay time
tsd in ms
Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms
Primary
Current
Ground-fault protection
Setting
range of
the
operating
current Ig
Operating
current
setting Ig
Primary
Current
Setting
range of
the delay
time tg in
ms
Delay time
tg in ms
In ...
1F1
3200A
INCOMER 1
ACB,ETU45
3F1
3200A
INCOMER 2
ACB,ETU45
2F1
3200A
BUSCOUPLER
ACB,ETU45
2500 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
2500 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
2500 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
2500 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
5000 100-200300-400
100 1.5-2.2-34-6-8-1012
15000 A-B-C-D-E
100-200300-400500
100
2500 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
5000 100-200300-400
100 1.5-2.2-34-6-8-1012
15000 A-B-C-D-E
100-200300-400500
100
0.8
2000 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
1.25
3125 100-200300-400
100 1.5-2.2-34-6-8-1012
10000 A-B-C-D-E
100-200300-400500
100
Location of
Device
device
description
and release
Sevice ID
Breaker Set
Current In
OVERLOAD PROTECTION
SETTING
RANGE
IR=In X
Long time
Pick up
Current
setting (I1)
Primary
Current
Setting
range for
time-lag
class tR at
I2t
Setting
range
Isd =
Short time
Pick up
Current
Settint (Isd)
Primary
Current
Setting
range for
delay time
tsd in ms
Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms
Primary
Current
Ground-fault protection
Setting
range of
the
operating
current Ig
Operating
current
setting Ig
Primary
Current
Setting
range of
the delay
time tg in
ms
Delay time
tg in ms
In ...
1F1
1600A
INCOMER 1
ACB,ETU45
3F1
1600A
INCOMER 2
ACB,ETU45
2F1
1600A
BUSCOUPLER
ACB,ETU45
1600 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1600 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1600 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1600 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
3200 100-200300-400
100 1.5-2.2-34-6-8-1012
9600 A-B-C-D-E
100-200300-400500
100
1600 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
3200 100-200300-400
100 1.5-2.2-34-6-8-1012
9600 A-B-C-D-E
100-200300-400500
100
0.65
1040 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
1.25
2000 100-200300-400
100 1.5-2.2-34-6-8-1012
6400 A-B-C-D-E
100-200300-400500
100
Location of
Device
device
description
and release
Sevice ID
Breaker Set
Current In
OVERLOAD PROTECTION
SETTING
RANGE
IR=In X
Long time
Pick up
Current
setting (I1)
Primary
Current
Setting
range for
time-lag
class tR at
I2t
Setting
range
Isd =
Short time
Pick up
Current
Settint (Isd)
Primary
Current
Setting
range for
delay time
tsd in ms
Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms
Primary
Current
Ground-fault protection
Setting
range of
the
operating
current Ig
Operating
current
setting Ig
Primary
Current
Setting
range of
the delay
time tg in
ms
Delay time
tg in ms
In ...
1F1
2000A
INCOMER 1
ACB,ETU45
3F1
2000A
INCOMER 2
ACB,ETU45
2F1
2000A
BUSCOUPLER
ACB,ETU45
2000 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
2000 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
2000 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
2000 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
4000 100-200300-400
100 1.5-2.2-34-6-8-1012
12000 A-B-C-D-E
100-200300-400500
100
2000 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
4000 100-200300-400
100 1.5-2.2-34-6-8-1012
12000 A-B-C-D-E
100-200300-400500
100
0.65
1300 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
1.25
2500 100-200300-400
100 1.5-2.2-34-6-8-1012
8000 A-B-C-D-E
100-200300-400500
100
Location of
Device
device
description
and release
Sevice ID
Breaker Set
Current In
OVERLOAD PROTECTION
SETTING
RANGE
IR=In X
Long time
Pick up
Current
setting (I1)
Primary
Current
Setting
range for
time-lag
class tR at
I2t
Setting
range
Isd =
Short time
Pick up
Current
Settint (Isd)
Primary
Current
Setting
range for
delay time
tsd in ms
Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms
Primary
Current
Ground-fault protection
Setting
range of
the
operating
current Ig
Operating
current
setting Ig
Primary
Current
Setting
range of
the delay
time tg in
ms
Delay time
tg in ms
In ...
1F1
3200A
INCOMER 1
ACB,ETU45
3F1
3200A
INCOMER 2
ACB,ETU45
2F1
3200A
BUSCOUPLER
ACB,ETU45
3200 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
3200 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
3200 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
3200 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
6400 100-200300-400
100 1.5-2.2-34-6-8-1012
19200 A-B-C-D-E
100-200300-400500
100
3200 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
6400 100-200300-400
100 1.5-2.2-34-6-8-1012
19200 A-B-C-D-E
100-200300-400500
100
0.8
2560 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
1.25
4000 100-200300-400
100 1.5-2.2-34-6-8-1012
12800 A-B-C-D-E
100-200300-400500
100
Location of
Device
device
description
and release
Sevice ID
Breaker Set
Current In
OVERLOAD PROTECTION
SETTING
RANGE
IR=In X
Long time
Pick up
Current
setting (I1)
Primary
Current
Setting
range for
time-lag
class tR at
I2t
Setting
range
Isd =
Short time
Pick up
Current
Settint (Isd)
Primary
Current
Setting
range for
delay time
tsd in ms
Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms
Primary
Current
Ground-fault protection
Setting
range of
the
operating
current Ig
Operating
current
setting Ig
Primary
Current
Setting
range of
the delay
time tg in
ms
Delay time
tg in ms
In ...
1F1
2000A
INCOMER 1
ACB,ETU45
3F1
2000A
INCOMER 2
ACB,ETU45
2F1
2000A
BUSCOUPLER
ACB,ETU45
2000 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
2000 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
2000 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
2000 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
4000 100-200300-400
100 1.5-2.2-34-6-8-1012
12000 A-B-C-D-E
100-200300-400500
100
2000 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
4000 100-200300-400
100 1.5-2.2-34-6-8-1012
12000 A-B-C-D-E
100-200300-400500
100
0.65
1300 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
1.25
2500 100-200300-400
100 1.5-2.2-34-6-8-1012
8000 A-B-C-D-E
100-200300-400500
100
Location of
Device
device
description
and release
Sevice ID
Breaker Set
Current In
OVERLOAD PROTECTION
SETTING
RANGE
IR=In X
Long time
Pick up
Current
setting (I1)
Primary
Current
Setting
range for
time-lag
class tR at
I2t
Setting
range
Isd =
Short time
Pick up
Current
Settint (Isd)
Primary
Current
Setting
range for
delay time
tsd in ms
Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms
Primary
Current
Ground-fault protection
Setting
range of
the
operating
current Ig
Operating
current
setting Ig
Primary
Current
Setting
range of
the delay
time tg in
ms
Delay time
tg in ms
In ...
1F1
1600A
INCOMER 1
ACB,ETU45
3F1
1600A
INCOMER 2
ACB,ETU45
2F1
1600A
BUSCOUPLER
ACB,ETU45
1600 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1600 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1600 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1600 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
3200 100-200300-400
100 1.5-2.2-34-6-8-1012
9600 A-B-C-D-E
100-200300-400500
100
1600 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
3200 100-200300-400
100 1.5-2.2-34-6-8-1012
9600 A-B-C-D-E
100-200300-400500
100
0.65
1040 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
1.25
2000 100-200300-400
100 1.5-2.2-34-6-8-1012
6400 A-B-C-D-E
100-200300-400500
100
Location of
Device
device
description
and release
Sevice ID
Breaker Set
Current In
OVERLOAD PROTECTION
SETTING
RANGE
IR=In X
Long time
Pick up
Current
setting (I1)
Primary
Current
Setting
range for
time-lag
class tR at
I2t
Setting
range
Isd =
Short time
Pick up
Current
Settint (Isd)
Primary
Current
Setting
range for
delay time
tsd in ms
Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms
Primary
Current
Ground-fault protection
Setting
range of
the
operating
current Ig
Operating
current
setting Ig
Primary
Current
Setting
range of
the delay
time tg in
ms
Delay time
tg in ms
In ...
1F1
1250A
INCOMER 1
ACB,ETU45
3F1
1250A
INCOMER 2
ACB,ETU45
2F1
1250A
BUSCOUPLER
ACB,ETU45
1250 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1250 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1250 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
0.5
625 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
2500 100-200300-400
100 1.5-2.2-34-6-8-1012
7500 A-B-C-D-E
100-200300-400500
100
0.5
625 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
2500 100-200300-400
100 1.5-2.2-34-6-8-1012
7500 A-B-C-D-E
100-200300-400500
100
0.65
812.5 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
1.25
1562.5 100-200300-400
100 1.5-2.2-34-6-8-1012
5000 A-B-C-D-E
100-200300-400500
100
Location of
Device
device
description
and release
Sevice ID
Breaker Set
Current In
OVERLOAD PROTECTION
SETTING
RANGE
IR=In X
Long time
Pick up
Current
setting (I1)
Primary
Current
Setting
range for
time-lag
class tR at
I2t
Setting
range
Isd =
Short time
Pick up
Current
Settint (Isd)
Primary
Current
Setting
range for
delay time
tsd in ms
Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms
Primary
Current
Ground-fault protection
Setting
range of
the
operating
current Ig
Operating
current
setting Ig
Primary
Current
Setting
range of
the delay
time tg in
ms
Delay time
tg in ms
In ...
1F1
1250A
INCOMER 1
ACB,ETU45
3F1
1250A
INCOMER 2
ACB,ETU45
2F1
1250A
BUSCOUPLER
ACB,ETU45
1250 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1250 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1250 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
0.5
625 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
2500 100-200300-400
100 1.5-2.2-34-6-8-1012
7500 A-B-C-D-E
100-200300-400500
100
0.5
625 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
2500 100-200300-400
100 1.5-2.2-34-6-8-1012
7500 A-B-C-D-E
100-200300-400500
100
0.35
437.5 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
1.25
1562.5 100-200300-400
100 1.5-2.2-34-6-8-1012
5000 A-B-C-D-E
100-200300-400500
100
Location of
Device
device
description
and release
Sevice ID
Breaker Set
Current In
OVERLOAD PROTECTION
SETTING
RANGE
IR=In X
Long time
Pick up
Current
setting (I1)
Primary
Current
Setting
range for
time-lag
class tR at
I2t
Setting
range
Isd =
Short time
Pick up
Current
Settint (Isd)
Primary
Current
Setting
range for
delay time
tsd in ms
Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms
Primary
Current
Ground-fault protection
Setting
range of
the
operating
current Ig
Operating
current
setting Ig
Primary
Current
Setting
range of
the delay
time tg in
ms
Delay time
tg in ms
In ...
1F1
4000A
INCOMER 1
ACB,ETU45
3F1
4000A
INCOMER 2
ACB,ETU45
2F1
4000A
BUSCOUPLER
ACB,ETU45
4000 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
4000 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
4000 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
4000 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
8000 100-200300-400
100 1.5-2.2-34-6-8-1012
24000 A-B-C-D-E
100-200300-400500
100
4000 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
8000 100-200300-400
100 1.5-2.2-34-6-8-1012
24000 A-B-C-D-E
100-200300-400500
100
0.8
3200 2-3.5-5.58-10-1417-21-2530 s
2 1.25-1.5-22.5-3-4-68-10-12 x
In
1.25
5000 100-200300-400
100 1.5-2.2-34-6-8-1012
16000 A-B-C-D-E
100-200300-400500
100
Range
Setting
Prime
CT rated primary
CT rated secondary
CT rated primary
CT rated secondary
10..50000 A
1A/5A
10..50000 A
1A/5A
3000
5A
3000
5A
Range
Diasabled/Enabled
0.05..2
20..60000
Setting
Enabled
0.1 x In
100ms
Range
Diasabled/Enabled
0.05..2
20..60000
Setting
Enabled
0.15 x In
500ms
Range
Setting
Prime
CT rated primary
CT rated secondary
CT rated primary
CT rated secondary
10..50000 A
1A/5A
10..50000 A
1A/5A
2000
5A
2000
5A
Range
Diasabled/Enabled
0.05..2
20..60000
Setting
Enabled
0.1 x In
100ms
Range
Diasabled/Enabled
0.05..2
20..60000
Setting
Enabled
0.15 x In
500ms
300
450
200
300
TIME CURRENT
CHARACTERISTIC
CURVES
10000
1000
TG_IC
AH17
AH01 BC
AH03
4F1:LBDS1
100
6.6kV_LBSS1_IC1
INT.PANEL
PELLET PLANT 1
GCB
TR_CB
10
LINE_CB
Time in Seconds
20000.0 KVA
Transformer
1600.0 KVA
Transformer
.01
.1
Inrush TG_TR
.5
10
100
Current in Amperes X 10
Time-Current Characteristic Curves
15000.0 KVA
Transformer
Inrush INRUSH
15 MVA 20MVA
1000
10000
12-27-2014
22:40:53
newjanki_06122014
10000
1000
192
AH17
AH03
100
4F1:LBDS1
6.6kV_LBSS1_IC1
INT.PANEL
PELLET PLANT 1
GCB
TR_CB
.01
.1
Time in Seconds
10
LINE_CB
.5
10
100
Current in Amperes
Time-Current Characteristic Curves
1000
10000
12-27-2014
22:40:06
newjanki_06122014
10000
1000
100
GCB
Time in Seconds
10
TR_CB
A
20000.0 KVA
Transformer
.01
.1
INRUSH 1000kVA
.5
10
100
Current in Amperes X 10
Time-Current Characteristic Curves
INRUSH 20MVA
1000
10000
12-27-2014
22:32:01
newjanki_06122014
10000
1000
100
TR_CB
.01
.1
Time in Seconds
10
GCB
.5
10
100
Current in Amperes
Time-Current Characteristic Curves
1000
10000
12-27-2014
22:33:07
newjanki_06122014
10000
1000
2600kW
1F1:HT MOTOR
100
6.6kV_LBSS1_IC1
.01
.1
Time in Seconds
10
.5
10
100
Current in Amperes X 10
Time-Current Characteristic Curves
1000
10000
12-27-2014
22:27:46
newjanki_06122014
10000
1000
AH FAN1_315kW
100
AH21
AH03
S
.01
.1
Time in Seconds
10
.5
10
100
Current in Amperes X 10
Time-Current Characteristic Curves
1000
10000
12-27-2014
22:25:49
newjanki_06122014
10000
1000
100
IDFAN_1000kW
AH19
AH03
S
.01
.1
Time in Seconds
10
.5
10
100
Current in Amperes X 10
Time-Current Characteristic Curves
1000
10000
12-27-2014
22:23:40
newjanki_06122014