Protection Coordination Report

Owner

JANKI CORPN LTD

Project:

JANKI CORPN LTD.,


STEEL DIVISION ,SIDIGINAMOLA VILLAGE,BELLARYI

Compiled by

Interface Electronics Pvt Ltd,Chennai


Email:ife@vsnl.com
website:www.ifepwrana.com
mobile:9884370326

Contents
Sl.No Descriptiion

Page No

Executive Summary

Reference Documents

Single Line Diagram

Short circuit Report Grid

Device Details

11

Transformer Relay Setting Calculations

12

Setting Details for Relay and Control Panel

24

Setting Details for 11 kV HT Switch Board

32

Setting Details for 6.6

57

10

Setting Details for LT PCC/ MCC

89

11

Time Current Characteristic Curves

102

12

Observation and Comments

109

kV HT Switch Board

Executive Summary
Introduction
Project:
Owner:
ElectricalDistribution System

Power System Data

1x 15 MW Captive Power Plant at Janki Corpn Ltd,Bellary


JCL Janki Corpn Ltd Steel Divn,Madpiya Chordia,Chittor Road,Bhilwara311001,Rajasthan
11 kV Power Generation,6.6 kV Station Service and 6.6 kV for Unit Auxiliary
system 110 kV for Transmission and Distribution and distribution at 0.415 kV

Max Source Fault level


5000 MVA sec at 110 kV
(assumed)
Min Source Fault level (assumed) 10000 MVA sec at 400 kV
Tools used:

Protection Coordination

Conclusion

Paladin Design Base 5- an Electrical Design software

The short circuit currents at various busbars are calculated based on the above
assumptions. Calculated Short circuit currents are shown in the SLD.
Selectivity of relays and circuit breakers were worked out based on the cable
size and flow of short circuit currents.
Time current characterstic curves are generated for every path and verified .
Settings for each device,short circuit currents at every busbars,detailed
calculations for the settings are given in the following pages. While doing this
exercise certain discrepencies were noticed and these are brought out
seperately under heading 'Comments and Observations'.

Reference Documents/Drawings
Sl.No
1
2
3
4
5
6
7
8
9
10
11
12
13
14

File name
JCLSLD.DWG
RELAYS IN JCL.DOCX
2600KW HT motor test report.pdf
211218 ID fan 1000KW.jpg
803448 AHF -1 315KW.jpg
2000KVA transformer.pdf
20 MVA TR 1.jpg
1250 kVA TR 1.jpg
1600 kVA TR 1.jpg
1000 kVA TR 1.jpg
3.5 TG 1.jpg
16 TG 1.jpg
15 MVA TR 1.jpg
750 kVA TR 1.jpg

Title of the Document


Document/drawing No
JCL-CPP-ELE-0001
OVERALL SINGLE LINE DIAGRAM FOR 15 MW,3.5MW &
110 KvLine diagram for 110 kV Switch Yard Extension
Single
TEST CERTIFICATE ON 2600kW MOTOR
TEST CERTIFICATE ON 1000kW MOTOR
TEST CERTIFICATE ON 315kW MOTOR
TECHNICAL PARTICULARS ON TRANSFORMERS
TECHNICAL PARTICULARS ON TRANSFORMERS 20 MVA
TECHNICAL PARTICULARS ON TRANSFORMERS 1250kVA
TECHNICAL PARTICULARS ON TRANSFORMERS 1600kVA
TECHNICAL PARTICULARS ON TRANSFORMERS 1000kVA
TECHNICAL PARTICULARS ON TRANSFORMERS 3.5 MW
TG
TECHNICAL
PARTICULARS ON TRANSFORMERS 16 MW TG
TECHNICAL PARTICULARS ON TRANSFORMERS 15 MVA
TECHNICAL PARTICULARS ON TRANSFORMERS 750 kVA

SINGLE LINE DIAGRAM

GRID

KPCTL

TG2

GEN

LINE_CB

TG1

GEN

50
51

TR_CB
50
51

50
51

125

TG_CABLE

110 kV BUS

126

GCB

50
51

TRAF01_20MVA

11 kV HT LCSS-1 UA IC1

BC

50
51

50
51

11 kV HT LCSS-1 UA IC2
50
51

11 kV HT LCSS-1 UA_RH

11 kV HT LCSS-1 UA_LH
KILN1&2

50
51

50
51

415V LCSS1 CPP IC3

50
51

INT.PANEL

50
51

CAB:AFBC2

DG1

RMP3 TR

AFBC FEEDER 2

50
51

CAB_SWTP

GEN

TRAF02_2MVA

STP

50
51

CAB_KILN 3

415V LCSS1 CPP IC1

KILN3&4

50
51

CAB_RMP3

TRAF01_2MVA

50
51

CAB_LCSS_FDR2

CAB_LCSS1_FDR1

141

138

RMP3

LCSS1_FDR2

50
51

50
51

CAB_PELLET

CAB_ET
ET

AFBC FEEDER

LCSS1_FDR1

50
51

CAB_KILN1

135

134

PELLET PLANT 1

50
51

11kV HT LCSS-1 UA BC

LCSS1_ET

133

STP PLANT1
50
51

AFBC TR2

KILN 3 TR

TRAF02_0.75 MVA
415V LCSS1 CPP IC2

415V LCSS1 CPP LH

kiln 3
KILN 3

415V LCSS1 CPP RH

415 V LCSS-7 STP IC1

415 V LCSS-7 STP IC2

415 V LCSS-7 STP LH


TRAF01_15 MVA
CAB_TRAFO_SWBD

415 V LCSS-7 STP LH1

6.6kV_LBSS1_IC2

6.6kV_LBSS1_IC1

50
51

50
51

1F1:HT MOTOR

2F1:LCSS2

50
51

5F1:LBDS2

4F1:LBDS1

3F1:LCSS3
50
51

50
51

50
51

6F1:SPARE
50
51

16F1:SPARE

17F1:HTMOTOR

50
51

50
51

TRAFO1_LCSS4

CAB_ORE GRINDING

TRAF03_LCSS3

50
51

CAB_SWBD_TRAFO1

TRAF2_LCSS2

15F1:LCSS2

50
51

CAB_SWBD_TRAFO

TRAFO1_LCSS3

14F1:LCSS3

50
51

50
51

2600kW

TRAFO1_LCSS2

13F1:LBDS2

12F1:LBDS2

CAB_ORE BEN PLANT

105

103

91

50
51

6.6kV_LBSS1_RH

6.6kV_LBSS1_BC

6.6kV_LBSS1_LH

ORE GRINDING MOTOR


415 V LCSS-3 APP IC2

415 V LCSS-2 OCGS IC2

415 V LCSS-3 APP IC1

415 V LCSS-3 APP RH


CAB_LBDS2

415 V LCSS-3 APP LH


415 V LCSS-2 OCGS RH

415 V LCSS-2 OCGS LH

415 V LCSS-2 OCGS IC4

415 V LCSS-2 OCGS IC3

415 V LCSS-2 OCGS IC1

415 V LCSS-2 OCGS1 RH

AH04

AH03

50
51

50
51

154
AH17
50
51

50
51

210

219

AH01 BC
50
51

AH6

AH8

50
51

50
51

AH10

AH12

AH14

AH16

AH18

AH20

50
51

50
51

50
51

50
51

50
51

50
51

293

AH07

50
51

283

AH09

50
51

170

AH 11

50
51

183

AH13

50
51

174

AH15

50
51

184

106

AH19

234

50
51

224

AH23

50
51

215

AH21

162

196

176

270

172

285

233

178

272

179

290

230

240

220

239

211

238

236

192

IDFAN_1000kW

226

CAP PNL1 500 kVAR

217

205

AH FAN1_315kW

SC MCC TR

295

208

191

AH FAN2_315kW

CAP PNL 2_500 kVAR

287

SC.BLDG.MCC LHS

SC.BLDG.MCC RHS

TG MCC1

BALLING MCC1

P_MIXING MCC2

BALLING MCC2

TG MCC2

P_MIXING MCC1

REV. DATE

ECO#

DESCRIPTION

DWN APP

THIS DRAWING IS PROPRIETARY INFORMA TION

Your Company Name


Address
Address
Phone and web site

Electrical One-Line Diagramfor Protection Coordination Study

DRAWN BY/DATE:

DWG. No.

DWG No.:

ENG. APP./DATE:

MFG. APP./DATE:
SCALE:

PART No.:
DWG SIZE:

REV.

SINGLE LINE DIAGRAM


SHORT CIRCUIT CURRENTS-GRID 2500 MVASEC

GRID

KPCTL
Ik" : 13145.13A
Vp: 110000 V

TG2

GEN

LINE_CB

TG1

GEN

50
51

TR_CB
50
51

50
51

125

TG_CABLE

110 kV BUS
Ik" : 13144.79A
Vp: 110000 V

126

GCB

50
51

TRAF01_20MVA

11 kV HT LCSS-1 UA IC1

BC

50
51

50

11 kV HT LCSS-1 UA_LH
51
Ik" : 9966.52A
Vp: 11000 V
LCSS1_FDR1

50
51

50
51

50
51

415V LCSS1 CPP IC3

50
51

INT.PANEL

RMP3 TR

50
51

50
51

CAB:AFBC2

DG1

TRAF02_2MVA

50
51

11 kV HT LCSS-1 UA_RH
Ik" : 9965.19A
Vp: 11000 V

AFBC FEEDER 2

CAB_SWTP

GEN

50
51

STP

CAB_KILN 3

415V LCSS1 CPP IC1

50
51

KILN3&4

CAB_RMP3

TRAF01_2MVA
138

RMP3

LCSS1_FDR2

CAB_LCSS_FDR2

ET
Ik" : 9864.91A
Vp: 11000 V 141

134

AFBC FEEDER

CAB_LCSS1_FDR1

CAB_KILN1

PELLET PLANT 1

CAB_PELLET

50
51

135

50
51

CAB_ET

50
51

KILN1&2

11kV HT LCSS-1 UA BC

LCSS1_ET

133

11 kV HT LCSS-1 UA IC2
50
51

STP PLANT1
50
51

AFBC TR2

KILN 3 TR

TRAF02_0.75 MVA
KILN
kiln 3 3
Ik" : 44146.08A
Vp: 415 V

415V LCSS1
IC2 CPP RH
415VCPP
LCSS1
Ik" : 39642.44A
Vp: 433 V

415V LCSS1 CPP LH


Ik" : 39626.53A
Vp: 433 V

415 V LCSS-7 STP IC1


415 V LCSS-7 STP LH
Ik" : 20049.81A
Vp: 433 V

415 V LCSS-7 STP IC2


TRAF01_15 MVA
CAB_TRAFO_SWBD

415 V LCSS-7 STP LH1


Ik" : 26090.57A
Vp: 433 V

6.6kV_LBSS1_IC2

6.6kV_LBSS1_IC1
50
51

2F1:LCSS2

50
51

5F1:LBDS2

4F1:LBDS1

3F1:LCSS3
50
51

50
51

50
51

6F1:SPARE
50
51

17F1:HTMOTOR

50
51

50
51

TRAFO1_LCSS4

ORE GRINDING MOTOR


Ik" : 7662.86A
Vp: 6600 V

415 V LCSS-3 APP IC2

CAB_LBDS2

415 V LCSS-2 OCGS RH


Ik" : 28200.14A
Vp: 433 V

16F1:SPARE

CAB_ORE GRINDING

TRAF03_LCSS3

415 V LCSS-2 OCGS IC2

415 V LCSS-3 APP IC1

415 V LCSS-3 APP LH


Ik" : 28186.51A
Vp: 433 V

50
51

CAB_SWBD_TRAFO1

TRAF2_LCSS2

15F1:LCSS2

50
51

CAB_SWBD_TRAFO

TRAFO1_LCSS3

14F1:LCSS3

50
51

50
51

2600kW
Ik" : 7735.31A
Vp: 6600 V

TRAFO1_LCSS2

13F1:LBDS2

12F1:LBDS2

CAB_ORE BEN PLANT

105

103

91

50
51

50
51

6.6kV_LBSS1_RH
Ik" : 7734.19A
Vp: 6600 V

6.6kV_LBSS1_BC

1F1:HT MOTOR

6.6kV_LBSS1_LH
Ik" : 7735.55A
Vp: 6600 V

415 V LCSS-3 APP RH


Ik" : 28200.14A
Vp: 433 V

415 V LCSS-2 OCGS LH


Ik" : 28186.51A
Vp: 433 V

50
51

AH17
50
51

154
Ik" : 7650.15A
Vp: 6600 V

50
51

210

219

AH01 BC
50
51

AH6

AH8

50
51

50
51

AH10

AH12

AH14

AH16

AH18

AH20

50
51

50
51

50
51

50
51

50
51

50
51

293

AH07

50
51

283

AH09

50
51

170

AH 11

50
51

183

AH13

50
51

50
51

162
Ik" : 7661.83A
Vp: 6600 V

174

AH15

50
51

184

106

AH19

234

50
51

AH04

AH03

224

AH23

50
51

415 V LCSS-2 OCGS1 RH


Ik" : 28200.14A
Vp: 433 V

215

AH21

415 V LCSS-2 OCGS IC4

415 V LCSS-2 OCGS IC3

415 V LCSS-2 OCGS IC1

196

176

270

172

285

BALLING MCC1
Ik" : 28456.18A
Vp: 433 V

P_MIXING MCC1
Ik" : 23433.37A
Vp: 433 V

178

233
SC.BLDG.MCC LHS
Ik" : 23433.37A
Vp: 433 V

SC.BLDG.MCC RHS
Ik" : 23441.38A
Vp: 433 V

272

P_MIXING MCC2
Ik" : 23441.38A
Vp: 433 V

179

BALLING MCC2
Ik" : 23441.38A
Vp: 433 V

290

230

240

220

239

211

238

236

TG MCC1
Ik" : 28456.18A
Vp: 433 V

I
226

192

IDFAN_1000kW
Ik" : 7577.09A
Vp: 6600 V

217

CAP PNL1 500 kVAR


Ik" : 7575.52A
Vp: 6600 V

205

AH FAN1_315kW
Ik" : 7564.94A
Vp: 6600 V

SC MCC TR

295

208

191

AH FAN2_315kW
Ik" : 7588.28A
Vp: 6600 V

CAP PNL 2_500 kVAR


Ik" : 7586.7A
Vp: 6600 V

287

TG MCC2
Ik" : 23441.38A
Vp: 433 V

REV. DATE

ECO#

DESCRIPTION

DWN APP

THIS DRAWING IS PROPRIETARY INFORMA TION

Your Company Name


Address
Address
Phone and web site

Electrical One-Line Diagramfor Protection Coordination Study


Short circuit currents for source fault of 2500 MVAsec @ 110kV
DRAWN BY/DATE:

DWG. No.

DWG No.:

ENG. APP./DATE:

MFG. APP./DATE:
SCALE:

PART No.:
DWG SIZE:

REV.

SINGLE LINE DIAGRAM


SHORT CIRCUIT CURRENTS-GRID 5000 MVASEC

GRID

KPCTL
Ik" : 26266.72A
Vp: 110000 V

TG2

GEN

LINE_CB

TG1

GEN

50
51

TR_CB
50
51

50
51

125

TG_CABLE

110 kV BUS
Ik" : 26265.38A
Vp: 110000 V

126

GCB

50
51

TRAF01_20MVA

11 kV HT LCSS-1 UA IC1

BC

50
51

50

11 kV HT LCSS-1 UA_LH
51
Ik" : 10338.33A
Vp: 11000 V
LCSS1_FDR1

50
51

50
51

50
51

415V LCSS1 CPP IC3

50
51

INT.PANEL

RMP3 TR

50
51

50
51

CAB:AFBC2

DG1

TRAF02_2MVA

50
51

11 kV HT LCSS-1 UA_RH
Ik" : 10336.89A
Vp: 11000 V

AFBC FEEDER 2

CAB_SWTP

GEN

50
51

STP

CAB_KILN 3

415V LCSS1 CPP IC1

50
51

KILN3&4

CAB_RMP3

TRAF01_2MVA
138

RMP3

LCSS1_FDR2

CAB_LCSS_FDR2

ET
Ik" : 10228.38A
Vp: 11000 V 141

134

AFBC FEEDER

CAB_LCSS1_FDR1

CAB_KILN1

PELLET PLANT 1

CAB_PELLET

50
51

135

50
51

CAB_ET

50
51

KILN1&2

11kV HT LCSS-1 UA BC

LCSS1_ET

133

11 kV HT LCSS-1 UA IC2
50
51

STP PLANT1
50
51

AFBC TR2

KILN 3 TR

TRAF02_0.75 MVA
415V LCSS1 CPP IC2

kiln 3

KILN 3
415 V LCSS-7 STP IC2 Ik" : 44412.14A
Vp: 415 V

415V LCSS1 CPP RH


Ik" : 39848.12A
Vp: 433 V

415V LCSS1 CPP LH


Ik" : 39832.03A
Vp: 433 V

415 V LCSS-7 STP IC1

TRAF01_15 MVA
CAB_TRAFO_SWBD

415 V LCSS-7 STP LH


Ik" : 20102.28A
Vp: 433 V

415 V LCSS-7 STP LH1


Ik" : 26179.51A
Vp: 433 V

6.6kV_LBSS1_IC2

6.6kV_LBSS1_IC1
50
51

2F1:LCSS2

50
51

5F1:LBDS2

4F1:LBDS1

3F1:LCSS3
50
51

50
51

50
51

6F1:SPARE
50
51

17F1:HTMOTOR

50
51

50
51

TRAFO1_LCSS4

ORE GRINDING MOTOR


Ik" : 7782.78A
Vp: 6600 V

415 V LCSS-3 APP IC2

CAB_LBDS2

415 V LCSS-2 OCGS RH


Ik" : 28297.62A
Vp: 433 V

16F1:SPARE

CAB_ORE GRINDING

TRAF03_LCSS3

415 V LCSS-2 OCGS IC2

415 V LCSS-3 APP IC1

415 V LCSS-3 APP LH


Ik" : 28283.92A
Vp: 433 V

50
51

CAB_SWBD_TRAFO1

TRAF2_LCSS2

15F1:LCSS2

50
51

CAB_SWBD_TRAFO

TRAFO1_LCSS3

14F1:LCSS3

50
51

50
51

2600kW
Ik" : 7857.85A
Vp: 6600 V

TRAFO1_LCSS2

13F1:LBDS2

12F1:LBDS2

CAB_ORE BEN PLANT

105

103

91

50
51

50
51

6.6kV_LBSS1_RH
Ik" : 7856.7A
Vp: 6600 V

6.6kV_LBSS1_BC

1F1:HT MOTOR

6.6kV_LBSS1_LH
Ik" : 7858.11A
Vp: 6600 V

415 V LCSS-3 APP RH


Ik" : 28297.62A
Vp: 433 V

415 V LCSS-2 OCGS LH


Ik" : 28283.92A
Vp: 433 V

50
51

AH17
50
51

154
Ik" : 7769.84A
Vp: 6600 V

50
51

210

219

AH01 BC
50
51

AH6

AH8

50
51

50
51

AH10

AH12

AH14

AH16

AH18

AH20

50
51

50
51

50
51

50
51

50
51

50
51

293

AH07

50
51

283

AH09

50
51

170

AH 11

50
51

183

AH13

50
51

50
51

162
Ik" : 7781.73A
Vp: 6600 V

174

AH15

50
51

184

106

AH19

234

50
51

AH04

AH03

224

AH23

50
51

415 V LCSS-2 OCGS1 RH


Ik" : 28297.62A
Vp: 433 V

215

AH21

415 V LCSS-2 OCGS IC4

415 V LCSS-2 OCGS IC3

415 V LCSS-2 OCGS IC1

196

176

270

172

285

BALLING MCC1
Ik" : 28555.3A
Vp: 433 V

P_MIXING MCC1
Ik" : 23500.59A
Vp: 433 V

178

233
SC.BLDG.MCC LHS
Ik" : 23500.59A
Vp: 433 V

SC.BLDG.MCC RHS
Ik" : 23508.66A
Vp: 433 V

272

P_MIXING MCC2
Ik" : 23508.66A
Vp: 433 V

179

BALLING MCC2
Ik" : 23508.66A
Vp: 433 V

290

230

240

220

239

211

238

236

TG MCC1
Ik" : 28555.3A
Vp: 433 V

I
226

192

IDFAN_1000kW
Ik" : 7694.37A
Vp: 6600 V

217

CAP PNL1 500 kVAR


Ik" : 7692.77A
Vp: 6600 V

205

AH FAN1_315kW
Ik" : 7681.84A
Vp: 6600 V

SC MCC TR

295

208

191

AH FAN2_315kW
Ik" : 7705.74A
Vp: 6600 V

CAP PNL 2_500 kVAR


Ik" : 7704.14A
Vp: 6600 V

287

TG MCC2
Ik" : 23508.66A
Vp: 433 V

REV. DATE

ECO#

DESCRIPTION

DWN APP

THIS DRAWING IS PROPRIETARY INFORMA TION

Your Company Name


Address
Address
Phone and web site

Electrical One-Line Diagramfor Protection Coordination Study


Short circuit currents for source fault of 5000 MVAsec @ 110kV
DRAWN BY/DATE:

DWG. No.

DWG No.:

ENG. APP./DATE:

MFG. APP./DATE:
SCALE:

PART No.:
DWG SIZE:

REV.

Details of Devices

Transformers

To

From

Primary Secondar Rating


Volt
y Volt
in kVA

11 kV Switch Board
GRID
110000
FDR 07 LBSS-1 6.6 kV LBSS-1 SWBD
FDR 4 11 kV SWBD
11000
Screening MCC LHS
AH11 HV distribution
6600
Screening MCC RHS
AH10 HV distribution
6600
TG MCC RHS
AH16 HV distribution
6600
TG MCC LHS
AH17 HV distribution
6600
BALLING SYSTEM LHS
AH15 HV distribution
6600
BALLING SYSTEM RHS
AH14 HV distribution
6600
PROPORTION & MIXING MCC LHS
AH13 HV distribution
6600
PROPORTION & MIXING MCC RHS
AH12 HV distribution
6600
ORE CRUSHING GRINDING SYSTEM LHS LCSS-2 FDR 02 6.6 kV LBBSS-1 SWBD
6600
ORE CRUSHING GRINDING SYSTEM RHS LCSS-1 FDR 15 6.6 kV LBBSS-1 SWBD
6600
CPP LCSS-1
FDR 5 11 kV SWBD
11000
CPP LCSS-1
FDR12 11 kV SWBD
11000
KILN 1&2
FDR 3 11 kV SWBD
11000
AFBC FEEDER LHS
FDR 6 11 kV SWBD
11000
AFBC FEEDER RHS
FDR 16 11 kV SWBD
11000
RMP3
FDR 13 11 kV SWBD
11000
KILN 3,4&5
FDR 14 11 kV SWBD
11000
STP FEEDER
FDR 15 11 kV SWBD
11000

11000
6900
433
433
433
433
433
433
433
433
433
433
433
433
433
433
433
433
433
433

20000
15000
1000
1000
1600
1600
1600
1600
1000
1000
1250
1250
2000
2000
1250
750
750
1000
2500
750

HV
STAR
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA
DELTA

LV
DELTA
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR
STAR

HV
LV RATED
RATED
CURRENT
CURRENT
10 ONAN/ONAF 104.98 1049.76
8.35 ONAN/ONAF 787.32 1255.15
5 ONAN
87.48 1333.38
5 ONAN
87.48 1333.38
5 ONAN
139.96
2133
5 ONAN
139.96
2133
5 ONAN
139.96
2133
5 ONAN
139.96
2133
5 ONAN
87.48 1333.38
5 ONAN
87.48 1333.38
5 ONAN
109.35 1666.76
5 ONAN
109.35 1666.76
6.25 ONAN
104.98 2666.82
6.25 ONAN
104.98 2666.82
5 ONAN
65.61 1666.76
5 ONAN
39.37 1000.06
5 ONAN
39.37 1000.06
5.16 ONAN
52.49 1333.38
6.5 ONAN
131.22 3333.53
5 ONAN
39.37 1000.06

Vector
Z in %
Group
YNd1
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11
Dyn11

Type of
Cooling

SETTING CALCULATIONS
FOR
FOR TRANSFORMERS
TRANSFORMERS
DG SETS

Setting Calculation for Distribution Transformers 2 MVA

433 V

11
3200

125/1
2000 kVA
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side ACB CT details
Percentage Impedance of Transformer
Through Fault current at 0.415 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current

Transformer HV side CT Secondary Pick up Current


IDMT setting at 11 kV side

Setting proposed on HV side Ip

PT
Vp
Vs

2000
kVA
11
kV
0.433
kV
125/1
CTRP 125
3200
Z
6.25%
33337
Amps
104.98
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 104.98/0.95
121.55
Isfl
0.97
1
1

Curve

Extreme Inverse

Transformer LV side current as per name plate


Relay drop off Ratio
LV Pick up Current

2666.82
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x 2666.82/0.95
3087.90

Transformer LV side CT Secondary Pick up Current


Relay setting for over current

=3087.90/3200

Setting proposed on LV side Ip

Through Fault current at 0.415kV Bus


HV side current due to fault at 0.415 kV bus
HV side CT Secondary current due to fault at 0.415kV bus
Setting proposed on HV side relay I>>
Setting proposed on LV side relay I>>

33337.00
1312.27

11

10.50

13.00
6

433 V

Amps
Amps
Amps
Amps

Setting Calculation for Distribution Transformers 1 MVA

433 V

11

1600 A

75/
1000 kVA
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side ACB Rating
Percentage Impedance of Transformer
Through Fault current at 0.415 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current

Transformer HV side CT Secondary Pick up Current


IDMT setting at 11 kV side

Setting proposed on HV side Ip

PT
Vp
Vs

1000
kVA
11
kV
0.433
kV
75/1
CTRP 75
1600
Z
5.16%
23208.00
Amps
52.49
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 52.49/0.95
60.78
Isfl
0.81
0.8
0.8

Curve

Extremel Inverse

Transformer LV side current as per name plate


Relay drop off Ratio
LV Pick up Current

1333.41
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x1333.41/0.95
1543.95

Transformer LV side CT Secondary Pick up Current


ACB setting for over current

=1543.95/1600

Setting proposal on ACB

Through Fault current at 0.415kV Bus


HV side current due to fault at 0.415 kV bus
HV side CT Secondary current due to fault at 0.415kV bus
Setting proposed on HV side relay I>>
Setting proposed on LV sideACB I>>

23208.00
913.55

0.96496875

12.18

14.00
6.00

Amps
Amps
Amps
Amps

Setting Calculation for Distribution Transformers 2.5 MVA

11

433 V
4000 A

800/1
2500 kVA
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side ACB Rating
Percentage Impedance of Transformer
Through Fault current at 0.415 kV Bus as per report
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current

Transformer HV side CT Secondary Pick up Current


IDMT setting at 11 kV side

Setting proposed on HV side Ip

PT
Vp
Vs

2500
kVA
11
kV
0.433
kV
150/1
CTRP 150
4000
Z
6.50%
36209
Amps
131.22
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 131.22/0.95
151.94
Isfl
1.01
1
1

Curve

Extreme Inverse

Transformer LV side current as per name plate


Relay drop off Ratio
LV Pick up Current

3333.53
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x 3333.53/0.95
3859.88

Transformer LV side CT Secondary Pick up Current


ACB setting for over current

=3859.88/4000

Setting proposed on LV side Ip

Through Fault current at 0.415kV Bus


HV side current due to fault at 0.415 kV bus
HV side CT Secondary current due to fault at 0.415kV bus
Setting proposed on HV side relay I>>
Setting proposed on LV side relay I>>

36209.00
1425.32

9.50

12.00
6

Amps
Amps
Amps
Amps

Setting Calculation for Distribution Transformers 1.25 MVA

433 V

11

2000 A

75/
1250 kVA
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side ACB Rating
Percentage Impedance of Transformer
Fault current at 0.415 kV Bus as per report
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current

Transformer HV side CT Secondary Pick up Current


IDMT setting at 11 kV side

Setting proposed on HV side Ip

PT
Vp
Vs

1250
kVA
11
kV
0.433
kV
100/1
CTRP 100
2000
Z
5.00%
25029.00
Amps
65.61
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x65.61/0.95
75.97
Isfl
0.76
0.75
0.75

Curve

Extreme l Inverse

Transformer LV side current as per name plate


Relay drop off Ratio
LV Pick up Current

1666.76
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x1666.76/0.95
1929.93

Transformer LV side CT Secondary Pick up Current


ACB setting for over current

=1929.93/2000

Setting proposed on LV side Ip

Through Fault current at 0.415kV Bus


HV side current due to fault at 0.415 kV bus
HV side CT Secondary current due to fault at 0.415kV bus
Setting proposed on HV side relay I>>
Setting proposed on LV side relay I>>

25029.00
985.23

0.964615

9.85

12.00
6

Amps
Amps
Amps
Amps

Setting Calculation for Transformers 0.75 MVA

433 V

11

1250 A

100/1
750 kVA
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side ACB Rating
Percentage Impedance of Transformer
Through Fault current at 0.433 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current

Transformer HV side CT Secondary Pick up Current


IDMT setting at 11 kV side

Setting proposed on HV side Ip

PT
Vp
Vs

750
kVA
11
kV
0.433
kV
100/1
CTRP 100
1250
Z
5.00%
18303.00
Amps
39.37
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x39.37/0.95
45.59
Isfl
0.46
0.5
0.5

Curve

Extreme Inverse

Transformer LV side current as per name plate


Relay drop off Ratio
LV Pick up Current

1000.06
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x1000.06/0.95
1157.96

Transformer LV side CT Secondary Pick up Current


ACB setting for over current

=1157/1250

Setting proposed onLV side Ip

0.95

Through Fault current at 0.415 kV Bus


HV side current due to fault at 0.415 kV bus
HV side CT Secondary current due to fault at 0.415 kV bus
Setting proposed on HV side relay I>>
Setting proposed on LV side relay I>>

18303.00
720.47

6.6kV

0.925616

7.20

9.00
6

433 V

Amps
Amps
Amps
Amps

Setting Calculation for Transformers 1 MVA Feeding Screening MCC

433 V

6.6kV
150/5
1000 kVA
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side ACB Rating
Percentage Impedance of Transformer
Through Fault current at 0.415 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current

Transformer HV side CT Secondary Pick up Current


IDMT setting at 6.6 kV side

Setting proposed on HV side Ip

1600 A
PT
Vp
Vs

1000
kVA
6.6
kV
0.433
kV
150/5
CTRP 30
1600
Z
5.00%
23208
Amps
87.48
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 87.48/0.95
101.29
Isfl
3.38
Amps
0.675283281
0.7

Curve

Extremel Inverse

Transformer LV side current as per name plate


Relay drop off Ratio
LV Pick up Current

1333.41
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x1333.41/0.95
1543.95

Transformer LV side CT Secondary Pick up Current


ACB setting for over current

=1543.95/1600

Setting proposal on ACB

Through Fault current at 0.415kV Bus


HV side current due to fault at 0.415 kV bus
HV side CT Secondary current due to fault at 0.415kV bus
Setting proposed on HV side relay I>>
Setting proposed on LV sideACB I>>

23208.00
1522.59

6.6kV

0.96496875

50.75

60 (12)
6.00

433 V

Amps
Amps
Amps
Amps

Setting Calculation for Transformers 1 MVA Feeding Proportion Mixing MCC

433 V

6.6kV

1600 A

300/5
1000 kVA
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side ACB Rating
Percentage Impedance of Transformer
Through Fault current at 0.415 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current

Transformer HV side CT Secondary Pick up Current


IDMT setting at 6.6 kV side

Setting proposed on HV side Ip

PT
Vp
Vs

1000
kVA
6.6
kV
0.433
kV
300/5
CTRP 60
1600
Z
5.00%
21210
Amps
87.48
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 87.48/0.95
101.29
Isfl
1.69
Amps
0.337641641
0.35

Curve

Extremel Inverse

Transformer LV side current as per name plate


Relay drop off Ratio
LV Pick up Current

1333.41
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x1333.41/0.95
1543.95

Transformer LV side CT Secondary Pick up Current


ACB setting for over current

=1543.95/1600

Setting proposal on ACB

Through Fault current at 0.415kV Bus


HV side current due to fault at 0.415 kV bus
HV side CT Secondary current due to fault at 0.415kV bus
Setting proposed on HV side relay I>>
Setting proposed on LV sideACB I>>

21210.00
1391.50

6.6kV

0.96496875

23.19

28(5.5)
6.00

433 V

Amps
Amps
Amps
Amps

Setting Calculation for Transformers 1.6 MVA Feeding TG/BALLING SYSTEM MCC

433 V

6.6kV
200/5
1600 kVA

2500 A

Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side ACB Rating
Percentage Impedance of Transformer
Through Fault current at 0.415 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current

Transformer HV side CT Secondary Pick up Current


IDMT setting at 6.6 kV side

Setting proposed on HV side Ip

PT
Vp
Vs

1600
kVA
6.6
kV
0.433
kV
200/5
CTRP 40
2500
Z
5.00%
25244.00
Amps
139.97
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x139.97/0.95
162.07
Isfl
4.05
Amps
0.810339938
0.85

Curve

Extremel Inverse

Transformer LV side current as per name plate


Relay drop off Ratio
LV Pick up Current

2133.46
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x2133.46/0.95
2470.32

Transformer LV side CT Secondary Pick up Current


ACB setting for over current

=2470/2500

Setting proposal on ACB

Through Fault current at 0.415kV Bus


HV side current due to fault at 0.415 kV bus
HV side CT Secondary current due to fault at 0.415kV bus
Setting proposed on HV side relay I>>
Setting proposed on LV sideACB I>>

25244.00
1656.16

6.6kV

0.988128146

41.40

50(10)
6.00

433 V

Amps
Amps
Amps
Amps

Setting Calculation for Transformers 1.25 MVA Feeding ORE C.SYSTEM MCC

433 V

6.6kV
200/5
1250 kVA
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side ACB Rating
Percentage Impedance of Transformer
Through Fault current at 0.415 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current

Transformer HV side CT Secondary Pick up Current


IDMT setting at 6.6 kV side

Setting proposed on HV side Ip

2000 A
PT
Vp
Vs

1250
kVA
6.6
kV
0.433
kV
125/1
CTRP 125
2500
Z
5.00%
28226.00
Amps
109.35
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x109.35/0.95
126.62
Isfl
1.01
Amps
1
1

Curve

Extremel Inverse

Transformer LV side current as per name plate


Relay drop off Ratio
LV Pick up Current

1666.76
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x1666.76/0.95
1929.94

Transformer LV side CT Secondary Pick up Current


ACB setting for over current

=1929/2500

Setting proposal on ACB

0.8

Through Fault current at 0.415kV Bus


HV side current due to fault at 0.415 kV bus
HV side CT Secondary current due to fault at 0.415kV bus
Setting proposed on HV side relay I>>
Setting proposed on LV sideACB I>>

28226.00
1851.80

0.771975114

14.81

17.00
4.00

Amps
Amps
Amps
Amps

Setting Calculation for Transformers 15 MVA

11

6.9kV
800/1
15000 kVA

Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
TransformerLV side CT details CTLV
Turns Ratio
Percentage Impedance of Transformer
Fault current at 6.6 kV Bus as per report
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current

Transformer HV side CT Secondary Pick up Current


IDMT setting at 11kV side

Setting proposed on HV side Ip

1500/1
PT
Vp
Vs

15000
kVA
11
kV
6.9
kV
800/1
CTRP 800
1500/1
1500
Z
8.35%
4915.00
Amps
787.32
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 787.32/0.95
911.63
Isfl
1.14
1.15
1.15

Curve

Normal Inverse

Transformer LV side current as per name plate


Relay drop off Ratio
LV Pick up Current

1255.15
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x1255.15/0.95
1453.33

Transformer LV side CT Secondary Pick up Current


ACB setting for over current

=1453/1500

Setting proposed onLV side Ip

Curve

Normal Inverse

0.968884708

Fault current at 6.6 kV Bus as per report,for MINIMUM SOURCE Fault


4915.00
HV side current due to fault at 6.6 kV bus
3083.05
3.85
HV side CT Secondary current due to fault at 6.6 kV bus
Setting proposed on HV side relay I>>
5.00
Setting proposed on LV side relay I>>
6

Amps
Amps
Amps

Setting Calculation for Transformer 20 MVA

110 kV

11 kV
125/1
20000 kVA

Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
TransformerLV side CT details CTLV
Turns Ratio
Percentage Impedance of Transformer
Fault current at 11 kV Bus as per report
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current

Transformer HV side CT Secondary Pick up Current


IDMT setting at 110kV side

Setting proposed on HV side Ip

1250/1
PT
Vp
Vs

20000
kVA
110
kV
11
kV
125/1
CTRP 125
1250/1
1250
Z
10.00%
9996
Amps
104.98
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x104.98/0.95
121.55
Isfl
0.97
1
1

Curve

Normal Inverse

Transformer LV side current as per name plate


Relay drop off Ratio
LV Pick up Current

1049.76
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x1049.76/0.95
1212.04

Transformer LV side CT Secondary Pick up Current


ACB setting for over current

=1212.04/1250

Setting proposed onLV side Ip

Curve

Normal Inverse

Through Fault current at 11 kV Bus


HV side current due to fault at 11 kV bus
HV side CT Secondary current due to fault at 11 kV bus
Setting proposed on HV side relay I>>
Setting proposed on LV side relay I>>

9996.00
999.60

0.969632

8.00

10.00
3

Amps
Amps
Amps

SETTING DETAILS FOR


RELAY CONTROL PANEL

110kV SwitchYard -Relay & Control Panel


Line Circuit Breaker
Relay type Siemens Reyrolle 7SA610
1 SYSTEM CONFIG
Description
System Frequency
Selects the Power System Frequency from 50 or 60 Hz
Setting Dependencies
When enabled only active settings are displayed and
all others hidden
2 CT/VT CONFIG
Description
CTs

Range
50, 60

Setting
50Hz

Prime

Enabled, Disabled

Enabled

Range

Setting

Prime

CT rated primary
CT rated secondary

10..50000 A
1A/5A

150A
1A

PT rated primary
PT rated Secondary

0~132000 V
110230

11000 V
110

Range
Enabled, Disabled
Enabled, Disabled

Setting
Enabled
Enabled

Prime

Range
Enabled, Disabled

Setting
Enabled

Prime

0.1..4.00 A STEP 0.1

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL Overcurrent element
is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent element is
enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time

150

Normal Inverse ,Very Normal


Inverse ,Extremely
Inverse-IEC
Inverse ,Long Inverse
0.05..3.20 s, oo
1

Range
Enabled, Disabled

Setting
Enabled

0.1..25.00 A STEP 0.1 10


0.00..60.00 s

1.05

Prime

1500

5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault
element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
51N-1 Time Mult (IEC/ANSI) (TEp)
Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
5.2 50N-1
Description
50N-1 Element
Selects whether the DTL derived Earth fault element is
enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time
6 Directional Current Protection :67

Range
Enabled, Disabled

Setting
Enabled

0.05..4.00 A STEP
0.125
0.01
Normal Inverse ,Very Normal Inverse
Inverse ,Extremely
Inverse ,Long Inverse
0.05..3.20 s, oo
0.5

Range
Enabled, Disabled

Setting
Enabled

0.05..25.00 A STEP
0.01
0.00..60.00 s

1.1

6.1 67-1
Description

Range

Setting

67 Element

Enabled, Disabled

Enabled

67 Setting
Pickup level
67 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL

0.05, 0.06 ... 2.49, 2.5 0.7

Selects whether the 51-1 IDMTL Overcurrent element is enabled

18.75

Prime

165

1.45

DTL, IEC-NI, IEC-VI,


IEC-NI
IEC-EI, IEC-LTI, ANSIMI, ANSI-VI, ANSI-EI
IEC-NI IEC-NI
0.025, 0.05 ... 1.575, 1.6
0.1

67 Time Mult (IEC/ANSI)


Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
Characteristic Angle
-179.180 deg

Prime

-45

Prime

105

6.2 67N-1
Description

67N-1 Element
Selects whether the DTL derived Earth fault element is

Range

Setting

Enabled, Disabled

Enabled

67N-1 Setting
0.05, 0.06 ... 49.5, 50 0.06X In
Pickup level
Gn 67N-1 Delay
0, 0.01 ... 14300, 144000.65
Sets operate delay time
Characteristic Angle
-179.180 deg
-45
7 Breaker failure Protection -CB Fail Supervision : 50LBB
Setting name
Range
Setting
50BF Element
Diasabled/Enabled
Enabled
50BF Setting
0.05..2
0.2 x In
50BF-1 delay
20..60000
100ms
50BF-2 delay
20..60000
250 ms
8 Distance Protection setting 21
Value (Range)
Parameter
Settings
Unom PRIMARY
1.0 .. 1200.0 kV
110
Unom Secondary
80..125
110
CT Primary
10~5000
150
CT Secondary
1A/5A
1
SystemStarpoint
Solid Earthed
Solid Earthed
Peterson-Coil
Isolated
Uph / Udelta
0.10
.. 9.99
1.73
Rated Frequency
50/60 Hz
50 Hz
Phase Seq
L1 L2 L3L1 L3 L2
L1 L2 L3
Distance Unit
km/Miles
km
Full scale volt
1.0~1200
110
Full scale Current
10~5000
150
Line Angle
10~89 deg
67.38
P,Q sign
Not reversedReversed not reversed
R1 Conductor in ohms per km @ 85 deg C
0.16
X1 Conductor in ohms per km
0.0050~9.5
0.39
c'
0.0~100
0.01
Z1 Moose conductor in ohms per km @ 85 deg C
0.42
0.31
R0 Zero seq.Moose conductor in ohms per km @ 85 deg C
0.0050~9.5
1.30
X0 zero seq.Moose conductor in ohms per km
1.34
Z0 Moose conductor in ohms per km @ 85 deg C
Line length
0.1~1000
5
Adj short line
5.22
Adj Long line
16.23
2.10
Line Positive Sequence impedance (mag)

Prime
9

30

Unit
kV
V
A
A

kV
A
deg
ohms/km
ohms/km
mfd / km
ohms/km
ohms/km
ohms/km
ohms/km
km
km
km
Ohms

Line Positive Sequence impedance (Phase angle )


Line Positive Sequence impedance (mag) sec
LineZero Sequence impedance (mag)
Line zero Sequence impedance (Phase angle )
LineZero Sequence impedance (mag)sec
Zone 1 reach impedance setting (mag)
Zone 1 reach impedance setting (Phase angle)
Zone 1 reach impedance setting (mag) sec
Zone 1 reach impedance setting (Phase angle)
Time delay Zone 1
CT ratio/VT ratio for impedance Conversion
Zone 2 reach impedance setting (mag)
Zone 2 reach impedance setting (Phase angle)
Zone 2 reach impedance setting (mag) sec
Zone2 reach impedance setting (Phase angle)
Zone 3 reach impedance setting (mag)
Zone 3 reach impedance setting (Phase angle)
Zone 3 reach impedance setting (mag) sec
Zone3 reach impedance setting (Phase angle)
Time delay Zone 2
Time delay Zone 3
Re/R1
Xe/X1
Ko
Rm/Ri
Xm/Xi
R1 Phase-Phase
X1 Phase-Phase
R2 Phase-Phase
X2 Phase-Phase
R3 Phase-Phase
X3 Phase-Phase
Reverse Resistive reach
Reverse Reactive Reach
Vector Surge Protection
Vector Surge Relay CSPC make MRG2
Function
Connection of the input V.T.s
Vector surge logic

Voltage theshold for vector surge measuring

67.38 deg
0.0050~9.5
0.0050~9.5

Range
Setting
Y/DELT
Y
1Ph / 3Ph
3Ph
2...22 (EXIT)
6
U N = 100 V: 5...100 80
V U N = 230 V:
12...230 V U N = 400
V: 20...400 V

0.32
6.70
76.60
1.01
1.68
67.38
0.25
67.38
0
0.15
1.10
67.38
0.16
67.38
6.83
79.46
1.02
79.46
0.5
1
0.31
0.79
0.73
0.54
0.59
0.70
0.23
0.79
0.44
1.12
1.24
0.05
0.12

Ohms
deg
Ohms
deg
Ohms
deg
sec
Ohms
deg
Ohms
deg
Ohms
deg
Ohms
deg
sec
sec

Units

deg
V

110kV SwitchYard -Relay & Control Panel


Transformer Circuit Breaker
Relay type Siemens Reyrolle 7UT612
1 SYSTEM CONFIG
Description
System Frequency
Selects the Power System Frequency from 50 or 60 Hz
Setting Dependencies
When enabled only active settings are displayed and
all others hidden
2 CT/VT CONFIG
Description
CTs

Range
50, 60

Setting
50Hz

Prime

Enabled, Disabled

Enabled

Range

Setting

Prime

CT rated primary
CT rated secondary

10..50000 A
1A/5A

125A
1A

PT rated primary
PT rated Secondary

0~132000 V
110230

11000 V
110

Range
Enabled, Disabled
Enabled, Disabled

Setting
Enabled
Enabled

Prime

Range
Enabled, Disabled

Setting
Enabled

Prime

0.1..4.00 A STEP 0.1

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL Overcurrent element
is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent element is
enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time

125

Normal Inverse ,Very Normal


Inverse ,Extremely
Inverse-IEC
Inverse ,Long Inverse
0.05..3.20 s, oo
1

Range
Enabled, Disabled

Setting
Enabled

0.1..25.00 A STEP 0.1 10


0.00..60.00 s

0.9

Prime

1250

5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault
element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
51N-1 Time Mult (IEC/ANSI) (TEp)
Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
5.2 50N-1
Description
50N-1 Element
Selects whether the DTL derived Earth fault element is
enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time
6 Differential Protection: 87

Description

Diff.Prot
Pick up value of differential current I-diff>
T I-diff> time delay T I-diff>
Pick up value of High set trip I-diff>>
T I-diff> time delay T I-diff>>
Slope 1 of tripping charecterstic Slope 1
Base point for slope1 of charecterstic Base point 1
Slope 2 of tripping charecterstic Slope 2
Base point for slope2 of charecterstic Base point 2
Pick up for add on stablisation I Add on stab
Duration for add on stablisation T Add on stab
7 RESTRICTED EARTH FAULT PROTECTION 64
Setting name
64R Element
64R Setting
64R-1 delay
8 RESTRICTED EARTH FAULT PROTECTION 51G
Setting name
51G Element
51G Setting
51G-1 delay

Range
Enabled, Disabled

Setting
Enabled

Prime

0.05..4.00 A STEP
0.125
0.01
Normal Inverse ,Very Normal Inverse
Inverse ,Extremely
Inverse ,Long Inverse
0.05..3.20 s, oo
0.5

Range
Enabled, Disabled

Setting
Enabled

0.05..25.00 A STEP
0.01
0.00..60.00 s

1.1

Range

Setting

Range
Diasabled/Enabled
0.05..2
20..60000

Setting
Enabled
0.1 x In
100ms

Range
Diasabled/Enabled
0.05..2
20..60000

Setting
Enabled
0.15 x In
500ms

ON/OFF
0.05..2 I/InO
0.00..60.00 s
0.5..35 I/InO
0.00..60.00 s
0.1..0.5
0.00..2 I/InO
0.25..0.95
0.00..10 I/InO
2..15 I/InO
2..250 Cycles

15.625

Prime

137.5

1.3

ON
0.2
0
8
0
0.3
0
0.7
2.5
4
15

Prime

12.5

18.75

110kV SwitchYard -Relay & Control Panel


Transformer Circuit Breaker overall Differential Protection
Relay type Siemens Reyrolle 7UT613
1 SYSTEM CONFIG
Description
Range
System Frequency
50, 60
Selects the Power System Frequency from 50 or 60 Hz
Setting Dependencies
Enabled, Disabled
When enabled only active settings are displayed and
all others hidden
2 CT/VT CONFIG
Description
Range
CTs
GT HV side
CT rated primary
CT rated secondary
GT LV side
CT rated primary
CT rated secondary
Generator neutral side
CT rated primary
CT rated secondary
PTs
PT rated primary
PT rated Secondary
3 Differential Protection: 87

Description

Diff.Prot
Pick up value of differential current I-diff>
T I-diff> time delay T I-diff>
Pick up value of High set trip I-diff>>
T I-diff> time delay T I-diff>>
Slope 1 of tripping charecterstic Slope 1
Base point for slope1 of charecterstic Base point 1
Slope 2 of tripping charecterstic Slope 2
Base point for slope2 of charecterstic Base point 2
Pick up for add on stablisation I Add on stab
Duration for add on stablisation T Add on stab

Range

ON/OFF
0.05..2 I/InO
0.00..60.00 s
0.5..35 I/InO
0.00..60.00 s
0.1..0.5
0.00..2 I/InO
0.25..0.95
0.00..10 I/InO
2..15 I/InO
2..250 Cycles

Setting
50Hz

Prime

Enabled

Setting

Prime

10..50000 A
1A/5A
10..50000 A
1A/5A
10..50000 A
1A/5A

125A
1A
1250A
1A
1250A
1A

0~132000 V
110230

11000 V
110

Setting

Prime

ON
0.2
0
8
0
0.3
0
0.7
2.5
4
15

SETTING DETAILS FOR


11kV SWITCH BOARD

11 kV HT LCSS-1 Unit Auxiliary Switch Board


Incomer from Generator Transformer
Relay type Siemens Reyrolle 7SJ803
1 SYSTEM CONFIG
Description
System Frequency
Selects the Power System Frequency from
50 or 60 Hz

Range
50, 60

Setting
50Hz

Enabled, Disabled

Enabled

Range

Setting

Prime

CT rated primary
CT rated secondary

10..50000 A
1A/5A

1250A
1A

PT rated primary
PT rated Secondary

0~132000 V
110230

11000 V
110

Range
Enabled, Disabled
Enabled, Disabled

Setting
Enabled
Enabled

Prime

Range
Enabled, Disabled

Setting
Enabled

Prime

51-1 Setting (Ip)


Pickup level
51-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)
4.2 50-1

0.1..4.00 A STEP 0.1

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse
0.05..3.20 s, oo

Normal InverseIEC

Description
50-1 Element
Selects whether the INST/DTL Overcurrent
element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time

Range
Enabled, Disabled

Setting
Enabled

0.1..25.00 A STEP 0.1

0.00..60.00 s

0.75

Setting Dependencies
When enabled only active settings are
displayed and all others hidden
2 CT/VT CONFIG
Description
CTs

Prime

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled

1250

0.9

Prime

8750

5 DERIVED E/F
5.1 51N-1
Description

Range

Setting

51N-1 Element
Selects whether the 51N-1 IDMTL derived
Earth Fault element is enabled

Enabled, Disabled

Enabled

51N-1 Setting (IEp)


Pickup level
51N-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
51N-1 Time Mult (IEC/ANSI) (TEp)
Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)

0.05..4.00 A STEP 0.01

0.1

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse
0.05..3.20 s, oo

Normal Inverse

Range
Enabled, Disabled

Setting
Enabled

0.05..25.00 A STEP 0.01

0.00..60.00 s

1.15s

Range

Setting

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

o/v

OFF, O/V, U/V


5.0, 5.580.0200.0

o/v

5.2 50N-1
Description
50N-1 Element
Selects whether the DTL derived Earth
fault element is enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time
6 Over Voltage Protection :59
Setting name
6.1 59-1 Element 1
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
6.2 59 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases

0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

Prime

125

0.4

Prime

1250

Prim Value

120
3

12000

5
Any

126
1.5
10
Any

12600

7 Under Voltage Protection:27


Setting name
7.1 27-1 Element 1
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay

Range

Setting

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

8.1 67-1
Description

Range

Setting

67 Element

Enabled, Disabled

Enabled

67 Setting
Pickup level
67 Char
Selects characteristic curve to be IEC or
ANSI
IDMTL
DTL
67
Time
Multor(IEC/ANSI)
Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)

0.05, 0.06 ... 2.49, 2.5

0.9

DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI


IEC-NI IEC-NI
0.025,
0.05 ... 1.575, 1.6

IEC-NI

Characteristic Angle

-179.180 deg

-45

V Hysteresis
V Block Threshold
V O/P Phases
7.2 27 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
8 Directional Current Protection :67

Selects whether the 51-1 IDMTL Overcurrent


element is enabled

Prim Value

99
1

9900

3
Any

93.5
1.5

9350

10
Any

0.12

Prime

1125

8.2 67N-1
Description

67N-1 Element
Selects whether the DTL derived Earth fault
element is enabled

Range

Enabled, Disabled

67N-1 Setting
0.05, 0.06 ... 49.5, 50
Pickup level
Gn 67N-1 Delay
0, 0.01 ... 14300, 14400
Sets operate delay time
Characteristic Angle
-179.180 deg
9 Breaker failure Protection -CB Fail Supervision : 50LBB
Setting name
Range
50BF Element
Diasabled/Enabled
50BF Setting
0.05..2
50BF-1 delay
20..60000
50BF-2 delay
20..60000

Setting

Enabled
0.08X In

Prime
187.5

0.5
-45
Setting
Enabled
0.2 x In
100ms
250 ms

250

Incomer from Turbo Generator 1


Relay type Siemens Reyrolle 7SJ803
1 SYSTEM CONFIG
Description
System Frequency
Selects the
Power System Frequency from
Setting
Dependencies
When
enabled
only active settings are
2 CT/VT CONFIG
Description
CTs

Range
50, 60
Enabled, Disabled

Setting
50Hz
Enabled

Prime

Range

Setting

Prime

CT rated primary
CT rated secondary

10..50000 A
1A/5A

1250A
1A

PT rated primary
PT rated Secondary

0~132000 V
110230

11000 V
110

Range
Enabled, Disabled
Enabled, Disabled

Setting
Enabled
Enabled

Prime

Range
Enabled, Disabled
0.1..4.00 A STEP 0.1
Normal Inverse ,Very Inverse
,Extremelys,Inverse
,Long
0.05..3.20
oo

Setting
Enabled
0.95
Normal InverseIEC
0.18

Prime

Range
Enabled, Disabled
0.1..25.00 A STEP 0.1
0.00..60.00 s

Setting
Enabled
4
0.7

Prime

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects
whether
51-1
Setting
(Ip)the 51-1 IDMTL
Pickup
level
51-1
Char
Selects
characteristic
curve to
be IEC or
51-1
Time
Mult (IEC/ANSI)
(Tp)
Time
multiplier (applicable to IEC and
4.2 50-1
Description
50-1 Element
Selects
whether
the INST/DTL Overcurrent
50-1 Setting
(I>>)
Pickup
level(T-I>>)
50-1
Delay
Sets operate delay time

1187.5

5000

5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
SelectsSetting
whether(IEp)
the 51N-1 IDMTL derived
51N-1
Pickup Char
level
51N-1
Selects
characteristic
curve to(TEp)
be IEC or
51N-1 Time
Mult (IEC/ANSI)
Time50N-1
multiplier (applicable to IEC and
5.2
Description
50N-1 Element
SelectsSetting
whether(IE>>)
the DTL derived Earth
50N-1
Pickup Delay
level (TE>>)
50N-1
Sets
operate
delay
time :59
6
Over
Voltage
Protection
Setting name
6.1 59-1 Element 1
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
6.2 59 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
7 Under Voltage Protection:27
Setting name
7.1 27-1 Element 1
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases

Range
Enabled, Disabled
0.05..4.00 A STEP 0.01
Normal Inverse ,Very Inverse
,Extremely
,Long
0.05..3.20 s,Inverse
oo

Setting
Enabled
0.08
direct
1.8

Prime

Range
Enabled, Disabled
0.05..25.00 A STEP 0.01
0.00..60.00 s

Setting
Enabled
1.8
0.01

Prime

Range

Setting

Prim Value

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

o/v

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

o/v

Range

Setting

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

100

2250

120
3
5

12000

126
1.5
10

12600

Any

Any
Prim Value

99
3
5
Any

9900

7.2 27 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
8 Directional Current Protection :67

8.1 67-1
Description

67 Element
Selects
whether the 51-1 IDMTL Overcurrent
67 Setting
Pickup
67
Charlevel
Selects
curve to be IEC or
67
Timecharacteristic
Mult (IEC/ANSI)
Time multiplierAngle
(applicable to IEC and
Characteristic

8.2 67N-1
Description

67N-1 Element
Selects
whether the DTL derived Earth fault
67N-1 Setting

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

Range

Setting

Enabled, Disabled
0.05, 0.06 ... 2.49, 2.5
DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI,
ANSI-EI
0.025,
0.05 ...ANSI-VI,
1.575, 1.6
-179.180 deg

Range

Enabled, Disabled
0.05, 0.06 ... 49.5, 50
Pickup
level
Gn
67N-1
Delay
0, 0.01 ... 14300, 14400
Sets operate delay
Characteristic
Angletime
-179.180 deg
9 Breaker failure Protection -CB Fail Supervision : 50LBB
Setting name
Range
50BF Element
Diasabled/Enabled
50BF Setting
0.05..2
50BF-1 delay
20..60000
50BF-2 delay
20..60000

93.5
1.5
10

9350

Any

Enabled
0.9
IEC-NI
0.12
-45

Setting

Enabled
0.08
0.5
-45
Setting
Enabled
0.2 x In
100ms
250 ms

Prime
1125

Prime
187.5

250

Incomer from Turbo Generator 2


Relay type Siemens Reyrolle 7SJ803
1 SYSTEM CONFIG
Description
System Frequency
Selects the
Power System Frequency from
Setting
Dependencies
When
enabled
only active settings are
2 CT/VT CONFIG
Description
CTs

Range
50, 60
Enabled, Disabled

Setting
50Hz
Enabled

Prime

Range

Setting

Prime

CT rated primary
CT rated secondary

10..50000 A
1A/5A

300A
1A

PT rated primary
PT rated Secondary

0~132000 V
110230

11000 V
110

Range
Enabled, Disabled
Enabled, Disabled

Setting
Enabled
Enabled

Prime

Range
Enabled, Disabled
0.1..4.00 A STEP 0.1
Normal Inverse ,Very Inverse
,Extremelys,Inverse
,Long
0.05..3.20
oo

Setting
Enabled
0.9
Normal InverseIEC
0.18

Prime

Range
Enabled, Disabled
0.1..25.00 A STEP 0.1
0.00..60.00 s

Setting
Enabled
4
0.7

Prime

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects
whether
51-1
Setting
(Ip)the 51-1 IDMTL
Pickup
level
51-1
Char
Selects
characteristic
curve to
be IEC or
51-1
Time
Mult (IEC/ANSI)
(Tp)
Time
multiplier (applicable to IEC and
4.2 50-1
Description
50-1 Element
Selects
whether
the INST/DTL Overcurrent
50-1 Setting
(I>>)
Pickup
level(T-I>>)
50-1
Delay
Sets operate delay time

270

1200

5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
SelectsSetting
whether(IEp)
the 51N-1 IDMTL derived
51N-1
Pickup Char
level
51N-1
Selects
characteristic
curve to(TEp)
be IEC or
51N-1 Time
Mult (IEC/ANSI)
Time50N-1
multiplier (applicable to IEC and
5.2
Description
50N-1 Element
SelectsSetting
whether(IE>>)
the DTL derived Earth
50N-1
Pickup Delay
level (TE>>)
50N-1
Sets
operate
delay
time :59
6
Over
Voltage
Protection
Setting name
6.1 59-1 Element 1
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
6.2 59 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
7 Under Voltage Protection:27
Setting name
7.1 27-1 Element 1
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases

Range
Enabled, Disabled
0.05..4.00 A STEP 0.01
Normal Inverse ,Very Inverse
,Extremely
,Long
0.05..3.20 s,Inverse
oo

Setting
Enabled
0.08
Direct
1.8

Prime

Range
Enabled, Disabled
0.05..25.00 A STEP 0.01
0.00..60.00 s

Setting
Enabled
3.5
0.01

Prime

Range

Setting

Prim Value

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

o/v

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

o/v

Range

Setting

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

100

4375

120
3
5

12000

126
1.5
10

12600

Any

Any
Prim Value

99
3
5
Any

9900

7.2 27 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
8 Directional Current Protection :67

8.1 67-1
Description

67 Element
Selects
whether the 51-1 IDMTL Overcurrent
67 Setting
Pickup
67
Charlevel
Selects
curve to be IEC or
67
Timecharacteristic
Mult (IEC/ANSI)
Time multiplierAngle
(applicable to IEC and
Characteristic

8.2 67N-1
Description

67N-1 Element
Selects
whether the DTL derived Earth fault
67N-1 Setting

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

Range

Setting

Enabled, Disabled
0.05, 0.06 ... 2.49, 2.5
DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI,
ANSI-EI
0.025,
0.05 ...ANSI-VI,
1.575, 1.6
-179.180 deg

Range

Enabled, Disabled
0.05, 0.06 ... 49.5, 50
Pickup
level
Gn
67N-1
Delay
0, 0.01 ... 14300, 14400
Sets operate delay
Characteristic
Angletime
-179.180 deg
9 Breaker failure Protection -CB Fail Supervision : 50LBB
Setting name
Range
50BF Element
Diasabled/Enabled
50BF Setting
0.05..2
50BF-1 delay
20..60000
50BF-2 delay
20..60000

93.5
1.5
10

9350

Any

Enabled
0.9
IEC-NI
0.12
-45

Setting

Enabled
0.08
0.5
-45
Setting
Enabled
0.2 x In
100ms
250 ms

Prime
270

Prime
45

60

Transformer Feeder 750 kVA STP & AFBC FDR 1 & 2 Panel Nos 5, 14&15
Relay type Siemens Reyrolle 7SJ600
1 SYSTEM CONFIG
Description
Range
System Frequency
50, 60
Selects the Power System Frequency from
50 or 60 Hz
Setting Dependencies
When enabled only active settings are
displayed and all others hidden
2 CT/VT CONFIG
Description
CTs

Setting
50Hz

Prime

Enabled, Disabled

Enabled

Range

Setting

Prime

CT rated primary
CT rated secondary

10..50000 A
1A/5A

100A
1A

PT rated primary
PT rated Secondary

0~132000 V
110230

11000 V
110

Range
Enabled, Disabled
Enabled, Disabled

Setting
Enabled
Enabled

Prime

Range
Enabled, Disabled

Setting
Enabled

Prime

0.1..4.00 A STEP 0.1

0.5

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse
0.05..3.20 s, oo

Extremely
Inverse-IEC

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)

4.2 50-1
Description
Range
50-1 Element
Enabled, Disabled
Selects whether the INST/DTL Overcurrent
element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time

50

Setting
Enabled

0.1..25.00 A STEP 0.1

10

0.00..60.00 s

0.05

Prime

1000

5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived
Earth Fault element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL

Range
Enabled, Disabled

Setting
Enabled

0.05..4.00 A STEP 0.01

0.1

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse

Normal Inverse

51N-1 Time Mult (IEC/ANSI) (TEp)


Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)
5.2 50N-1
Description
50N-1 Element
Selects whether the DTL derived Earth
fault element is enabled

0.05..3.20 s, oo

0.1

Range
Enabled, Disabled

Setting
Enabled

50N-1 Setting (IE>>)


Pickup level
50N-1 Delay (TE>>)
Sets operate delay time

0.05..25.00 A STEP 0.01

0.00..60.00 s

0.25s

Prime

10

Prime

100

Transformer Feeder LCSS 1 2000 kVA FDR 1 & 2 Panel Nos 4 & 11
Relay type Siemens Reyrolle 7SJ600
1 SYSTEM CONFIG
Description
Range
System Frequency
50, 60
Selects the Power System Frequency from
50 or 60 Hz
Setting Dependencies
When enabled only active settings are
displayed and all others hidden
2 CT/VT CONFIG
Description
CTs

Setting
50Hz

Prime

Enabled, Disabled

Enabled

Range

Setting

Prime

CT rated primary
CT rated secondary

10..50000 A
1A/5A

125A
1A

PT rated primary
PT rated Secondary

0~132000 V
110230

11000 V
110

Range
Enabled, Disabled
Enabled, Disabled

Setting
Enabled
Enabled

Prime

Range
Enabled, Disabled

Setting
Enabled

Prime

0.1..4.00 A STEP 0.1

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse
0.05..3.20 s, oo

Extremely
Inverse-IEC

Range
Enabled, Disabled

Setting
Enabled

0.1..25.00 A STEP 0.1

13

0.00..60.00 s

0.05

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent
element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time

125

Prime

1625

5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived
Earth Fault element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL

Range
Enabled, Disabled

Setting
Enabled

0.05..4.00 A STEP 0.01

0.1

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse

Normal Inverse

51N-1 Time Mult (IEC/ANSI) (TEp)


Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)
5.2 50N-1
Description
50N-1 Element
Selects whether the DTL derived Earth
fault element is enabled

0.05..3.20 s, oo

0.3

Range
Enabled, Disabled

Setting
Enabled

50N-1 Setting (IE>>)


Pickup level
50N-1 Delay (TE>>)
Sets operate delay time

0.05..25.00 A STEP 0.01

0.8

0.00..60.00 s

0.25s

Prime

12.5

Prime

100

Transformer Feeder RMP3 1000 kVA

Panel Nos

Relay type Siemens Reyrolle 7SJ600


1 SYSTEM CONFIG
Description
System Frequency
Selects the Power System Frequency from
50 or 60 Hz
Setting Dependencies
When enabled only active settings are
displayed and all others hidden
2 CT/VT CONFIG
Description
CTs

Range
50, 60

Setting
50Hz

Prime

Enabled, Disabled

Enabled

Range

Setting

Prime

CT rated primary
CT rated secondary

10..50000 A
1A/5A

100A
1A

PT rated primary
PT rated Secondary

0~132000 V
110230

11000 V
110

Range
Enabled, Disabled
Enabled, Disabled

Setting
Enabled
Enabled

Prime

Range
Enabled, Disabled

Setting
Enabled

Prime

0.1..4.00 A STEP 0.1

0.6

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse
0.05..3.20 s, oo

Extremely
Inverse-IEC

Range
Enabled, Disabled

Setting
Enabled

0.1..25.00 A STEP 0.1

10.5

0.00..60.00 s

0.05

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent
element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time

60

Prime

1050

5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived
Earth Fault element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL

Range
Enabled, Disabled

Setting
Enabled

0.05..4.00 A STEP 0.01

0.08

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse

Normal Inverse

51N-1 Time Mult (IEC/ANSI) (TEp)


Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)
5.2 50N-1
Description
50N-1 Element
Selects whether the DTL derived Earth
fault element is enabled

0.05..3.20 s, oo

0.3

Range
Enabled, Disabled

Setting
Enabled

50N-1 Setting (IE>>)


Pickup level
50N-1 Delay (TE>>)
Sets operate delay time

0.05..25.00 A STEP 0.01

0.6

0.00..60.00 s

0.25s

Prime

Prime

60

Transformer Feeder 1250 kVA KILN 1&2 Panel No 2


Relay type Siemens Reyrolle 7SJ600
1 SYSTEM CONFIG
Description
System Frequency
Selects the Power System Frequency from
50 or 60 Hz
Setting Dependencies
When enabled only active settings are
displayed and all others hidden
2 CT/VT CONFIG
Description
CTs

Range
50, 60

Setting
50Hz

Prime

Enabled, Disabled

Enabled

Range

Setting

Prime

CT rated primary
CT rated secondary

10..50000 A
1A/5A

100A
1A

PT rated primary
PT rated Secondary

0~132000 V
110230

11000 V
110

Range
Enabled, Disabled
Enabled, Disabled

Setting
Enabled
Enabled

Prime

Range
Enabled, Disabled

Setting
Enabled

Prime

0.1..4.00 A STEP 0.1

0.75

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse
0.05..3.20 s, oo

Extremely
Inverse-IEC

Range
Enabled, Disabled

Setting
Enabled

0.1..25.00 A STEP 0.1

12

0.00..60.00 s

0.05

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent
element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time

75

Prime

1200

5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived
Earth Fault element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL

Range
Enabled, Disabled

Setting
Enabled

0.05..4.00 A STEP 0.01

0.08

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse

Normal Inverse

51N-1 Time Mult (IEC/ANSI) (TEp)


Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)
5.2 50N-1
Description
50N-1 Element
Selects whether the DTL derived Earth
fault element is enabled

0.05..3.20 s, oo

0.3

Range
Enabled, Disabled

Setting
Enabled

50N-1 Setting (IE>>)


Pickup level
50N-1 Delay (TE>>)
Sets operate delay time

0.05..25.00 A STEP 0.01

0.8

0.00..60.00 s

0.25s

Prime

Prime

80

Transformer Feeder 15000 kVA Pellet Plant Panel No 3


Relay type Siemens Reyrolle 7SJ600
1 SYSTEM CONFIG
Description
System Frequency
Selects the Power System Frequency from
50 or 60 Hz
Setting Dependencies
When enabled only active settings are
displayed and all others hidden
2 CT/VT CONFIG
Description
CTs

Range
50, 60

Setting
50Hz

Prime

Enabled, Disabled

Enabled

Range

Setting

Prime

CT rated primary
CT rated secondary

10..50000 A
1A/5A

800A
1A

PT rated primary
PT rated Secondary

0~132000 V
110230

11000 V
110

Range
Enabled, Disabled
Enabled, Disabled

Setting
Enabled
Enabled

Prime

Range
Enabled, Disabled

Setting
Enabled

Prime

0.1..4.00 A STEP 0.1

1.15

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse
0.05..3.20 s, oo

Normal InverseIEC

Range
Enabled, Disabled

Setting
Enabled

0.1..25.00 A STEP 0.1

0.00..60.00 s

0.6

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent
element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time

920

0.8

Prime

5600

5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived
Earth Fault element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL

Range
Enabled, Disabled

Setting
Enabled

0.05..4.00 A STEP 0.01

0.125

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse

Normal Inverse

51N-1 Time Mult (IEC/ANSI) (TEp)


Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)
5.2 50N-1
Description
50N-1 Element
Selects whether the DTL derived Earth
fault element is enabled

0.05..3.20 s, oo

0.4

Range
Enabled, Disabled

Setting
Enabled

50N-1 Setting (IE>>)


Pickup level
50N-1 Delay (TE>>)
Sets operate delay time

0.05..25.00 A STEP 0.01

0.00..60.00 s

Prime

12.5

Prime

800

Transformer Feeder KILN 3 2500 kVA Panel No13


Relay type Siemens Reyrolle 7SJ600
1 SYSTEM CONFIG
Description
System Frequency
Selects the Power System Frequency from
50 or 60 Hz
Setting Dependencies
When enabled only active settings are
displayed and all others hidden
2 CT/VT CONFIG
Description
CTs

Range
50, 60

Setting
50Hz

Prime

Enabled, Disabled

Enabled

Range

Setting

Prime

CT rated primary
CT rated secondary

10..50000 A
1A/5A

150A
1A

PT rated primary
PT rated Secondary

0~132000 V
110230

11000 V
110

Range
Enabled, Disabled
Enabled, Disabled

Setting
Enabled
Enabled

Prime

Range
Enabled, Disabled

Setting
Enabled

Prime

0.1..4.00 A STEP 0.1

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse
0.05..3.20 s, oo

Extremely
Inverse-IEC

Range
Enabled, Disabled

Setting
Enabled

0.1..25.00 A STEP 0.1

12

0.00..60.00 s

0.05

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent
element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time

150

Prime

1800

5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived
Earth Fault element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL

Range
Enabled, Disabled

Setting
Enabled

0.05..4.00 A STEP 0.01

0.125

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse

Normal Inverse

51N-1 Time Mult (IEC/ANSI) (TEp)


Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)
5.2 50N-1
Description
50N-1 Element
Selects whether the DTL derived Earth
fault element is enabled

0.05..3.20 s, oo

0.3

Range
Enabled, Disabled

Setting
Enabled

50N-1 Setting (IE>>)


Pickup level
50N-1 Delay (TE>>)
Sets operate delay time

0.05..25.00 A STEP 0.01

0.9

0.00..60.00 s

0.25s

Prime

18.75

Prime

135

11 kV HT LBSS-1 Switch Board


Inter Panel Incomer from Main Panel for 15 MVA Transformer standalone Panel
Relay type Siemens Reyrolle 7UT612
1 SYSTEM CONFIG
Description
Range
Setting
System Frequency
50, 60
50Hz
Selects the Power System Frequency from
50 or 60 Hz
Setting Dependencies
When enabled only active settings are
displayed and all others hidden
2 CT/VT CONFIG
Description
CTs

Prime

Enabled, Disabled

Enabled

Range

Setting

Prime

CT rated primary
CT rated secondary

10..50000 A
1A/5A

800A
1A

PT rated primary
PT rated Secondary

0~132000 V
110230

11000 V
110

Range
Enabled, Disabled
Enabled, Disabled

Setting
Enabled
Enabled

Prime

Range
Enabled, Disabled

Setting
Enabled

Prime

0.1..4.00 A STEP 0.1

1.15

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse
0.05..3.20 s, oo

Extremely
Inverse-IEC

Range
Enabled, Disabled

Setting
Enabled

0.1..25.00 A STEP 0.1

0.00..60.00 s

0.52

Range
Enabled, Disabled

Setting
Enabled

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent
element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time
5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived
Earth Fault element is enabled

920

0.65

Prime

4800

Prime

51N-1 Setting (IEp)


Pickup level
51N-1 Char
Selects characteristic curve to be IEC or
ANSI IDMTL or DTL

0.05..4.00 A STEP 0.01

0.11

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse

Normal Inverse

51N-1 Time Mult (IEC/ANSI) (TEp)


Time multiplier (applicable to IEC and
ANSI curves but not DTL selection)

0.05..3.20 s, oo

0.35

Range
Enabled, Disabled

Setting
Enabled

0.05..25.00 A STEP 0.01

0.95

0.00..60.00 s

0.9s

Description

Range

Setting

Base point for slope1 of charecterstic


Base point 1
Slope 2 of tripping charecterstic Slope 2

0.00..2 I/InO

5.2 50N-1
Description
50N-1 Element
Selects whether the DTL derived Earth
fault element is enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time

88

Prime

760

6 Differential Protection: 87
Diff.Prot
Pick up value of differential current I-diff>
T I-diff> time delay T I-diff>
Pick up value of High set trip I-diff>>
T I-diff> time delay T I-diff>>
Slope 1 of tripping charecterstic Slope 1

ON/OFF
0.05..2 I/InO
0.00..60.00 s
0.5..35 I/InO
0.00..60.00 s
0.1..0.5

0.25..0.95

Base point for slope2 of charecterstic


0.00..10 I/InO
Base point 2
Pick up for add on stablisation I Add on 2..15 I/InO
stab
Duration for add on stablisation T Add on 2..250 Cycles
stab

ON
0.2
0
8
0
0.3
0
0.7
2.5
4
15

Prime

SETTING DETAILS FOR


6.6 kV SWITCH BOARDS

6.6 kV HV Distribution Board


Incomers 1 and 2 from Siemens make 6.6kV Board
Relay type ABB REF615
1 SYSTEM CONFIG
Description
Range
System Frequency
50, 60
Selects the Power System
Frequency from 50 or 60 Hz
Setting Dependencies
When enabled only active settings
are displayed and all others hidden
2 CT/VT CONFIG
Description
CTs

Setting
50Hz

Prime

Enabled, Disabled

Enabled

Range

Setting

Prime

CT rated primary
CT rated secondary

10..50000 A
1A/5A

600A
1A

PT rated primary
PT rated Secondary

0~132000 V
110230

6600 V
110

Range
Enabled, Disabled
Enabled, Disabled

Setting
Enabled
Enabled

Prime

Range
Enabled, Disabled

Setting
Enabled

Prime

0.1..4.00 A STEP 0.1

0.9

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse
0.05..3.20 s, oo

Normal InverseIEC

Range
Enabled, Disabled

Setting
Enabled

0.1..25.00 A STEP 0.1

0.00..60.00 s

0.15

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC
and ANSI curves but not DTL
selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL
Overcurrent element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time

540

0.7

Prime

4800

5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL
derived Earth Fault element is
enabled
51N-1
Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL

Range
Enabled, Disabled

Setting
Enabled

0.05..4.00 A STEP 0.01

0.1

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse

Normal Inverse

51N-1 Time Mult (IEC/ANSI) (TEp)


Time multiplier (applicable to IEC
and ANSI curves but not DTL
selection)
5.2 50N-1

0.05..3.20 s, oo

0.2

Description

Range

Setting

50N-1 Element
Selects whether the DTL derived
Earth fault element is enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time
6 Over Voltage Protection :59
Setting name
6.1 59-1 Element 1
V Operation
V Setting (Ph-N) Gn V Setting (PhPh)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
6.2 59 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (PhPh)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
7 Under Voltage Protection:27
Setting name
7.1 27-1 Element 1
V Operation
V Setting (Ph-N) Gn V Setting (PhPh)
V Delay

Enabled, Disabled

Enabled

0.05..25.00 A STEP 0.01

0.8

0.00..60.00 s

0.4

Range

Setting

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

o/v

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

o/v

Range

Setting

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

V Hysteresis
V Block Threshold
V O/P Phases

Prime

60

Prime

480

Prim Value

120
3
5

7200

126
1.5
10

7560

Any

Any
Prim Value

99
1
3
Any

5940

7.2 27 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (PhPh)
V Delay

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
V Hysteresis
1,290
V Block Threshold
OFF,1,25100
V O/P Phases
Any One, All
8 Breaker failure Protection -CB Fail Supervision : 50LBB
Setting name
Range
50BF Element
Diasabled/Enabled
50BF Setting
0.05..2
50BF-1 delay
20..60000
50BF-2 delay
20..60000

u/v
93.5
1.5

5610

10
Any
Setting
Enabled
0.2 x In
100ms
250 ms

250

Buscoupler panel
Relay type ABB REF610
1 SYSTEM CONFIG
Description
System Frequency
Selects the Power System
Frequency from 50 or 60 Hz
Setting Dependencies
When enabled only active settings
are displayed and all others hidden
2 CT/VT CONFIG
Description
CTs

Range
50, 60

Setting
50Hz

Prime

Enabled, Disabled

Enabled

Range

Setting

Prime

CT rated primary
CT rated secondary

10..50000 A
1A/5A

600A
1A

PT rated primary
PT rated Secondary

0~132000 V
110230

6600 V
110

Range
Enabled, Disabled
Enabled, Disabled

Setting
Enabled
Enabled

Prime

Range
Enabled, Disabled

Setting
Enabled

Prime

0.1..4.00 A STEP 0.1

0.9

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse
0.05..3.20 s, oo

Normal InverseIEC

Range
Enabled, Disabled

Setting
Enabled

0.1..25.00 A STEP 0.1

0.00..60.00 s

0.15

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC
and ANSI curves but not DTL
selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL
Overcurrent element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time

540

0.7

Prime

4800

5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL
derived Earth Fault element is
enabled
51N-1
Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL

Range
Enabled, Disabled

Setting
Enabled

0.05..4.00 A STEP 0.01

0.1

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse

Normal Inverse

51N-1 Time Mult (IEC/ANSI) (TEp)


Time multiplier (applicable to IEC
and ANSI curves but not DTL
selection)
5.2 50N-1

0.05..3.20 s, oo

0.2

Description
50N-1 Element
Selects whether the DTL derived
Earth fault element is enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time

Range
Enabled, Disabled

Setting
Enabled

0.05..25.00 A STEP 0.01

0.8

0.00..60.00 s

0.4

Prime

60

Prime

480

Transformer Feeder 1600 kVA TG FDR1 &2 Panels No__& __


Relay type ABB REF 610
1 SYSTEM CONFIG
Description
Range
System Frequency
50, 60
Selects the Power System
Frequency from 50 or 60 Hz
Setting Dependencies
When enabled only active settings
are displayed and all others hidden
2 CT/VT CONFIG
Description
CTs

Setting
50Hz

Prime

Enabled, Disabled

Enabled

Range

Setting

Prime

CT rated primary
CT rated secondary

10..50000 A
1A/5A

200A
5A

PT rated primary
PT rated Secondary

0~132000 V
110230

6600 V
110

Range
Enabled, Disabled
Enabled, Disabled

Setting
Enabled
Enabled

Prime

Range
Enabled, Disabled

Setting
Enabled

Prime

0.1..4.00 A STEP 0.1

0.85

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse
0.05..3.20 s, oo

Extremely
Inverse-IEC

Range
Enabled, Disabled

Setting
Enabled

0.1..25.00 A STEP 0.1

10

0.00..60.00 s

0.05

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC
and ANSI curves but not DTL
selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL
Overcurrent element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time

170

Prime

2000

5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL
derived Earth Fault element is
enabled
51N-1
Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL

Range
Enabled, Disabled

Setting
Enabled

0.05..4.00 A STEP 0.01

0.08

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse

Normal Inverse

51N-1 Time Mult (IEC/ANSI) (TEp)


Time multiplier (applicable to IEC
and ANSI curves but not DTL
selection)
5.2 50N-1

0.05..3.20 s, oo

0.1

Description
50N-1 Element
Selects whether the DTL derived
Earth fault element is enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time

Range
Enabled, Disabled

Setting
Enabled

0.05..25.00 A STEP 0.01

0.8

0.00..60.00 s

0.25s

Prime

16

Prime

160

Transformer Feeder 1600 kVA BALLING SYSTEM FDR1 &2 Panels No__& __
Relay type ABB REF 610
1 SYSTEM CONFIG
Description
Range
Setting
System Frequency
50, 60
50Hz
Selects the Power System
Frequency from 50 or 60 Hz
Setting Dependencies
When enabled only active settings
are displayed and all others hidden
2 CT/VT CONFIG
Description
CTs

Prime

Enabled, Disabled

Enabled

Range

Setting

Prime

CT rated primary
CT rated secondary

10..50000 A
1A/5A

200A
5A

PT rated primary
PT rated Secondary

0~132000 V
110230

6600 V
110

Range
Enabled, Disabled
Enabled, Disabled

Setting
Enabled
Enabled

Prime

Range
Enabled, Disabled

Setting
Enabled

Prime

0.1..4.00 A STEP 0.1

0.85

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse
0.05..3.20 s, oo

Extremely
Inverse-IEC

Range
Enabled, Disabled

Setting
Enabled

0.1..25.00 A STEP 0.1

10

0.00..60.00 s

0.05

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC
and ANSI curves but not DTL
selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL
Overcurrent element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time

170

Prime

2000

5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL
derived Earth Fault element is
enabled
51N-1
Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL

Range
Enabled, Disabled

Setting
Enabled

0.05..4.00 A STEP 0.01

0.08

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse

Normal Inverse

51N-1 Time Mult (IEC/ANSI) (TEp)


Time multiplier (applicable to IEC
and ANSI curves but not DTL
selection)
5.2 50N-1

0.05..3.20 s, oo

0.1

Description
50N-1 Element
Selects whether the DTL derived
Earth fault element is enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time

Range
Enabled, Disabled

Setting
Enabled

0.05..25.00 A STEP 0.01

0.8

0.00..60.00 s

0.25s

Prime

16

Prime

160

Transformer Feeder 1000 kVA SCREENING MCC FDR 1 &2 Panels No__& __
Relay type ABB REF 610
1 SYSTEM CONFIG
Description
Range
Setting
System Frequency
50, 60
50Hz
Selects the Power System
Frequency from 50 or 60 Hz
Setting Dependencies
When enabled only active settings
are displayed and all others hidden
2 CT/VT CONFIG
Description
CTs

Prime

Enabled, Disabled

Enabled

Range

Setting

Prime

CT rated primary
CT rated secondary

10..50000 A
1A/5A

150A
5A

PT rated primary
PT rated Secondary

0~132000 V
110230

6600 V
110

Range
Enabled, Disabled
Enabled, Disabled

Setting
Enabled
Enabled

Prime

Range
Enabled, Disabled

Setting
Enabled

Prime

0.1..4.00 A STEP 0.1

0.7

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse
0.05..3.20 s, oo

Extremely
Inverse-IEC

Range
Enabled, Disabled

Setting
Enabled

0.1..25.00 A STEP 0.1

12

0.00..60.00 s

0.05

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC
and ANSI curves but not DTL
selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL
Overcurrent element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time

105

Prime

1800

5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL
derived Earth Fault element is
enabled
51N-1
Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL

Range
Enabled, Disabled

Setting
Enabled

0.05..4.00 A STEP 0.01

0.1

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse

Normal Inverse

51N-1 Time Mult (IEC/ANSI) (TEp)


Time multiplier (applicable to IEC
and ANSI curves but not DTL
selection)
5.2 50N-1

0.05..3.20 s, oo

0.1

Description
50N-1 Element
Selects whether the DTL derived
Earth fault element is enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time

Range
Enabled, Disabled

Setting
Enabled

0.05..25.00 A STEP 0.01

0.9

0.00..60.00 s

0.25s

Prime

15

Prime

135

Transformer Feeder 1000 kVA PROPORTION & MIXING MCC FDR1 &2 Panels No__& __
Relay type ABB REF 610
1 SYSTEM CONFIG
Description
Range
Setting
Prime
System Frequency
50, 60
50Hz
Selects the Power System
Frequency from 50 or 60 Hz
Setting Dependencies
When enabled only active settings
are displayed and all others hidden
2 CT/VT CONFIG
Description
CTs

Enabled, Disabled

Enabled

Range

Setting

Prime

CT rated primary
CT rated secondary

10..50000 A
1A/5A

300A
5A

PT rated primary
PT rated Secondary

0~132000 V
110230

6600 V
110

Range
Enabled, Disabled
Enabled, Disabled

Setting
Enabled
Enabled

Prime

Range
Enabled, Disabled

Setting
Enabled

Prime

0.1..4.00 A STEP 0.1

0.35

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse
0.05..3.20 s, oo

Extremely
Inverse-IEC

Range
Enabled, Disabled

Setting
Enabled

0.1..25.00 A STEP 0.1

0.00..60.00 s

0.05

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL
Overcurrent element is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC
and ANSI curves but not DTL
selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL
Overcurrent element is enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time

105

Prime

1800

5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL
derived Earth Fault element is
enabled
51N-1
Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be
IEC or ANSI IDMTL or DTL

Range
Enabled, Disabled

Setting
Enabled

0.05..4.00 A STEP 0.01

0.05

Normal Inverse ,Very Inverse


,Extremely Inverse ,Long
Inverse

Normal Inverse

51N-1 Time Mult (IEC/ANSI) (TEp)


Time multiplier (applicable to IEC
and ANSI curves but not DTL
selection)
5.2 50N-1

0.05..3.20 s, oo

0.1

Description
50N-1 Element
Selects whether the DTL derived
Earth fault element is enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time

Range
Enabled, Disabled

Setting
Enabled

0.05..25.00 A STEP 0.01

0.45

0.00..60.00 s

0.25s

Prime

15

Prime

135

Capacitor Feeder 600 kVAr FDR 1 &2 Panels No__& __


Relay type ABB REF 615
1 SYSTEM CONFIG
Description
Range
System Frequency
50, 60
Selects the
Power System
Setting
Dependencies
Enabled, Disabled
When
enabled
only active settings
2 CT/VT
CONFIG
Description
Range
CTs
CT rated primary
CT rated secondary
PTs
PT rated primary
PT rated Secondary
3 FUNCTION CONFIG
Description
Range
Phase Overcurrent 50/51
Enabled, Disabled
Derived E/F 50N/51N
Enabled, Disabled
4 CURRENT PROTECTION
4.1 51-1
Description
Range
51-1 Element
Enabled, Disabled
Selects
whether
51-1
Setting
(Ip)the 51-1 IDMTL
0.1..4.00 A STEP 0.1
Pickup
level
51-1 Char
Normal Inverse ,Very Inverse
Selects
characteristic
curve to
be
,Extremelys,Inverse
,Long
51-1
Time
Mult (IEC/ANSI)
(Tp)
0.05..3.20
oo
Time
multiplier (applicable to IEC
4.2 50-1
Description
Range
50-1 Element
Enabled, Disabled
Selects
whether
the INST/DTL
50-1
Setting
(I>>)
0.1..25.00 A STEP 0.1
Pickup
level(T-I>>)
50-1
Delay
0.00..60.00 s
Sets operate delay time

Setting
50Hz
Enabled

Prime

Setting

Prime

10..50000 A
1A/5A

150A
5A

0~132000 V
110230

6600 V
110

Setting
Enabled
Enabled

Prime

Setting
Enabled
0.4
Normal Inverse
0.2

Prime

Setting
Enabled
12
0.05

Prime

60

1800

5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects
whether(IEp)
the 51N-1 IDMTL
51N-1 Setting
Pickup Char
level
51N-1
SelectsTime
characteristic
curve to(TEp)
be
51N-1
Mult (IEC/ANSI)
Time50N-1
multiplier (applicable to IEC
5.2
Description
50N-1 Element
SelectsSetting
whether(IE>>)
the DTL derived
50N-1
Pickup Delay
level (TE>>)
50N-1
Sets
operate
delay time
6 OVER
VOLTAGE
PROTECTION :59
Setting name
6.1 59-1 Element 1
V Operation
V Setting (Ph-N) Gn V Setting (PhPh)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases
6.2 59 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (PhPh)
V Delay
V Hysteresis
V Block Threshold
V O/P Phases

Range
Enabled, Disabled
0.05..4.00 A STEP 0.01
Normal Inverse ,Very Inverse
,Extremelys,Inverse
,Long
0.05..3.20
oo

Setting
Enabled
0.05
Normal Inverse
0.2

Prime

Range
Enabled, Disabled
0.05..25.00 A STEP 0.01
0.00..60.00 s

Setting
Enabled
0.5
0.25s

Prime

Range

Setting

Prim Value

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

o/v

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

o/v

7.5

75

126.5
1
5

7590

132
0.5
10

7920

Any

Any

7 UNBALANCE PROTECTION : 46
Parameter

Value (Range)

Set Value

Current Set I2>


0.04 to 0.8 In, STEP 0.01
Time delay
0.02 to 99.9, STEP 0.1
Current Set I2>>
0.04 to 0.8 In, STEP 0.01
Time Multiple setting ( TMS) I2>>
0.2 to 2, STEP 0.1
8 NEUTRAL VOLTAGE DISPLACEMENT PROTECTION : 59N
Setting name
Range
Setting
59N Element
Diasabled/Enabled
Enabled
59N Element setting
1.8 V to 200 V in steps of 0.1 V
59 N Element Delay
0.04 to 320 sec

Set Units
0.1 xIn
1s
0.2 xIn
1

10 Volts
1 sec

Motor Feeders 315kW Panel Nos 1 &17 Relay: ABB REM 615
ANTI HEAT FAN 1 &2
1. Available motor data

Size

Value

Power
Rated voltage
Motor rated current IA
Max. starting current (at 100 % Vn)
Starting time (at 100% Vn
Starting time (at 80% Vn
Heating time constant
Cooling time constant at standstill
Max. continuous thermal rating current
Max. blocked rotor time HOT
Max. blocked rotor time COLD
Locked rotor Current
Permissible max.accelerating time (WITH LOAD )
General power system data

Parameter

315
6.6
32.87
6X IA
1.7
3.2
45
240
34.5135
10
20
197.22
1.7

CurrentTransformer rated current,phase primary


Transformer rated current, phase secondary
Core Balance CurrentTransformer rated current,phase primary
Transformer rated current, earth secondary
Thermal replica (ANSI 49)
Parameter
Value (Range)
Thermal current threshold I>
0.2 to 1.5 x In
Trip thermal threshold Set to 100%
Thermal Alarm stage:
20 to 100%
Reset ratio for Thermal trip
30 to 99%
Tripping time
0.1 to 50 s
Io> (Earth Fault) (ANSI 50N/51N)
Parameter
Value (Range)
Current set
0.002 to 1.0
Time delay
0-100 sec

units
kW
kV
A

sec
sec
min
min
A
sec
sec
A
sec

Value

Unit
100
1
50
1

A
A
A
A

0.01

Set Value
0.35

Step

1.00%
1.00%
0.1

Step
0.01
0.01

80%
70%
2
Set Value
0.1
0.05

Short Circuit Protection (ANSI 50/51)


Parameter
Value (Range)
Current set I>>
0.5 to 40
Time delay t>>
0-150
Current set I>
0.1 to 25
Time delay t> ( tms)
0.1 -3.2
Curve
IEC-NI,IEC-EI,IEC-VI
Unbalance Protection ( ANSI 46)
Parameter
Value (Range)
Current Set I2>
0.04 to 0.8 In
Time delay
0.02 to 99.9
Current Set I2>>
0.04 to 0.8 In
Time Multiple setting ( TMS) I2>>
0.2 to 2
Ph:AS (Load Assymetry) (ANSi 47)
Parameter
Value (Range)
Current set
15 to 50%
Time delay
0.02 to 99.9
Number of permitted starts (ANSI 66)
Parameter
Value (Range)
Number of Cold Starts
0-5
Number of Hot Starts
0-5
T reference
10-120 mins
Restart Inhibition time
1-120 mins
Time between 2 Start ups
1-120 mins
Locked Rotor Protection ( ANSI 51LR/50s)
Current set
0.5 to 5 In
Time Delay for prolonged start:
1 to 60 s

Step
1
0.1
0.1
0.1

Step

Set Value
2.7
0.05
0.4
2.7
IEC-VI

0.01
0.1
0.01
0.1

Set Value
0.1
1
0.2
1

1
0.1

Set Value
15
1

1
1
5
1
1

Set Value
3
2
60
20
20

0.01
1

2
4

Step

Step

Motor Feeders 1000kW Panel Nos 1 &17 Relay: ABB REM 615
ID FAN 1
1. Available motor data

Size

Value

Power
Rated voltage
Motor rated current IA
Max. starting current (at 100 % Vn)
Starting time (at 100% Vn
Starting time (at 80% Vn
Heating time constant
Cooling time constant at standstill
Max. continuous thermal rating current
Max. blocked rotor time HOT
Max. blocked rotor time COLD
Locked rotor Current
Permissible max.accelerating time (WITH LOAD )
General power system data

Parameter

1000
6.6
105.39
6X IA
1.7
3.2
45
240
110.6595
10
20
632.34
1.7

CurrentTransformer rated current,phase primary


Transformer rated current, phase secondary
Core Balance CurrentTransformer rated current,phase primary
Transformer rated current, earth secondary
Thermal replica (ANSI 49)
Parameter
Value (Range)
Thermal current threshold I>
0.2 to 1.5 x In
Trip thermal threshold Set to 100%
Thermal Alarm stage:
20 to 100%
Reset ratio for Thermal trip
30 to 99%
Tripping time
0.1 to 50 s
Io> (Earth Fault) (ANSI 50N/51N)
Parameter
Value (Range)
Current set
0.002 to 1.0
Time delay
0-100 sec
Short Circuit Protection (ANSI 50/51)

units
kW
kV
A

sec
sec
min
min
A
sec
sec
A
sec

Value

Unit
150
1
50
1

A
A
A
A

0.01

Set Value
0.75

Step

1.00%
1.00%
0.1

Step
0.01
0.01

80%
70%
2
Set Value
0.1
0.05

Parameter
Value (Range)
Current set I>>
0.5 to 40
Time delay t>>
0-150
Current set I>
0.1 to 25
Time delay t> ( tms)
0.1 -3.2
Curve
IEC-NI,IEC-EI,IEC-VI
Unbalance Protection ( ANSI 46)
Parameter
Value (Range)
Current Set I2>
0.04 to 0.8 In
Time delay
0.02 to 99.9
Current Set I2>>
0.04 to 0.8 In
Time Multiple setting ( TMS) I2>>
0.2 to 2
Ph:AS (Load Assymetry) (ANSi 47)
Parameter
Value (Range)
Current set
15 to 50%
Time delay
0.02 to 99.9
Number of permitted starts (ANSI 66)
Parameter
Value (Range)
Number of Cold Starts
0-5
Number of Hot Starts
0-5
T reference
10-120 mins
Restart Inhibition time
1-120 mins
Time between 2 Start ups
1-120 mins
Locked Rotor Protection ( ANSI 51LR/50s)
Current set
0.5 to 5 In
Time Delay for prolonged start:
1 to 60 s

Step
1
0.1
0.1
0.1

Step

Set Value
5.5
0.05
0.77
3
IEC-VI

0.01
0.1
0.01
0.1

Set Value
0.1
1
0.2
1

1
0.1

Set Value
15
1

1
1
5
1
1

Set Value
3
2
60
20
20

0.01
1

4.5
4

Step

Step

6.6 kV HT LBSS-1 Switch Board


Incomer from 15 MVA Transformer
Relay type Siemens Reyrolle 7SJ803
1 SYSTEM CONFIG
Description
System Frequency
Selects the Power System Frequency from 50 or 60 Hz
Setting Dependencies
When enabled only active settings are displayed and
all others hidden
2 CT/VT CONFIG
Description
CTs

Range
50, 60

Setting
50Hz

Prime

Enabled, Disabled Enabled

Range

Setting

Prime

CT rated primary 10..50000 A


CT rated secondary1 A / 5 A

1500A
1A

PT rated primary 0~132000 V


PT rated Secondary110230

6600 V
110

Range
Setting
Enabled, Disabled Enabled

Prime

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL Overcurrent element
is enabled

Enabled, Disabled Enabled

51-1 Setting (Ip)


Pickup level
51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL

0.1..4.00 A STEP
0.1
Normal Inverse
,Very Inverse
,Extremely
Inverse ,Long
Inverse

51-1 Time Mult (IEC/ANSI) (Tp)


Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)

0.05..3.20 s, oo

0.5

4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent element is
enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time

Range
Setting
Enabled, Disabled Enabled

Prime

1500

Normal
Inverse-IEC

Range
Setting
Enabled, Disabled Enabled

0.1..25.00 A STEP 4.5


0.1
0.00..60.00 s
0.45

Prime

6750

5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault
element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL

51N-1 Time Mult (IEC/ANSI) (TEp)


Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
5.2 50N-1
Description
50N-1 Element
Selects whether the DTL derived Earth fault element is
enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time
6 Over Voltage Protection :59
Setting name
6.1 59-1 Element 1
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay

V Hysteresis
V Block Threshold
V O/P Phases
6.2 59 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay

V Hysteresis
V Block Threshold
V O/P Phases

Range
Setting
Enabled, Disabled Enabled

Prime

0.05..4.00 A STEP 0.08


0.01
Normal Inverse
Normal Inverse
,Very Inverse
,Extremely
Inverse ,Long
Inverse
0.05..3.20 s, oo

120

0.35

Range
Setting
Enabled, Disabled Enabled

0.05..25.00 A
STEP 0.01
0.00..60.00 s

0.8

Range

Setting

Prime

1200

0.7

OFF, O/V, U/V


o/v
5.0, 5.580.0200.0
0.00,
0.0120,20.5
100.0,101.0600.
01,290
OFF,1,25100 Any One, All
Any
OFF, O/V, U/V
o/v
5.0, 5.580.0200.0
0.00,
0.0120,20.5
100.0,101.0600.
01,290
OFF,1,25100 Any One, All
Any

Prim Value

120
3

7200

126
1.5

10

7560

7 Under Voltage Protection:27


Setting name
7.1 27-1 Element 1
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay

V Hysteresis
V Block Threshold
V O/P Phases
7.2 27 Element 2
V Operation
V Setting (Ph-N) Gn V Setting (Ph-Ph)
V Delay

Range

Setting

OFF, O/V, U/V


u/v
5.0, 5.580.0200.0
0.00,
0.0120,20.5
100.0,101.0600.
01,290
OFF,1,25100
Any One, All

Prim Value

99
1

5940

Any

OFF, O/V, U/V


u/v
5.0, 5.580.0200.0
93.5
0.00,
1.5
0.0120,20.5
100.0,101.0600.
01,290
V Hysteresis
10
V Block Threshold
OFF,1,25100 V O/P Phases
Any One, All
Any
8 Breaker failure Protection -CB Fail Supervision : 50LBB
Setting name
Range
Setting
50BF Element
Diasabled/Enabled Enabled
50BF Setting
0.05..2
0.2 x In
50BF-1 delay
20..60000
100ms
50BF-2 delay
20..60000
250 ms
9 RESTRICTED EARTH FAULT PROTECTION 64
Setting name
Range
Setting
64R Element
Diasabled/Enabled Enabled
64R Setting
0.05..2
0.1 x In
64R-1 delay
20..60000
100ms
10 RESTRICTED EARTH FAULT PROTECTION 51G
Setting name
Range
Setting
51G Element
Diasabled/Enabled Enabled
51G Setting
0.05..2
0.15 x In
51G-1 delay
20..60000
500ms

5610

250

150

15

Transformer Feeder 1250 kVA LCSS1 ,LCSS3& Spare Panels No 2,3,6,14 &15
Relay type Siemens Reyrolle 7SJ600
1 SYSTEM CONFIG
Description
Range
Setting
System Frequency
Selects the Power System Frequency from 50 or 60 Hz
Setting Dependencies
When enabled only active settings are displayed and
all others hidden

50, 60

Enabled, Disabled Enabled

2 CT/VT CONFIG
Description
CTs

Range

Prime

50Hz

Setting

Prime

CT rated primary 10..50000 A


CT rated secondary1 A / 5 A

125A
1A

PT rated primary 0~132000 V


PT rated Secondary110230

6600 V
110

Range
Setting
Enabled, Disabled Enabled
Enabled, Disabled Enabled

Prime

Range
Setting
Enabled, Disabled Enabled

Prime

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL Overcurrent element
is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent element is
enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time

0.1..4.00 A STEP
0.1
Normal Inverse
,Very Inverse
,Extremely
Inverse ,Long
Inverse
0.05..3.20 s, oo

125

Extremely
Inverse-IEC

Range
Setting
Enabled, Disabled Enabled

0.1..25.00 A STEP 17
0.1
0.00..60.00 s
0.05

Prime

2550

5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault
element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
51N-1 Time Mult (IEC/ANSI) (TEp)
Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
5.2 50N-1
Description
50N-1 Element
Selects whether the DTL derived Earth fault element is
enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time

Range
Setting
Enabled, Disabled Enabled

0.05..4.00 A STEP 0.1


0.01
Normal Inverse
Normal Inverse
,Very Inverse
,Extremely
Inverse ,Long
Inverse
0.05..3.20 s, oo
0.3

Range
Setting
Enabled, Disabled Enabled

0.05..25.00 A
STEP 0.01
0.00..60.00 s

1
0.25s

Prime

12.5

Prime

125

Feeders LBDS1& Spare Panels No 4,13 &16


Relay type Siemens Reyrolle 7SJ600
1 SYSTEM CONFIG
Description
System Frequency
Selects the Power System Frequency from 50 or 60 Hz
Setting Dependencies
When enabled only active settings are displayed and
all others hidden
2 CT/VT CONFIG
Description
CTs

Range
50, 60

Setting
50Hz

Prime

Enabled, Disabled Enabled

Range

Setting

Prime

CT rated primary 10..50000 A


CT rated secondary1 A / 5 A

600A
1A

PT rated primary 0~132000 V


PT rated Secondary110230

6600 V
110

Range
Setting
Enabled, Disabled Enabled
Enabled, Disabled Enabled

Prime

Range
Setting
Enabled, Disabled Enabled

Prime

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL Overcurrent element
is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent element is
enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time

0.1..4.00 A STEP
0.1
Normal Inverse
,Very Inverse
,Extremely
Inverse ,Long
Inverse
0.05..3.20 s, oo

600

Extremely
Inverse-IEC

0.7

Range
Setting
Enabled, Disabled Enabled

0.1..25.00 A STEP 10
0.1
0.00..60.00 s
0.3

Prime

6000

5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault
element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
51N-1 Time Mult (IEC/ANSI) (TEp)
Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
5.2 50N-1
Description
50N-1 Element
Selects whether the DTL derived Earth fault element is
enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time

Range
Setting
Enabled, Disabled Enabled

Prime

0.05..4.00 A STEP 0.125


0.01
Normal Inverse
Normal Inverse
,Very Inverse
,Extremely
Inverse ,Long
Inverse
0.05..3.20 s, oo
0.3

Range
Setting
Enabled, Disabled Enabled

0.05..25.00 A
STEP 0.01
0.00..60.00 s

0.9
0.55s

75

Prime

540

Feeders Ore Benefl Plant LBDS2 Panels No 5 &12


Relay type Siemens Reyrolle 7SJ600
1 SYSTEM CONFIG
Description
System Frequency
Selects the Power System Frequency from 50 or 60 Hz
Setting Dependencies
When enabled only active settings are displayed and
all others hidden
2 CT/VT CONFIG
Description
CTs

Range
50, 60

Setting
50Hz

Prime

Enabled, Disabled Enabled

Range

Setting

Prime

CT rated primary 10..50000 A


CT rated secondary1 A / 5 A

750 A
1A

PT rated primary 0~132000 V


PT rated Secondary110230

6600 V
110

Range
Setting
Enabled, Disabled Enabled
Enabled, Disabled Enabled

Prime

Range
Setting
Enabled, Disabled Enabled

Prime

PTs

3 FUNCTION CONFIG
Description
Phase Overcurrent 50/51
Derived E/F 50N/51N
4 CURRENT PROTECTION
4.1 51-1
Description
51-1 Element
Selects whether the 51-1 IDMTL Overcurrent element
is enabled
51-1 Setting (Ip)
Pickup level
51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
4.2 50-1
Description
50-1 Element
Selects whether the INST/DTL Overcurrent element is
enabled
50-1 Setting (I>>)
Pickup level
50-1 Delay (T-I>>)
Sets operate delay time

0.1..4.00 A STEP
0.1
Normal Inverse
,Very Inverse
,Extremely
Inverse ,Long
Inverse s, oo
0.05..3.20

750

Extremely
Inverse-IEC

0.6

Range
Setting
Enabled, Disabled Enabled

0.1..25.00 A STEP 8
0.1
0.00..60.00 s
0.3

Prime

6000

5 DERIVED E/F
5.1 51N-1
Description
51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault
element is enabled
51N-1 Setting (IEp)
Pickup level
51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL
or DTL
51N-1 Time Mult (IEC/ANSI) (TEp)
Time multiplier (applicable to IEC and ANSI curves but
not DTL selection)
5.2 50N-1

Range
Setting
Enabled, Disabled Enabled

Prime

0.05..4.00 A STEP 0.08


0.01
Normal Inverse
Normal Inverse
,Very Inverse
,Extremely
Inverse ,Long
Inverse
0.05..3.20 s, oo
0.3

Description

Range

50N-1 Element
Selects whether the DTL derived Earth fault element is
enabled
50N-1 Setting (IE>>)
Pickup level
50N-1 Delay (TE>>)
Sets operate delay time

Enabled, Disabled Enabled

0.05..25.00 A
STEP 0.01
0.00..60.00 s

Setting

0.8
0.55

60

Prime

600

Motor Feeders 2600kW Panel Nos 1 &17 Relay: 7UM621


Iron Ore Grinding
1. Available motor data

Size

Power
Rated voltage
Motor rated current IA
Max. starting current (at 100 % Vn)
Starting time (at 100% Vn
Starting time (at 80% Vn
Heating time constant
Cooling time constant at standstill
Max. continuous thermal rating current
Max. blocked rotor time HOT
Max. blocked rotor time COLD
Locked rotor Current
Permissible max.accelerating time (WITH LOAD )
General power system data

Value

Parameter

2600
6.6
294
6X IA
1.7
3.2
45
240
308.7
10
20
1764
1.7

CurrentTransformer rated current,phase primary


Transformer rated current, phase secondary
Core Balance CurrentTransformer rated current,phase primary
Transformer rated current, earth secondary
Thermal replica (ANSI 49)
Parameter
Value (Range)
Thermal current threshold I>
0.2 to 1.5 x In
Trip thermal threshold Set to 100%
Thermal Alarm stage:
20 to 100%
Reset ratio for Thermal trip
30 to 99%
Tripping time
0.1 to 50 s
Io> (Earth Fault) (ANSI 50N/51N)
Parameter
Value (Range)
Current set
0.002 to 1.0
Time delay
0-100 sec

units
kW
kV
A

sec
sec
min
min
A
sec
sec
A
sec

Value

Unit
400
1
50
1

A
A
A
A

0.01

Set Value
0.77

Step

1.00%
1.00%
0.1

Step
0.01
0.01

80%
70%
2
Set Value
0.1
0.05

Short Circuit Protection (ANSI 50/51)


Parameter
Current set I>>
Time delay t>>
Current set I>
Time delay t> ( tms)
Curve
Unbalance Protection ( ANSI 46)
Parameter
Current Set I2>
Time delay
Current Set I2>>
Time Multiple setting ( TMS) I2>>
Ph:AS (Load Assymetry) (ANSi 47)
Parameter
Current set
Time delay
Number of permitted starts (ANSI 66)
Parameter
Number of Cold Starts
Number of Hot Starts
T reference
Restart Inhibition time
Time between 2 Start ups
Locked Rotor Protection ( ANSI 51LR/50s)
Current set
Time Delay for prolonged start:

Value (Range)
Step
0.5 to 40
0-150
0.1 to 25
0.1 -3.2
IEC-NI,IEC-EI,IEC-VI
Value (Range)
0.04 to 0.8 In
0.02 to 99.9
0.04 to 0.8 In
0.2 to 2

Step

Value (Range)
15 to 50%
0.02 to 99.9

Step

Value (Range)
0-5
0-5
10-120 mins
1-120 mins
1-120 mins

Step

0.5 to 5 In
1 to 60 s

1
0.1
0.1
0.1

Set Value
5.8
0.05
0.8
2
IEC-VI

0.01
0.1
0.01
0.1

Set Value
0.1
1
0.2
1

1
0.1

Set Value
15
1

1
1
5
1
1

Set Value
3
2
60
20
20

0.01
1

4.4
4

SETTING DETAILS FOR


LT MCC PANELS
S

Setting Details for 415V LT TG MCC

Location of
Device
device
description
and release

Sevice ID

Breaker Set
Current In

Phase Current Settings


OVERLOAD PROTECTION

SETTING
RANGE
IR=In X

Long time
Pick up
Current
setting (I1)

Primary
Current

Setting
range for
time-lag
class tR at
I2t

Ground Current Settings

Short-time delayed short-circuit protection


time lag
setting in
sec

Setting
range
Isd =

Short time
Pick up
Current
Settint (Isd)

Primary
Current

Setting
range for
delay time
tsd in ms

Instantaneous short-circuit protection

Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms

Primary
Current

Ground-fault protection
Setting
range of
the
operating
current Ig

Operating
current
setting Ig

Primary
Current

Setting
range of
the delay
time tg in
ms

Delay time
tg in ms

In ...
1F1

3200A
INCOMER 1
ACB,ETU45

3F1

3200A
INCOMER 2
ACB,ETU45

2F1

3200A
BUSCOUPLER
ACB,ETU45

2500 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
2500 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
2500 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0

2500 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

5000 100-200300-400

100 1.5-2.2-34-6-8-1012

15000 A-B-C-D-E

100-200300-400500

100

2500 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

5000 100-200300-400

100 1.5-2.2-34-6-8-1012

15000 A-B-C-D-E

100-200300-400500

100

0.8

2000 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

1.25

3125 100-200300-400

100 1.5-2.2-34-6-8-1012

10000 A-B-C-D-E

100-200300-400500

100

Setting Details for 415V LT SCREENING MCC

Location of
Device
device
description
and release

Sevice ID

Breaker Set
Current In

Phase Current Settings

OVERLOAD PROTECTION
SETTING
RANGE
IR=In X

Long time
Pick up
Current
setting (I1)

Primary
Current

Setting
range for
time-lag
class tR at
I2t

Ground Current Settings

Short-time delayed short-circuit protection


time lag
setting in
sec

Setting
range
Isd =

Short time
Pick up
Current
Settint (Isd)

Primary
Current

Setting
range for
delay time
tsd in ms

Instantaneous short-circuit protection

Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms

Primary
Current

Ground-fault protection
Setting
range of
the
operating
current Ig

Operating
current
setting Ig

Primary
Current

Setting
range of
the delay
time tg in
ms

Delay time
tg in ms

In ...
1F1

1600A
INCOMER 1
ACB,ETU45

3F1

1600A
INCOMER 2
ACB,ETU45

2F1

1600A
BUSCOUPLER
ACB,ETU45

1600 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1600 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1600 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0

1600 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

3200 100-200300-400

100 1.5-2.2-34-6-8-1012

9600 A-B-C-D-E

100-200300-400500

100

1600 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

3200 100-200300-400

100 1.5-2.2-34-6-8-1012

9600 A-B-C-D-E

100-200300-400500

100

0.65

1040 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

1.25

2000 100-200300-400

100 1.5-2.2-34-6-8-1012

6400 A-B-C-D-E

100-200300-400500

100

Setting Details for 415V LT BALLING SYSTEM MCC

Location of
Device
device
description
and release

Sevice ID

Breaker Set
Current In

Phase Current Settings

OVERLOAD PROTECTION
SETTING
RANGE
IR=In X

Long time
Pick up
Current
setting (I1)

Primary
Current

Setting
range for
time-lag
class tR at
I2t

Ground Current Settings

Short-time delayed short-circuit protection


time lag
setting in
sec

Setting
range
Isd =

Short time
Pick up
Current
Settint (Isd)

Primary
Current

Setting
range for
delay time
tsd in ms

Instantaneous short-circuit protection

Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms

Primary
Current

Ground-fault protection
Setting
range of
the
operating
current Ig

Operating
current
setting Ig

Primary
Current

Setting
range of
the delay
time tg in
ms

Delay time
tg in ms

In ...
1F1

3200A
INCOMER 1
ACB,ETU45

3F1

3200A
INCOMER 2
ACB,ETU45

2F1

3200A
BUSCOUPLER
ACB,ETU45

2500 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
2500 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
2500 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0

2500 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

5000 100-200300-400

100 1.5-2.2-34-6-8-1012

15000 A-B-C-D-E

100-200300-400500

100

2500 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

5000 100-200300-400

100 1.5-2.2-34-6-8-1012

15000 A-B-C-D-E

100-200300-400500

100

0.8

2000 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

1.25

3125 100-200300-400

100 1.5-2.2-34-6-8-1012

10000 A-B-C-D-E

100-200300-400500

100

Setting Details for 415V LT PROPORTION & MIXING MCC

Location of
Device
device
description
and release

Sevice ID

Breaker Set
Current In

Phase Current Settings

OVERLOAD PROTECTION
SETTING
RANGE
IR=In X

Long time
Pick up
Current
setting (I1)

Primary
Current

Setting
range for
time-lag
class tR at
I2t

Ground Current Settings

Short-time delayed short-circuit protection


time lag
setting in
sec

Setting
range
Isd =

Short time
Pick up
Current
Settint (Isd)

Primary
Current

Setting
range for
delay time
tsd in ms

Instantaneous short-circuit protection

Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms

Primary
Current

Ground-fault protection
Setting
range of
the
operating
current Ig

Operating
current
setting Ig

Primary
Current

Setting
range of
the delay
time tg in
ms

Delay time
tg in ms

In ...
1F1

1600A
INCOMER 1
ACB,ETU45

3F1

1600A
INCOMER 2
ACB,ETU45

2F1

1600A
BUSCOUPLER
ACB,ETU45

1600 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1600 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1600 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0

1600 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

3200 100-200300-400

100 1.5-2.2-34-6-8-1012

9600 A-B-C-D-E

100-200300-400500

100

1600 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

3200 100-200300-400

100 1.5-2.2-34-6-8-1012

9600 A-B-C-D-E

100-200300-400500

100

0.65

1040 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

1.25

2000 100-200300-400

100 1.5-2.2-34-6-8-1012

6400 A-B-C-D-E

100-200300-400500

100

Setting Details for 415V LT ORE CRUSHING GRINDING SYSTEM MCC

Location of
Device
device
description
and release

Sevice ID

Breaker Set
Current In

Phase Current Settings

OVERLOAD PROTECTION
SETTING
RANGE
IR=In X

Long time
Pick up
Current
setting (I1)

Primary
Current

Setting
range for
time-lag
class tR at
I2t

Ground Current Settings

Short-time delayed short-circuit protection


time lag
setting in
sec

Setting
range
Isd =

Short time
Pick up
Current
Settint (Isd)

Primary
Current

Setting
range for
delay time
tsd in ms

Instantaneous short-circuit protection

Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms

Primary
Current

Ground-fault protection
Setting
range of
the
operating
current Ig

Operating
current
setting Ig

Primary
Current

Setting
range of
the delay
time tg in
ms

Delay time
tg in ms

In ...
1F1

2000A
INCOMER 1
ACB,ETU45

3F1

2000A
INCOMER 2
ACB,ETU45

2F1

2000A
BUSCOUPLER
ACB,ETU45

2000 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
2000 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
2000 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0

2000 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

4000 100-200300-400

100 1.5-2.2-34-6-8-1012

12000 A-B-C-D-E

100-200300-400500

100

2000 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

4000 100-200300-400

100 1.5-2.2-34-6-8-1012

12000 A-B-C-D-E

100-200300-400500

100

0.65

1300 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

1.25

2500 100-200300-400

100 1.5-2.2-34-6-8-1012

8000 A-B-C-D-E

100-200300-400500

100

Setting Details for 415V LT CPP LCSS

Location of
Device
device
description
and release

Sevice ID

Breaker Set
Current In

Phase Current Settings

OVERLOAD PROTECTION
SETTING
RANGE
IR=In X

Long time
Pick up
Current
setting (I1)

Primary
Current

Setting
range for
time-lag
class tR at
I2t

Ground Current Settings

Short-time delayed short-circuit protection


time lag
setting in
sec

Setting
range
Isd =

Short time
Pick up
Current
Settint (Isd)

Primary
Current

Setting
range for
delay time
tsd in ms

Instantaneous short-circuit protection

Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms

Primary
Current

Ground-fault protection
Setting
range of
the
operating
current Ig

Operating
current
setting Ig

Primary
Current

Setting
range of
the delay
time tg in
ms

Delay time
tg in ms

In ...
1F1

3200A
INCOMER 1
ACB,ETU45

3F1

3200A
INCOMER 2
ACB,ETU45

2F1

3200A
BUSCOUPLER
ACB,ETU45

3200 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
3200 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
3200 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0

3200 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

6400 100-200300-400

100 1.5-2.2-34-6-8-1012

19200 A-B-C-D-E

100-200300-400500

100

3200 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

6400 100-200300-400

100 1.5-2.2-34-6-8-1012

19200 A-B-C-D-E

100-200300-400500

100

0.8

2560 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

1.25

4000 100-200300-400

100 1.5-2.2-34-6-8-1012

12800 A-B-C-D-E

100-200300-400500

100

Setting Details for 415V LT KILN 1 &2 MCC

Location of
Device
device
description
and release

Sevice ID

Breaker Set
Current In

Phase Current Settings

OVERLOAD PROTECTION
SETTING
RANGE
IR=In X

Long time
Pick up
Current
setting (I1)

Primary
Current

Setting
range for
time-lag
class tR at
I2t

Ground Current Settings

Short-time delayed short-circuit protection


time lag
setting in
sec

Setting
range
Isd =

Short time
Pick up
Current
Settint (Isd)

Primary
Current

Setting
range for
delay time
tsd in ms

Instantaneous short-circuit protection

Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms

Primary
Current

Ground-fault protection
Setting
range of
the
operating
current Ig

Operating
current
setting Ig

Primary
Current

Setting
range of
the delay
time tg in
ms

Delay time
tg in ms

In ...
1F1

2000A
INCOMER 1
ACB,ETU45

3F1

2000A
INCOMER 2
ACB,ETU45

2F1

2000A
BUSCOUPLER
ACB,ETU45

2000 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
2000 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
2000 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0

2000 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

4000 100-200300-400

100 1.5-2.2-34-6-8-1012

12000 A-B-C-D-E

100-200300-400500

100

2000 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

4000 100-200300-400

100 1.5-2.2-34-6-8-1012

12000 A-B-C-D-E

100-200300-400500

100

0.65

1300 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

1.25

2500 100-200300-400

100 1.5-2.2-34-6-8-1012

8000 A-B-C-D-E

100-200300-400500

100

Setting Details for 415V LT RMP 3 MCC

Location of
Device
device
description
and release

Sevice ID

Breaker Set
Current In

Phase Current Settings

OVERLOAD PROTECTION
SETTING
RANGE
IR=In X

Long time
Pick up
Current
setting (I1)

Primary
Current

Setting
range for
time-lag
class tR at
I2t

Ground Current Settings

Short-time delayed short-circuit protection


time lag
setting in
sec

Setting
range
Isd =

Short time
Pick up
Current
Settint (Isd)

Primary
Current

Setting
range for
delay time
tsd in ms

Instantaneous short-circuit protection

Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms

Primary
Current

Ground-fault protection
Setting
range of
the
operating
current Ig

Operating
current
setting Ig

Primary
Current

Setting
range of
the delay
time tg in
ms

Delay time
tg in ms

In ...
1F1

1600A
INCOMER 1
ACB,ETU45

3F1

1600A
INCOMER 2
ACB,ETU45

2F1

1600A
BUSCOUPLER
ACB,ETU45

1600 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1600 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1600 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0

1600 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

3200 100-200300-400

100 1.5-2.2-34-6-8-1012

9600 A-B-C-D-E

100-200300-400500

100

1600 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

3200 100-200300-400

100 1.5-2.2-34-6-8-1012

9600 A-B-C-D-E

100-200300-400500

100

0.65

1040 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

1.25

2000 100-200300-400

100 1.5-2.2-34-6-8-1012

6400 A-B-C-D-E

100-200300-400500

100

Setting Details for 415V LT STP MCC

Location of
Device
device
description
and release

Sevice ID

Breaker Set
Current In

Phase Current Settings

OVERLOAD PROTECTION
SETTING
RANGE
IR=In X

Long time
Pick up
Current
setting (I1)

Primary
Current

Setting
range for
time-lag
class tR at
I2t

Ground Current Settings

Short-time delayed short-circuit protection


time lag
setting in
sec

Setting
range
Isd =

Short time
Pick up
Current
Settint (Isd)

Primary
Current

Setting
range for
delay time
tsd in ms

Instantaneous short-circuit protection

Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms

Primary
Current

Ground-fault protection
Setting
range of
the
operating
current Ig

Operating
current
setting Ig

Primary
Current

Setting
range of
the delay
time tg in
ms

Delay time
tg in ms

In ...
1F1

1250A
INCOMER 1
ACB,ETU45

3F1

1250A
INCOMER 2
ACB,ETU45

2F1

1250A
BUSCOUPLER
ACB,ETU45

1250 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1250 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1250 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0

0.5

625 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

2500 100-200300-400

100 1.5-2.2-34-6-8-1012

7500 A-B-C-D-E

100-200300-400500

100

0.5

625 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

2500 100-200300-400

100 1.5-2.2-34-6-8-1012

7500 A-B-C-D-E

100-200300-400500

100

0.65

812.5 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

1.25

1562.5 100-200300-400

100 1.5-2.2-34-6-8-1012

5000 A-B-C-D-E

100-200300-400500

100

Setting Details for 415V LT AFBC MCC

Location of
Device
device
description
and release

Sevice ID

Breaker Set
Current In

Phase Current Settings

OVERLOAD PROTECTION
SETTING
RANGE
IR=In X

Long time
Pick up
Current
setting (I1)

Primary
Current

Setting
range for
time-lag
class tR at
I2t

Ground Current Settings

Short-time delayed short-circuit protection


time lag
setting in
sec

Setting
range
Isd =

Short time
Pick up
Current
Settint (Isd)

Primary
Current

Setting
range for
delay time
tsd in ms

Instantaneous short-circuit protection

Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms

Primary
Current

Ground-fault protection
Setting
range of
the
operating
current Ig

Operating
current
setting Ig

Primary
Current

Setting
range of
the delay
time tg in
ms

Delay time
tg in ms

In ...
1F1

1250A
INCOMER 1
ACB,ETU45

3F1

1250A
INCOMER 2
ACB,ETU45

2F1

1250A
BUSCOUPLER
ACB,ETU45

1250 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1250 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
1250 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0

0.5

625 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

2500 100-200300-400

100 1.5-2.2-34-6-8-1012

7500 A-B-C-D-E

100-200300-400500

100

0.5

625 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

2500 100-200300-400

100 1.5-2.2-34-6-8-1012

7500 A-B-C-D-E

100-200300-400500

100

0.35

437.5 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

1.25

1562.5 100-200300-400

100 1.5-2.2-34-6-8-1012

5000 A-B-C-D-E

100-200300-400500

100

Setting Details for 415V LT KILN 3 MCC

Location of
Device
device
description
and release

Sevice ID

Breaker Set
Current In

Phase Current Settings

OVERLOAD PROTECTION
SETTING
RANGE
IR=In X

Long time
Pick up
Current
setting (I1)

Primary
Current

Setting
range for
time-lag
class tR at
I2t

Ground Current Settings

Short-time delayed short-circuit protection


time lag
setting in
sec

Setting
range
Isd =

Short time
Pick up
Current
Settint (Isd)

Primary
Current

Setting
range for
delay time
tsd in ms

Instantaneous short-circuit protection

Short time
Setting
Instantaneo
delay in
range Ii = In us Current
sec (Tsd) in
...
setting (I3)
ms

Primary
Current

Ground-fault protection
Setting
range of
the
operating
current Ig

Operating
current
setting Ig

Primary
Current

Setting
range of
the delay
time tg in
ms

Delay time
tg in ms

In ...
1F1

4000A
INCOMER 1
ACB,ETU45

3F1

4000A
INCOMER 2
ACB,ETU45

2F1

4000A
BUSCOUPLER
ACB,ETU45

4000 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
4000 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0
4000 0.4-0.450.5-0.550.6-0.650.7-0.80.9-1.0

4000 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

8000 100-200300-400

100 1.5-2.2-34-6-8-1012

24000 A-B-C-D-E

100-200300-400500

100

4000 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

8000 100-200300-400

100 1.5-2.2-34-6-8-1012

24000 A-B-C-D-E

100-200300-400500

100

0.8

3200 2-3.5-5.58-10-1417-21-2530 s

2 1.25-1.5-22.5-3-4-68-10-12 x
In

1.25

5000 100-200300-400

100 1.5-2.2-34-6-8-1012

16000 A-B-C-D-E

100-200300-400500

100

Relay setting data for LT MCC s


CPP LCSS 1
1 CT/VT CONFIG
Description
CTs
for Restricted Earth fault Protection
for Earth fault Protection
2 RESTRICTED EARTH FAULT PROTECTION 64
Setting name
64R Element
64R Setting
64R-1 delay
3 DIRECT EARTH FAULT PROTECTION 51N
Setting name
51N Element
51N Setting
51N-1 delay
ORE CRUSHING & GRINDING SYSTEM LCSS 2
1 CT/VT CONFIG
Description
CTs
for Restricted Earth fault Protection
for Earth fault Protection
2 RESTRICTED EARTH FAULT PROTECTION 64
Setting name
64R Element
64R Setting
64R-1 delay
3 DIRECT EARTH FAULT PROTECTION 51N
Setting name
51N Element
51N Setting
51N-1 delay

Range

Setting

Prime

CT rated primary
CT rated secondary
CT rated primary
CT rated secondary

10..50000 A
1A/5A
10..50000 A
1A/5A

3000
5A
3000
5A

Range
Diasabled/Enabled
0.05..2
20..60000

Setting
Enabled
0.1 x In
100ms

Range
Diasabled/Enabled
0.05..2
20..60000

Setting
Enabled
0.15 x In
500ms

Range

Setting

Prime

CT rated primary
CT rated secondary
CT rated primary
CT rated secondary

10..50000 A
1A/5A
10..50000 A
1A/5A

2000
5A
2000
5A

Range
Diasabled/Enabled
0.05..2
20..60000

Setting
Enabled
0.1 x In
100ms

Range
Diasabled/Enabled
0.05..2
20..60000

Setting
Enabled
0.15 x In
500ms

300

450

200

300

TIME CURRENT
CHARACTERISTIC

CURVES

10000
1000

TG_IC
AH17
AH01 BC
AH03
4F1:LBDS1

100

6.6kV_LBSS1_IC1
INT.PANEL
PELLET PLANT 1
GCB
TR_CB

10

LINE_CB

Time in Seconds

20000.0 KVA
Transformer

1600.0 KVA
Transformer

.01

.1

Inrush TG_TR

.5

11000 Volt Phase


2 - PATH:GRID-TGMCC

10

100
Current in Amperes X 10
Time-Current Characteristic Curves

15000.0 KVA
Transformer

Inrush INRUSH
15 MVA 20MVA

1000

10000
12-27-2014
22:40:53
newjanki_06122014

10000
1000

192
AH17
AH03

100

4F1:LBDS1

6.6kV_LBSS1_IC1
INT.PANEL
PELLET PLANT 1
GCB
TR_CB

.01

.1

Time in Seconds

10

LINE_CB

.5

11000 Volt Ground


2 - PATH:GRID-TGMCC

10

100
Current in Amperes
Time-Current Characteristic Curves

1000

10000
12-27-2014
22:40:06
newjanki_06122014

10000
1000
100

415 V LCSS-7 STP

GCB

Time in Seconds

10

TR_CB

A
20000.0 KVA
Transformer

RMP3 TR 1000.0 KVA


Transformer
RMP3

.01

.1

INRUSH 1000kVA

.5

10

11000 Volt Phase


8 - PATH:GRID-RMP1000kVA TRAFO

100
Current in Amperes X 10
Time-Current Characteristic Curves

INRUSH 20MVA

1000

10000
12-27-2014
22:32:01
newjanki_06122014

10000
1000
100

415 V LCSS-7 STP


RMP3

TR_CB

.01

.1

Time in Seconds

10

GCB

.5

10

11000 Volt Ground


8 - PATH:GRID-RMP1000kVA TRAFO

100
Current in Amperes
Time-Current Characteristic Curves

1000

10000
12-27-2014
22:33:07
newjanki_06122014

10000
1000

2600kW
1F1:HT MOTOR

100

6.6kV_LBSS1_IC1

.01

.1

Time in Seconds

10

Cold Stall Time


Hot Stall Time

.5

11000 Volt Phase


11 - Path:2600 kW MOTOR

10

100
Current in Amperes X 10
Time-Current Characteristic Curves

1000

10000
12-27-2014
22:27:46
newjanki_06122014

10000
1000

AH FAN1_315kW

100

AH21

AH03
S

.01

.1

Time in Seconds

10

Cold Stall Time


Hot Stall Time

.5

11000 Volt Phase


12 - Path:315kW MOTORFEEDER

10

100
Current in Amperes X 10
Time-Current Characteristic Curves

1000

10000
12-27-2014
22:25:49
newjanki_06122014

10000
1000
100

IDFAN_1000kW
AH19
AH03
S

.01

4641 SCA @ 11000V


(IDFAN_1000kW)

.1

Time in Seconds

10

Cold Stall Time


Hot Stall Time

.5

10

11000 Volt Phase


12 - Path:1000kW MOTORFEEDER

100
Current in Amperes X 10
Time-Current Characteristic Curves

1000

10000
12-27-2014
22:23:40
newjanki_06122014

Observations and Comments:


1) The Single line diagram furnished by the customer has got many discrepencies with actuals at
site,especially the CT details furnished in the drawing are not matching.The customer has to prepare as fitted
drawing for their future reference.
2) The Second Turbo Generator 3 MW set has got CT ratio of 300/1.However it is noticed that the incomer
in the 11 kV switch board from this Generator has got CT of 1250/1.We have given the settings assuming this
CT will be matched with Generator CTs
3) There is one overall Differential Protection Relay, CTs from 15 MW Generator,HV side and LV side of
Generator Transformer connected.This relay operation will be in order when only one Generator 15 MW is in
operation.If the 3 MW set is in operation , this differential relay will pick up and trip the Breaker.Modification
of the circuitary is required.