Plug-in surge arrester for 3-phase power supply networks with N and PE in a common conductor (4-conductor
system: L1, L2, L3, PEN), with remote indication contact.
1 pc
GTIN
Weight per Piece (excluding packing)
299.4 g
85369010
Country of origin
Germany
Technical data
Dimensions
Height
98.5 mm
Width
37.25 mm
Depth
70 mm
Ambient conditions
02/03/2015Page1/7
https://www.phoenixcontact.com/gb/products/2859466
IP20
-40 C ... 80 C
-40 C ... 80 C
Altitude
5 % ... 95 %
Shock (operation)
Vibration (operation)
General
Standards/specifications
II
T2
EN type
T2
Number of ports
One
SPD design
Voltage-limiting type
Mode of protection
L-PEN
Mounting type
DIN rail: 35 mm
Color
gray/blue
black
Housing material
PBT-FR
Pollution degree
V-0
Type
Number of positions
Protective circuit
Nominal voltage UN
120/208 V AC (TN-C)
Nominal frequency fN
50 Hz (60 Hz)
175 V AC
20 kA
40 kA
25 kA
0.85 kV
https://www.phoenixcontact.com/gb/products/2859466
25 ns
315 A AC (gG)
Indicator/remote signaling
Connection name
Switching function
PDT contact
Operating voltage
5 V AC ... 250 V AC
125 V AC (UL)
125 V DC (200 mA DC)
Operating current
5 mA AC ... 1 A AC
1 A AC (UL)
1 A DC (30 V DC)
Connection method
Screw thread
M2
Tightening torque
0.25 Nm
2 lbf-in. ... 4 lbf-in. (UL)
Stripping length
7 mm
0.14 mm
1.5 mm
0.14 mm
1.5 mm
28 ... 16
30 ... 14 (UL)
Connection data
Connection method
Screw connection
2.5 mm
16 mm
2.5 mm
25 mm
12 ... 4
14 ... 2 (Solid - UL)
14 ... 4 (Stranded - UL)
Screw thread
M5
Tightening torque
4.5 Nm
40 lbf-in. ... 50 lbf-in. (UL)
02/03/2015Page3/7
https://www.phoenixcontact.com/gb/products/2859466
16 mm
UL specifications
UL class
350 V AC
175 V AC
Nom. voltage
120/208 V AC
Mode of protection
L-L
L-G
3Y
Nominal frequency
50/60 Hz
1.2 kV
0.7 kV
20 kA
20 kA
Classifications
eCl@ss
eCl@ss 4.0
27140201
eCl@ss 4.1
27130801
eCl@ss 5.0
27130801
eCl@ss 5.1
27130801
eCl@ss 6.0
27130805
eCl@ss 7.0
27130805
eCl@ss 8.0
27130805
ETIM
ETIM 2.0
EC000941
ETIM 3.0
EC000941
ETIM 4.0
EC000941
ETIM 5.0
EC000941
UNSPSC
UNSPSC 6.01
30212010
UNSPSC 7.0901
39121610
UNSPSC 11
39121610
UNSPSC 12.01
39121610
UNSPSC 13.2
39121620
02/03/2015Page4/7
https://www.phoenixcontact.com/gb/products/2859466
Approvals
UL Recognized / KEMA-KEUR / cUL Recognized / IECEE CB Scheme / CCA / EAC / cULus Recognized
Ex Approvals
Approvals submitted
Approval details
UL Recognized
KEMA-KEUR
cUL Recognized
IECEE CB Scheme
CCA
EAC
cULus Recognized
Accessories
Accessories
Bridge
02/03/2015Page5/7
https://www.phoenixcontact.com/gb/products/2859466
Wiring bridge set, consisting of three flexible bridges 15 cm black, 1 bridge 27 cm blue.
Marker pen
Marker pen-X-PEN 0,35-0811228
Marker pen without ink cartridge, for manual labeling of markers, labeling extremely wipe-proof, line thickness 0.35
mm
Terminal marking
Zack Marker strip, flat-ZBF 12:UNBEDRUCKT-0809735
Zack Marker strip, flat, Strip, white, unlabeled, can be labeled with: Plotter, Mounting type: Snap into flat marker
groove, for terminal block width: 12 mm, Lettering field: 5.15 x 12.15 mm
Spare parts
Type 2 surge protection plug-VAL-CP-175-ST-2859628
Replacement plug for VAL-CP surge arrester with high-capacity varistor free of leakage current.
Drawings
02/03/2015Page6/7
https://www.phoenixcontact.com/gb/products/2859466
Circuit diagram
PEN
98
22,5
11
14
FM
64
51,5
71,5
45
12
L1
L2
L3
02/03/2015Page7/7