Sie sind auf Seite 1von 18

WATER AND

REMOTE AIR
COOLED LIQUID
CHILLER
R407C REFRIGERANT
COOLING CAPACITIES
126 kW to 316 kW

YCSE/YCRE Model
Cooling Capacity (YCSE) kW
Cooling Capacity (YCRE) kW

040
126
120

050
158
145

060
194
180

080
252
240

100
316
290

YORK YCSE Water Cooled Liquid Chillers


are a compact design suitable for chilled
water or glycol cooling. YCRE models are
for applications where remote condensers
are necessary.

YCSE: Cooling capacities at 7C leaving chilled water temperature and 35C leaving
condenser water temperature
YCRE: Cooling capacities at 7C leaving chilled water temperature and 45C
condensing temperature

They are designed to be located inside a


plant room and require a cooling tower or
dry cooler for heat rejection.

AVAILABLE MODELS & NOMINAL COOLING CAPACITIES TABLE 1

Units are available with one or two


independent refrigerant circuits with a
single evaporator and on YCSE models a
single condenser.
The units utilise advanced electronic
control to position the variable capacity
control
slide
valve
within
each
compressor. This ensures exact load
control,
accurate
chilled
water
temperature control and improved part
load performance.

CONTENTS
Specification
Controls
Operating Limitations
Accessories and Options
Refrigeration Flow Diagram
Selection Guide
Fouling Factors
Pressure Drop Calculations
Glycol Application Factors
Pressure Drop Graphs
Cooling Capacities
Part Load Performance
Physical Data
Acoustic Data
Electrical Data
Electrical Connections
Dimensions
Space Requirements
Weight Distribution and
Centre of Gravity

FEATURES

BENEFITS

Small footprint and compact design

Ideal replacement for existing chillers in


refurbished buildings.

Models with two refrigerant circuits.

System stand-by security.

Single power and control supplies.

Easy to install.

Full factory run test.

Operating quality control.

Accessible components.

Ideal for maintenance operations.

Microprocessor control with visual display


of operating parameters and alarms.

Simple operation.

Manufactured to ISO 9001/EN 29001.

High standard of quality control.

Painted galvanised steel framework.

Durable and corrosion resistant.

Low sound operation.

No additional sound proofing required.

Star delta starter.

Low inrush current.

Plate heater exchangers.

Low unit refrigerant volume.

SPECIFICATION
The unit shall be completely factory assembled with all interconnecting refrigerant
piping and wiring ready for field installation. After assembly the YCSE units shall be
fully tested with water flowing through the evaporator and condenser. The unit shall
be pressure tested, evacuated and fully charged with refrigerant and oil. YCRE units
shall be pressure tested, evacuated and filled with 0.35 bar g pressure of nitrogen
per independent circuit.
The unit base and frame shall be of heavy gauge galvanised steel fastened with
stainless steel nuts and bolts. Steel parts shall be electrostatically painted in
Carribean Blue.
Compressor(s)
The screw compressor(s) will have twin screw rotors and solenoid valve capacity
control. A built-in oil separator, oil sight glass, oil heater and suction filter shall be
included.
The compressor will have a reliable two pole motor with overcurrent and thermostat
protection. Star/delta starting is utilised.

Page C.1
Doc. No. PC154-100 Rev 1(0905)

YCSE WATER COOLED LIQUID CHILLER

YCSE/YCRE

Evaporator and Condenser


The evaporator and condenser shall be stainless steel plate type
heat exchangers thermally insulated with flexible closed cell
material. Design working pressure 10 bar g on the water side
and 30 bar g on the refrigerant side. For YCRE units water
cooled condensers shall be factory removed. Remote air-cooled
condenser to be supplied by others.
Refrigerant Circuit(s)
Refrigerant circuit(s) shall be provided, each circuit shall include:
a check valve, liquid line stop valve with charging port, drier, a
sight glass and a thermostatic expansion valve.

Power and Control Panel


All controls and motor starting equipment necessary for full unit
operation shall be factory wired and tested. The panel shall be
designed to IP34 weather protection.
The panel shall contain compressor contactors, fuses and
protection devices, and the electronic circuit boards, push button
switches and display for controlling operation and display of
alarms and stops.
A terminal block is provided for interface with customer controls
and equipment.

CONTROLS

FIGURE 1

LED

PUSH
BUTTON
SWITCH

7 SEGMENTS

MAIN SWITCH

ACCESSORIES AND OPTIONS


BMS Interface
To integrate the unit into the building management system. The
interface permits the connection of up to 4 units using the Lon
communications protocol (Lon Works).

Glycol Cooling
Factory set-up for applications requiring water outlet
temperatures below 5C: Category 1: Outlet temperature 0 to
4C; Category 2: Outlet temperature -1 to - 5C and Category 3:
Outlet temperature - 6 to - 10C. The system must have the
Central Station (CSC-5S)
correct percentage weight of glycol added, refer to glycol
Provides individual control and monitoting for up to 8
application factors.
YCSE/YCRE units within the air conditioning system. This
allows the units to be managed remotely from the plant room.
Discharge and/or Suction Stop Valves
Factory fitted valve(s) to allow refrigerant isolation during
Compressor Circuit Breakers
servicing.
Circuit breakers to replace the standard fuses for protection
against over current. The breakers provide more precise Compressor Safety Valve(s)
monitoring than fuses and easy reset after fault.
Factory fitted single or dual compressor safety valve(s).
Differential Water Pressure Switch(es)
Dual Pressure Relief Valves
Differential pressure switches between the water inlet and Two safety valves in parallel of which one is operational to assist
outlets to ensure liquid flow during operation.
in valve replacement during maintenance.
Flow Switch(es)
PN16 Flanges
Field installed flow switches to ensure liquid flow during Welded PN16 flanges on the water connections with gasket
operation.
seals.
Suction Pressure Relief Valves
AVM Rubber
Additional pressure relief valve on suction side of compressor Rubber anti-vibration pads underneath the unit to avoid
when required.
transmission of vibration to the plant room structure.
High Condensing Water Temperatures
Factory set-up for applications requiring condensing water
temperatures above 45C. Enables higher condenser water
temperatures up to 55C, on dry cooler applications where
condenser size is important.

Page C.2
Doc. No. PC154-100 Rev 1(0905)

OPERATING LIMITATIONS
YCSE/YCRE-SB
Chilled
Liquid

Evaporator Water outlet


outlet
Brine outlet
temperature Temp. spread
Flow rate (YCSE)
Pressure drop (YCSE)
Flow rate (YCRE)
Pressure drop (YCRE)
Max. working pressure
Cooling Liquid outlet Water outlet
Liquid
temperature Temp. spread
(YCSE)
Flow rate
Pressure drop
Max. working pressure
Power supply voltage 400 V, 3 , 50 Hz
Recommended chilled system volume (3)

C
C
C
l/s
kPa
l/s
kPa
bar
C
K
l/s
kPa
bar
V
l

040
Min. Max.

050
Min. Max.

4.5
17.1
4.3
15.6

10.0
75.2
9.6
68.7

5.7
16.8
5.2
14.2

12.6
75.4
11.6
64.2

3.8
10.1

12.6
96.5

4.7
10.9

15.8
106.5

750

750

TABLE 2
060
Min. Max.
5 to 15
15 to -10(1)
4 to 8
6.9
15.4
16.2 74.1
6.4
14.3
14.1 64.3
10
22 to 55(2)
2 to 10
5.8
19.4
10.5 103.2
10
360 to 440
910

080
Min. Max.

100
Min. Max.

9.0
27.7
8.6
25.3

20.1
128.3
19.1
116.9

11.3
34.3
10.4
29.0

25.2
160.6
23.1
136.1

7.5
17.2

25.1
174.9

9.5
21.9

31.5
227.1

1500

1500

(1) Refer to Accessories and Options for further details.


(2) Standard outlet temperature is 45C, refer to Accessories and Options for further details.
(3) Based on 2C On/Off differential. System volume should be increased if differential is lowered.
(1) The recommended volume ensures a minimum of 5 minutes cooling without interruption.

REFRIGERANT FLOW DIAGRAM (YCSE-SB)

Condensing Water Outlet


Option
Condensing Water Inlet

Option
Option

Option
Option

Chilled
Water Inlet
Chilled
Water Outlet

Flange Connection
Flare Connection
Solder Connection
Refrigerant Cycle

No.
1
2
3
4
5
6
7
8

Name
Compressor
Check Valve
Stop Valve (Option)
Pressure Relief Valve
Water Condenser
Stop Valve (with check joint)
Drier
Sight Glass

No.
9
10
11
12
13
14
15
16

Name
Expansion Valve
Water Cooler
Stop Valve (Option)
Pressure Sensor (Low)
High Pressure Switch
Pressure Sensor (High)
Compressor Safety Valve (Option)
Compressor Dual Safety Valve (Option)

Cooling Mode - YCSE


Low pressure liquid refrigerant enters the cooler (Evaporator) and is evaporated and superheated by the heat energy absorbed from
the chilled water passing through the cooler plates. Low pressure vapour enters the compressor where pressure and superheat are
increased. Heat is rejected by the water cooled condenser. The fully condensed and subcooled liquid refrigerant then enters the
expansion valve where pressure reduction and further cooling takes place before returning to the cooler.
Page C.3
Doc. No. PC154-100 Rev 1(0905)

REFRIGERANT FLOW DIAGRAM (YCRE-SB)


Field
Supplied

Condensing
Water Outlet
Condensing
Water Inlet

Option
Option

Option
Option

Chilled
Water Inlet
Chilled
Water Outlet

Flange Connection
Flare Connection
Solder Connection
Refrigerant Cycle

No.
1
2
3
4
5
6
7
8
9

Name
Compressor
Check Valve
Stop Valve
Pressure Relief Valve
Remote Condenser (Field Supplied)
Stop Valve (with check joint)
Drier
Solenoid Valve
Sight Glass

No.
10
11
12
13
14
15
16
17

Name
Expansion Valve
Water Cooler
Stop Valve (Option)
Pressure Sensor (Low)
High Pressure Switch
Pressure Sensor (High)
Compressor Safety Valve (Option)
Compressor Dual Safety Valve (Option)

Cooling Mode - YCRE


Low pressure liquid refrigerant enters the cooler (Evaporator) and is evaporated and superheated by the heat energy absorbed from
the chilled water passing through the cooler plates. Low pressure vapour enters the compressor where pressure and superheat are
increased. Heat is rejected by the remote condenser. The fully condensed and subcooled liquid refrigerant then enters the
expansion valve where pressure reduction and further cooling takes place before returning to the cooler.

SELECTION GUIDE
DATA REQUIRED
To select a YORK YCSE/YCRE chiller the following information
is required:

2. Apply correction factors for fouling factor to the capacity and


power values from the capacity tables. Ensure the corrected
capacity is still sufficient for requirements.

1. Design cooling capacity.

3. Using the corrected capacity of the selected chiller adjust the


design temperature range, or flow rate, to balance the
formulae shown above.

2. Chilled water entering and leaving temperatures.


3. Condenser water entering and leaving temperature.
4. Chilled water flow (L/s) if one of the temperatures in (2) is
unknown.
5. Condenser water flow (L/s) if one of the temperatures in (3) is
unknown.

4. Physical and electrical data can now be determined from the


tables.
5. Always re-check that selections fall within the operating
limitations.
YCSE SAMPLE SELECTION

Determine the capacity or water flow from:


Cooling Capacity (kW)
= Range (C) x chilled water flow rate (L/s) x 4.18
Determine the heat rejection or water flow from:
Heat Rejection (kW)
= Range (C) x condenser water flow rate (L/s) x 4.18
CHILLER SELECTION METHOD
1. Determine the correct size of chiller by selecting the model
that most closely matches the required capacity at the design
conditions of leaving water temperature and condenser
leaving water temperature.
Page C.4
Doc. No. PC154-100 Rev 1(0905)

1. Confirm the system requirements


Cooling Capacity:
Chilled Water Inlet Temperature:
Chilled Water Outlet Temperature:
Condenser Water Inlet Temperature:
Condenser Water Outlet Temperature:
Evaporator and Condenser Fouling Factors:

240 kW
12 C
7 C
32 C
37 C
0

2. Select Model and Read the Performance

Flow Rate

From the capacity table, modelYCSE080SB can be selected


with the following performance.

When the water Inlet/Outlet temperature difference is not 5C,


correct the flow rate by the following formula:

Cooling Capacity:
Compressor Input Power:
Heat Rejection

Corrected Flow Rate

247.7 kW
66.9 kW
314.6 kW.

= 5 (C) X Flow Rate


Temp. Difference(C)

The corrected Flow Rate must be confirmed to be within the


working range.

3. Determine the Flow Rate

Glycol Application

Cooling Capacity (kW)


= Range (C) x chilled water flow rate (L/s) x 4.18
Flow Rate
= 247.7 = 11.8 L/s
5 x 4.18
Heat Rejection (kW)
= Range (C) x chilled water flow rate (L/s) x 4.18
Flow Rate
= 314.6 = 15.1 L/s
5 x 4.18

On applications with leaving chilled temperatures below 5C the


Glycol Application Factors given below should be applied.
5. Determine the Pressure Drops
Calculate the pressure drops using the graphs or formulae given
below.
Evaporator pressure drop at a flow rate of 11.8 L/s would be 46.3
kPa.

4. Correct the Data


Fouling Factor
The cooling capacity and the compressor input should be
corrected using the factors given below, if applicable.
Recalculate flow rates as required.

Condenser pressure drop at a flow rate of 15.1 L/s would be 65.5


kPa.
6. Check the Data is within Limits
The data is within the unit operating limitations.

FOULING FACTORS
Fouling Factor m C/kW
0.000
0.043
0.086

EVAPORATOR
Capacity Factor
1.00
1.00
0.99

Comp. Input Factor


1.00
1.00
1.01

Fouling Factor m C/kW


0.000
0.086
0.172

PRESSURE DROP CALCULATIONS

TABLE 3
CONDENSER
Capacity Factor
1.00
0.98
0.96

Comp. Input Factor


1.00
1.03
1.06

TABLE 4

Model
YCSE40SB

Evaporator Pressure Drop Calculation


Pressure Drop [kPa] = 1.0254 x (Flow Rate [L/s]1.863)

Condenser Pressure Drop Calculation


Pressure Drop [kPa] = 0.8325 x (Flow Rate [L/s]1.877)

YCSE50SB

Pressure Drop [kPa] = 0.6404 x (Flow Rate [L/s]1.883)

Pressure Drop [kPa] = 0.5857 x (Flow Rate [L/s]1.886)

Pressure Drop [kPa] = 0.4076 x (Flow Rate [L/s]

1.901

Pressure Drop [kPa] = 0.3737 x (Flow Rate [L/s]1.897)

Pressure Drop [kPa] = 0.4066 x (Flow Rate [L/s]

1.919

Pressure Drop [kPa] = 0.3513 x (Flow Rate [L/s]1.926)

YCSE100SB Pressure Drop [kPa] = 0.3116 x (Flow Rate [L/s]


)
1.863
YCRE40SB Pressure Drop [kPa] = 1.0254 x (Flow Rate [L/s]
)

Pressure Drop [kPa] = 0.2794 x (Flow Rate [L/s]1.942)

YCSE60SB
YCSE80SB

1.936

YCRE50SB

Pressure Drop [kPa] = 0.6404 x (Flow Rate [L/s]1.883)

YCRE60SB

Pressure Drop [kPa] = 0.4076 x (Flow Rate [L/s]1.901)

YCRE80SB

Pressure Drop [kPa] = 0.4066 x (Flow Rate [L/s]1.919)

YCRE100SB Pressure Drop [kPa] = 0.3116 x (Flow Rate [L/s]1.936)

Page C.5
Doc. No. PC154-100 Rev 1(0905)

GLYCOL APPLICATION FACTORS (YCSE)

Ethylene
Glycol

LCLT

TABLE 5

(wt%)

20

30

40

4
3
2
1
0
-1
-2
-3
-4
-5
-6
-7
-8
-9
-10

Flow
Rate
Factor
(Kf)
1.011
1.012
1.013
1.013
1.014
1.034
1.035
1.037
1.037
1.038
1.073
1.075
1.076
1.076
1.077

Pressure
Drop
Factor
(Kp)
1.15
1.16
1.17
1.18
1.19
1.3
1.32
1.34
1.36
1.38
1.5
1.52
1.54
1.56
1.58

Condenser Water Outlet Temperature (C) - CWOT


25
30
35
40
45
50
55
Cool I.P. Cool I.P. Cool I.P. Cool I.P. Cool I.P. Cool I.P. Cool I.P.
(%) (%) (%) (%) (%) (%) (%) (%) (%) (%) (%) (%) (%) (%)
100 86 95 90 90 95 84 99 79 107 74 118 68 133
97 85 92 89 87 94 82 98 77 106 72 117 66 132
94 84 89 88 84 93 79 97 74 105 70 116 64 131
91 83 86 87 81 92 77 96 72 104 67 115 62 130
88 82 84 86 79 91 74 95 70 103 65 114 60 129
85 81 81 85 76 90 72 94 67 102 63 113
82 80 78 84 73 89 69 93 65 101 61 112
79 79 75 83 71 88 67 92 62 100 58 111
76 78 72 82 68 87 64 91 60
99
56 110
73 77 69 81 65 86 62 90 58
98
54 109
70 76 66 80 63 85 59 89 55
97
67 75 64 79 60 84 56 88 53
96
Not Available
64 74 61 78 57 83 54 87 51
95
61 73 58 77 55 82 51 86 48
94
58 72 55 76 52 81 49 85 46
93

Cool = Cooling Capacity and I.P. = Input Power as a percentage of nominal conditions LCLT 12/7C and CWOT 30/35C.
Water Flow Rate and Pressure Drop can be calculated by the Correction Factor Kf and Kp.
For Example: YCSE100SB, nominal condition: Capacity 316 kW, Compressor Input 80.0 kW
Required leaving chilled liquid temperature -3/2C with a condenser water outlet temperature of 35C.
Therefore: Required ethylene glycol 30% of weight.
Corrected capacity = 316 X 0.75 = 237 kW, corrected compressor Input = 80.0 X 0.83 = 66.4 kW.
Corrected Water Flow (L/s) = Kf X Capacity (kW) / 4.18 /T (T=Inlet Temp.-Outlet Temp.).
= 1.037 X 237 / 4.18 /(2-(-3)) = 11.8 L/s
Pressure Drop = Kp X Pressure Drop (Water) = 1.34 X 0.3116 X 11.81.936 = 49.6 kPa. Refer to Pressure Drop Graph.

GLYCOL APPLICATION FACTORS (YCRE)

Ethylene
Glycol

LCLT

TABLE 6

(wt%)

20

30

40

4
3
2
1
0
-1
-2
-3
-4
-5
-6
-7
-8
-9
-10

Flow
Rate
Factor
(Kf)
1.011
1.012
1.013
1.013
1.014
1.034
1.035
1.037
1.037
1.038
1.073
1.075
1.076
1.076
1.077

Pressure
Drop
Factor
(Kp)
1.15
1.16
1.17
1.18
1.19
1.3
1.32
1.34
1.36
1.38
1.5
1.52
1.54
1.56
1.58

25
Cool
(%)
100
97
94
91
88
85
83
80
77
74
71
68
65
62
59

I.P.
(%)
76
75
74
73
73
72
71
70
70
69
68
67
66
66
65

Condenser Temperature (C)


30
35
Cool
I.P.
Cool
I.P.
(%)
(%)
(%)
(%)
96
87
91
100
93
86
88
99
90
86
85
99
87
85
83
98
84
84
80
98
81
84
77
97
78
83
74
97
75
82
71
96
72
81
68
96
69
81
65
96
66
80
62
95
63
79
59
95
61
79
56
94
58
78
54
99
55
77
51
93

40
Cool
(%)
89
84
81
78
75
73
70
67
69
61
58
55
52
49
46

I.P.
(%)
111
111
110
110
110
110
109
109
109
108
108
108
107
107
107

Cool = Cooling Capacity and I.P. = Input Power as a percentage of nominal conditions LCLT 12/7C and Condensing
Temperature 30/35C.
Water Flow Rate and Pressure Drop can be calculated by the Correction Factor Kf and Kp.
For Example: YCRE100SB, nominal condition: Capacity 290 kW, Compressor Input 84.8 kW
Required leaving chilled liquid temperature -3/2C with a condenser water outlet temperature of 30C.
Therefore: Required ethylene glycol 30% of weight.
Corrected capacity = 290 X 0.75 = 217.5 kW, corrected compressor Input = 84.8 X 0.82 = 69.5 kW.
Corrected Water Flow (L/s) = Kf X Capacity (kW) / 4.18 /T (T=Inlet Temp.-Outlet Temp.).
= 1.037 X 217.5 / 4.18 /(2-(-3)) = 10.6 L/s
Pressure Drop = Kp X Pressure Drop (Water) = 1.34 X 0.3116 X 10.61.936 = 40.3 kPa. Refer to Pressure Drop Graph.
Page C.6
Doc. No. PC154-100 Rev 1(0905)

PRESSURE DROP GRAPHS


YCSE EVAPORATOR

YCRE EVAPORATOR

160
150
140
130
120
110
100

150
140
130
120
110
100

100
080

100
080

75

75

65

65

55

Pressure Drop kPa

Pressure Drop kPa

85

85

55
50
45
40
35
30

50
45
40
35
30
25

25

20

040

050

060

040

050

060

20
15

15

12

16

20

24 28

Flow Rate l/s

12

12

16

20

24 28

Flow Rate l/s

YCSE CONDENSER
230
200

100

080

150

100
90

Pressure Drop kPa

80
70
60
50
45
40
35
30
25

20

15

040

10

050

060

12

16

20

24

28

32

Flow Rate l/s

Page C.7
Doc. No. PC154-100 Rev 1(0905)

YCSE COOLING CAPACITIES

35
37
40
55

50

45

Condenser Leaving Water Temperature (C)

30

25

22

LCLT

TABLE 7

5
7
9
11
13
15
5
7
9
11
13
15
5
7
9
11
13
15
5
7
9
11
13
15
5
7
9
11
13
15
5
7
9
11
13
15
5
7
9
11
13
15
5
7
9
11
13
15
5
7
9
11
13
15

YCSE040SB
Cool
kW
132
139
147
154
161
169
130
137
144
152
159
166
124
131
139
146
153
161
119
126
133
141
148
155
117
124
131
139
146
153
113
121
128
135
143
150
108
115
123
130
137
145
92.3
98.9
105.5
112.1
118.7
125.3
87.4
94.0
100.6
107.2
113.8
120.4

P.I.
kW
22
23
23
24
24
25
24
25
25
26
26
27
28
28
29
29
30
30
32
32
32
33
33
33
33
33
34
34
34
35
35
36
36
36
36
37
39
39
40
40
40
40
42.6
42.9
43.1
43.3
43.5
43.8
45.6
45.8
45.9
46.1
46.2
46.4

H.R.
kW
154
162
170
178
186
194
154
162
170
177
185
193
152
160
168
175
183
191
150
158
166
173
181
189
150
157
165
173
180
188
149
156
164
172
179
187
147
155
162
170
177
185
134.9
141.7
148.6
155.4
162.2
169.1
133.0
139.8
146.5
153.3
160.0
166.8

YCSE050SB
Cool
kW
165.7
174.9
184.1
193.3
202.5
211.7
162.5
171.7
180.9
190.1
199.3
208.5
155.4
164.6
173.8
183.0
192.2
201.4
148.8
158.0
167.2
176.4
185.6
194.8
146.1
155.3
164.5
173.7
182.9
192.1
142.1
151.3
160.5
169.8
179.0
188.2
135.3
144.6
153.8
163.0
172.2
181.4
115.7
124.0
132.3
140.5
148.8
157.1
109.6
117.9
126.1
134.4
142.7
151.0

LCLT = Leaving Chilled Liquid Temperature

Page C.8
Doc. No. PC154-100 Rev 1(0905)

P.I.
kW
27.8
28.4
29.1
29.8
30.5
31.2
30.6
31.2
31.8
32.4
33.1
33.7
35.2
35.7
36.2
36.7
37.2
37.7
39.6
40.0
40.4
40.8
41.2
41.6
41.6
41.9
42.3
42.6
43.0
43.3
44.4
44.7
45.0
45.3
45.6
45.9
49.2
49.4
49.6
49.8
49.9
50.1
53.4
53.7
54.0
54.3
54.6
54.9
57.2
57.4
57.6
57.8
57.9
58.1

H.R.
kW
193.4
203.3
213.2
223.1
233.0
242.9
193.1
202.9
212.8
222.6
232.4
242.2
190.7
200.4
210.0
219.7
229.4
239.1
188.4
198.0
207.6
217.2
226.8
236.4
187.7
197.2
206.8
216.3
225.9
235.4
186.6
196.1
205.6
215.1
224.6
234.0
184.5
193.9
203.3
212.7
222.1
231.5
169.1
177.7
186.3
194.9
203.4
212.0
166.8
175.3
183.7
192.2
200.7
209.1

YCSE060SB
Cool
kW
203.4
214.7
226.0
237.3
248.6
259.9
199.6
210.9
222.2
233.5
244.8
256.1
190.8
202.1
213.4
224.7
236.0
247.3
182.7
194.0
205.3
216.6
227.9
239.2
179.4
190.7
202.0
213.3
224.6
235.9
174.5
185.8
197.1
208.4
219.7
231.0
166.2
177.5
188.8
200.1
211.4
222.7
142.1
152.2
162.4
172.6
182.7
192.9
134.6
144.7
154.9
165.1
175.2
185.4

P.I.
kW
34.063
34.91
35.765
36.62
37.467
38.32
37.562
38.31
39.067
39.82
40.573
41.33
43.269
43.87
44.464
45.06
45.659
46.26
48.609
49.1
49.591
50.08
50.573
51.06
51.064
51.49
51.915
52.34
52.766
53.19
54.562
54.91
55.266
55.62
55.97
56.32
60.393
60.62
60.851
61.08
61.309
61.54
65.6
66.0
66.3
66.7
67.0
67.4
70.2
70.4
70.7
70.9
71.1
71.4

H.R. = Condenser Heat Rejection

H.R.
kW
237.5
249.6
261.8
274
286.1
298.3
237.11
249.2
261.22
273.3
285.33
297.4
234.09
246
257.89
269.8
281.68
293.6
231.28
243.1
254.87
266.7
278.45
290.2
230.44
242.2
253.89
265.6
277.35
289.1
229.09
240.7
252.39
264
275.7
287.4
226.58
238.1
249.64
261.2
272.7
284.2
207.7
218.2
228.7
239.2
249.8
260.3
204.8
215.2
225.6
236.0
246.4
256.8

YCSE080SB
Cool
kW
264.25
278.9
293.61
308.3
322.97
337.6
259.21
273.9
288.57
303.3
317.93
332.6
247.87
262.6
277.23
291.9
306.59
321.3
237.29
252
266.65
281.3
296.01
310.7
233.01
247.7
262.36
277
291.72
306.4
226.71
241.4
256.06
270.7
285.42
300.1
215.87
230.5
245.23
259.9
274.59
289.3
184.5
197.7
211.0
224.2
237.4
250.6
174.8
188.0
201.2
214.4
227.6
240.8

P.I.
kW
44.261
45.37
46.473
47.58
48.685
49.79
48.807
49.79
50.764
51.74
52.72
53.7
56.224
57
57.776
58.55
59.329
60.1
63.162
63.8
64.438
65.08
65.714
66.35
66.352
66.9
67.458
68.01
68.564
69.12
70.898
71.35
71.812
72.27
72.726
73.18
80.494
81.6
82.706
83.81
84.918
86.02
85.3
85.7
86.2
86.6
87.1
87.5
91.2
91.5
91.8
92.1
92.4
92.7

H.R.
kW
308.51
324.3
340.08
355.9
371.65
387.4
308.02
323.7
339.34
355
370.65
386.3
304.1
319.6
335.01
350.5
365.92
381.4
300.45
315.8
331.09
346.4
361.72
377
299.36
314.6
329.82
345.1
360.29
375.5
297.6
312.7
327.88
343
358.15
373.3
296.36
312.1
327.93
343.7
359.5
375.3
269.8
283.5
297.1
310.8
324.5
338.1
266.0
279.5
293.0
306.5
320.0
333.6

YCSE100SB
Cool
kW
331.37
349.8
368.18
386.6
404.99
423.4
325.05
343.5
361.86
380.3
398.67
417.1
310.83
329.2
347.64
366
384.45
402.9
297.55
316
334.37
352.8
371.18
389.6
292.18
310.6
329
347.4
365.81
384.2
284.28
302.7
321.1
339.5
357.91
376.3
270.69
289.1
307.51
325.9
344.32
362.7
231.4
248.0
264.5
281.1
297.7
314.2
219.2
235.7
252.3
268.9
285.4
302.0

P.I. = Compressor Input Power

P.I.
kW
55.5
56.89
58.273
59.66
61.047
62.43
61.2
62.43
63.654
64.88
66.107
67.33
70.5
71.47
72.447
73.42
74.393
75.37
79.2
80
80.8
81.6
82.4
83.2
83.2
83.89
84.586
85.28
85.973
86.67
88.9
89.47
90.046
90.62
91.193
91.77
100.93
102.3
103.71
105.1
106.48
107.9
106.9
107.5
108.0
108.6
109.2
109.8
114.4
114.8
115.1
115.5
115.9
116.3

H.R.
kW
386.87
406.7
426.45
446.2
466.04
485.8
386.25
405.9
425.51
445.1
464.78
484.4
381.33
400.7
420.09
439.5
458.85
478.2
376.75
396
415.17
434.4
453.58
472.8
375.38
394.5
413.58
432.7
451.78
470.9
373.18
392.2
411.14
430.1
449.1
468.1
371.63
391.4
411.21
431
450.8
470.6
338.3
355.4
372.6
389.7
406.9
424.0
333.6
350.5
367.4
384.4
401.3
418.3

45
55

50

Condening Temperature (C)

40

35

LCLT

YCRE COOLING CAPACITIES

5
7
9
11
13
15
5
7
9
11
13
15
5
7
9
11
13
15
5
7
9
11
13
15
5
7
9
11
13
15

YCRE040SB
Cool
kW
123.4
130.4
137.4
144.4
151.4
158.4
118.0
125.0
132.0
139.0
146.0
153.0
113.0
120.0
127.0
134.0
141.0
147.9
108.0
114.9
121.9
128.9
135.9
142.9
102.8
109.8
116.8
123.8
130.8
137.7

P.I.
kW
26.3
26.8
27.4
27.9
28.4
28.9
30.2
30.6
31.1
31.6
32.1
32.5
34.4
34.4
35.1
35.4
35.7
36.0
38.3
38.5
38.7
38.9
39.1
39.4
42.2
42.3
42.4
42.5
42.6
42.7

H.R.
kW
149.7
157.3
164.8
172.3
179.8
187.3
148.2
155.7
163.1
170.6
178.1
185.5
147.4
154.4
162.0
169.4
176.7
184.0
146.3
153.5
160.7
167.9
175.1
182.3
145.0
152.1
159.2
166.3
173.4
180.5

YCRE050SB
Cool
kW
149.2
157.6
166.0
174.5
182.9
191.4
142.6
151.1
159.5
168.0
176.4
184.9
136.5
145.0
153.4
161.9
170.3
178.8
130.4
138.9
147.3
155.8
164.2
172.7
124.2
132.7
141.1
149.5
158.0
166.4

LCLT = Leaving Chilled Liquid Temperature

P.I.
kW
32.4
33.1
33.7
34.4
35.0
35.7
37.2
37.8
38.3
38.9
39.5
40.1
42.4
42.4
43.2
43.6
44.0
44.4
47.2
47.5
47.7
48.0
48.3
48.5
52.0
52.1
52.3
52.4
52.5
52.7

H.R.
kW
181.6
190.7
199.8
208.9
218.0
227.1
179.8
188.8
197.9
206.9
215.9
225.0
179.0
187.4
196.7
205.5
214.3
223.2
177.7
186.4
195.1
203.8
212.5
221.2
176.2
184.8
193.4
202.0
210.5
219.1

YCRE060SB
Cool
kW
185.2
195.6
206.1
216.6
227.1
237.6
177.1
187.5
198.0
208.5
219.0
229.5
169.5
180.0
190.5
200.9
211.4
221.9
161.9
172.4
182.9
193.4
203.9
214.4
154.2
164.7
175.2
185.6
196.1
206.6

P.I.
kW
39.8
40.6
41.4
42.2
43.0
43.8
45.7
46.4
47.1
47.8
48.6
49.3
52.2
52.1
53.1
53.6
54.1
54.6
58.0
58.3
58.6
59.0
59.3
59.6
63.9
64.1
64.2
64.4
64.6
64.7

H.R. = Condenser Heat Rejection

H.R.
kW
225.0
236.3
247.6
258.8
270.1
281.4
222.7
233.9
245.1
256.3
267.5
278.8
221.6
232.1
243.6
254.5
265.5
276.5
219.9
230.7
241.6
252.4
263.2
274.0
218.1
228.7
239.4
250.0
260.7
271.3

TABLE 8

YCRE080SB
Cool
kW
246.9
260.9
274.8
288.8
302.8
316.8
236.1
250.1
264.0
278.0
292.0
306.0
226.0
240.0
254.0
267.9
281.9
295.9
215.9
229.9
243.9
257.9
271.8
285.8
205.6
219.6
233.6
247.5
261.5
275.5

P.I.
kW
52.6
53.7
54.7
55.8
56.8
57.9
60.3
61.3
62.2
63.2
64.1
65.1
68.9
68.8
70.1
70.8
71.4
72.0
76.6
77.0
77.4
77.8
78.2
78.8
84.4
84.6
84.8
85.0
85.2
85.5

H.R.
kW
299.5
314.5
329.5
344.6
359.6
374.7
296.4
311.3
326.2
341.2
356.1
371.0
294.9
308.8
324.1
338.7
353.3
367.9
292.5
306.9
321.3
335.7
350.0
364.6
290.0
304.2
318.4
332.6
346.8
360.9

YCRE100SB
Cool
kW
298.3
315.2
332.1
349.0
365.9
382.8
285.3
302.1
319.0
335.9
352.8
369.7
273.1
290.0
306.9
323.7
340.6
357.5
260.9
277.8
294.7
311.6
328.5
345.4
248.4
265.3
282.2
299.1
316.0
332.9

P.I.
kW
64.8
66.1
67.4
68.7
70.0
71.3
74.3
75.5
76.7
77.9
79.0
80.2
84.9
84.8
86.5
87.2
88.0
88.8
94.4
95.0
95.4
96.0
96.6
97.0
104.0
104.3
104.5
104.8
105.1
105.3

H.R.
kW
363.1
381.3
399.5
417.7
435.9
454.1
359.6
377.7
395.7
413.8
431.9
449.9
358.0
374.8
393.3
411.0
428.7
446.3
308.1
325.3
342.4
359.6
376.7
393.9
352.4
369.6
386.8
403.9
421.1
438.2

P.I. = Compressor Input Power

Page C.9
Doc. No. PC154-100 Rev 1(0905)

YCSE PART LOAD PERFORMANCE

TABLE 9

YCSE040SB

Condenser Water Outlet Temperature

Performance

55C
50C
45C
40C
35C
30C
25C
22C

Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input

Compressor Load 33~99%

%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%

40
64
40
58
40
49
40
43
40
38
43
34
46
30

50
77
50
69
50
56
50
49
50
43
50
37
50
32
50
29

60
96
60
85
60
65
60
56
60
48
60
42
60
36
60
32

70
125
70
107
70
78
70
66
70
56
70
48
70
40
70
36

80
94
80
80
80
67
80
57
80
47
80
41

Full Load

90
119
90
98
90
80
90
67
90
55
90
49

75
144
78
134
92
124
96
112
100
100
100
82
100
65
100
57

104
89
109
78
110
70

90
119
90
98
90
80
90
69
90
59
90
52

75
144
78
134
92
124
96
112
100
100
100
83
100
70
100
60

90
119
90
98
90
80
90
69
90
59
90
52

75
144
78
134
92
124
96
112
100
100
100
83
100
70
100
60

106
94
112
88
110
70

90
119
90
98
90
80
90
69
90
59
90
52

75
144
78
134
92
124
96
112
100
100
100
83
100
70
100
60

111
71

YCSE050SB & YCSE060SB

Condenser Water Outlet Temperature

Performance

55C
50C
45C
40C
35C
30C
25C
22C

Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input

Compressor Load 25~99%

%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%

30
55
30
50
30
44
30
40
30
35
32
33
34
31
35
29

40
64
40
58
40
49
40
43
40
38
40
35
40
32
40
30

50
77
50
69
50
56
50
49
50
43
50
39
50
35
50
33

60
96
60
85
60
65
60
56
60
48
60
44
60
39
60
36

70
125
70
107
70
78
70
66
70
56
70
50
70
44
70
40

Full Load

80
94
80
80
80
67
80
58
80
51
80
45

106
94
112
88
110
70

120
84

YCSE080SB
16.5%

Condenser Water Outlet Temperature

Performance

55C
50C
45C
40C
35C
30C
25C
22C

Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input

%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%

20
32
20
29
20
25
20
22
20
19
22
18
23
17
25
16

Compressor Load 33~99%

40
64
40
58
40
49
40
43
40
38
43
36
46
34

50
77
50
69
50
56
50
49
50
43
50
39
50
35
50
33

60
96
60
85
60
65
60
56
60
48
60
44
60
39
60
36

70
125
70
107
70
78
70
66
70
56
70
50
70
44
70
40

80
94
80
80
80
67
80
58
80
51
80
45

Full Load

120
84

YCSE0100SB
12.5%

Condenser Water Outlet Temperature

Performance

55C
50C
45C
40C
35C
30C
25C
22C

Page C.10
Doc. No. PC154-100 Rev 1(0905)

Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input

%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%

15
27
15
25
15
22
15
20
15
18
16
16
17
15
18
15

Compressor Load 25~100%

30
55
30
50
30
44
30
40
30
35
32
33
34
31
35
29

40
64
40
58
40
49
40
43
40
38
40
35
40
32
40
30

50
77
50
69
50
56
50
49
50
43
50
39
50
35
50
33

60
96
60
85
60
65
60
56
60
48
60
44
60
39
60
36

70
125
70
107
70
78
70
66
70
56
70
50
70
44
70
40

Full Load

80
94
80
80
80
67
80
58
80
51
80
45

106
94
112
88
110
70

120
84

YCRE PART LOAD PERFORMANCE

TABLE 10

YCRE040SB, YCRE050SB & YCRE060SB

Condensing Temp.

Performance

55C
50C
45C
40C
35C

Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input

Compressor Load 15~99%

%
%
%
%
%
%
%
%
%
%

20
43
20
37
20
33
20
28
21
25

30
52
30
46
30
39
30
35
30
30

40
59
40
53
40
46
40
40
40
34

50
68
50
60
50
53
50
45
50
39

60
77
60
68
60
59
60
51
60
44

Full Load

70
89
70
77
70
66
70
58
70
51

80
103
80
88
80
76
80
66
80
54

90
119
90
104
90
87
90
73
90
62

92
123
96
112
100
100
100
85
100
70

104
89
109
78

80
103
80
88
80
76
80
66
80
54

90
119
90
104
90
87
90
73
90
62

92
123
96
112
100
100
100
85
100
70

YCRE080SB & YCRE100SB


7.5%

Condensing Temp.

Performance

55C
50C
45C
40C
35C

Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input

%
%
%
%
%
%
%
%
%
%

10
22
10
19
10
17
10
14
11
13

Compressor Load 15~99%

20
43
20
37
20
33
20
28
21
25

TABLE 11
YCSE-SB
Refrigerant Circuits
Refrigerant charge per circuit
Type
Compressor
Oil charge per compressor
Capacity Control
Evaporator
Number
Connections (Inlet & Outlet)
Water volume per evaporator
Water
Number
Cooled
Type
Condenser
Water volume per condenser
Weight
Operating
Shipping
Length
Dimensions
Width
Height
YCRE-SB
Refrigerant Circuits
Type
Compressor
Oil charge per compressor
Capacity Control
Evaporator
Number
Connections (Inlet & Outlet)
Water volume per evaporator
Liquid Line (outer diameter)
Refrigerant
Discharge Line (outer diameter)
piping
Weight
Shipping
Length
Dimensions
Width
Height

30
52
30
46
30
39
30
35
30
30

40
59
40
53
40
46
40
40
40
34

50
68
50
60
50
53
50
45
50
39

60
77
60
68
60
59
60
51
60
44

70
89
70
77
70
66
70
58
70
51

Full Load

104
89
109
78

PHYSICAL DATA

kg

040
1
12.0

l
%

6.0
33-100

12.1

l
kg
kg
mm
mm
mm

13.5
770
710
1362
677
1275
040
1

l
%

6.0
15-100

l
mm
mm
kg
mm
mm
mm

12.1

590
1064
935
1343

050
060
080
100
1
1
2
2
14.0
16.0
12.0
14.0
Semi-Hermetic Screw Type
6.0
6.0
6.0
6.0
25-100
25-100
16.5-100
12.5-100
1
4 " Victaulic
3 " Victaulic
15.9
21.7
32.3
40.7
1
3 " Victaulic
4 " Victaulic
16.9
21.7
36.5
44.9
865
930
1360
1560
800
860
1,250
1,440
1449
1449
1210
1210
677
677
1340
1450
1275
1275
1465
1465
050
060
080
100
1
1
2
2
Semi-Hermetic Screw Type
6.0
6.0
6.0
6.0
15-100
15-100
7.5-100
7.5-100
1
3 " Victaulic
4 " Victaulic
15.9
21.7
32.3
40.7
28.6
41.3
755
690
1,140
1,250
1088
1152
1184
1184
935
935
1432
1432
1343
1343
1531
1531

Page C.11
Doc. No. PC154-100 Rev 1(0905)

ACOUSTIC DATA

TABLE 12

Model
63
74
76
77
77
79

YCSE/YCRE40SB
YCSE/YCRE50SB
YCSE/YCRE60SB
YCSE/YCRE80SB
YCSE/YCRE100SB

125
67
68
69
70
71

Sound Pressure Level (dB)


Frequency Band (Hz)
250
500
1000
2000
67
68
59
61
67
64
65
64
67
62
68
66
70
71
62
64
70
67
68
67

4000
47
51
53
50
54

8000
36
35
35
39
38

Overall
(dBA)
68
69
71
71
72

Sound pressure level at:


Chilled water inlet/outlet temperature of 12/7C and condenser water .inlet/outlet temperature of 30/35C
1 meter from the control panel surface and 1.5 meter from the floor level.
Supply voltage of 380 V, for 415 V the values will increase by 1 dB.
Measured in an anechoic chamber, so that reflected sound should be taken into consideration in the field.

ELECTRICAL DATA

TABLE 13
The following connections are required:

One 400 V, 3 phase, 50 Hz supply plus neutral and earth.


Control interlocks if required.
The power connections are made to the unit screw terminals in
the control panel. Interlocks are made to a terminals in the
control panel.
Model
YCSE40SB
YCSE50SB
YCSE60SB
YCSE80SB
YCSE100SB
YCRE40SB
YCRE50SB
YCRE60SB
YCRE80SB
YCRE100SB

Unit
Power
(V)
(Hz)
380
50
415
50
380
50
415
50
380
50
415
50
380
50
415
50
380
50
415
50
380
415
380
415
380
415
380
415
380
415

50
50
50
50
50
50
50
50
50
50

Instantaneous Voltage
Max.
Min.
(V)
(V)
418
342
457
374
418
342
457
374
418
342
457
374
418
342
457
374
418
342
457
374
418
457
418
457
418
457
418
457
418
457

342
374
342
374
342
374
342
374
342
374

Supply cables should enter the unit via the holes provided in the
panel.
A customer supplied mains isolator switches should be located
adjacent to the unit and should incorporate provision for locking
in the off position.

Unit

I.P.
(kW)
31,9
31,9
40,0
40,0
49,1
49,1
63,8
63,8
80,0
80,0

Commpressor
NRA
(A)
54,7
53,7
68,5
67,0
82,2
79,0
109
107
137
134

LRA
(A)
114,6
125,2
147,5
161,1
178,4
194,8
114,6
125,2
147,5
161,1

MRA
(A)
90
89
113
111
136
130
181
177
226
221

SMRA
(A)
115
125
148
161
178
195
142
152
174
187

34,4
34,4
42,4
42,4
52,1
52,1
68,8
68,8
84,8
84,8

59,4
57,7
73,2
71,1
88,0
84,3
118,8
115,4
146,4
142,2

114
125
148
161
178
195
114
125
148
161

74
72
92
89
110
105
149
144
183
178

114
125
148
161
178
195
134
144
172
184

I.P. = Input Power; NRA = Nominal Running Current; LRA = Starting Current; MRA = Maximum Running Currrent;
SMRA = Maximum Running Currrent during Starting.
Compressor I.P. and NRA based on chilled water inlet/outlet temperature of 12/7C and condenser water .
inlet/outlet temperature of 30/35C
MRA is the maximum total unit running current at a supply voltage of 90% of the rated voltage with unit capacity of
100% at maximum operating conditions. The power supply cables must be sized to cover this maximum current value.
LRA is the first compressor starting current. SMRA is MRA and starting current, when other compressor starts.

Page C.12
Doc. No. PC154-100 Rev 1(0905)

CUSTOMER

YORK

L3

L2

L1

Pump
Interlock

Cont.
2

Cont.
1

Cont.
2

Thermal Thermal
Relay
Relay
2
3

PCB - CPU

Pump operation

Cont.
1

Thermal
Relay
1
Pilot Lamp for
Remote Indication
(Unit Operation, Cool/Heat)

: Customer Wiring

NOTE:
1. All the setting shall be performed before Power ON.
2. Remote/Local Change over Switch on Operation Switch shall be set to "Remote".
3. Terminals 1 to 17 are for 220-240Vac Terminals A to D are for 24 Vdc.

3 380-415V
+N+PE

Contactor for
Tower

Main Power/Terminal Board

ON/OFF

RUN/STOP
SIGNAL

ALARM
LAMP

MODE 2
Pulse

MODE 1

No Use Low Voltage Control)

NORMAL MODE

MODE

DSW 1 SETTING

Flow Switch Differential


Water Pressure Switch Option.

ALARM DC24V
SIGNAL

SETTING OF LOW VOLTAGE CONTROL

Pilot Lamp for


Remote Indication (Alarm)-2

LOW VOLTAGE REMOTE CONTROL

ELECTRICAL CONNECTIONS

Page C.13
Doc. No. PC154-100 Rev 1(0905)

Water Pressure Switch,


Water Flow Switch,
Condenser Circuit
Water Pressure Switch,
Water Flow Switch,
Evaporator Circuit

Pilot Lamp for


Remote Indication (Alarm)-1

Condenser Water Inlet


(3" Victaulic)

Cooler Water Outlet


(3" Victaulic)

160

190

4 x Lifting eyebolt
Inlet for Control Wiring

122

773

YCSE 40
YCSE 50
YCSE 60

140

DIM A
76
10
-83

DIM A
(condenser)

DIM B
391
316
204

DIM B
(cooler)

DIM C
1362
1449
1449

1139

DIM C

1275

Page C.14
Doc. No. PC154-100 Rev 1(0905)

Condenser Water Outlet


(3" Victaulic)

Cooler Water Inlet


(3" Victaulic)

Electrical Box

Inlet for Power


Supply Wiring
89

677

772.5

YCSE40SB, YCSE50SB and YCSE60SB

DIMENSIONS

763

1050

336

Cooler Water Outlet


(4 Victaulic)

Condenser Water Inlet


(4 Victaulic)

420

Electrical Box

DIM B
(cooler)

YCSE 80
YCSE 100

DIM A
(condenser)

Cooler Water
Inlet
(4 Victaulic)

Condenser Water
Outlet (4 Victaulic)

4 x Lifting eyebolt

Inlet for
Control Wiring

122

590
178

DIM A
273
176

DIM B
204
107

1139

DIM C

DIM C
1340
1450

Inlet for Power


Supply Wiring
89

1373

1092

1277

YCSE80SB and YCSE100SB

DIMENSIONS

Page C.15
Doc. No. PC154-100 Rev 1(0905)

955

1262

1465

925

Page C.16
Doc. No. PC154-100 Rev 1(0905)

Cooler Water Outlet


(3B Victaulic)

Cooler Water inlet


(3B Victaulic)

Dim A

Electrical Box

YCRE 40
YCRE 50
YCRE 60

Power Wiring Inlet (Frontal side)


Control Wiring Inlet (Rear Side)

4x 35 Lifting Hole

DIM A
1064
1088
1152

DIM B
107
32
80

Dim B

4 - 26 Hole
For unit fixing

A View

YCRE40SB, YCRE50SB and YCRE60SB

DIMENSIONS

Electrical Box

Power Wiring Inlet (Frontal side)


Control Wiring Inlet (Rear Side)

Cooler Water Outlet


(4B Victaulic)

4x 35 Lifting Hole

Cooler Water inlet


(4B Victaulic)

YCRE 80
YCRE 100

DIM A
80
159

Dim A

4 - 26 Hole
For unit fixing

A View

YCRE80SB and YCRE100SB

DIMENSIONS

Page C.17
Doc. No. PC154-100 Rev 1(0905)

SPACE REQUIREMENTS

WEIGHT DISTRIBUTION AND CENTRE OF GRAVITY

Page C.18
Doc. No. PC154-100 Rev 1(0905)

Model
Position
1
2
3
4
Dimension
A
B

YCSE40SB

Model
Position
1
2
3
4
Dimension
A
B

YCRE40SB

180
145
245
200
637
380

190
120
210
130
420
565

YCSE50SB

YCSE60SB

YCSE80SB

Weight Distribution (kg)


205
235
285
160
180
240
275
295
455
225
220
380
Location of Centre of Gravity (mm)
645
680
612
380
393
650
YCRE50SB

YCRE60SB

YCRE80SB

Weight Distribution (kg)


205
225
350
130
135
290
230
250
335
145
150
275
Location of Centre of Gravity (mm)
415
415
535
570
575
895

YCSE100SB

270
330
520
440
612
645
YCRE100SB

405
325
355
285
555
905

Das könnte Ihnen auch gefallen