Beruflich Dokumente
Kultur Dokumente
1)
11)Calculate the output in mA of Electronics D.P Tx. When applied a D.P of 125 inches of
water gauge, knowing that the range is 0 to 300 inches of WG?
a) Gas Service
b) Liquid Service?
Liquids lines: On liquids line the transmitter is mounted below the orifice plate because liquids
have a property of self draining.
Gas Service: On gas service the transmitter is mounted above the orifice plate because gases
have a property of self venting and secondly condensate formation.
17) Name 3 types of instrument related protections against explosions in Hazardous area?
There are three basic methods of protectionexplosion containment, segregation and
prevention.
Explosion containment: The only method that allows the explosion to occur but confines it to a
well-defined area, thus avoiding the propagation to the surrounding atmosphere. Explosionproof enclosures are based on this method.
Segregation: A method that attempts to physically separate or isolate the electrical parts or hot
surfaces from the explosive mixture. This method includes various techniques, such as
pressurization, encapsulation, etc.
Prevention: A method that limits the energy, both electrical and thermal, to safe levels under
both normal operation and fault conditions. Intrinsic safety is the most representative
technique of this method.
18)Why are compensating leads used with thermocouples?
19)Explain how differential pressure measurement can be used to measure the level of liquid
in a open tank. Give a sketch.
The bottom connection of the vessel is connected to high pressure side of the transmitter.
This difference pressure is applied to H.P. side of the transmitted and calibrated.
On an open tank level measurement the L.P. side is vented to atmosphere. Whatever pressure
acts is on the H.P. side which is a measure of level.
SPAN=(X)(SP.GRAVITY)
ZERO SUPPRESSION=(Y) (SP.GRAVITY)
4. STD PG.
I/P MMWC
O/P MA
0.00
4.00
25
250.00
8.00
50
500.00
12.00
75
750.00
16.00
100
1000.00
20.00
Calibration
Step 1: turn on the transmitter and allow the internal components to each normal operating
temperature.
Step 2: connect AFR with STD PG in HP side (low side open to atmosphere) for giving input
pressure to the instrument
Step 3: apply 0 mmwc to the instrument and check whether the out put is 4 mA. If there is any
variation, adjust the zero and set it to 4 mA.
Step 3: apply 1000 mmwc to the instrument and check whether the out put is 20 mA. If there is
any variation, adjust the zero and set it to 20 mA.
Step 4: apply 25%, 50%, 75% input to the instrument and check whether the output obtained
according to the input.
28)What is hot loop check and cold loop check?
Cold Loop checking: Checking of wires continuity of respective field instrument-Junction boxDCS/PLC -marshalling panel terminal.
Hot loop checking: Once you powerup your field instrument through DCS/PLC system, by
stimulating process input from respective field instrument and cross check its response at
DCS/PLC system
29)What is the maximum operating temperature?
The Maximum Operating Temperature is the maximum body temperature at which the
thermistor is designed to operate for extended periods of time with acceptable stability of its
electrical characteristics.
30)What is the potential free contact?
Potential free contacts (also called "dry contacts") are simply contacts which are physically
operated with the main device, but not electrically connected to it.
31)What is the voltage range used for caliberation?
0-24 V, 9(4-20 mA
32)What happen if transmitter wire gets shorted?
The Tx will show error.
33)What are analog input/output & Digital input/output?
Digital signals are either ON (binary 1) or OFF (binary 0). Digital input signals are used to
represent items that only have two (2) states, such as... ON or OFF states ALARM or NORMAL
conditions Similarily, Digital output signals are used to control items that again only have two
states, such as.. START or STOP a device turn an indicator ON or OFF.
Analog signals are variable, they have multiple states. Analog input signals can represent such
items as temperature or level or rate of flow. Analog output signals are also variable and can be
used for such things as opening a valve to a desired position. So, use digitals for 2 state devices
and analogs for multiple state devices
34)What is open loop & close loop?
OPEN LOOP SYSTEM: An Open loop System is also known as the control system without
feedback . These systems do not have any any portion of output feedback to the input for
comparison and measurement. The components of these system are: input, processing system
and output.