kymark VAC self-contained


air conditioning packages offer a
complete line of unit options for indoor,
through-the-wall installation for high rise
and single story building applications.
Skymarks compact, low profile indoor
design protects against potential vandalism,
weathering and eliminates the need for
any unsightly exterior equipment.
Floor-by-floor installation provides independent
zone and temperature control, eliminating many
of the complications encountered with roof-top
equipment. Renovation and restoration projects are
simplified where roof load, cooling tower, and construction
restrictions can present installation problems.
Skymarks VAC Air Cooled Indoor Vertical air
conditioning design features high efficiency,
quality engineering and dependable operation.

VAC
VERTICAL
Air Cooled Self Contained
Air Conditioning Packages
8 - 25 Ton Series

Skymark VAC Features


Ideal for tenant change/renovation.

Convertible horizontal or vertical evaporator discharge.

Protected from extreme weather conditions and vandalism.

Static capability to suit various installation requirements

Convenient access to all parts and service needs, while


running in place.
Allows independent metering / temperature control.

using centrifugal blowers and adjustable pulleys.


Available in 8, 10, 12, 15, 20 and 25 capacities.

GENERAL DATA

9
1

5
KEY COMPONENTS
1. Belt driven centrifugal evaporator blowers with adjustable pulleys
2. Heavy gauge galvanized steel cabinet. Separate evaporator and condensing modules,
allowing easy separation if required.
3. Belt driven centrifugal condenser blowers with adjustable pulleys
4. Convenient indoor access to all parts and service needs
5. 8 through 25 ton units feature multiple high efficiency compressors in parallel for
efficient part-load cooling.
6. Filter drier
7. Sub-cooling built into draw through coil
8. Sight glass
9. TX valve

GENERAL DATA

SKYMARK MODEL # NOMENCLATURE CODE


Model# VAC

096

32

Product Type
Vertical Air-cooled
Nominal Capacity
096 = 96,000 BTHU
120 = 120,000 BTHU
144 = 144,000 BTHU
180 = 180,000 BTHU
240 = 200,000 BTHU
300 = 300,000 BTHU

Service Digit
Production Variant
Voltage
32 = 208-230/3/60
34 = 460/3/60
35 = 575/3/60
Design Series

COOLING PERFORMANCE DATA

All figures shown are gross cooling capacities and do not include the effect of fan motor heat.

COOLING PERFORMANCE DATA

All figures shown are gross cooling capacities and do not include the effect of fan motor heat.

FAN PERFORMANCE
Supply Air Blower Performance

Condenser Air Blower Performance

ELECTRICAL DATA

Standard Evaporator and Condenser Motors

Oversized Evaporator Motors

8 - 10 TON UNIT DIMENSIONS

12 - 15 TON UNIT DIMENSIONS

20 TON UNIT DIMENSIONS

NOTE: SHIPPED SPLIT,


NITROGEN CHARGE ONLY

10

25 TON UNIT DIMENSIONS

NOTE: SHIPPED SPLIT,


NITROGEN CHARGE ONLY

11

GENERAL MECHANICAL
SPECIFICATIONS
VAC VERTICAL
SERIES SYSTEMS

EVAPORATOR AND
CONDENSER COILS

All models 8-15 tons ship as factory-charged unitized packages. The 20 and 25 ton models shall be shipped as separate evaporator and condensing unit modules (nitrogen holding charge only). All units may be field split and installed as
separate modules to suit on-site requirements. All packages
are designed for freestanding mounting on the floor, or on a
field fabricated structural steel stand. The 8 and 10 ton models are shipped with vertical evaporator fan discharge as
standard. The 12, 15, 20, and 25 ton models are shipped horizontal discharge as standard.

The evaporator and condenser coils are constructed of internally enhanced copper tubes mechanically bonded to rippled
aluminum plate fins. Both coils are employed in a draw-thru
configuration. Large evaporator coil face area minimizes
potential water blow-off.

CABINET
All cabinets are completely constructed of heavy gauge galvanized steel. The entire unit interior (both evaporator and
condensing section) is insulated with 1/2" thick, 2 lb. density
insulation. Service panels are equipped with lifting handles
for ease of removal and handling. Duct flanges for condenser discharge, condenser intake, and evaporator discharge,
are provided with the unit for field installation. Duct flange for
evaporator return is incorporated into the filter frame.

COMPRESSORS
All models utilize "Scroll" type hermetic compressors.
Compressors are mounted on rubber isolators to minimize
vibration transmission. Internal overload protection is provided. External high pressure and low pressure cutout switches
are included in each compressor control circuit. Crankcase
heaters are standard on all models.

REFRIGERANT CIRCUITS
The 8-20 ton units feature two independent refrigeration circuits. The 25 ton unit features three independent refrigeration
circuits, with fully interwoven evaporator coil circuitry. Each
refrigeration circuit includes an adjustable thermal expansion
valve (with external equalizer), liquid line filter drier, sight
glass/moisture indicator, and service gauge ports.

12

INDOOR/OUTDOOR FANS
Forward curved, double inlet and double width centrifugal
blowers are used for both evaporator and condenser air
movement. Blower wheels are fabricated of galvanized steel.
Blowers employ solid steel shafts, supported in permanently
lubricated ball bearing. All blowers are belt driven. Variablepitch motor sheaves allow for field adjustment of blower rpm.

ELECTRICAL/CONTROLS
All units are completely factory wired with all necessary controls. Manual reset protection is provided on both evaporator
and condenser motors. A manual reset circuit is also provided on each compressor control circuit in the event of high/low
pressure cutout. A 24 volt control circuit, with oversize transformer, is provided for field connection.

FILTERS
All models are shipped with 2 inch thick medium-efficiency
throwaway filters, factory installed. Filter rack is external to
the cabinet (shipped loose).

OPTIONAL ACCESSORIES
FACTORY INSTALLED

FIELD INSTALLED

Oversized Evaporator Fan Motors

Low Ambient Control

Increased horsepower motors and drive components are


available for those applications where external static pressure
requirements exceed the capability of the standard motor.

Head pressure control damper kit will allow unit operation


down to 0oF ambient. Damper assembly fits over condenser
air intake. The kit includes damper actuator, and low pressure
switch bypass timer(s).

Corrosion Resistant Coatings


Condenser and/or evaporator coils shall receive a 1-mil thickness of a cathodic epoxy type electro-deposition coating,
applied in a multiple dip and brake process.

Stainless Steel Drain Pan


Evaporator drain pan shall be fabricated of 304 stainless
steel material. The 3/4 in NPT drain connection fitting is also
of 304 stainless steel.

Hot Gas Bypass


Adjustable hot gas regulator and all necessary piping shall be
installed on lead compressor circuit. Bypass capacity shall be
minimum 50% of compressor capacity. The Bypass valve
opens at a preset suction pressure to prevent coil freeze-up
at light evaporator load, or low airflow conditions. The use of
the field installed Low Ambient Control is strongly recommended when Hot Gas Bypass is installed.

Hot Water & Steam Coils


Hydronic heating coils shall mount on return air side of cooling coil. The unit filter rack shall mount to the entering air side of
the heating coil.

Discharge Plenum
Plenums shall mount on top of the evaporator section, with
fans arranged for vertical discharge. Double deflection grills
shall allow air discharge in multiple directions.

Oversized Evaporator Fan Motors


Increased horsepower motors and drive components are
available as a kit. Units are field upgradeable for applications
where external static pressure requirements exceed the
capability of the standard motor.

Anti-Short Cycle Timer


Time delay relay will be provided for each compressor circuit.
Compressor will be locked out for 5 minutes when thermostat
contacts open, or there is a momentary power outage.

AIRSIDE ECONOMIZER ACCESSORY


APPLICATION

GENERAL

Skymarks air side economizers are designed to meet current building and legislated codes for indoor ventilation. In
addition to improving indoor air quality, economizers provide substantial energy savings by utilizing cool outside air
instead of mechanical cooling whenever outside conditions permit.

Consisting of an integrated mixing box and control assembly,


the economizer mates easily to all Skymark vertical air handlers. A factory supplied wiring harness and jack plug assembly simplifies field wiring, reducing valuable installation time.
No additional controls or transformers are necessary to complete the installation.

The outlet or discharge of the air side economizer is fitted


to the return air inlet of the packaged air conditioning unit.
The two inlets to the economizer are fitted to the return air
and outside air ductwork. Opposed blade dampers located in each inlet modulate the incoming air streams as
they enter the mixing box. The outside air damper can be
maintained at a predetermined minimum position. In this
way the buildings ventilation requirements can be met at
all times.

Mixing Box - The mixing box is manufactured from heavy


gauge steel and completely insulated with one half inch of
insulation. The mixing box is complete with fully modulating
opposed blade dampers and linkage.

Low Leakage - Low leakage dampers meet the criteria of


less than 10 cfm per square foot at 4 w.g. (0.5% at 2000
fpm). All damper blades are provided with neoprene seals
providing a tight seal and quiet operation.
Honeywell W7215 Economizer Control Module - The
W7215 is a multi-functional controller capable of analyzing
dry bulb, enthalpy and air quality inputs. An output from the
economizer module will position the mixing box dampers to
provide energy saving through the introduction of outside air
for free cooling.
13

DISCHARGE PLENUMS
& HEATING COILS

Hot Water Coils


60 F Entering Air Temperature
180 F Entering Water Temperature
Unit
Model #

Airflow
CFM

Coil
Model #

Air P.D
In. Wg.

Water
GPM

Water P.D.
PSIG

Capacity
MBH

Lat
F

VAC096

3200

VHCL-120B

0.09
0.09
0.09

15.0
20.0
25.0

0.47
0.77
1.14

191.5
199.6
204.8

115.4
117.8
119.3

20.0
25.0
30.0

0.77
1.14
1.58

228.1
235.1
240.0

112.8
114.4
115.6

VAC120

4000

VHCL-120B

0.14
0.14
0.14

VAC144

4800

VHCL-180B

0.13
0.13
0.13

25.0
30.0
35.0

0.18
0.24
0.32

269.6
277.5
283.4

112.0
113.5
114.7

VAC180

6000

VHCL-180B

0.15
0.15
0.15

30.0
35.0
40.0

0.28
0.36
0.46

331.6
339.7
346.0

111.2
112.4
113.4

VAC240

8000

VHCL-240B

0.11
0.11
0.11

35.0
40.0
45.0

1.48
1.86
2.28

473.7
483.0
400.4

114.8
115.9
116.8

VHCL-300B

0.16
0.16
0.16

40.0
45.0
50.0

1.94
2.37
2.85

557.4
567.5
575.8

111.6
112.5
113.3

VAC300

10000

Plenum Dimensions (Inches)


A

Side Grille

Front Grille

8 Ton

60

29

28

20x16 (2x)

38x16

10 Ton

60

29

28

20x18 (2x)

48x18

Plenum Dimensions (Inches)


A

Side Grille Front Grille

12 Ton

78

32

28

20x18 (2x)

28x18 (2x)

15 Ton

78

32

28

24x20 (2x)

28x20 (2x)

20 Ton

83

32.5

28

24x20 (2x)

32x20 (2x)

25 Ton

88

34

28

24x20 (2x)

32x20 (2x)

Steam Coils
60 F Entering Air Temperature
Unit
Model #

Airflow
CFM

Coil
Model #

Air P.D
In. Wg.

Steam Pressure
PSIG

Capacity
MBH

Lat
F

VAC096

3200

VSCL-120B

0.08
0.08
0.08

2.0
5.0
10.0

193.0
203.4
215.5

115.8
118.9
122.4

VAC120

4000

VSCL-120B

0.10
0.10
0.10

2.0
5.0
10.0

214.0
225.6
239.0

109.5
112.2
115.3

VAC144

4800

VSCL-180B

0.10
0.10
0.10

2.0
5.0
10.0

257.8
271.8
267.9

109.7
112.4
115.5

VAC180

6000

VSCL-180B

0.12
0.12
0.12

2.0
5.0
10.0

308.5
325.3
344.6

107.6
110.2
113.2

VAC240

8000

VSCL-240B

0.09
0.09
0.09

2.0
5.0
10.0

454.8
479.4
507.9

112.6
115.5
118.8

VAC300

14

10000

VSCL-300B

0.12
0.12
0.12

2.0
5.0
10.0

514.5
542.4
574.6

107.6
110.2
113.2

Heating Coil Dimensions (Inches)


A

8 Ton

52

5.50

28

Inlet (MPT) Outlet (MPT)


1 1/2

1 1/2

10 Ton

52

5.50

28

1 1/2

1 1/2

12 Ton

71

5.50

28.25

15 Ton

71

5.50

28.25

20 Ton

76.5

5.50

40.13

25 Ton

79.5

5.50

40.13

VERTICAL AIRSIDE ECONOMIZER


8 THRU 25 TON FEATURES

Vertical Unit Economizer Weight


/ lbs.
Model #
Model #

VAC 096/120

ASE-120V

192

49.50 28.00

26.50 44.00

19.50

8.00

15.00

VAC 144/180

ASE-180V

238

69.25 29.00

26.50 64.00

19.50

8.00

15.00

VAC 240

ASE-240V

306

75.00 40.25

32.00 69.00

25.00

8.00

15.00

VAC 300

ASE-300V

310

78.00 40.25

32.00 69.00

25.00

8.00

15.00

All Economizers are Shipped Complete with:


18-gauge galvanized cabinet, fully insulated.
Opposed blade, low leakage damper sections.
Steel securing strip for unit support*.
Honeywell ML Series return damper actuator.
Filters and access.
Honeywell W7215 logic module with
protective cabinet.
7 - One step jack/plug wiring assembly.
8 - Access doors on both sides of cabinet.
9 - Enthalpy sensor.
10 - Discharge sensor
11 - Return air/outside air configuration is field
convertible. (Economizers are shipped with
airflow arrangement indicated in bold type)
1
2
3
4
5
6

2
1

3
4
5
6

7
8
9

NOTE: Additional field support required.

10

15

SKYMARK PRODUCT WARRANTY

Skymark International warrants to the original owner/user of the Skymark

of such defect was given by the original Owner/User within the Warranty period.

International unit identified above to be free of original defects in material or

An optional, additional four year protection plan on the compressor is available

workmanship for a period of one year from the effective date of this warranty.

at modest cost at the time of original unit sale only. This obligates Skymark
International to replace f.o.b. factory, a defective compressor of equal capacity

This warranty extends to twelve (12) months from the date of start-up, but no

free of charge. No responsibility is assumed by Skymark International for refrig-

longer than eighteen (18) months from the date of shipment. The warranty does

erant, labor, or freight to and from the factory.

not include the filter.


This warranty on the unit obligates Skymark International to repair or replace, free
of charge, any part or parts that show evidence of being defective in material and
workmanship and are so deemed so defective by authorized personnel of Skymark
International. The part must be returned for replacement with the proper information
when requested.
Skymark International assumes no obligation for labor required to replace the
defective part or parts nor the freight or postage required to return or to

THIS WARRANTY IS IN LIEU OF ALL OTHER EXPRESSED WARRANTIES. ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES
OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE ARE LIMITED IN DURATION TO ONE (1) YEAR FROM EFFECTIVE DATE OF THIS WARRANTY. SKYMARK INTERNATIONAL IS
NOT LIABLE FOR CONSEQUENTIAL DAMAGES RESULTING FROM
ANY DEFECT IN PART. THERE ARE NO OTHER OBLIGATIONS ON
THE PART OF SKYMARK INTERNATIONAL.

secure the part which shall be at the cost and expense of the original
Owner/User.

WARRANTY OF FITNESS
Skymark International does not provide a warranty of fitness since, in good faith,

Skymark International will replace the defective part or parts within 21 days after

Skymark International cannot anticipate or control the many different conditions

the return to Skymark International of such defective part or parts provided notice

under which Skymark International information and products may be used.

City of New York


Department of Buildings
MEA

Skymark maintains a continuous product improvement policy, therefore specifications are subject to change without notice.

PHONE: 905-426-1812
FAX: 905-426-1804
TOLL FREE: 1-888-SKYMARK (759-6275)
WEB: www.skymarkinternational.com

06/04

Das könnte Ihnen auch gefallen