1. Object
This document defines the design and manufacturing characteristics of the cables type
RHZ1-OL 18/30 kV Al+H16 manufactured by Top Cable.
2. Design
This type of cables is designed, manufactured and tested according to UNE-HD 620-5E1 and
IEC 60502-2.
3. Applications
Cables for fixed installations. Suitable for transport and distribution of electric power in
medium voltage networks. Halogen free. These cables are suitable for indoor, outdoor and
buried installations.
4. Characteristics
Nominal voltage: 18/30 (36) kV
Minimum service temperature: -15 C
Maximum conductor temperature: 90 C
Maximum short-circuit temperature: 250 C (maximum 5 s)
Minimum bending radius: 15 x cable
Halogen free: according EN 50267 / IEC 60754
HCl content < 0,5 %
pH > 4,3
conductivity < 10 S/mm.
1 of 5
TECHNICAL SPECIFICATION
Rev. 1 27 May 2009
Issued: M. Canovas Margarit
2 of 5
TECHNICAL SPECIFICATION
Rev. 1 27 May 2009
Issued: M. Canovas Margarit
6. Current-carrying capacities
6.1 Nominal current-carrying capacities
Table 1 show the current-carrying capacities and electric parameters detailed for every
cable.
Current-carrying capacities, in ampers, are calculated according to UNE 211435 and for the
following conditions:
- Open air installation: three single-core cables in trefoil formation and ambient
temperature of 40 C; protected from direct sun radiation and with adequate ventilation
(supported by cleats and hangers or on perforated tray).
- Buried installation: three single-core cables in trefoil formation direct buried at a depth of
1 m, ground temperature of 25 C and soil thermal resistivity of 1,5 Km/W.
- In all cases it is supossed a three-phase circuit.
Reactance (X) is calculated at 50 Hz and for three single-core cables (in triangle or trefoil
formation).
For conditions other than this apply the adequate correction factors (point 6.3).
3 of 5
TECHNICAL SPECIFICATION
Rev. 1 27 May 2009
Issued: M. Canovas Margarit
Approved: F. Daz Rubio
Open air
/km
F/km
Buried
installation
A
1 x 50
0,148
0,134
170
140
1 x 70
0,141
0,147
210
170
1 x 95
0,135
0,160
255
205
1 x 120
0,130
0,171
295
235
1 x 150
0,126
0,183
335
260
1 x 185
0,122
0,197
385
295
1 x 240
0,116
0,217
455
345
1 x 300
0,112
0,236
520
390
1 x 400
0,107
0,262
610
445
1 x 500
0,102
0,292
720
510
1 x 630
0,097
0,333
840
580
Cross-section
mm
Table 1
0,2
0,5
51.100
32.500
23.100
16.450
Table 2
6.3 Correction factors
The current-carrying capacities must be multiplied with the adequate correction factor when
the installation conditions differs from point 6.1
Correction factors for air temperatures other than 40C.
Air Temp. (C)
Factor
20
25
30
35
40
45
50
55
60
1,18
1,14
1,10
1,05
0,95
0,89
0,84
0,77
Table 3
4 of 5
TECHNICAL SPECIFICATION
Rev. 1 27 May 2009
Issued: M. Canovas Margarit
Approved: F. Daz Rubio
10
15
20
25
30
35
40
45
50
1,11
1,07
1,04
0,96
0,92
0,88
0,83
0,78
Table 4
Correction factors for soil thermal resistivity, that depend of damp, other than 1,5 Km/W
(calculated for 240 mm2 cable).
Very
damp
Slightly
damp
Slightly
dry
Dry
Very dry
Very dry
0,8
1,0
1,5
2,0
2,5
3,0
Factor
1,29
1,18
0,88
0,80
0,73
Table 5
7. Dimensions
Table 6 show diameters and weight detailed for every cable.
Cross-section
mm
Outer
Weight
mm
1 x 50
35,5
kg/km
1100
1 x 70
36,5
1190
1 x 95
37,9
1290
1 x 120
39,0
1400
1 x 150
40,4
1520
1 x 185
41,9
1680
1 x 240
44,4
1920
1 x 300
46,7
2170
1 x 400
49,5
2630
1 x 500
54,4
2995
1 x 630
58,1
3580
Table 6
5 of 5