Water Treatment Witnessing Test

T&C Forms Air Conditioning System

JKR/CKM/T & C :______________________


CAWANGAN KEJURUTERAAN MEKANIKAL
JABATAN KERJA RAYA

WATER FLUSHING WITNESSING TESTING AND COMMISSIONING PROCEDURE

Air Conditioning System Water Flushing Witnessing and Test


Item
1

Description
Chiller water / Hot water / Condenser water piping
( Water / Flushing )
(a) Close all valves
(b) Fill the pipe with JBA water
(c) Drain the water
(d) Visual check for dirt free clear water (if fails,
repeat a, b & c til d passes)
(e) Fill JBA water and run the pump for 15 30
Minutes
(f) Drain the water
(g) Clean the strainers
(h) Water cleanliness physical test (if fails, repeat
e, f & g till h passes)
( I ) Fill the JBA water

Chilled / Hot water piping ( Chemical Flushing )


(a) Add CL 2001 thru pot feeder ( Manufacturer
recommendation )
(b) Run the pump for 48 hours
(c) Drain the water and flush the system til clear
water is obtained
(d) Clean the strainers
(e) Alkalinity test
( f )System ready for chemical treatment

Condenser water piping ( Chemical Flushing )


(a)Add CL 2001 thru pot feeder ( Manufacturer
recommendation )
(b) Run the pump for 2 hours
(c) Drain the water and flush the system til clear
water is obtained
(d) Clean the strainers
(e) Alkalinity test
( f )System ready for chemical treatment

Result / Remark

Page 1 of 3

Water Treatment Witnessing Test

T&C Forms Air Conditioning System

Air Conditioning System Water Treatment Witnessing test


Item
Description
1
Condenser water piping
(a) System ready for chemical treatment ( refer check list for
flushing )
(b) Fill the pipe with JBA water
(c) Add the following thru the cooling tower basin ( as per
Manufacturer recommendation )
- C 501 ( as corrosion inhibitor )
- T 837 as non oxidizing microbiocide
(d) System ready for start up
(e) Clean the strainers
2
Chiller / Hot water piping
(a) System ready for chemical treatment
(b) Fill the pipe with JBA water
(c) Add the following thru the pot feeder chemical dosing
pump unit :
( as per Manufacturer recommendation )
- C 303 ( as corrosion, scaling inhibitor )
(d) System ready for start up

Result / Remark

Field test
Item

Water
Volume

Chemical
Type
Qty Added

pH

Alkalinity

Hardness

Result /
Remark

Chilled
water
Condenser
water
Reheat
water
*Calculation of chemical treatment to be endorsed by specialists and submitted.
*The following test criteria to be verified by the specialist after treatment done
and complete done and complete report to be submitted :
- Total hardness
- Total dissolved solids ( applicable for condenser water )
- M alkalinity
- Bacteria count
- Chloride
- pH

Page 2 of 3

Water Treatment Witnessing Test

T&C Forms Air Conditioning System

Checked By Contractor:

Witness By JKR Representative:

Sign:..

Sign :

Name:

Name:

Date:

Date:..

Page 3 of 3