Purging & gas leakage test sequences

This document is the property of Wrtsil Finland Oy and shall not be copied, shown or communicated to a third party without the consent of the owner.

Subtitle

Product

Sequential function chart

DF

Made
Approved

ABA009

Bckstrm

KWE008

Westerlund

Page

Document No.

Rev.

1 (6)

DAAB526476

1. PURGING SEQUENCE AT TRIP OR TRANSFER FROM GAS OPERATING MODE


1.1

Purging sequence at trip or transfer from gas operating mode.

Trip or transfer from gas operating mode initiated


AND Purge GVU command = false

Trip or transfer from gas operating mode initiated


AND Purge GVU command = true
Open CV947
Close V15, V18
Open V07, V14, V16, V20

1.2

Open CV947
Close V07, V15, V18
Open V14, V16, V20

1.4

5 sec
Purge GVU command = false
1.5
Close V07 & V14

20 sec

25 sec

1.6

GVU venting completed

Close CV947 & V20

Wrtsil purging sequence completed


Activate: Purge
engine vent. line

1.7

1.8

True

Open Vx5

1.11

1.12

Close Vx5

Open Vx4

x sec, depending on ventilation piping arrangement

x sec, depending on ventilation piping arrangement

1.9

Activate: Purge
GVU vent. line

1.10

True

External-system

1.3

Close V14

Close Vx4

Purging sequence completed

1.13

End of purging sequence at trip or transfer from gas operating mode.

Page

Document No.

Rev.

2 (6)

DAAB526476

2. PURGING SEQUENCE AT STOP OR SHUTDOWN IN GAS OPERATING MODE

2.1

Purging sequence at stop or shutdown in gas operating mode.

Stop or shutdown in gas operating mode.


AND Purge GVU command = false

Stop or shutdown in gas operating mode


AND Purge GVU command = true
Open CV947
Close V15, V18
Open V07, V14, V16, V20

2.2

Open CV947
Close V07, V15, V18
Open V14, V16, V20

2.4

5 sec
Purge GVU command = false
2.5
Close V07 & V14

25 sec

2.6

20 sec

GVU venting completed

Close V20

Wrtsil purging sequence completed


Activate: Purge
engine vent. line

2.7

2.8

True

Open Vx5

2.11

2.12

Close Vx5

Open Vx4

x sec, depending on ventilation piping arrangement

x sec, depending on ventilation piping arrangement

2.9

Activate: Purge
GVU vent. line

2.10

True

External-system

2.3

Close V14

Close Vx4

Purging sequence completed

2.13

End of purging sequence at stop or shutdown in gas operating mode.

3. PURGING SEQUENCE OF GVU

3.1

Purging sequence of GVU.

Purge GVU command = true


AND sequence 1.1 started = false
AND sequence 2.1 started = false

3.2

Open V07 & V14

Purge GVU command = false

3.3

Close V07 & V14

Purging sequence completed

3.4

End of GVU purging sequence

Page

Document No.

Rev.

3 (6)

DAAB526476

Page

Document No.

Rev.

4 (6)

DAAB526476

4. PURGING SEQUENCE AT LOAD REDUCTION

4.1

Purging sequence at load reduction.

Load reduction command

4.2

Open CV947

x sec, load dependent

4.3

Close CV947

Pressure reduction completed

Activate: Purge
engine vent. line

4.4

True

External-system

4.5

Open Vx5

x sec, depending on ventilation piping arrangement

4.6

Close Vx5

Purging sequence completed

4.7

End of purging sequence at load reduction.

Page

Document No.

Rev.

5 (6)

DAAB526476

5. PURGING SEQUENCE AT EMERGENCY SHUTDOWN


-Due to

60% LFL

5.1

Purging sequence at emergency shutdown.

Engine room shutdown, ESD (= 60% LFL)

5.2

Energy cut off in engine


room; MCC and UCP

Energy cut off = true

5.3

Open CV947
Close V07, V15, V18 and V20
Open V14, V16 and V19

Purging sequence completed

5.4

End of purging sequence at emergency shutdown.

Page

Document No.

Rev.

6 (6)

DAAB526476

6. GAS LEAKAGE TEST

6.1

Gas leakage test.

Perform gas leakage test

6.2

Reset leakage test failure


Open V07, V19
Close V15, V18, V14, V16

10 sec, no pressure at P06

6.3

10 sec, pressure at P06


6.4

Open V15

V15 leaking alarm

6.10 Gas leak test failure


2 sec, pressure at P06

6.5

2 sec, no pressure at P06


6.6

Close V15

V15 stuck alarm

6.10 Gas leak test failure

10 sec, no pressure at P06

10 sec, pressure at P06

6.7

Open V15
Close V19

6.8

V18 leaking alarm

True
Close V18
Open V16
Gas leak test failure alarm

6.10
Gas leak test successful
20 sec

6.9

6.11

Gas leak test completed

Close V19
True
Activate: Purge
GVU vent. line

6.11
True

External system

6.12

Sequence completed
6.14

End of gas leakage test.

Open Vx4
x sec, depending on ventilation piping arrangement

6.13

Close Vx4