Sie sind auf Seite 1von 83

ANSUL

Vertical and Horizontal


Bladder Tank Manual
Part No. 74177-07
7-1-2011

004293

004327

VERTICAL AND HORIZONTAL


BLADDER TANKS
Filling and Maintenance Manual

INTRODUCTION

This manual is intended as a guide for both the ANSUL


Vertical Bladder Tanks and Horizontal Bladder Tanks. If
there are any questions, or further information is required,
contact Tyco Fire Protection Products, Applications
Engineering, Marinette, Wl 54143-2542.
Those who design, install, operate, refill, inspect, or maintain
these systems should read this entire manual.

IMPORTANT
This equipment is designed for use on
only Class A Fires and Class B
Hydrocarbon Fires.
Bladder tanks are mechanical devices. They need periodic
care. Inspections provide reasonable assurance that the
bladder tank is full and the system is operable. Inspection
should take into consideration the environment, system use,
and user inspection policy; but as a minimum should be
conducted semi-annually. Maintenance, which provides
maximum assurance that the ANSUL foam concentrate is
effective and the system is operable, should be conducted
at annual intervals, or earlier when indicated by an
inspection.

WARNING

Maximum working pressure for an ANSUL bladder tank is


175 psi (12.06 bar).
ASME Code requires over pressure protection prior to
placing this vessel in service. Tyco Fire Protection
Products has not provided over pressure protection with
this vessel. It shall be the responsibility of Owner to
arrange for such over pressure protection.
Note: Tyco Fire Protection Products has not provided an
over pressurization device because the water supply pressure and flow capacity of your fire protection system and
the details of the complete system design must be known
before an over pressure protection device can be
provided. Therefore, the owner or the engineer designing
the fire protection system shall have the responsibility of
determining and arranging for the type of over pressure
protection that should be provided for this vessel as part
of the fire protection system. If additional information or
assistance is required, please contact your fire protection
system engineer.

CAUTION

Do not weld on the bladder tank. The tank contains an


elastomeric bladder and interior protective coating which
will be destroyed by welding temperatures. For additional
information contact Tyco Fire Protection Products,
Applications Engineering, Marinette, Wl 54143-2542.
Because the foam concentrate will undergo thermal
expansion as the temperature increases, it is important,
that at the time of filling, the temperature of the concentrate be as close as possible to the actual ambient
temperature where the tank will be located.

NOTICE
ANSUL Foam Concentrates must be
stored within the temperature range listed
on the tank nameplate. If the concentrates
require storage outside of these temperature ranges, consult Tyco Fire Protection
Products, Applications Engineering,
Marinette, Wl 54143-2542.
Also, particular attention should be given
to the Field Inspection Manual (Part No.
31274) which deals with the testing procedures for ANSUL Foam Concentrates.

CAUTION

Lifting lugs are designed to lift the tank empty while utilizing two lift lugs on vertical tanks and four lift lugs on horizontal tanks. The angle of the rope or chain from
horizontal must be 30 degrees or greater.

008397

TABLEOFCONTENTS

SECTION
________

PAGE
_____

Equipment Description

System Schematics

24

Installation

Auxiliary Filling Equipment

Initial Fill

78

Minor Refill*

9 10

Major Refill**

10 12

Inspection

13

Maintenance

14 15

Service and Repair

16 18

* A Minor Refill is replacement of less than 25% of the concentrate.


** A Major Refill is replacement of more than 25% of the concentrate.

EQUIPMENT DESCRIPTION
Page 1

EQUIPMENT DESCRIPTION
BLADDER VENT/
FILL VALVE

The ANSUL Bladder Tank is the main component in a


bladder storage proportioning system. These tanks are
available in vertical or horizontal configurations.

TANK SHELL
VENT VALVE

CONCENTRATE
OUTLET

Both the vertical and horizontal bladder tanks consist of the


following components:
1. ASME constructed steel pressure vessel
WATER
CHANNEL

2. Flexible elastomeric bladder


3. Perforated center discharge tubes

TANK

4. Four one-inch ball valves:


Bladder Vent/Fill Valve
Bladder Drain/Fill Valve
Tank Shell Vent Valve
Tank Shell Drain Valve

WATER
INLET

BLADDER

CENTER
TUBE

TANK SHELL
DRAIN VALVE

BLADDER
DRAIN/FILL
VALVE

SIGHT GAUGE
TEE

FIGURE 1
004295

WATER
INLET

BLADDER VENT/
FILL VALVE

CONCENTRATE
OUTLET

TANK SHELL
VENT VALVE

CENTER
TUBES
TANK

WATER
CHANNEL
TANK SHELL
DRAIN VALVE

BLADDER

BLADDER DRAIN/
FILL VALVE

SIGHT
GAUGE TEE

FIGURE2
004296

SYSTEM SCHEMATICS
Page 2

SYSTEM SCHEMATICS
The following schematics (Figures 3 and 4) represent typical
system piping and valving arrangements for bladder proportioning systems with vertical or horizontal tank configurations. These systems, however, must be designed by
competent, experienced engineers to ensure equipment
compatibility; proper functioning of the system; and compliance with NFPA codes, as well as local and end-user
requirements.
Tyco Fire Protection Products typically supplies:
Foam agent
Bladder tank with tank valves
Proportioner with built-in metering orifice
Most discharge devices

IMPORTANT
Because of the similarities between vertical and horizontal bladder tanks, the
procedures and tank valve functions are
identical. Therefore, vertical bladder tank
schematics are used exclusively throughout the remainder of this manual. For horizontal bladder tanks, refer back to Figures
2 or 4 for valve locations.

TO DISCHARGE
DEVICES

Supplied by others:
Special operational valves (manual or automated)
Strainers
Interconnecting piping

STRAINER (REQUIRED
WITH PROTEIN-BASED
FOAMS)
BLADDER
VENT/FILL
VALVE

PROPORTIONER

STRAINER (REQUIRED WITH


PROTEIN-BASED FOAMS)

SYSTEM ACTUATION VALVE


(MANUAL OR AUTOMATED)

BLADDER
VENT/FILL
VALVE
TO
DISCHARGE
DEVICES
SWING
CHECK VALVE

PRESSURIZED
WATER
SOURCE

CONCENTRATION
ISOLATION VALVE
WATER INLET VALVE
(MANUAL OR
AUTOMATED)

Typical Bladder Tank System Piping Requirements are


shown on Pages 3 and 4.
PROPORTIONER

SYSTEM ACTUATION
VALVE (MANUAL OR
AUTOMATED)

TANK SHELL
VENT VALVE

SWING CHECK
VALVE

PRESSURIZED
WATER SOURCE
TANK SHELL
VENT VALVE

CONCENTRATE
ISOLATION
VALVE

BLADDER
DRAIN/FILL
VALVE
TANK SHELL DRAIN VALVE
WATER INLET
VALVE (MANUAL
OR AUTOMATED)

SIGHT
GAUGE TEE

FIGURE 4
004298

SIGHT
GAUGE TEE

TANK SHELL
DRAIN VALVE

BLADDER DRAIN/
FILL VALVE

FIGURE 3
004297

SYSTEMSCHEMATICS
Page 3

One Stanton Street


Marinette, WI 54143 USA

006912

SYSTEM SCHEMATICS
Page 4

ANSUL

SIGHT GAUGE
(OPTIONAL)

BLADDER TANK

ER
KL M
RIN AR
SP E-AL
FIR

NO.

10

SEE NOTE (3)

11
SEE NOTE (8)

CLOSED

CLOSED

CLOSED

CLOSED

FLOWMAX CL
VARIABLE RANGE
PROPORTIONER

LOCAL CODES MAY REQUIRE


BACKFLOW PREVENTER IN
WATER FEED LINE.

NORMAL POSITION
- 1"

CLOSED

CLOSED

DESCRIPTION
BLADDER VENT/FILL

- 1"

CLOSED

OPEN
8

SWING CHECK - 2"

HYDRAULIC CONCENTRATE - 2"

CONCENTRATE SUPPLY - 2"

---

---

---

CLOSED

TANK SHELL VENT

- 1"

CLOSED

---

CLOSED

---

OPEN

2. IT IS RECOMMENDED THAT THE FLOWMAX CL PROPORTIONER


IS LOCATED ON THE SUPPLY SIDE OF THE SPRINKLER
VALVE TO ALLOW STANDARD SPRINKLER VALVE DRAIN
TRIM TO BE UTILIZED IF REQUIRED.

3. DISCHARGE DEVICE MAY BE SPRINKLER HEADS (AS SHOWN)


OR OTHER TYPE DEVICE SUCH AS MONITOR NOZZLES,
HANDLINE NOZZLES, OR FOAM CHAMBERS AS REQUIRED
BY SYSTEM DESIGN.

4. ARROWS INDICATE DIRECTION OF FLOW.

5. RECOMMENDED INTERCONNECTING PIPE, FITTINGS, AND


VALVE (SEE CHART, NUMBERS 6 THRU 9) SIZES TO
BLADDER TANK ARE GIVEN CORRESPONDING TO
PROPORTIONER SIZE.

6. THE FLOWMAX PROPORTIONER(S) CAN BE LOCATED


UP TO 35 EQUIVALENT LENGTH FEET OF PIPING
FROM THE CONCENTRATE OUTLET OF THE BLADDER TANK
(VALVES AS SHOWN ON THIS DRAWING ARE NOT REQUIRED
TO BE INCLUDED IN EQUIVALENT LENGTH CALCULATION).

7. THE HYDRAULIC CONCENTRATE VALVE (VALVE #8) MAY BE


ELIMINATED ON AN AUTOMATIC SYSTEM HAVING ONE
PROPORTIONER PROVIDED THE FLOWMAX PROPORTIONER IS
LOCATED AT AN ELEVATION AT OR ABOVE THE BLADDER TANK
FOAM CONCENTRATE OUTLET CONNECTION LOCATED AT THE
TOP OF THE TANK.

DWN.

DATE

EEH

03-19-07

SCALE

APPD.

NONE

One Stanton
ANSULStreet
FIRE PROTECTION
MARINETTE,
WI 54143-2542
Marinette,
WI 54143
USA

CHKD.

SHEET 1 OF 1

AE-60124

DRAWING NUMBER

TYPICAL BLADDER TANK/FLOWMAX CL SYSTEM


PIPING REQUIREMENTS

8. TEST CONNECTION FOR WET PIPE SYSTEMS SHOULD BE


LOCATED AT END OF SYSTEM MAIN FOR PREPRIMING PURPOSES.
THE VALVE SHOULD BE SIZED FOR THE REQUIRED FLOW OF
THE PROPORTIONER. CONSIDERATION SHALL BE GIVEN TO
FRICTION LOSSES BEYOND THE VALVE FOR TEMPORARY FIRE
HOSES USED TO DISCHARGE INTO THE SOLUTION COLLECTION
AREA. METHODS OF DISPOSAL VARY-REFER TO TECHNICAL
BULLETIN 52 AND 60.

CLOSED OR OPEN

---

CLOSED

1. SPRINKLER VALVE MAY BE ALARM CHECK, DRY PIPE,


OR PRE-ACTION TYPES AS REQUIRED BY SYSTEM DESIGN.

NOTES:

AUTO SYSTEM
2

TANK SHELL DRAIN

- 1"

OPEN

SPRINKLER ACTUATION/ALARM - 6"

CLOSED
3

BLADDER DRAIN/FILL

- 1/2"

MANUAL SYSTEM

WATER INLET - 2"

SIGHT GAUGE (OPTIONAL)

DESCRIPTION

10

FLOWMAX CL PROPORTIONER - 6"

OS&Y - 6"

OPEN

11

CLOSED

12

REV.

007596

INSTALLATION
Page 5

INSTALLATION
To prepare the bladder tank for placement in service:
1. Remove all cord, wrapping, and banding ties. Examine
entire system and component parts for concealed shipping damage before placement or securement on site.

NOTICE
If the bladder tank is to be connected
to a Closed Head Sprinkler System,
contact Tyco Fire Protection Products,
Applications Engineering, Marinette,
Wl 54143-2542.

NOTICE
For bladder tank dimensions, refer to
Vertical and Horizontal Bladder Tank
Data Sheet (Form No. F-83179).
2.

CAUTION

Lifting lugs are designed to lift the tank empty while


utilizing two lift lugs on vertical tanks and four lift lugs
on horizontal tanks. The angle of the rope or chain
from horizontal must be 30 degrees or greater.
3. Anchor system to floor and remove plastic shipping
plugs from bladder tank valves.

CAUTION

Do not weld on the bladder tank. The tank contains an


elastomeric bladder and interior protective coating
which will be destroyed by welding temperatures. For
additional information contact Tyco Fire Protection
Products, Applications Engineering, Marinette, Wl
54143-2542.
4. Install foam proportioner in main distribution supply pipe
to discharge device(s).

NOTICE
The proportioner must be mounted at
the same elevation as the top flange
of the tank or a normally-closed valve
(manual or automated) must be
installed in the foam concentrate line
to prevent agent migration. A concentrate isolation valve is required to
isolate the tank during filling procedures.

5. Install piping from water supply upstream of proportioner


(see Figures 3 and 4) and to the bladder tank water inlet
using the appropriate piping, valves, gauges, unions,
etc., as determined by the system design engineer.

WARNING

Maximum working pressure for an ANSUL bladder


tank is 175 psi (12.06 bar).
ASME Code requires over pressure protection prior to
placing this vessel in service. Tyco Fire Protection
Products has not provided over pressure protection
with this vessel. It shall be the responsibility of Owner
to arrange for such over pressure protection.
Verify that over pressure protection has been
provided for this vessel within the fire protection
system. If additional information or assistance is
required, please contact the fire protection system
design engineer.
6. Install piping from the bladder tank foam concentrate
outlet to the proportioner concentrate inlet using appropriate piping, valves, strainers, check valves, unions,
etc., as determined by the system design engineer.
7. If an optional sight gauge is provided, install gauge by
completing the following steps:
a. Remove plug from tee located adjacent to the
Bladder Drain/Fill Valve near the bottom of the tank.
(See Figure 1 or 2.)
b. Screw sight gauge assembly into tee using Teflon
tape on male threads of nipple.
c. Snap end of support into adapter located on side of
tank.
HYDRAULIC ACTUATED BALL VALVE INSTALLATION /
OPERATION
The hydraulic actuated ball valve requires pressure to
open.
There are two 1/8 in. ports on each actuator, one is labeled
in and the other is unlabeled. Most valve sizes use a
single actuator, but some larger valves use a twin actuator
assembly.
With the ball valve in the closed position, the actuation
piping is piped to the in port(s); the vent port(s) is left open
to allow air pressure to be relieved as the internal piston is
pushed over by the water pressure.
The actuator has to be manually reset by relieving the
actuation water pressure and with a wrench manually
turning the indicator stub back to the closed position.
If the in label has been removed, with the valve in the
closed position, put a finger over both ports and manually
open the valve with a wrench. The port(s) that is pulling a
suction is the port(s) to pipe the actuation piping to.
Remember the vent port(s) must be left open to atmosphere and not plugged, otherwise the valve will not
open.

AUxILIARY FILLING EQUIPMENT


Page 6

The following equipment is not supplied by Tyco Fire


Protection Products, but is required for Initial Fill and
Major Refill. (See Figures 3 and 4.)
1. A Wet/Dry shop vacuum with a 2 HP (1.5 Kw) motor or
larger.
2. Appropriate pipe fittings and duct tape to connect the
vacuum hose to the 1 inch NPT Tank Shell Vent Valve.
3. Concentrate fill pump* capable of 25 GPM (94.6 Lpm)
maximum output at 15 psi (1.03 bar), pump suction and
discharge hose, a two-position ball valve, and all appropriate fittings for connecting to the 1 inch NPT Bladder
Drain/Fill Valve.
*ANSUL Bladder Tank Fill Pump (includes suction and
clear discharge hose) Part No. 72724, or equal.

NOTICE
Prior to adding foam concentrate to
the tank, its refractive index should be
measured and recorded on the Field
Inspection Record (see FIeld
Inspection Manual), along with a
refractive index vs. concentration
curve. The procedures for these operations are covered in the Field
Inspection Manual (Part No. 31274). It
is also required that the batch
numbers from the concentrate pails
be recorded for future reference.

INITIAL FILL
Page 7

To initially fill a bladder tank:

4. Connect vacuum hose to shop vacuum and start


vacuum. Note the high pitched sound from the vacuum
before opening Tank Shell Vent Valve. This will be the
same pitch heard in Step No. 6.

CAUTION

Because the foam concentrate will undergo thermal


expansion as the temperature increases, it is important,
that at the time of filling, the temperature of the concentrate be as close as possible to the actual ambient
temperature where the tank will be located.
Fill the bladder only to the capacity specified on tank
nameplate. Overfilling may result in bladder damage.

5. Open Tank Shell Vent Valve to pull the air out between
the bladder and tank shell, which will pull the bladder
out to the tank shell wall (see Figure 6).
6. When the change in pitch from the vacuum is heard,
this indicates the bladder is now completely pulled out
to the tank shell wall. First close the Tank Shell Vent
Valve, then turn off the vacuum (see Figure 6).
BLADDER
VENT/FILL VALVE

1. Confirm plastic shipping plugs are removed from all


bladder tank valves.
2. Make certain bladder tank valve handles are in the
following positions (see Figure 5).
Water Inlet Valve . . . . . . . . . . . . . . . . . . . . . . . . .Closed
Tank Shell Drain Valve . . . . . . . . . . . . . . . . . . . . .Closed
Bladder Drain/Fill Valve . . . . . . . . . . . . . . . . . . . . .Open

TANK SHELL
VENT VALVE
CONCENTRATE
ISOLATION
VALVE

Tank Shell Vent Valve . . . . . . . . . . . . . . . . . . . . . .Closed

WATER INLET
VALVE
(MANUAL
OR
AUTOMATED)

Bladder Vent/Fill Valve . . . . . . . . . . . . . . . . . . . . . .Open


Concentrate Isolation Valve . . . . . . . . . . . . . . . . .Closed
If provided:

BLADDER

Sight Gauge Valve . . . . . . . . . . . . . . . . . . . . . .Operating

2 HP

3. Connect vacuum hose to the Tank Shell Vent Valve.


This may be accomplished by using pipe fittings and
securing with duct tape (see Figure 5).

WET/DRY
SHOP
VACUUM

BLADDER VENT/
FILL VALVE

TANK SHELL
DRAIN VALVE

BLADDER
DRAIN/FILL
VALVE

CONNECT
TO HOSE

FIGURE 6
TANK SHELL
VENT VALVE
CONCENTRATE
ISOLATION
VALVE

AIR

AIR

WATER INLET
VALVE
(MANUAL OR
AUTOMATED)

004301

7. Open the concentrate fill pump valve and prime the


pump with concentrate; then close pump valve.
8. Connect concentrate fill pump to the Bladder Drain/Fill
Valve. Only the ANSUL foam concentrate specified
on tank nameplate may be pumped into bladder.

NOTICE
If the type of foam concentrate is not
specified on the tank nameplate, this
information must be supplied by the
customers contracting/engineering
agent.

BLADDER

TANK SHELL
DRAIN VALVE

9. Start concentrate fill pump and open pump valve.


BLADDER DRAIN/
FILL VALVE

FIGURE 5
004299

INITIAL FILL
Page 8

10. Proceed to fill the Bladder Tank with concentrate. At this


point the only valves that should be open are the pump
valve, Bladder Drain/Fill Valve and the Bladder Vent/Fill
Valve, which is venting the air being displaced by foam
concentrate (see Figure 7).

14. If an optional sight gauge is attached, take a reading


and mark the full level on sight gauge tube. Refer to
the Bladder Tanks Measurement Guide (Part No.
71676) for instructions or other options.
NOTICE

CAUTION

If using a dipstick or weighted line to


measure concentrate, take a reading and
mark the full level on the dipstick/line. Do
this after initially filling the tank with the
exact amount of concentrate as specified
on the tank nameplate.

Monitor pumping of concentrate to avoid pumping air


into the tank as this would cause frothing of concentrate within tank.
BLADDER VENT/
FILL VALVE

15. Return bladder tank valve handles to the operating


positions (see Figure 8):
Water Inlet Valve . . . . . . . . . . . . . . . . . . . . . . . . . . .Open
Tank Shell Drain Valve . . . . . . . . . . . . . . . . . . . . .Closed
Bladder Drain/Fill Valve . . . . . . . . . . . . . . . . . . . .Closed
Tank Shell Vent Valve . . . . . . . . . . . . . . . . . . . . . .Closed
Bladder Vent/Fill Valve . . . . . . . . . . . . . . . . . . . . .Closed
Concentrate Isolation
Valve . . . . . . . . . . . . . . . . . . .Normal Operating Position

AIR

CONCENTRATE

If Provided:
Sight Gauge Valve . . . . . . . . . . . . . . . . . . . . .Operating
2 HP
CONCENTRATE
PUMP

BLADDER VENT/
FILL VALVE

WET/DRY
SHOP
VACUUM

BLADDER
DRAIN/
FILL VALVE

TANK SHELL
VENT VALVE
PUMP VALVE

TANK SHELL
DRAIN VALVE

FIGURE 7

CONCENTRATE
ISOLATION
VALVE
WATER INLET
VALVE (MANUAL
OR AUTOMATED)

004311

11. Once the Bladder Tank is filled to the rated capacity


stamped on the tank nameplate, close the Bladder
Drain/Fill Valve, shut off concentrate fill pump and close
Bladder Vent/Fill Valve. For use of partial 55 gallon
(208 L) drums, refer to the Bladder Tank Measurement
Guide (Part No. 71676) to confirm tank is filled to rated
capacity.
12. Disconnect vacuum hose from Tank Shell Vent Valve.
13. Disconnect concentrate fill pump from Bladder Drain/Fill
Valve.

CONCENTRATE

SIGHT
GAUGE TEE
BLADDER
DRAIN/FILL
VALVE

TANK SHELL
DRAIN VALVE

FIGURE 8
004312

16. Insert ring pins through valve handles into brackets and
install visual inspection seals.
17. To give maximum assurance that the system will
operate effectively and safely, a maintenance examination should be performed at this time.
18. Record date of placement in service and instruct
personnel in operation of the system.

MINOR REFILL
Page 9

A MINOR REFILL IS REQUIRED WHEN LESS THAN 25%


OF THE CONCENTRATE MUST BE REPLACED WITHIN
THE BLADDER TANK. Refer to the Bladder Tank
Measurement Guide (Part No. 71676) to determine the
amount of agent required.
BLADDER VENT/
FILL VALVE

TANK SHELL
VENT VALVE

Pour-In Method:

NOTICE
Pour-In Method may only be used in
Minor Refill procedures. Do not
attempt to use the Pour-In Method in
the Initial Fill or Major Refill sections.
4. Insert plastic funnel into Bladder Vent/Fill Valve and
pour in only the ANSUL foam concentrate specified
on tank nameplate until filled.

IMPORTANT

CONCENTRATE
ISOLATION
VALVE
WATER INLET
VALVE (MANUAL
OR AUTOMATED)

If the type of foam concentrate is not


specified on the tank nameplate, this
information must be supplied by the
customers contracting/engineering
agent.
5. After completing Step 4, proceed to Step 11 and
complete the Minor Refill Section.
Pump-In Method:

SIGHT
GAUGE TEE

6. Open the concentrate fill pump valve and prime the


pump with concentrate; then close pump valve.
TANK SHELL
DRAIN VALVE

BLADDER
DRAIN/FILL
VALVE

FIGURE 9
004313

To refill the bladder tank:


1. Close Water Inlet Valve and Concentrate Isolation
Valve.
2. Slowly open Tank Shell Drain Valve and Tank Shell Vent
Valve to drain water from tank shell (see Figure 9).

WARNING

TANK MAY BE UNDER PRESSURE AT THIS TIME.


DO NOT PLACE FACE OR BODY IN FRONT OF
VALVES AS INJURY MAY RESULT.
3. Open Bladder Vent/Fill Valve.

NOTICE
Either the Pour-In Method of filling,
Steps 4 and 5, or Pump-In Method of
filling, Steps 6 through 13, may be
used.

7. Connect the concentrate fill pump and valve to the


Bladder Drain/Fill Valve. Only the ANSUL foam
concentrate specified on tank nameplate may be
pumped into bladder.

IMPORTANT
If the type of foam concentrate is not
specified on the tank nameplate, this
information must be supplied by the
customers contracting/engineering
agent.
8. Start concentrate fill pump, open pump valve, and build
pump pressure.
9. Slowly open the Bladder Drain/Fill Valve and start
pumping the concentrate into bladder until the bladder
is filled with the amount of concentrate stamped on tank
nameplate.
10. Close Bladder Drain/Fill Valve and disconnect concentrate pump.

MAJORREFILL
Page 10

11. Return bladder tank valve handles to the operating


positions (see Figure 8):
Water Inlet Valve . . . . . . . . . . . . . . . . . . . . . . . . . .Open

5. Connect vacuum hose to the Tank Shell Vent Valve.


This may be accomplished by using pipe fittings and
securing with duct tape (see Figure 10).

Tank Shell Drain Valve . . . . . . . . . . . . . . . . . . . .Closed

BLADDER VENT/
FILL VALVE

Bladder Drain/Fill Valve . . . . . . . . . . . . . . . . . . . .Closed


Tank Shell Vent Valve . . . . . . . . . . . . . . . . . . . . .Closed

CONNECT
TO HOSE

Bladder Vent/Fill Valve . . . . . . . . . . . . . . . . . . . .Closed


Concentrate Isolation
Valve . . . . . . . . . . . . . . . . . . .Normal Operating Position
If Provided:
Sight Gauge Valve . . . . . . . . . . . . . . . . . . . . .Operating
12. Insert ring pins through valve handles into brackets and
install visual inspection seals.

TANK SHELL
VENT VALVE
CONCENTRATE
ISOLATION
VALVE

BLADDER

13. Record date of Minor Refill and notify operating personnel that system is back in service.

AIR

AIR

WATER INLET
VALVE
(MANUAL
OR AUTOMATED)

A MAJOR REFILL IS REQUIRED WHEN MORE THAN


25% OF THE CONCENTRATE MUST BE REPLACED
WITHIN THE BLADDER TANK. Refer to the Bladder Tanks
Measurement Guide (Part No. 71676) to determine the
amount of agent required. Refer to the Auxiliary Equipment
Section for a list of necessary equipment.
To refill the bladder tank:
1. Close Water Inlet Valve and Concentrate Isolation
Valve.
2. Slowly open Tank Shell Vent Valve to relieve water
pressure.

WARNING

TANK MAY BE UNDER PRESSURE AT THIS TIME.


DO NOT PLACE FACE OR BODY IN FRONT OF
VALVES AS INJURY MAY RESULT.
3. Open Tank Shell Drain Valve until all water is drained
and all pressure is relieved from tank.
4. When water has been drained from the tank place
bladder tank valve handles in the following position (see
Figure 10).
Water Inlet Valve . . . . . . . . . . . . . . . . . . . . . . . . .Closed
Tank Shell Drain Valve . . . . . . . . . . . . . . . . . . . .Closed
Bladder Drain/Fill Valve . . . . . . . . . . . . . . . . . . . .Closed
Tank Shell Vent Valve . . . . . . . . . . . . . . . . . . . . .Closed
Bladder Vent/Fill Valve . . . . . . . . . . . . . . . . . . . . . .Open
Concentrate Isolation Valve . . . . . . . . . . . . . . . . .Closed
If provided:
Sight Gauge Valve . . . . . . . . . . . . . . . . . . . . .Operating

BLADDER
DRAIN/FILL
VALVE

TANK SHELL
DRAIN VALVE

FIGURE 10
004314

6. Connect vacuum hose to shop vacuum and start


vacuum. Note the high pitched sound from the vacuum
before opening valve. This will be the same pitch heard
in Step No. 8.
7. Open Tank Shell Vent Valve to pull the air out between
bladder and tank shell, which will pull the bladder out to
the tank shell wall (see Figure 11).

MAJOR REFILL
Page 11

8. When the change in pitch from the vacuum is heard this


indicates the bladder is now completely pulled out to the
tank shell wall. First close the Tank Shell Vent Valve,
then turn off the vacuum (see Figure 11).

12. Proceed to fill the Bladder Tank with concentrate. At this


point the only valves that should be open are the pump
valve, Bladder Drain/Fill Valve and the Bladder Vent/Fill
Valve, which is venting the air being displaced by foam
concentrate (see Figure 12).

BLADDER VENT/
FILL VALVE

CAUTION

Monitor pumping of concentrate to avoid pumping air


into the tank as this would cause frothing of concentrate within tank.
TANK SHELL
VENT VALVE
BLADDER VENT/
FILL VALVE
CONCENTRATE
ISOLATION
VALVE

WATER INLET
VALVE
(MANUAL OR
AUTOMATED)
AIR

BLADDER

2 HP

WET/DRY
SHOP
VACUUM

BLADDER
DRAIN/
FILL VALVE

CONCENTRATE

TANK SHELL
DRAIN VALVE

2 HP
CONCENTRATE
PUMP

FIGURE 11
004315

9. Open the concentrate fill pump valve and prime the


pump with concentrate; then close pump valve.
10. Connect concentrate fill pump to the Bladder Drain/Fill
Valve. Only the ANSUL foam concentrate specified
on tank nameplate may be pumped into bladder.

NOTICE
If the type of foam concentrate is not
specified on the tank nameplate, this
information must be supplied by the
customers contracting/engineering
agent.
11. Start concentrate fill pump and open pump valve, then
open Bladder Drain/Fill Valve.

WET/DRY
SHOP
VACUUM

BLADDER
DRAIN/
FILL VALVE

PUMP VALVE

TANK SHELL
DRAIN VALVE

FIGURE 12
004311

13. Once the Bladder Tank is filled to the rated capacity


stamped on the tank nameplate, close the Bladder
Drain/ Fill Valve, shut off concentrate fill pump and close
Bladder Vent/Fill Valve. For use of partial 55 gallon
(208 L) drums, refer to the Bladder Tanks Measurement
Guide (Part No. 71676) to confirm tank is filled to rated
capacity.
14. Disconnect vacuum hose from Tank Shell Vent Valve.
15. Disconnect concentrate fill pump from Bladder Drain/Fill
Valve.

MAJOR REFILL
Page 12

16. Return bladder tank valve handles to the operating


positions (see Figure 13).
Water Inlet Valve . . . . . . . . . . . . . . . . . . . . . . . . . .Open
Tank Shell Drain Valve . . . . . . . . . . . . . . . . . . . .Closed
Bladder Drain/Fill Valve . . . . . . . . . . . . . . . . . . . .Closed
Tank Shell Vent Valve . . . . . . . . . . . . . . . . . . . . . .Closed
Bladder Vent/Fill Valve . . . . . . . . . . . . . . . . . . . . .Closed
Concentrate Isolation
Valve . . . . . . . . . . . . . . . . . .Normal Operating Position
If Provided:
Sight Gauge Valve . . . . . . . . . . . . . . . . . . . . .Operating
BLADDER VENT/
FILL VALVE

TANK SHELL
VENT VALVE
CONCENTRATE
ISOLATION
VALVE
WATER INLET
VALVE (MANUAL
OR AUTOMATED)

CONCENTRATE

SIGHT
GAUGE TEE
BLADDER
DRAIN/FILL
VALVE

TANK SHELL
DRAIN VALVE

FIGURE 13
004312

17. Insert ring pins through valve handles into brackets and
install visual inspection seals.
18. Record date of Major Refill and notify operating personnel that system is back in service.

INSPECTION
Page 13

Inspection should take into consideration the environment, system use, and user inspection policy; but as a
minimum should be conducted semi-annually.
To provide reasonable assurance that the ANSUL
bladder tank is full and operable:
1. Note general appearance of the system and component
parts, checking for mechanical damage or corrosion.
2. Inspect all auxiliary equipment in accordance with the
manufacturers instructions.
3. Check all nameplates for readability.
4. Examine piping and supports for mechanical damage or
corrosion.
5. Check the concentrate fill level by referring to the
Bladder Tank Measurement Guide (Part No. 71676).
6. Make certain bladder tank valve handles are ringpinned and sealed in the operating positions (see
Figure 14):
Water Inlet Valve . . . . . . . . . . . . . . . . . . . . . . . . . .Open
Tank Shell Drain Valve . . . . . . . . . . . . . . . . . . . .Closed
Bladder Drain/Fill Valve . . . . . . . . . . . . . . . . . . . .Closed
Tank Shell Vent Valve . . . . . . . . . . . . . . . . . . . . .Closed
Bladder Vent/Fill Valve . . . . . . . . . . . . . . . . . . . . .Closed
Concentrate Isolation
Valve . . . . . . . . . . . . . . . . . . .Normal Operating Position
If Provided:
Sight Gauge Valve . . . . . . . . . . . . . . . . . . . . .Operating
PROPORTIONER

BLADDER VENT/
FILL VALVE

TO
DISCHARGE
DEVICES

SYSTEM ACTUATION VALVE


(MANUAL OR AUTOMATED)

PRESSURIZED
WATER SOURCE
TANK SHELL
VENT VALVE

SWING
CHECK VALVE

CONCENTRATE
ISOLATION
VALVE

WATER INLET
VALVE (MANUAL
OR AUTOMATED)

CONCENTRATE

SIGHT
GAUGE TEE
BLADDER
DRAIN/FILL
VALVE

TANK SHELL
DRAIN VALVE

FIGURE 14
004312

7. Record date of inspection and any service performed.


8. Notify operating personnel that system is back in
service.

MAINTENANCE
Page 14

To provide maximum assurance that the ANSUL bladder


tank will operate effectively and safely, maintenance
must be performed annually, or sooner when indicated
by an inspection.

d. Open Tank Shell Drain Valve and Tank Shell Vent


Valve until all water is drained from tank.

1. Note general appearance of system and component


parts, checking for mechanical damage or corrosion.

e. With Water Inlet Valve and Concentrate Isolation


Valve closed, turn on water supply to flush remaining
solution from distribution piping, then shut off water
supply.

2. Check nameplates for readability, corrosion, or looseness.

f. Analyze foam solution sample by referring to Field


Inspection Manual (Part No. 31274).

3. Examine all auxiliary equipment in accordance with the


manufacturers instructions.

8. Refer to the Bladder Tanks Measurement Guide (Part


No. 71676) to determine the type of refill required.
Then, refill the tank.

4. Examine piping and supports for mechanical damage or


corrosion.
5. Collect a small sample of foam concentrate from the
bladder tank by completing the following steps:
a. Open Bladder Drain/Fill Valve and discharge a small
quantity of concentrate, approximately 1 pint (0.5 L),
into a clean container; then close.
b. Check the foam concentrate by referring to the Field
Inspection Manual, Part No. 31274.

9. Return bladder tank valve handles to the operating


positions (see Figure 15):
Water Inlet Valve . . . . . . . . . . . . . . . . . . . . . . . . . . .Open
Tank Shell Drain Valve . . . . . . . . . . . . . . . . . . . . .Closed
Bladder Drain/Fill Valve . . . . . . . . . . . . . . . . . . . .Closed
Tank Shell Vent Valve . . . . . . . . . . . . . . . . . . . . . .Closed
Bladder Vent/Fill Valve . . . . . . . . . . . . . . . . . . . . .Closed

6. Make certain bladder tank valve handles are ringpinned in the operating position (see Figure 15):

Concentrate Isolation
Valve . . . . . . . . . . . . . . . . . .Normal Operating Position

Water Inlet Valve . . . . . . . . . . . . . . . . . . . . . . . . . .Open

If Provided:
Sight Gauge Valve . . . . . . . . . . . . . . . . . . . . . .Operating

Tank Shell Drain Valve . . . . . . . . . . . . . . . . . . . .Closed


Bladder Drain/Fill Valve . . . . . . . . . . . . . . . . . . . .Closed
Tank Shell Vent Valve . . . . . . . . . . . . . . . . . . . . .Closed
Bladder Vent/Fill Valve . . . . . . . . . . . . . . . . . . . .Closed
Concentrate Isolation
Valve . . . . . . . . . . . . . . . . . . .Normal Operating Position

10. Insert ring pins through valve handles into brackets and
install visual inspection seals.
11. Record date of annual maintenance examination and
any service performed.
12. Notify operating personnel that system is back in service.
PROPORTIONER

If Provided:
Sight Gauge Valve . . . . . . . . . . . . . . . . . . . . .Operating
7. Collect a foam solution sample by completing the
following steps:
a. Turn on the water supply and allow system to
discharge for two minutes.

BLADDER VENT/
FILL VALVE

TO
DISCHARGE
DEVICES

SYSTEM ACTUATION VALVE


(MANUAL OR AUTOMATED)

PRESSURIZED
WATER SOURCE
TANK SHELL
VENT VALVE

SWING
CHECK VALVE

NOTICE
Make certain solution is properly
disposed of in accordance with
applicable laws, codes and regulations.

CONCENTRATE
ISOLATION
VALVE

WATER INLET
VALVE (MANUAL
OR AUTOMATED)

CONCENTRATE

b. After two minutes, collect 1 quart (1 L) of solution in a


clean container.
c. Close Water Inlet Valve and shut off water source.
SIGHT
GAUGE TEE
BLADDER
DRAIN/FILL
VALVE

TANK SHELL
DRAIN VALVE

FIGURE 15
004312

MAINTENANCE
Page 15

SUGGESTED FOAM SYSTEM TESTING (BLADDER


TANK WITH TEST HEADER)
1. If bladder tanks are not filled, fill per ANSUL Bladder
Tank Manual or authorized ANSUL representatives
instruction.
2. Prepare required refractive index standards, and
generate refractive index curve for testing foam
discharge samples. Refer to Field Inspection Manual.
3. Prior to testing, make sure all valves on bladder tanks
are in the correct position. All 1 in. vent, fill, and drain
valves should be closed. The hydraulic actuated
concentrate valve should be closed (1/8 in. connection
not used should be left open to vent air). The
Concentrate Isolation Valve should be closed. Slowly
open the Water Inlet Valve to pressurize tank.
4. Connect hoses to test header. With only water flowing,
adjust hose valve to establish the desired system test
flow. (Note: Recommended system test flow for closed
head system is typically at the low end listed flow rate
for the size proportioner being tested.) Shut down
system valve without closing the adjusted hose valve,
and reset system valve for test actuation. If using a
containment truck for the foam solution, attach
discharge hoses to truck. A test sample valve (1/4 in.
minimum) is required in the discharge piping somewhere between the proportioner and the containment
truck. Note: Spraying or pretreating the truck tank with
a defoaming agent is recommended to prevent
nuisance foaming in the truck tank during testing.
5. Once the bladder tank has been filled and hose valves
have been adjusted, one zone is selected for foam
discharge. Personnel are required to be stationed at
the test sample valve to take samples of foam
discharge and at the bladder tank to shut off the foam
concentrate once the foam sample is taken.
Communication between these two persons is important to minimize concentrate used.
6. Once everyone is in their positions, trip selected zone.
Thirty to forty-five seconds after foam appears from the
test valve, take a sample of the solution discharge.
Shut Concentrate Isolation Valve as soon as the
samples are taken. Check refractive index against the
standard curve that was made in step #2. If sample is
low, retest. When sample tests OK, shut down test
valve, and change over to other risers that need to be
tested repeating procedure.
7. After system tests are completed, refill bladder tank if
required; and return valves to their normal operating
positions. On the main tank, the hydraulic valves need
to be closed (this has to be done manually). The Water
Inlet Valve and the Concentrate Isolation Valves are to
be in the open position. On the reserve tank, all valves
are to be in the closed position as this is a reserve
supply to put the system back in service quickly after a
discharge.
Note: Containment and disposal of the foam solution is the responsibility of others.

SERVICEANDREPAIR
Page 16

The best assurance against system malfunction is proper operation, recharge, inspection, and maintenance. To
remedy, as quickly as possible, any disorder that may occur, the following table lists some of the probable irregularities that may develop and gives suggestions for corrective action.
To remedy any disorder detected through periodic inspection and maintenance examinations:
Component
__________

Disorder
_______

Corrective Action
________________

Bladder Tanks

Dents* or Abrasions

Hydrostatically test (see ASME plate affixed to tank) and


refinish (clean damaged area and repaint, using a compatible
primer and finish coat), or replace tank.

Paint Peeling

Remove loose paint with a wire brush and repaint using a


compatible primer and finish coat.

Seam Welds Evidencing


Discoloration or Pin Holes

Replace tank or consult Product Services, Tyco Fire


Protection Products, Marinette, Wisconsin 54143-2542.

Rust Spots, Pits, or Corrosion


Deposits

Clean corroded areas with a wire brush, replacing tank if


there is any corrosion penetration; or repaint, using a primer
and finish coat.

Cracking, Flaking, or Aging

See Bladder Integrity Verification Procedure. Replace bladder


or consult Product Services, Tyco Fire Protection Products,
Marinette, Wisconsin 54143-2542.

Torn or Ruptured

See Bladder Integrity Verification Procedure. Replace bladder


or consult Product Services, Tyco Fire Protection Products,
Marinette, Wisconsin 54143-2542.

Unreadable Wording

Use a mild abrasive (scouring powder) to clean plate. If readability cannot be improved, replace nameplate.

Loose

Remove nameplate and inspect area under plate. If corroded,


see section on Bladder Tanks Rust Spots, Pits, or
Corrosion Deposits and take corrective action as surface
condition would indicate, or clean area (repaint, using a
primer and finish coat if necessary) and reaffix plate, using a
good grade of heatless adhesive.

Missing

Replace with correct nameplate. (See applicable parts list.)

Broken or Missing Visual Seal

Replace visual inspection seal.

Bent, Corroded, or Binding Ring


Pin

Replace ring pin.

Cracked, Corroded, or Binding


Chain

Replace chain.

Bent, Broken, or Missing Valve


Handle

Remove, repair, and reassemble; or replace.

Valve Immovable, Stiff,


Inoperable, or Leaking

Disconnect, disassemble and clean. Replace parts as


required.

Little or No Agent Flow

Check concentrate line for obstructions or damage. Replace


if necessary. Check for obstruction in tank valves. Make
certain adequate water and water pressure are available.

Bladder

Nameplate

Valves

*RECORD DENTS FOR REFERENCE IN FUTURE SERVICING, REPLACING TANK IF DENTS ARE DEEP.

SERVICEANDREPAIR
Page 17

BLADDER INTEGRITY VERIFICATION PROCEDURE

1. Isolate the bladder tank from the system by closing


both the Water Inlet and Concentrate Isolation Valves.
Drain water from the tank shell by opening Tank Shell
Drain and Shell Vent Valves.

CAUTION

Tank may be under pressure at this time. Do not


place face or body in front of valves as injury may
result.
2. Transfer remaining foam concentrate in bladder to 55
gallon (208 L) drums or some other container.
3. When tank is completely drained, the valves on the
bladder tank should be in the following positions:
Water Inlet Valve . . . . . . . . . . . . . . . . . . . . . . . . Closed
Concentrate Isolation Valve . . . . . . . . . . . . . . . . Closed
Tank Shell Drain Valve . . . . . . . . . . . . . . . . . . . . Closed
Tank Shell Vent Valve . . . . . . . . . . . . . . . . . . . . Closed
Bladder Vent/Fill Valve . . . . . . . . . . . . . . . . . . . . . Open
Bladder Drain/Fill Valve . . . . . . . . . . . . . . . . . . . . Open
4. Using a Wet/Dry shop vacuum of 2 HP (1.5 Kw)
minimum, attach the vacuum hose to the Tank Shell
Vent Valve. This may be accomplished by using pipe
fitting and securing with duct tape.
5. Connect vacuum hose to shop vacuum and start
vacuum. Note the high pitched sound from the
vacuum before opening the valve. This is the same
sound that should be heard in step #7.
6. Open Tank Shell Vent Valve to pull the air out between
the bladder and the tank shell, which will pull the
bladder out to the tank shell wall.
7. When the change in pitch from the vacuum is heard,
this indicates that bladder is now completely pulled out
to the tank shell wall.
8. If no change in pitch is noted after about 15 minutes,
the bladder is damaged and needs to be replaced.
9. If there is a change in pitch, the bladder is not
damaged. Close the Tank Shell Vent Valve and turn off
the vacuum. The bladder tank can now be refilled as
per the ANSUL Bladder Tanks Filling and Maintenance
Manual (Part No. 74177), using the vacuum method.

BLADDER REMOVAL & REPLACEMENT PROCEDURES

NOTICE
Review all steps before beginning procedure.
1. Remove all water from tank shell by opening both the
Tank Shell Vent Valve and the Tank Shell Drain Valve.
A hose should be connected to the drain valve to direct
the flow of water to an approved disposal area.
2. Remove all foam concentrate from the bladder by
opening the Bladder Vent/Fill Valve and the Bladder
Drain/Fill Valve. A hose should be connected to the
Bladder Drain/Fill Valve to direct the concentrate using
a transfer pump to an approved disposal containment
tank/drums.
3. Remove top and bottom flange from the tank.
4. Slowly remove the vertical center tube out through the
top flange opening. This tube must be removed on all
horizontal tanks. (If the center tube cannot be
completely removed on the vertical tanks, drop the
tube through the lower flange opening and remove
bladder out through the top flange opening sliding the
bladder past the center tube.)
5. Remove end flanges on horizontal tanks and slowly
remove the horizontal center tube so as not to damage
the bladder.
6. Before removing the bladder, attach cords (ropes) to
the flange bolt holes on all ends of the bladder with the
exception of the end where the bladder will be pulled
out. The cords will also be used for installing the new
bladder. After the cords are attached, slowly pull the
bladder out of the end that does not have the cords
attached.
7. Prior to reinstalling the replacement bladder, mark the
bladder flanges to ensure proper alignment once it has
been reinstalled. Re-attach the cords on the flange
ends to help guide them back into place. Use of duct
tape to compress bladder flanges is helpful in reinstalling the bladder.
8. Re-install the bladder and check to ensure that the
bladder is properly aligned. Before re-inserting the
center tubes, close the Tank Shell Drain Valve and
attach a vacuum cleaner hose to the Tank Shell Vent
Valve. With this valve open, start the vacuum. This will
pull the bladder out toward the tank shell wall. Once
the bladder has been sucked out toward the shell wall,
look through the flange end to ensure that the bladder
is not twisted (if twisted make the adjustment to correct
this). Once the bottom flange opening is visible, close
the Tank Shell Vent Valve and then shut vacuum off.

SERVICEANDREPAIR
Page 18

9. Re-insert the center tubes taking care not to damage


the bladder.
10 .

NOTICE
Torque specification below is a
maximum. If during torquing of bolts
bladder flange appears to become
deformed, stop torquing at this point.
Only torque bolts further if a leak is
present while inspecting during tank
pressurization.
Re-install the flanges following the procedure for bolting
instruction per ASME flange torquing procedures. This is
tightening the bolts to 162 ft lb (219.6 Nm) each in 1/5
increments using 0-180, 90-270, 45-225, 135-315 degree
sequence.

Part No. 70343-06

Copyright 2011 Tyco Fire Protection Products. All rights reserved.

TYCO FIRE PROTECTION PRODUCTS


MARINETTE, WI 54143-2542
715-745-7411

004316

VERTICAL AND HORIZONTAL


BLADDER TANKS
Measurement Guide

This measurement guide is intended for estimating the amount of


concentrate contained within ANSUL vertical and horizontal bladder tanks.
Those who install, fill, inspect, or maintain ANSUL bladder tanks
should read and thoroughly understand the contents of this measurement guide as well as the ANSUL Vertical and Horizontal
Bladder Tanks, Filling and Maintenance Manual (Part No. 70343).

TABLE Of CONTENTS

Section
_______

Page(s)
_______

MEASUREMENTPROCEDURES

Introduction
Using The Sight Gauge
Using a Dip Stick/Line
VERTICALBLADDERTANK
MEASUREMENTTABLES
50 Gallon Vertical Bladder Tank
100 Gallon Vertical Bladder Tank
150 Gallon Vertical Bladder Tank
200 Gallon Vertical Bladder Tank
300 Gallon Vertical Bladder Tank

12

1
1
2
3 24
4
4
5
6
7

400 Gallon Vertical Bladder Tank 42 in. Dia.


400 Gallon Vertical Bladder Tank 48 in. Dia.
500 Gallon Vertical Bladder Tank 42 in. Dia.
500 Gallon Vertical Bladder Tank 48 in . Dia.
600 Gallon Vertical Bladder Tank

8
9
10
11
12

700 Gallon Vertical Bladder Tank


800 Gallon Vertical Bladder Tank 48 in. Dia.
800 Gallon Vertical Bladder Tank 54 in. Dia.
900 Gallon Vertical Bladder Tank 48 in. Dia.
900 Gallon Vertical Bladder Tank 54 in. Dia.

13
14
15
16
17

1000 Gallon Vertical Bladder Tank 48 in. Dia.


1000 Gallon Vertical Bladder Tank 54 in. Dia.
1100 Gallon Vertical Bladder Tank
1200 Gallon Vertical Bladder Tank
1300 Gallon Vertical Bladder Tank

18
19
20
21
22

1400 Gallon Vertical Bladder Tank


1500 Gallon Vertical Bladder Tank

23
24

HORIZONTAL BLADDER TANK


MEASUREMENT TABLES

25 41

100 Gallon Horizontal Bladder Tank


150 Gallon Horizontal Bladder Tank
200 Gallon Horizontal Bladder Tank
300 Gallon Horizontal Bladder Tank
400 Gallon Horizontal Bladder Tank 42 in. Dia.

26
26
27
27
28

400 Gallon Horizontal Bladder Tank 48 in. Dia.


500 Gallon Horizontal Bladder Tank 42 in. Dia.
500 Gallon Horizontal Bladder Tank 48 in. Dia.
600 Gallon Horizontal Bladder Tank
700 Gallon Horizontal Bladder Tank

28
29
29
30
30

800 Gallon Horizontal Bladder Tank 48 in. Dia.


800 Gallon Horizontal Bladder Tank 54 in. Dia.
900 Gallon Horizontal Bladder Tank 48 in. Dia.
900 Gallon Horizontal Bladder Tank 54 in. Dia.
1000 Gallon Horizontal Bladder Tank 48 in. Dia.

31
31
32
32
33

1000 Gallon Horizontal Bladder Tank 54 in . Dia.


1100 Gallon Horizontal Bladder Tank
1200 Gallon Horizontal Bladder Tank
1300 Gallon Horizontal Bladder Tank
1400 Gallon Horizontal Bladder Tank

33
34
34
35
35

1500 Gallon Horizontal Bladder Tank


1600 Gallon Horizontal Bladder Tank
1700 Gallon Horizontal Bladder Tank

36
36
37

Section
_______

Page(s)
_______

HORIZONTAL BLADDER TANK


MEASUREMENT TABLES (Continued)
1800 Gallon Horizontal Bladder Tank
1900 Gallon Horizontal Bladder Tank
2000 Gallon Horizontal Bladder Tank
2200 Gallon Horizontal Bladder Tank
2400 Gallon Horizontal Bladder Tank

37
38
38
39
39

2600 Gallon Horizontal Bladder Tank


2800 Gallon Horizontal Bladder Tank
3000 Gallon Horizontal Bladder Tank

40
40
41

MEASUREMENT PROCEDURES
Page 1

Introduction
Depending on the equipment provided, two methods are acceptable for estimating the foam concentrate contained within the
bladder: (1) Using The Sight Gauge or (2) Using A Dip Stick/Line.
Both methods can be used for either vertical or horizontal tanks.
Neither of the methods is exact, but both will provide a close estimate of the bladder contents.
The measurement tables listed in this guide provide an estimate
of the amount of concentrate remaining in the tank after operation.
The approximate quantity of gallons (liters) required to refill the
bladder can be determined by subtracting the table reading
(Concentrate In Tank) from the capacity specified on the tank
nameplate:

Tank Capacity
(gallons (L))

Concentrate
In Tank
(gallons (L))

Concentrate
Required
To Refill
(gallons (L))

4. Measure and record the concentrate depth in the sight gauge


tube. The measurement must be taken from the tube connector at top of the valve body to the concentrate level in the sight
gauge tube as shown in Figure 1.

NOTICE
It is also a good idea to mark the full
level on the sight gauge tube. Do this
after initially filling the tank with the
exact amount of concentrate as specified on the tank nameplate. The full
level can then be verified following
tank refills or during inspection and
maintenance procedures.

The percentage of concentrate to be replaced can be determined


by dividing the number of gallons (L) required to refill the tank by
the rated capacity specified on the tank nameplate. If the percentage of concentrate to be replaced is more than 25%, a major refill
is required. Otherwise the instructions for a minor refill may be followed (refer to Bladder Tanks Filling and Maintenance Manual,
Part No. 70343).
Concentrate
Required
To Refill
(gallons (L))

Tank Capacity
X 100
(gallons (L))

Percentage (%)
of Concentrate
to be Replaced

DANGER

MEASURE
CONCENTRATE
DEPTH

Drain all water and relieve all pressure from tank before
operating any valves or the sight gauge. Do not put your
face in front of valve outlets or near sight gauge tube while
operating. Failure to comply will result in personal injury or
sight gauge damage due to the unrestricted release of
water or concentrate through the valve outlet or into the
sight gauge.

GAUGE USE

OPERATING

Using The Sight Gauge


The following procedures are provided for those tanks that have a
sight gauge installed. If a sight gauge is not provided, refer to the
Using A Dip Stick/Line section.
1. Close Water Inlet Valve.
2. Open Tank Shell Drain Valve and Tank Shell Vent Valve until
all water is drained and all pressure is relieved from tank.

NOTICE
To obtain an accurate reading, all
water must be drained and all pressure must be relieved from tank.
3. Pull ring pin and turn sight gauge valve handle to READ position. Allow concentrate to enter and come to a stable level in
sight gauge tube.

fIGURE 1
004317

5. Return sight gauge valve to the OPERATING position, insert


ring pin, and install visual inspection seal. The concentrate will
automatically drain from the sight gauge tube at this time.
6. Using the measurement recorded in Step No. 4, refer to the
corresponding measurement table to determine the approximate gallons (L) contained within the bladder. The Table of
Contents lists the measurement table page numbers according to tank size and type.
7. If bladder tank capacity is below system requirement, tank
must be refilled. Refer to Minor or Major refill procedure in the
Bladder Tanks Filling and Maintenance Manual (Part No.
70343).
8. Close Tank Shell Drain Valve and slowly open Water Inlet
Valve to vent air between bladder and tank shell.
9. Close Tank Shell Vent Valve.

MEASUREMENT PROCEDURES
Page 2

Using A Dip Stick/Line


To perform these procedures, the user must supply either a wooden rod or weighted line.
A wooden rod is recommended where tank size and space considerations make it practical. The rod must be no larger than 1/2
in. (12 mm) in diameter and must be long enough to reach from
the top of the Bladder Vent/Fill Valve to the bottom of the tank.
Marking 1 inch (25 mm) increments on the rod will simplify the
measurement process.
Where tank size and the free space above the tank do not allow
for use of a wooden rod, a weighted line can be used. The line
must be long enough to reach from the top of the Bladder Vent/Fill
Valve to the bottom of the tank. The weight must not be larger than
1/2 in. (12 mm) in diameter.

NOTICE
It is also a good idea to mark the full
level on the dip stick/line. Do this after
initially filling the tank with the exact
amount of concentrate as specified on
the tank nameplate. The full level can
then be verified following tank refills or
during inspection and maintenance
procedures.

BLADDER VENT/
FILL VALVE

1. Close Water Inlet Valve.


2. Open Tank Shell Drain Valve and Tank Shell Vent Valve until
all water is drained and all pressure is vented from tank.

DIP
STICK/LINE

TANK SHELL
VENT VALVE

NOTICE
To obtain an accurate reading, all
water must be drained and all pressure must be relieved from tank.
3. Open the Bladder Vent/Fill Valve and lower the dip stick/line
through the valve until it reaches the bottom of the tank.
(When using a dip line, it will begin to slacken when the weight
has reached the bottom of the tank.)

MEASURE
CONCENTRATE
DEPTH

4. Remove the dip stick/line from the tank. Measure and record
the length of the dampened portion of the dip stick/line. This
measurement is the depth of the concentrate in the bladder as
shown in Figures 2 and 3.

TANK SHELL
DRAIN VALVE

fIGURE 3
004319

5. Close Bladder Vent/Fill Valve.

BLADDER VENT/
FILL VALVE
DIP
STICK/LINE

6. Using the measurement recorded in Step No. 4, refer to the


corresponding measurement table to determine the approximate gallons (L) contained within the bladder. The Table of
Contents lists the measurement table page numbers according to tank size and type.

TANK SHELL
VENT VALVE

7. If bladder tank capacity is below system requirement, tank


must be refilled. Refer to Minor or Major refill procedure in the
Bladder Tanks Filling and Maintenance Manual (Part No.
70343).
8. Close Tank Shell Drain Valve and slowly open Water Inlet
Valve to vent air between bladder and tank shell.
MEASURE
CONCENTRATE
DEPTH

9. Close Tank Shell Vent Valve.

TANK SHELL
DRAIN VALVE

fIGURE 2
004318

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 3

VERTICALBLADDERTANKMEASUREMENTTABLES

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 4

50 GALLONVERTICALBLADDERTANK

100 GALLONVERTICALBLADDERTANK

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)

Concentrate in Tank
gal.
(L)
___
___
0
(0)
1
(2)
2
(6)
3
(11)
5
(17)
6
(24)
8
(31)
10
(38)
12
(45)
14
(53)
16
(60)
18
(67)
20
(74)
21
(81)
23
(88)
25
(95)
27
(102)
29
(109)
31
(116)
33
(124)
35
(131)
36
(138)
38
(145)
40
(152)
42
(159)
44
(166)
46
(173)
48
(180)
50
(189)

Concentrate in Tank
gal.
(L)
___
___
0
(0)
1
(2)
2
(6)
3
(11)
5
(17)
6
(24)
8
(31)
10
(38)
12
(45)
14
(53)
16
(60)
18
(67)
20
(74)
21
(81)
23
(88)
25
(95)
27
(102)
29
(109)
31
(116)
33
(124)
35
(131)
36
(138)
38
(145)
40
(152)
42
(159)
44
(166)
46
(173)
48
(180)
50
(188)
51
(195)
53
(202)
55
(209)
57
(216)
59
(223)
61
(230)
63
(237)
65
(244)
66
(251)
68
(259)
70
(266)
72
(273)
74
(280)
76
(287)
78
(294)
80
(301)
81
(308)
83
(315)
85
(323)
87
(330)
89
(337)
91
(344)
93
(351)
95
(358)
96
(365)
98
(372)
100
(379)

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 5

150 GALLONVERTICALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)

Concentrate in Tank
gal.
(L)
___
___
0
(1)
1
(5)
3
(12)
5
(20)
8
(29)
10
(40)
13
(51)
16
(62)
19
(73)
22
(84)
25
(95)
28
(106)
31
(117)
34
(128)
37
(140)
40
(151)
43
(162)
46
(173)
49
(184)
52
(195)
55
(206)
57
(217)
60
(229)
63
(240)
66
(251)
69
(262)
72
(273)
75
(284)
78
(295)
81
(306)
84
(318)
87
(329)
90
(340)
93
(351)
96
(362)
99
(373)
102
(384)
104
(395)
107
(407)
110
(418)
113
(429)
116
(440)
119
(451)
122
(462)
125
(473)
128
(484)
131
(496)
134
(507)
137
(518)
140
(529)
143
(540)
146
(551)
149
(562)

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 6

200 GALLONVERTICALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)

Concentrate in Tank
gal.
(L)
___
___
0
(1)
1
(5)
3
(12)
5
(20)
8
(29)
10
(40)
13
(51)
16
(62)
19
(73)
22
(84)
25
(95)
28
(106)
31
(117)
34
(128)
37
(140)
40
(151)
43
(162)
46
(173)
49
(184)
52
(195)
55
(206)
57
(217)
60
(229)
63
(240)
66
(251)
69
(262)
72
(273)
75
(284)
78
(295)
81
(306)
84
(318)
87
(329)
90
(340)
93
(351)
96
(362)
99
(373)
102
(384)
104
(395)
107
(407)
110
(418)
113
(429)
116
(440)
119
(451)
122
(462)
125
(473)
128
(484)
131
(496)
134
(507)

Depth of Concentrate
in.
(cm)
__
____
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)
63
(160.0)
64
(162.6)
65
(165.1)
66
(167.6)
67
(170.2)
68
(172.7)
69
(175.3)
70
(177.8)
71
(180.3)
72
(182.9)

Concentrate in Tank
gal.
(L)
___
___
137
(518)
140
(529)
143
(540)
146
(551)
149
(562)
151
(573)
154
(585)
157
(596)
160
(607)
163
(618)
166
(629)
169
(640)
172
(651)
175
(662)
178
(674)
181
(685)
184
(696)
187
(707)
190
(718)
193
(729)
196
(740)
199
(751)

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 7

300 GALLONVERTICALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)

Concentrate in Tank
gal.
(L)
___
___
0
(2)
2
(6)
4
(14)
6
(24)
10
(37)
13
(50)
17
(65)
21
(81)
26
(97)
30
(113)
34
(129)
38
(145)
43
(161)
47
(177)
51
(193)
55
(209)
60
(226)
64
(242)
68
(258)
72
(274)
77
(290)
81
(306)
85
(322)
89
(338)
93
(354)
98
(370)
102
(386)
106
(402)
110
(418)
115
(434)
119
(450)
123
(466)
127
(482)
132
(498)
136
(514)
140
(530)
144
(546)
149
(562)
153
(578)
157
(594)
161
(610)
166
(626)
170
(642)
174
(659)
178
(675)
182
(691)
187
(707)
191
(723)

Depth of Concentrate
in.
(cm)
__
____
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)
63
(160.0)
64
(162.6)
65
(165.1)
66
(167.6)
67
(170.2)
68
(172.7)
69
(175.3)
70
(177.8)
71
(180.3)
72
(182.9)
73
(185.4)
74
(188.0)
75
(190.5)

Concentrate
gal.
___
195
199
204
208
212
216
221
225
229
233
238
242
246
250
254
259
263
267
271
276
280
284
288
293
297

in Tank
(L)
___
(739)
(755)
(771)
(787)
(803)
(819)
(835)
(851)
(867)
(883)
(899)
(915)
(931)
(947)
(963)
(979)
(995)
(1011)
(1027)
(1043)
(1059)
(1075)
(1091)
(1108)
(1124)

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 8

42 INCH DIAMETER*
400 GALLONVERTICALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
*Not available after 1996.

Concentrate in Tank
gal.
(L)
___
___
0
(2)
2
(8)
4
(17)
8
(29)
12
(44)
16
(61)
21
(80)
27
(101)
32
(122)
38
(144)
44
(166)
50
(188)
55
(210)
61
(232)
67
(254)
73
(276)
79
(298)
84
(320)
90
(342)
96
(364)
102
(386)
108
(407)
113
(429)
119
(451)
125
(473)
131
(495)
137
(517)
142
(539)
148
(561)
154
(583)
160
(605)
166
(627)
171
(649)
177
(671)
183
(693)
189
(715)
195
(737)
200
(759)
206
(781)
212
(803)
218
(825)
224
(846)
229
(868)
235
(890)
241
(912)
247
(934)
253
(956)
258
(978)

Depth of Concentrate
in.
(cm)
__
____
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)
63
(160.0)
64
(162.6)
65
(165.1)
66
(167.6)
67
(170.2)
68
(172.7)
69
(175.3)
70
(177.8)
71
(180.3)
72
(182.9)
73
(185.4)
74
(188.0)

Concentrate in Tank
gal.
(L)
___
___
264
(1000)
270
(1022)
276
(1044)
282
(1066)
287
(1088)
293
(1110)
299
(1132)
305
(1154)
311
(1176)
316
(1198)
322
(1220)
328
(1242)
334
(1264)
340
(1285)
345
(1307)
351
(1329)
357
(1351)
363
(1373)
369
(1395)
374
(1417)
380
(1439)
386
(1461)
392
(1483)
398
(1505)

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 9

48 INCH DIAMETER
400 GALLONVERTICALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)

Concentrate
gal.
___
0
2
5
9
13
19
25
31
38
45
53
60
68
75
83
91
98
106
113
121
128
136
143
151
158
166
173
181
189
196
204
211
219
226
234
241
249
256
264
272
279
287
294
302
309
317
324
332

in Tank
(L)
___
(2)
(8)
(19)
(33)
(50)
(70)
(93)
(118)
(144)
(171)
(200)
(228)
(257)
(286)
(314)
(343)
(371)
(400)
(428)
(457)
(485)
(514)
(542)
(571)
(600)
(628)
(657)
(685)
(714)
(742)
(771)
(799)
(828)
(857)
(885)
(914)
(942)
(971)
(999)
(1028)
(1056)
(1085)
(1113)
(1142)
(1171)
(1199)
(1228)
(1256)

Depth of Concentrate
in.
(cm)
__
____
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)

Concentrate
gal.
___
339
347
355
362
370
377
385
392
398

in Tank
(L)
___
(1285)
(1313)
(1342)
(1370)
(1399)
(1427)
(1456)
(1485)
(1505)

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 10

42 INCH DIAMETER*
500 GALLONVERTICALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
*Not available after 1996.

Concentrate in Tank
gal.
(L)
___
___
0
(2)
2
(8)
4
(17)
8
(29)
12
(44)
16
(61)
21
(80)
27
(101)
32
(122)
38
(144)
44
(166)
50
(188)
55
(210)
61
(232)
67
(254)
73
(276)
79
(298)
84
(320)
90
(342)
96
(364)
102
(386)
108
(407)
113
(429)
119
(451)
125
(473)
131
(495)
137
(517)
142
(539)
148
(561)
154
(583)
160
(605)
166
(627)
171
(649)
177
(671)
183
(693)
189
(715)
195
(737)
200
(759)
206
(781)
212
(803)
218
(825)
224
(846)
229
(868)
235
(890)
241
(912)
247
(934)
253
(956)
258
(978)

Depth of Concentrate
in.
(cm)
__
____
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)
63
(160.0)
64
(162.6)
65
(165.1)
66
(167.6)
67
(170.2)
68
(172.7)
69
(175.3)
70
(177.8)
71
(180.3)
72
(182.9)
73
(185.4)
74
(188.0)
75
(190.5)
76
(193.0)
77
(195.6)
78
(198.1)
79
(200.7)
80
(203.2)
81
(205.7)
82
(208.3)
83
(210.8)
84
(213.4)
85
(215.9)
86
(218.4)
87
(221.0)
88
(223.5)
89
(226.1)
90
(228.6)
91
(231.1)

Concentrate
gal.
___
264
270
276
282
287
293
299
305
311
316
322
328
334
340
345
351
357
363
369
374
380
386
392
398
403
409
415
421
427
432
438
444
450
456
461
467
473
479
485
490
496

in Tank
(L)
___
(1000)
(1022)
(1044)
(1066)
(1088)
(1110)
(1132)
(1154)
(1176)
(1198)
(1220)
(1242)
(1264)
(1285)
(1307)
(1329)
(1351)
(1373)
(1395)
(1417)
(1439)
(1461)
(1483)
(1505)
(1527)
(1549)
(1571)
(1593)
(1615)
(1637)
(1659)
(1681)
(1703)
(1724)
(1746)
(1768)
(1790)
(1812)
(1834)
(1856)
(1878)

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 11

48 INCH DIAMETER
500 GALLONVERTICALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)

Concentrate
gal.
___
0
2
5
9
13
19
25
31
38
45
53
60
68
75
83
91
98
106
113
121
128
136
143
151
158
166
173
181
189
196
204
211
219
226
234
241
249
256
264
272
279
287
294
302
309
317
324
332

in Tank
(L)
___
(2)
(8)
(19)
(33)
(50)
(70)
(93)
(118)
(144)
(171)
(200)
(228)
(257)
(286)
(314)
(343)
(371)
(400)
(428)
(457)
(485)
(514)
(542)
(571)
(600)
(628)
(657)
(685)
(714)
(742)
(771)
(799)
(828)
(857)
(885)
(914)
(942)
(971)
(999)
(1028)
(1056)
(1085)
(1113)
(1142)
(1171)
(1199)
(1228)
(1256)

Depth of Concentrate
in.
(cm)
__
____
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)
63
(160.0)
64
(162.6)
65
(165.1)
66
(167.6)
67
(170.2)
68
(172.7)
69
(175.3)
70
(177.8)
71
(180.3)
72
(182.9)

Concentrate
gal.
___
339
347
355
362
370
377
385
392
400
407
415
422
430
437
445
453
460
468
475
483
490
496

in Tank
(L)
___
(1285)
(1313)
(1342)
(1370)
(1399)
(1427)
(1456)
(1485)
(1513)
(1542)
(1570)
(1599)
(1627)
(1656)
(1684)
(1713)
(1742)
(1770)
(1799)
(1827)
(1856)
(1878)

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 12

600 GALLONVERTICALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)

Concentrate
gal.
___
0
2
5
9
13
19
25
31
38
45
53
60
68
75
83
91
98
106
113
121
128
136
143
151
158
166
173
181
189
196
204
211
219
226
234
241
249
256
264
272
279
287
294
302
309
317
324
332

in Tank
(L)
___
(2)
(8)
(19)
(33)
(50)
(70)
(93)
(118)
(144)
(171)
(200)
(228)
(257)
(286)
(314)
(343)
(371)
(400)
(428)
(457)
(485)
(514)
(542)
(571)
(600)
(628)
(657)
(685)
(714)
(742)
(771)
(799)
(828)
(857)
(885)
(914)
(942)
(971)
(999)
(1028)
(1056)
(1085)
(1113)
(1142)
(1171)
(1199)
(1228)
(1256)

Depth of Concentrate
in.
(cm)
__
____
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)
63
(160.0)
64
(162.6)
65
(165.1)
66
(167.6)
67
(170.2)
68
(172.7)
69
(175.3)
70
(177.8)
71
(180.3)
72
(182.9)
73
(185.4)
74
(188.0)
75
(190.5)
76
(193.0)
77
(195.6)
78
(198.1)
79
(200.7)
80
(203.2)
81
(205.7)
82
(208.3)
83
(210.8)
84
(213.4)
85
(215.9)

Concentrate
gal.
___
339
347
355
362
370
377
385
392
400
407
415
422
430
437
445
453
460
468
475
483
490
498
505
513
520
528
536
543
551
558
566
573
581
588
594

in Tank
(L)
___
(1285)
(1313)
(1342)
(1370)
(1399)
(1427)
(1456)
(1485)
(1513)
(1542)
(1570)
(1599)
(1627)
(1656)
(1684)
(1713)
(1742)
(1770)
(1799)
(1827)
(1856)
(1884)
(1913)
(1941)
(1970)
(1998)
(2027)
(2056)
(2084)
(2113)
(2141)
(2170)
(2198)
(2225)
(2250)

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 13

700 GALLONVERTICALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)

Concentrate
gal.
___
0
2
5
9
13
19
25
31
38
45
53
60
68
75
83
91
98
106
113
121
128
136
143
151
158
166
173
181
189
196
204
211
219
226
234
241
249
256
264
272
279
287
294
302
309
317
324
332

in Tank
(L)
___
(2)
(8)
(19)
(33)
(50)
(70)
(93)
(118)
(144)
(171)
(200)
(228)
(257)
(286)
(314)
(343)
(371)
(400)
(428)
(457)
(485)
(514)
(542)
(571)
(600)
(628)
(657)
(685)
(714)
(742)
(771)
(799)
(828)
(857)
(885)
(914)
(942)
(971)
(999)
(1028)
(1056)
(1085)
(1113)
(1142)
(1171)
(1199)
(1228)
(1256)

Depth of Concentrate
in.
(cm)
__
____
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)
63
(160.0)
64
(162.6)
65
(165.1)
66
(167.6)
67
(170.2)
68
(172.7)
69
(175.3)
70
(177.8)
71
(180.3)
72
(182.9)
73
(185.4)
74
(188.0)
75
(190.5)
76
(193.0)
77
(195.6)
78
(198.1)
79
(200.7)
80
(203.2)
81
(205.7)
82
(208.3)
83
(210.8)
84
(213.4)
85
(215.9)
86
(218.4)
87
(221.0)
88
(223.5)
89
(226.1)
90
(228.6)
91
(231.1)
92
(233.7)
93
(236.2)
94
(238.8)
95
(241.3)
96
(243.8)
97
(246.4)
98
(248.9)
99
(251.5)

Concentrate
gal.
___
339
347
355
362
370
377
385
392
400
407
415
422
430
437
445
453
460
468
475
483
490
498
505
513
520
528
536
543
551
558
566
573
581
588
596
603
611
619
626
634
641
649
656
664
671
679
686
693
700

in Tank
(L)
___
(1285)
(1313)
(1342)
(1370)
(1399)
(1427)
(1456)
(1485)
(1513)
(1542)
(1570)
(1599)
(1627)
(1656)
(1684)
(1713)
(1742)
(1770)
(1799)
(1827)
(1856)
(1884)
(1913)
(1941)
(1970)
(1998)
(2027)
(2056)
(2084)
(2113)
(2141)
(2170)
(2198)
(2227)
(2255)
(2284)
(2312)
(2341)
(2370)
(2398)
(2427)
(2455)
(2484)
(2512)
(2541)
(2569)
(2597)
(2624)
(2650)

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 14

48 INCHDIAMETER
800 GALLONVERTICALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)

Concentrate in Tank
gal.
(L)
___
___
0
(2)
2
(8)
5
(19)
9
(33)
13
(50)
19
(70)
25
(93)
31
(118)
38
(144)
45
(171)
53
(200)
60
(228)
68
(257)
75
(286)
83
(314)
91
(343)
98
(371)
106
(400)
113
(428)
121
(457)
128
(485)
136
(514)
143
(542)
151
(571)
158
(600)
166
(628)
173
(657)
181
(685)
189
(714)
196
(742)
204
(771)
211
(799)
219
(828)
226
(857)
234
(885)
241
(914)
249
(942)
256
(971)
264
(999)
272
(1028)
279
(1056)
287
(1085)
294
(1113)
302
(1142)
309
(1171)
317
(1199)
324
(1228)
332
(1256)
339
(1285)
347
(1313)
355
(1342)
362
(1370)
370
(1399)
377
(1427)
385
(1456)

Depth of Concentrate
in.
(cm)
__
____
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)
63
(160.0)
64
(162.6)
65
(165.1)
66
(167.6)
67
(170.2)
68
(172.7)
69
(175.3)
70
(177.8)
71
(180.3)
72
(182.9)
73
(185.4)
74
(188.0)
75
(190.5)
76
(193.0)
77
(195.6)
78
(198.1)
79
(200.7)
80
(203.2)
81
(205.7)
82
(208.3)
83
(210.8)
84
(213.4)
85
(215.9)
86
(218.4)
87
(221.0)
88
(223.5)
89
(226.1)
90
(228.6)
91
(231.1)
92
(233.7)
93
(236.2)
94
(238.8)
95
(241.3)
96
(243.8)
97
(246.4)
98
(248.9)
99
(251.5)
100
(254.0)
101
(256.5)
102
(259.1)
103
(261.6)
104
(264.2)
105
(266.7)
106
(269.2)
107
(271.8)
108
(274.3)
109
(276.9)
110
(279.4)
111
(281.9)
112
(284.5)

Concentrate
gal.
___
392
400
407
415
422
430
437
445
453
460
468
475
483
490
498
505
513
520
528
536
543
551
558
566
573
581
588
596
603
611
619
626
634
641
649
656
664
671
679
686
694
702
709
717
724
732
739
747
754
762
769
777
785
792
799

in Tank
(L)
___
(1485)
(1513)
(1542)
(1570)
(1599)
(1627)
(1656)
(1684)
(1713)
(1742)
(1770)
(1799)
(1827)
(1856)
(1884)
(1913)
(1941)
(1970)
(1998)
(2027)
(2056)
(2084)
(2113)
(2141)
(2170)
(2198)
(2227)
(2255)
(2284)
(2312)
(2341)
(2370)
(2398)
(2427)
(2455)
(2484)
(2512)
(2541)
(2569)
(2597)
(2627)
(2657)
(2684)
(2714)
(2741)
(2771)
(2797)
(2828)
(2854)
(2884)
(2911)
(2941)
(2972)
(2998)
(3025)

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 15

54 INCHDIAMETER*
800 GALLONVERTICALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
*Not available after 1996.

Concentrate
gal.
___
0
1
3
7
11
17
23
30
38
47
56
65
74
84
94
103
113
122
132
141
151
161
170
180
189
199
209
218
228
237
247
256
266
276
285
295
304
314
324
333
343
352
362
372
381
391
400
410
419

in Tank
(L)
___
(0)
(3)
(12)
(25)
(42)
(63)
(87)
(115)
(145)
(177)
(210)
(245)
(281)
(318)
(354)
(390)
(426)
(463)
(499)
(535)
(572)
(608)
(644)
(680)
(717)
(753)
(789)
(826)
(862)
(898)
(934)
(971)
(1007)
(1043)
(1080)
(1116)
(1152)
(1188)
(1225)
(1261)
(1297)
(1334)
(1370)
(1406)
(1442)
(1479)
(1515)
(1551)
(1588)

Depth of Concentrate
in.
(cm)
__
____
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)
63
(160.0)
64
(162.6)
65
(165.1)
66
(167.6)
67
(170.2)
68
(172.7)
69
(175.3)
70
(177.8)
71
(180.3)
72
(182.9)
73
(185.4)
74
(188.0)
75
(190.5)
76
(193.0)
77
(195.6)
78
(198.1)
79
(200.7)
80
(203.2)
81
(205.7)
82
(208.3)
83
(210.8)
84
(213.4)
85
(215.9)
86
(218.4)
87
(221.0)
88
(223.5)
89
(226.1)

Concentrate
gal.
___
429
439
448
458
467
477
487
496
506
515
525
534
544
554
563
573
582
592
602
611
621
630
640
650
659
669
678
688
697
707
717
726
736
745
755
765
774
783
792

in Tank
(L)
___
(1624)
(1660)
(1696)
(1733)
(1769)
(1805)
(1842)
(1878)
(1914)
(1950)
(1987)
(2023)
(2059)
(2096)
(2132)
(2168)
(2204)
(2241)
(2277)
(2313)
(2350)
(2386)
(2422)
(2458)
(2495)
(2531)
(2567)
(2604)
(2640)
(2676)
(2712)
(2749)
(2785)
(2821)
(2858)
(2894)
(2930)
(2965)
(2999)

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 16

48 INCHDIAMETER
900 GALLONVERTICALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)
63
(160.0)
64
(162.6)

Concentrate
gal.
___
0
2
5
9
13
19
25
31
38
45
53
60
68
75
83
91
98
106
113
121
128
136
143
151
158
166
173
181
189
196
204
211
219
226
234
241
249
256
264
272
279
287
294
302
309
317
324
332
339
347
355
362
370
377
385
392
400
407
415
422
430
437

in Tank
(L)
___
(2)
(8)
(19)
(33)
(50)
(70)
(93)
(118)
(144)
(171)
(200)
(228)
(257)
(286)
(314)
(343)
(371)
(400)
(428)
(457)
(485)
(514)
(542)
(571)
(600)
(628)
(657)
(685)
(714)
(742)
(771)
(799)
(828)
(857)
(885)
(914)
(942)
(971)
(999)
(1028)
(1056)
(1085)
(1113)
(1142)
(1171)
(1199)
(1228)
(1256)
(1285)
(1313)
(1342)
(1370)
(1399)
(1427)
(1456)
(1485)
(1513)
(1542)
(1570)
(1599)
(1627)
(1656)

Depth of Concentrate
in.
(cm)
__
____
65
(165.1)
66
(167.6)
67
(170.2)
68
(172.7)
69
(175.3)
70
(177.8)
71
(180.3)
72
(182.9)
73
(185.4)
74
(188.0)
75
(190.5)
76
(193.0)
77
(195.6)
78
(198.1)
79
(200.7)
80
(203.2)
81
(205.7)
82
(208.3)
83
(210.8)
84
(213.4)
85
(215.9)
86
(218.4)
87
(221.0)
88
(223.5)
89
(226.1)
90
(228.6)
91
(231.1)
92
(233.7)
93
(236.2)
94
(238.8)
95
(241.3)
96
(243.8)
97
(246.4)
98
(248.9)
99
(251.5)
100
(254.0)
101
(256.5)
102
(259.1)
103
(261.6)
104
(264.2)
105
(266.7)
106
(269.2)
107
(271.8)
108
(274.3)
109
(276.9)
110
(279.4)
111
(281.9)
112
(284.5)
113
(287.0)
114
(289.6)
115
(292.1)
116
(294.6)
117
(297.2)
118
(299.7)
119
(302.3)
120
(304.8)
121
(307.3)
122
(309.9)
123
(312.4)
124
(315.0)
125
(317.5)

Concentrate
gal.
___
445
453
460
468
475
483
490
498
505
513
520
528
536
543
551
558
566
573
581
588
596
603
611
619
626
634
641
649
656
664
671
679
686
694
702
709
717
724
732
739
747
754
762
769
777
785
792
800
807
815
822
830
837
845
852
860
868
875
883
890
897

in Tank
(L)
___
(1684)
(1713)
(1742)
(1770)
(1799)
(1827)
(1856)
(1884)
(1913)
(1941)
(1970)
(1998)
(2027)
(2056)
(2084)
(2113)
(2141)
(2170)
(2198)
(2227)
(2255)
(2284)
(2312)
(2341)
(2370)
(2398)
(2427)
(2455)
(2484)
(2512)
(2541)
(2569)
(2597)
(2627)
(2657)
(2684)
(2714)
(2741)
(2771)
(2797)
(2828)
(2854)
(2884)
(2911)
(2941)
(2972)
(2998)
(3028)
(3055)
(3085)
(3112)
(3142)
(3168)
(3199)
(3225)
(3255)
(3285)
(3312)
(3343)
(3369)
(3396)

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 17

54 INCHDIAMETER*
900 GALLONVERTICALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
*Not available after 1996.

Concentrate
gal.
___
0
1
3
7
11
17
23
30
38
47
56
65
74
84
94
103
113
122
132
141
151
161
170
180
189
199
209
218
228
237
247
256
266
276
285
295
304
314
324
333
343
352
362
372
381
391
400
410
419

in Tank
(L)
___
(0)
(3)
(12)
(25)
(42)
(63)
(87)
(115)
(145)
(177)
(210)
(245)
(281)
(318)
(354)
(390)
(426)
(463)
(499)
(535)
(572)
(608)
(644)
(680)
(717)
(753)
(789)
(826)
(862)
(898)
(934)
(971)
(1007)
(1043)
(1080)
(1116)
(1152)
(1188)
(1225)
(1261)
(1297)
(1334)
(1370)
(1406)
(1442)
(1479)
(1515)
(1551)
(1588)

Depth of Concentrate
in.
(cm)
__
____
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)
63
(160.0)
64
(162.6)
65
(165.1)
66
(167.6)
67
(170.2)
68
(172.7)
69
(175.3)
70
(177.8)
71
(180.3)
72
(182.9)
73
(185.4)
74
(188.0)
75
(190.5)
76
(193.0)
77
(195.6)
78
(198.1)
79
(200.7)
80
(203.2)
81
(205.7)
82
(208.3)
83
(210.8)
84
(213.4)
85
(215.9)
86
(218.4)
87
(221.0)
88
(223.5)
89
(226.1)
90
(228.6)
91
(231.1)
92
(233.7)
93
(236.2)
94
(238.8)
95
(241.3)
96
(243.8)
97
(246.4)
98
(248.9)
99
(251.5)
100
(254.0)

Concentrate
gal.
___
429
439
448
458
467
477
487
496
506
515
525
534
544
554
563
573
582
592
602
611
621
630
640
650
659
669
678
688
697
707
717
726
736
745
755
765
774
784
793
803
813
822
832
841
851
860
870
880
889
898

in Tank
(L)
___
(1624)
(1660)
(1696)
(1733)
(1769)
(1805)
(1842)
(1878)
(1914)
(1950)
(1987)
(2023)
(2059)
(2096)
(2132)
(2168)
(2204)
(2241)
(2277)
(2313)
(2350)
(2386)
(2422)
(2458)
(2495)
(2531)
(2567)
(2604)
(2640)
(2676)
(2712)
(2749)
(2785)
(2821)
(2858)
(2894)
(2930)
(2966)
(3003)
(3039)
(3075)
(3112)
(3148)
(3184)
(3220)
(3257)
(3293)
(3329)
(3364)
(3398)

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 18

48 INCHDIAMETER
1000 GALLONVERTICALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)
63
(160.0)
64
(162.6)
65
(165.1)
66
(167.6)
67
(170.2)
68
(172.7)
69
(175.3)
70
(177.8)
71
(180.3)

Concentrate
gal.
___
0
2
5
9
13
19
25
31
38
45
53
60
68
75
83
91
98
106
113
121
128
136
143
151
158
166
173
181
189
196
204
211
219
226
234
241
249
256
264
272
279
287
294
302
309
317
324
332
339
347
355
362
370
377
385
392
400
407
415
422
430
437
445
453
460
468
475
483
490

in Tank
(L)
___
(2)
(8)
(19)
(33)
(50)
(70)
(93)
(118)
(144)
(171)
(200)
(228)
(257)
(286)
(314)
(343)
(371)
(400)
(428)
(457)
(485)
(514)
(542)
(571)
(600)
(628)
(657)
(685)
(714)
(742)
(771)
(799)
(828)
(857)
(885)
(914)
(942)
(971)
(999)
(1028)
(1056)
(1085)
(1113)
(1142)
(1171)
(1199)
(1228)
(1256)
(1285)
(1313)
(1342)
(1370)
(1399)
(1427)
(1456)
(1485)
(1513)
(1542)
(1570)
(1599)
(1627)
(1656)
(1684)
(1713)
(1742)
(1770)
(1799)
(1827)
(1856)

Depth of Concentrate
in.
(cm)
__
____
72
(182.9)
73
(185.4)
74
(188.0)
75
(190.5)
76
(193.0)
77
(195.6)
78
(198.1)
79
(200.7)
80
(203.2)
81
(205.7)
82
(208.3)
83
(210.8)
84
(213.4)
85
(215.9)
86
(218.4)
87
(221.0)
88
(223.5)
89
(226.1)
90
(228.6)
91
(231.1)
92
(233.7)
93
(236.2)
94
(238.8)
95
(241.3)
96
(243.8)
97
(246.4)
98
(248.9)
99
(251.5)
100
(254.0)
101
(256.5)
102
(259.1)
103
(261.6)
104
(264.2)
105
(266.7)
106
(269.2)
107
(271.8)
108
(274.3)
109
(276.9)
110
(279.4)
111
(281.9)
112
(284.5)
113
(287.0)
114
(289.6)
115
(292.1)
116
(294.6)
117
(297.2)
118
(299.7)
119
(302.3)
120
(304.8)
121
(307.3)
122
(309.9)
123
(312.4)
124
(315.0)
125
(317.5)
126
(320.0)
127
(322.6)
128
(325.1)
129
(327.7)
130
(330.2)
131
(322.7)
132
(335.3)
133
(337.8)
134
(340.4)
135
(342.9)
136
(345.4)
137
(348.0)
138
(350.5)
139
(353.1)

Concentrate
gal.
___
498
505
513
520
528
536
543
551
558
566
573
581
588
596
603
611
619
626
634
641
649
656
664
671
679
686
694
702
709
717
724
732
739
747
754
762
769
777
785
792
800
807
815
822
830
837
845
852
860
868
875
883
890
898
905
913
920
928
935
943
951
958
964
971
979
986
993
1000

in Tank
(L)
___
(1884)
(1913)
(1941)
(1970)
(1998)
(2027)
(2056)
(2084)
(2113)
(2141)
(2170)
(2198)
(2227)
(2255)
(2284)
(2312)
(2341)
(2370)
(2398)
(2427)
(2455)
(2484)
(2512)
(2541)
(2569)
(2597)
(2627)
(2657)
(2684)
(2714)
(2741)
(2771)
(2797)
(2828)
(2854)
(2884)
(2911)
(2941)
(2972)
(2998)
(3028)
(3055)
(3085)
(3112)
(3142)
(3168)
(3199)
(3225)
(3255)
(3285)
(3312)
(3343)
(3369)
(3399)
(3426)
(3456)
(3483)
(3513)
(3539)
(3570)
(3600)
(3626)
(3649)
(3676)
(3706)
(3732)
(3759)
(3785)

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 19

54 INCHDIAMETER*
1000 GALLONVERTICALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
*Not available after 1996.

Concentrate
gal.
___
0
1
3
7
11
17
23
30
38
47
56
65
74
84
94
103
113
122
132
141
151
161
170
180
189
199
209
218
228
237
247
256
266
276
285
295
304
314
324
333
343
352
362
372
381
391
400
410
419
429
439
448
458
467

in Tank
(L)
___
(0)
(3)
(12)
(25)
(42)
(63)
(87)
(115)
(145)
(177)
(210)
(245)
(281)
(318)
(354)
(390)
(426)
(463)
(499)
(535)
(572)
(608)
(644)
(680)
(717)
(753)
(789)
(826)
(862)
(898)
(934)
(971)
(1007)
(1043)
(1080)
(1116)
(1152)
(1188)
(1225)
(1261)
(1297)
(1334)
(1370)
(1406)
(1442)
(1479)
(1515)
(1551)
(1588)
(1624)
(1660)
(1696)
(1733)
(1769)

Depth of Concentrate
in.
(cm)
__
____
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)
63
(160.0)
64
(162.6)
65
(165.1)
66
(167.6)
67
(170.2)
68
(172.7)
69
(175.3)
70
(177.8)
71
(180.3)
72
(182.9)
73
(185.4)
74
(188.0)
75
(190.5)
76
(193.0)
77
(195.6)
78
(198.1)
79
(200.7)
80
(203.2)
81
(205.7)
82
(208.3)
83
(210.8)
84
(213.4)
85
(215.9)
86
(218.4)
87
(221.0)
88
(223.5)
89
(226.1)
90
(228.6)
91
(231.1)
92
(233.7)
93
(236.2)
94
(238.8)
95
(241.3)
96
(243.8)
97
(246.4)
98
(248.9)
99
(251.5)
100
(254.0)
101
(256.5)
102
(259.1)
103
(261.6)
104
(264.2)
105
(266.7)
106
(269.2)
107
(271.8)
108
(274.3)
109
(276.9)
110
(279.4)

Concentrate
gal.
___
477
487
496
506
515
525
534
544
554
563
573
582
592
602
611
621
630
640
650
659
669
678
688
697
707
717
726
736
745
755
765
774
784
793
803
813
822
832
841
851
860
870
880
889
899
908
918
928
937
947
956
966
976
985
994

in Tank
(L)
___
(1805)
(1842)
(1878)
(1914)
(1950)
(1987)
(2023)
(2059)
(2096)
(2132)
(2168)
(2204)
(2241)
(2277)
(2313)
(2350)
(2386)
(2422)
(2458)
(2495)
(2531)
(2567)
(2604)
(2640)
(2676)
(2712)
(2749)
(2785)
(2821)
(2858)
(2894)
(2930)
(2966)
(3003)
(3039)
(3075)
(3112)
(3148)
(3184)
(3220)
(3257)
(3293)
(3329)
(3366)
(3402)
(3438)
(3474)
(3511)
(3547)
(3583)
(3620)
(3656)
(3692)
(3728)
(3763)

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 20

1100 GALLONVERTICALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)

Concentrate
gal.
___
0
1
4
9
14
21
28
37
46
56
67
78
89
101
113
125
137
148
160
172
184
196
208
220
232
243
255
267
279
291
303
315
327
338
350
362
374
386
398
410
422
434
445
457
469
481
493
505
517

in Tank
(L)
___
(0)
(6)
(16)
(32)
(53)
(78)
(106)
(139)
(174)
(212)
(252)
(294)
(338)
(382)
(427)
(472)
(517)
(562)
(607)
(652)
(697)
(742)
(787)
(832)
(877)
(922)
(967)
(1012)
(1056)
(1101)
(1146)
(1191)
(1236)
(1281)
(1326)
(1371)
(1416)
(1461)
(1506)
(1551)
(1596)
(1641)
(1686)
(1731)
(1776)
(1821)
(1866)
(1910)
(1955)

Depth of Concentrate
in.
(cm)
__
____
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)
63
(160.0)
64
(162.6)
65
(165.1)
66
(167.6)
67
(170.2)
68
(172.7)
69
(175.3)
70
(177.8)
71
(180.3)
72
(182.9)
73
(185.4)
74
(188.0)
75
(190.5)
76
(193.0)
77
(195.6)
78
(198.1)
79
(200.7)
80
(203.2)
81
(205.7)
82
(208.3)
83
(210.8)
84
(213.4)
85
(215.9)
86
(218.4)
87
(221.0)
88
(223.5)
89
(226.1)
90
(228.6)
91
(231.1)
92
(233.7)
93
(236.2)
94
(238.8)
95
(241.3)
96
(243.8)
97
(246.4)
98
(248.9)
99
(251.5)

Concentrate
gal.
___
529
540
552
564
576
588
600
612
624
635
647
659
671
683
695
707
719
730
742
754
766
778
790
802
814
825
837
849
861
873
885
897
909
920
932
944
956
968
980
992
1004
1015
1027
1039
1051
1063
1075
1087
1099

in Tank
(L)
___
(2000)
(2045)
(2090)
(2135)
(2180)
(2225)
(2270)
(2315)
(2360)
(2405)
(2450)
(2495)
(2540)
(2585)
(2630)
(2675)
(2720)
(2765)
(2809)
(2854)
(2899)
(2944)
(2989)
(3034)
(3079)
(3124)
(3169)
(3214)
(3259)
(3304)
(3349)
(3394)
(3439)
(3484)
(3529)
(3574)
(3619)
(3664)
(3708)
(3753)
(3798)
(3843)
(3888)
(3933)
(3978)
(4023)
(4068)
(4113)
(4158)

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 21

1200 GALLONVERTICALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)

Concentrate
gal.
___
0
1
4
9
14
21
28
37
46
56
67
78
89
101
113
125
137
148
160
172
184
196
208
220
232
243
255
267
279
291
303
315
327
338
350
362
374
386
398
410
422
434
445
457
469
481
493
505
517
529
540
552
564
576

in Tank
(L)
___
(0)
(6)
(16)
(32)
(53)
(78)
(106)
(139)
(174)
(212)
(252)
(294)
(338)
(382)
(427)
(472)
(517)
(562)
(607)
(652)
(697)
(742)
(787)
(832)
(877)
(922)
(967)
(1012)
(1056)
(1101)
(1146)
(1191)
(1236)
(1281)
(1326)
(1371)
(1416)
(1461)
(1506)
(1551)
(1596)
(1641)
(1686)
(1731)
(1776)
(1821)
(1866)
(1910)
(1955)
(2000)
(2045)
(2090)
(2135)
(2180)

Depth of Concentrate
in.
(cm)
__
____
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)
63
(160.0)
64
(162.6)
65
(165.1)
66
(167.6)
67
(170.2)
68
(172.7)
69
(175.3)
70
(177.8)
71
(180.3)
72
(182.9)
73
(185.4)
74
(188.0)
75
(190.5)
76
(193.0)
77
(195.6)
78
(198.1)
79
(200.7)
80
(203.2)
81
(205.7)
82
(208.3)
83
(210.8)
84
(213.4)
85
(215.9)
86
(218.4)
87
(221.0)
88
(223.5)
89
(226.1)
90
(228.6)
91
(231.1)
92
(233.7)
93
(236.2)
94
(238.8)
95
(241.3)
96
(243.8)
97
(246.4)
98
(248.9)
99
(251.5)
101
(256.5)
102
(259.1)
103
(261.6)
104
(264.2)
105
(266.7)
106
(269.2)
107
(271.8)

Concentrate
gal.
___
588
600
612
624
635
647
659
671
683
695
707
719
730
742
754
766
778
790
802
814
825
837
849
861
873
885
897
909
920
932
944
956
968
980
992
1004
1015
1027
1039
1051
1063
1075
1087
1099
1122
1134
1146
1158
1170
1182
1194

in Tank
(L)
___
(2225)
(2270)
(2315)
(2360)
(2405)
(2450)
(2495)
(2540)
(2585)
(2630)
(2675)
(2720)
(2765)
(2809)
(2854)
(2899)
(2944)
(2989)
(3034)
(3079)
(3124)
(3169)
(3214)
(3259)
(3304)
(3349)
(3394)
(3439)
(3484)
(3529)
(3574)
(3619)
(3664)
(3708)
(3753)
(3798)
(3843)
(3888)
(3933)
(3978)
(4023)
(4068)
(4113)
(4158)
(4248)
(4293)
(4338)
(4383)
(4428)
(4473)
(4518)

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 22

1300 GALLONVERTICALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)

Concentrate
gal.
___
0
1
4
9
14
21
28
37
46
56
67
78
89
101
113
125
137
148
160
172
184
196
208
220
232
243
255
267
279
291
303
315
327
338
350
362
374
386
398
410
422
434
445
457
469
481
493
505
517
529
540
552
564
576
588
600
612

in Tank
(L)
___
(0)
(6)
(16)
(32)
(53)
(78)
(106)
(139)
(174)
(212)
(252)
(294)
(338)
(382)
(427)
(472)
(517)
(562)
(607)
(652)
(697)
(742)
(787)
(832)
(877)
(922)
(967)
(1012)
(1056)
(1101)
(1146)
(1191)
(1236)
(1281)
(1326)
(1371)
(1416)
(1461)
(1506)
(1551)
(1596)
(1641)
(1686)
(1731)
(1776)
(1821)
(1866)
(1910)
(1955)
(2000)
(2045)
(2090)
(2135)
(2180)
(2225)
(2270)
(2315)

Depth of Concentrate
in.
(cm)
__
____
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)
63
(160.0)
64
(162.6)
65
(165.1)
66
(167.6)
67
(170.2)
68
(172.7)
69
(175.3)
70
(177.8)
71
(180.3)
72
(182.9)
73
(185.4)
74
(188.0)
75
(190.5)
76
(193.0)
77
(195.6)
78
(198.1)
79
(200.7)
80
(203.2)
81
(205.7)
82
(208.3)
83
(210.8)
84
(213.4)
85
(215.9)
86
(218.4)
87
(221.0)
88
(223.5)
89
(226.1)
90
(228.6)
91
(231.1)
92
(233.7)
93
(236.2)
94
(238.8)
95
(241.3)
96
(243.8)
97
(246.4)
98
(248.9)
99
(251.5)
100
(254.0)
101
(256.5)
102
(259.1)
103
(261.6)
104
(264.2)
105
(266.7)
106
(269.2)
107
(271.8)
108
(274.3)
109
(276.9)
110
(279.4)
111
(281.9)
112
(284.5)
113
(287.0)
114
(289.6)
115
(292.1)
116
(294.6)

Concentrate
gal.
___
624
635
647
659
671
683
695
707
719
730
742
754
766
778
790
802
814
825
837
849
861
873
885
897
909
920
932
944
956
968
980
992
1004
1015
1027
1039
1051
1063
1075
1087
1099
1110
1122
1134
1146
1158
1170
1182
1194
1205
1217
1229
1241
1253
1265
1277
1289
1300

in Tank
(L)
___
(2360)
(2405)
(2450)
(2495)
(2540)
(2585)
(2630)
(2675)
(2720)
(2765)
(2809)
(2854)
(2899)
(2944)
(2989)
(3034)
(3079)
(3124)
(3169)
(3214)
(3259)
(3304)
(3349)
(3394)
(3439)
(3484)
(3529)
(3574)
(3619)
(3664)
(3708)
(3753)
(3798)
(3843)
(3888)
(3933)
(3978)
(4023)
(4068)
(4113)
(4158)
(4203)
(4248)
(4293)
(4338)
(4383)
(4428)
(4473)
(4518)
(4562)
(4607)
(4652)
(4697)
(4742)
(4787)
(4832)
(4877)
(4921)

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 23

1400 GALLONVERTICALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)

Concentrate
gal.
___
0
1
4
9
14
21
28
37
46
56
67
78
89
101
113
125
137
148
160
172
184
196
208
220
232
243
255
267
279
291
303
315
327
338
350
362
374
386
398
410
422
434
445
457
469
481
493
505
517
529
540
552
564
576
588
600
612
624
635
647
659

in Tank
(L)
___
(0)
(6)
(16)
(32)
(53)
(78)
(106)
(139)
(174)
(212)
(252)
(294)
(338)
(382)
(427)
(472)
(517)
(562)
(607)
(652)
(697)
(742)
(787)
(832)
(877)
(922)
(967)
(1012)
(1056)
(1101)
(1146)
(1191)
(1236)
(1281)
(1326)
(1371)
(1416)
(1461)
(1506)
(1551)
(1596)
(1641)
(1686)
(1731)
(1776)
(1821)
(1866)
(1910)
(1955)
(2000)
(2045)
(2090)
(2135)
(2180)
(2225)
(2270)
(2315)
(2360)
(2405)
(2450)
(2495)

Depth of Concentrate
in.
(cm)
__
____
63
(160.0)
64
(162.6)
65
(165.1)
66
(167.6)
67
(170.2)
68
(172.7)
69
(175.3)
70
(177.8)
71
(180.3)
72
(182.9)
73
(185.4)
74
(188.0)
75
(190.5)
76
(193.0)
77
(195.6)
78
(198.1)
79
(200.7)
80
(203.2)
81
(205.7)
82
(208.3)
83
(210.8)
84
(213.4)
85
(215.9)
86
(218.4)
87
(221.0)
88
(223.5)
89
(226.1)
90
(228.6)
91
(231.1)
92
(233.7)
93
(236.2)
94
(238.8)
95
(241.3)
96
(243.8)
97
(246.4)
98
(248.9)
99
(251.5)
100
(254.0)
101
(256.5)
102
(259.1)
103
(261.6)
104
(264.2)
105
(266.7)
106
(269.2)
107
(271.8)
108
(274.3)
109
(276.9)
110
(279.4)
111
(281.9)
112
(284.5)
113
(287.0)
114
(289.6)
115
(292.1)
116
(294.6)
117
(297.2)
118
(299.7)
119
(302.3)
120
(304.8)
121
(307.3)
122
(309.9)
123
(312.4)
124
(315.0)

Concentrate
gal.
___
671
683
695
707
719
730
742
754
766
778
790
802
814
825
837
849
861
873
885
897
909
920
932
944
956
968
980
992
1004
1015
1027
1039
1051
1063
1075
1087
1099
1110
1122
1134
1146
1158
1170
1182
1194
1205
1217
1229
1241
1253
1265
1277
1289
1300
1312
1324
1336
1348
1360
1372
1384
1395

in Tank
(L)
___
(2540)
(2585)
(2630)
(2675)
(2720)
(2765)
(2809)
(2854)
(2899)
(2944)
(2989)
(3034)
(3079)
(3124)
(3169)
(3214)
(3259)
(3304)
(3349)
(3394)
(3439)
(3484)
(3529)
(3574)
(3619)
(3664)
(3708)
(3753)
(3798)
(3843)
(3888)
(3933)
(3978)
(4023)
(4068)
(4113)
(4158)
(4203)
(4248)
(4293)
(4338)
(4383)
(4428)
(4473)
(4518)
(4562)
(4607)
(4652)
(4697)
(4742)
(4787)
(4832)
(4877)
(4922)
(4967)
(5012)
(5057)
(5102)
(5147)
(5192)
(5237)
(5282)

VERTICAL BLADDER TANK MEASUREMENT TABLES


Page 24

1500 GALLONVERTICALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)
63
(160.0)
64
(162.6)
65
(165.1)
66
(167.6)
67
(170.2)

Concentrate
gal.
___
0
1
4
9
14
21
28
37
46
56
67
78
89
101
113
125
137
148
160
172
184
196
208
220
232
243
255
267
279
291
303
315
327
338
350
362
374
386
398
410
422
434
445
457
469
481
493
505
517
529
540
552
564
576
588
600
612
624
635
647
659
671
683
695
707
719

in Tank
(L)
___
(0)
(6)
(16)
(32)
(53)
(78)
(106)
(139)
(174)
(212)
(252)
(294)
(338)
(382)
(427)
(472)
(517)
(562)
(607)
(652)
(697)
(742)
(787)
(832)
(877)
(922)
(967)
(1012)
(1056)
(1101)
(1146)
(1191)
(1236)
(1281)
(1326)
(1371)
(1416)
(1461)
(1506)
(1551)
(1596)
(1641)
(1686)
(1731)
(1776)
(1821)
(1866)
(1910)
(1955)
(2000)
(2045)
(2090)
(2135)
(2180)
(2225)
(2270)
(2315)
(2360)
(2405)
(2450)
(2495)
(2540)
(2585)
(2630)
(2675)
(2720)

Depth of Concentrate
in.
(cm)
__
____
68
(172.7)
69
(175.3)
70
(177.8)
71
(180.3)
72
(182.9)
73
(185.4)
74
(188.0)
75
(190.5)
76
(193.0)
77
(195.6)
78
(198.1)
79
(200.7)
80
(203.2)
81
(205.7)
82
(208.3)
83
(210.8)
84
(213.4)
85
(215.9)
86
(218.4)
87
(221.0)
88
(223.5)
89
(226.1)
90
(228.6)
91
(231.1)
92
(233.7)
93
(236.2)
94
(238.8)
95
(241.3)
96
(243.8)
97
(246.4)
98
(248.9)
99
(251.5)
100
(254.0)
101
(256.5)
102
(259.1)
103
(261.6)
104
(264.2)
105
(266.7)
106
(269.2)
107
(271.8)
108
(274.3)
109
(276.9)
110
(279.4)
111
(281.9)
112
(284.5)
113
(287.0)
114
(289.6)
115
(292.1)
116
(294.6)
117
(297.2)
118
(299.7)
119
(302.3)
120
(304.8)
121
(307.3)
122
(309.9)
123
(312.4)
124
(315.0)
125
(317.5)
126
(320.0)
127
(322.6)
128
(325.1)
129
(327.7)
130
(330.2)
131
(332.7)
132
(335.3)

Concentrate
gal.
___
730
742
754
766
778
790
802
814
825
837
849
861
873
885
897
909
920
932
944
956
968
980
992
1004
1015
1027
1039
1051
1063
1075
1087
1099
1110
1122
1134
1146
1158
1170
1182
1194
1205
1217
1229
1241
1253
1265
1277
1289
1300
1312
1324
1336
1348
1360
1372
1384
1395
1407
1419
1431
1443
1455
1467
1479
1490

in Tank
(L)
___
(2765)
(2809)
(2854)
(2899)
(2944)
(2989)
(3034)
(3079)
(3124)
(3169)
(3214)
(3259)
(3304)
(3349)
(3394)
(3439)
(3484)
(3529)
(3574)
(3619)
(3664)
(3708)
(3753)
(3798)
(3843)
(3888)
(3933)
(3978)
(4023)
(4068)
(4113)
(4158)
(4203)
(4248)
(4293)
(4338)
(4383)
(4428)
(4473)
(4518)
(4562)
(4607)
(4652)
(4697)
(4742)
(4787)
(4832)
(4877)
(4922)
(4967)
(5012)
(5057)
(5102)
(5147)
(5192)
(5237)
(5282)
(5327)
(5372)
(5417)
(5461)
(5506)
(5551)
(5596)
(5641)

HORIZONTAL BLADDER TANK MEASUREMENT TABLES


Page 25

HORIZONTAL BLADDERTANKMEASUREMENTTABLES

HORIZONTAL BLADDER TANK MEASUREMENT TABLES


Page 26

100 GALLONHORIZONTALBLADDERTANK

150 GALLONHORIZONTALBLADDERBANK

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)

Concentrate in Tank
gal.
(L)
___
___
0
(1)
2
(9)
5
(20)
9
(34)
13
(51)
18
(69)
23
(88)
29
(109)
35
(131)
40
(153)
46
(176)
53
(199)
59
(222)
65
(245)
71
(268)
77
(290)
82
(311)
88
(332)
93
(351)
98
(369)

Concentrate in Tank
gal.
(L)
___
___
0
(1)
2
(8)
5
(20)
9
(36)
14
(53)
19
(73)
25
(95)
31
(118)
38
(142)
44
(168)
51
(194)
58
(221)
66
(249)
73
(277)
81
(305)
88
(333)
96
(362)
103
(390)
110
(417)
117
(444)
124
(471)
131
(496)
137
(520)
144
(543)
149
(565)

HORIZONTAL BLADDER TANK MEASUREMENT TABLES


Page 27

200 GALLONHORIZONTALBLADDERTANK

300 GALLONHORIZONTALBLADDERTANK

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)

Concentrate in Tank
gal.
(L)
___
___
0
(1)
3
(11)
7
(27)
13
(47)
19
(71)
26
(97)
33
(125)
41
(155)
49
(187)
58
(220)
67
(254)
77
(290)
86
(326)
96
(362)
105
(399)
115
(436)
125
(472)
134
(509)
144
(544)
153
(580)
162
(614)
171
(647)
179
(678)
187
(708)
195
(736)

Concentrate
gal.
___
0
3
8
14
21
28
37
46
56
66
77
88
99
111
123
135
147
159
171
183
195
207
219
231
242
253
263
274
283
292

in Tank
(L)
___
(1)
(12)
(29)
(52)
(78)
(108)
(140)
(175)
(212)
(250)
(291)
(332)
(375)
(419)
(464)
(509)
(555)
(601)
(647)
(693)
(739)
(784)
(829)
(872)
(915)
(957)
(997)
(1036)
(1072)
(1107)

HORIZONTAL BLADDER TANK MEASUREMENT TABLES


Page 28

48 INCHDIAMETER
400 GALLONHORIZONTALBLADDERTANK

42 INCHDIAMETER*
400 GALLONHORIZONTALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
*Not available after 1996.

Concentrate
gal.
___
0
3
8
14
21
29
37
47
57
68
79
90
102
115
127
140
153
167
180
194
207
221
234
248
261
274
288
300
313
325
337
349
360
371
381
390
399

in Tank
(L)
___
(1)
(12)
(29)
(52)
(79)
(109)
(142)
(178)
(216)
(256)
(298)
(342)
(388)
(434)
(482)
(531)
(580)
(631)
(682)
(733)
(784)
(835)
(887)
(938)
(989)
(1039)
(1088)
(1137)
(1185)
(1231)
(1277)
(1320)
(1362)
(1402)
(1440)
(1476)
(1509)

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)

Concentrate
gal.
___
0
2
6
11
17
23
30
37
46
54
63
73
82
92
102
113
124
135
146
157
169
180
191
203
214
226
238
249
261
271
283
294
305
315
325
335
345
354
363
371
379
387
394
400

in Tank
(L)
___
(1)
(8)
(23)
(42)
(64)
(87)
(114)
(140)
(174)
(205)
(239)
(276)
(310)
(348)
(386)
(428)
(469)
(511)
(553)
(594)
(640)
(681)
(723)
(768)
(810)
(856)
(901)
(943)
(988)
(1026)
(1071)
(1113)
(1155)
(1192)
(1230)
(1268)
(1306)
(1340)
(1374)
(1404)
(1435)
(1465)
(1492)
(1514)

HORIZONTAL BLADDER TANK MEASUREMENT TABLES


Page 29

48 INCHDIAMETER
500 GALLONHORIZONTALBLADDERTANK

42 INCHDIAMETER*
500 GALLONHORIZONTALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
*Not available after 1996.

Concentrate
gal.
___
0
4
10
17
26
36
47
58
71
84
98
112
127
142
157
173
189
205
222
238
255
272
288
305
321
337
354
369
385
400
415
429
442
455
468
479
490
500

in Tank
(L)
___
(1)
(15)
(37)
(65)
(99)
(136)
(177)
(221)
(268)
(318)
(370)
(424)
(480)
(537)
(596)
(655)
(716)
(778)
(840)
(903)
(965)
(1028)
(1091)
(1154)
(1216)
(1277)
(1338)
(1398)
(1456)
(1514)
(1569)
(1623)
(1675)
(1724)
(1771)
(1815)
(1855)
(1892)

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)

Concentrate
gal.
___
0
3
8
14
21
29
37
46
57
68
79
91
103
115
128
141
155
169
182
196
211
225
239
254
268
283
297
311
326
339
354
367
381
394
406
419
431
443
454
464
474
484
492
500

in Tank
(L)
___
(0)
(11)
(30)
(53)
(80)
(110)
(140)
(174)
(216)
(257)
(299)
(345)
(390)
(435)
(485)
(534)
(587)
(640)
(689)
(742)
(799)
(852)
(905)
(962)
(1015)
(1071)
(1124)
(1177)
(1234)
(1283)
(1340)
(1389)
(1442)
(1492)
(1537)
(1586)
(1632)
(1677)
(1719)
(1756)
(1794)
(1832)
(1862)
(1893)

HORIZONTAL BLADDER TANK MEASUREMENT TABLES


Page 30

700 GALLONHORIZONTALBLADDERTANK

600 GALLONHORIZONTALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)

Concentrate
gal.
___
0
3
9
16
24
34
44
55
67
80
94
108
122
137
153
168
185
201
218
235
252
269
286
304
321
338
356
373
390
407
423
440
456
472
487
502
517
530
544
556
568
580
590
599

in Tank
(L)
___
(0)
(13)
(33)
(60)
(91)
(127)
(166)
(209)
(255)
(303)
(354)
(407)
(462)
(519)
(577)
(637)
(699)
(761)
(824)
(888)
(953)
(1018)
(1083)
(1149)
(1215)
(1281)
(1346)
(1411)
(1476)
(1540)
(1603)
(1665)
(1726)
(1786)
(1844)
(1900)
(1955)
(2008)
(2058)
(2106)
(2152)
(2194)
(2233)
(2268)

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)

Concentrate
gal.
___
0
4
11
19
29
40
52
65
80
94
110
127
144
161
179
198
217
236
255
275
295
315
335
355
375
396
416
436
456
475
495
514
533
551
569
587
603
620
635
650
664
677
689
700

in Tank
(L)
___
(1)
(15)
(40)
(71)
(109)
(151)
(197)
(247)
(301)
(358)
(417)
(479)
(544)
(610)
(678)
(748)
(820)
(892)
(966)
(1040)
(1116)
(1192)
(1268)
(1344)
(1421)
(1498)
(1574)
(1650)
(1725)
(1799)
(1873)
(1945)
(2016)
(2086)
(2154)
(2220)
(2284)
(2346)
(2405)
(2461)
(2514)
(2564)
(2610)
(2650)

HORIZONTAL BLADDER TANK MEASUREMENT TABLES


Page 31

54 INCHDIAMETER*
800 GALLONHORIZONTALBLADDERTANK

48 INCHDIAMETER
800 GALLONHORIZONTALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)

Concentrate
gal.
___
0
5
13
22
33
46
59
74
91
109
126
145
165
184
205
226
248
270
291
314
337
360
383
406
429
453
475
498
521
543
566
587
609
630
650
671
690
709
726
743
759
774
787
800

in Tank
(L)
___
(1)
(19)
(49)
(83)
(125)
(174)
(223)
(280)
(345)
(413)
(477)
(549)
(625)
(697)
(776)
(856)
(939)
(1022)
(1102)
(1189)
(1276)
(1363)
(1450)
(1537)
(1624)
(1715)
(1798)
(1885)
(1972)
(2056)
(2143)
(2222)
(2305)
(2385)
(2461)
(2540)
(2612)
(2684)
(2748)
(2813)
(2873)
(2930)
(2979)
(3028)

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
*Not available after 1996.

Concentrate
gal.
___
0
4
10
18
27
37
49
62
75
90
105
121
138
155
172
190
209
228
247
267
287
307
328
348
369
390
410
431
452
473
493
514
534
555
574
594
613
632
651
669
686
703
720
736
751
765
779
791

in Tank
(L)
___
(1)
(14)
(37)
(67)
(102)
(142)
(186)
(234)
(286)
(340)
(398)
(458)
(521)
(585)
(652)
(721)
(791)
(863)
(936)
(1011)
(1086)
(1163)
(1240)
(1318)
(1396)
(1475)
(1553)
(1632)
(1711)
(1790)
(1868)
(1945)
(2023)
(2099)
(2174)
(2248)
(2321)
(2393)
(2463)
(2532)
(2598)
(2663)
(2725)
(2785)
(2842)
(2896)
(2947)
(2994)

HORIZONTAL BLADDER TANK MEASUREMENT TABLES


Page 32

54 INCHDIAMETER*
900 GALLONHORIZONTALBLADDERTANK

48 INCHDIAMETER
900 GALLONHORIZONTALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)

Concentrate
gal.
___
0
5
14
24
37
51
67
84
103
122
141
163
185
207
230
255
279
303
328
354
379
405
431
456
482
509
535
561
586
611
636
661
685
708
732
755
777
797
816
836
854
870
886
900

in Tank
(L)
___
(1)
(19)
(53)
(91)
(140)
(193)
(254)
(318)
(390)
(462)
(534)
(617)
(700)
(784)
(871)
(965)
(1056)
(1147)
(1242)
(1340)
(1435)
(1533)
(1632)
(1726)
(1825)
(1927)
(2025)
(2124)
(2218)
(2313)
(2408)
(2502)
(2593)
(2680)
(2771)
(2858)
(2941)
(3017)
(3089)
(3165)
(3233)
(3293)
(3354)
(3407)

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
*Not available after 1996.

Concentrate
gal.
___
0
4
11
20
31
43
56
70
86
102
119
137
156
175
195
215
236
257
279
301
324
346
369
392
415
439
462
485
509
532
555
578
601
624
646
668
690
711
732
752
772
791
810
827
844
861
876
890

in Tank
(L)
___
(1)
(16)
(42)
(76)
(116)
(162)
(212)
(266)
(324)
(386)
(451)
(519)
(589)
(662)
(737)
(815)
(894)
(975)
(1057)
(1140)
(1225)
(1311)
(1397)
(1485)
(1572)
(1661)
(1749)
(1837)
(1926)
(2014)
(2101)
(2189)
(2275)
(2361)
(2445)
(2529)
(2611)
(2691)
(2770)
(2847)
(2922)
(2994)
(3065)
(3132)
(3196)
(3257)
(3315)
(3369)

HORIZONTAL BLADDER TANK MEASUREMENT TABLES


Page 33

48 INCHDIAMETER
1000 GALLONHORIZONTALBLADDERTANK

54 INCHDIAMETER*
1000 GALLONHORIZONTALBLADDERTANK

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)

Concentrate
gal.
___
0
6
16
27
41
57
74
93
114
136
157
181
206
230
256
283
310
337
364
393
421
450
479
507
536
566
594
623
651
679
707
734
761
787
813
839
863
886
907
929
949
967
984
1000

in Tank
(L)
___
(1)
(23)
(61)
(102)
(155)
(216)
(280)
(352)
(432)
(515)
(594)
(685)
(780)
(871)
(969)
(1071)
(1173)
(1276)
(1378)
(1487)
(1594)
(1703)
(1813)
(1919)
(2029)
(2143)
(2249)
(2358)
(2464)
(2570)
(2676)
(2779)
(2881)
(2979)
(3078)
(3176)
(3267)
(3354)
(3433)
(3517)
(3592)
(3631)
(3725)
(3785)

*Not available after 1996.

Concentrate
gal.
___
0
5
13
23
35
48
63
79
96
114
133
153
174
195
217
240
263
287
311
336
360
385
411
436
462
488
514
540
565
591
617
642
668
693
718
742
766
790
813
835
857
879
899
919
938
956
973
989

in Tank
(L)
___
(1)
(18)
(48)
(86)
(131)
(181)
(237)
(298)
(363)
(432)
(504)
(579)
(658)
(739)
(823)
(908)
(996)
(1086)
(1177)
(1270)
(1364)
(1459)
(1555)
(1652)
(1749)
(1847)
(1945)
(2043)
(2140)
(2238)
(2335)
(2432)
(2528)
(2623)
(2716)
(2809)
(2900)
(2989)
(3077)
(3162)
(3245)
(3326)
(3404)
(3479)
(3551)
(3619)
(3683)
(3743)

HORIZONTAL BLADDER TANK MEASUREMENT TABLES


Page 34

1100 GALLONHORIZONTALBLADDERTANK

1200 GALLONHORIZONTALBLADDERTANK

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)

Concentrate
gal.
___
1
6
14
24
36
50
64
80
97
115
134
154
175
196
218
241
264
288
312
337
362
388
414
440
466
493
519
546
573
600
627
654
681
708
734
761
787
813
838
864
889
913
937
961
984
1006
1027
1048
1069
1088

in Tank
(L)
___
(3)
(24)
(54)
(93)
(137)
(188)
(244)
(304)
(368)
(437)
(508)
(584)
(662)
(743)
(826)
(912)
(1000)
(1091)
(1183)
(1276)
(1372)
(1468)
(1566)
(1665)
(1765)
(1865)
(1966)
(2068)
(2170)
(2272)
(2374)
(2476)
(2577)
(2678)
(2779)
(2879)
(2978)
(3077)
(3174)
(3269)
(3364)
(3456)
(3547)
(3636)
(3723)
(3807)
(3889)
(3968)
(4044)
(4117)

Concentrate
gal.
___
1
7
16
27
40
54
71
88
107
126
147
169
191
214
238
263
288
314
341
368
395
423
451
479
508
537
566
595
624
653
682
712
741
770
799
827
856
884
912
939
966
993
1019
1045
1070
1094
1117
1140
1162
1183

in Tank
(L)
___
(4)
(26)
(60)
(102)
(151)
(206)
(267)
(333)
(403)
(478)
(556)
(638)
(723)
(811)
(902)
(996)
(1092)
(1190)
(1290)
(1392)
(1495)
(1600)
(1706)
(1814)
(1922)
(2031)
(2141)
(2251)
(2362)
(2472)
(2583)
(2694)
(2804)
(2914)
(3023)
(3132)
(3240)
(3346)
(3452)
(3556)
(3658)
(3759)
(3857)
(3954)
(4049)
(4140)
(4230)
(4316)
(4399)
(4478)

HORIZONTAL BLADDER TANK MEASUREMENT TABLES


Page 35

1300 GALLONHORIZONTALBLADDERTANK

1400 GALLONHORIZONTALBLADDERTANK

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)

Concentrate
gal.
___
1
8
17
29
43
59
77
96
116
137
160
183
207
233
259
285
313
341
369
398
428
458
488
519
549
581
612
643
675
706
738
769
801
832
863
894
925
955
985
1015
1044
1073
1101
1129
1156
1182
1207
1232
1256
1279
1300

in Tank
(L)
___
(4)
(28)
(65)
(111)
(164)
(225)
(291)
(362)
(438)
(519)
(604)
(693)
(785)
(880)
(979)
(1080)
(1183)
(1289)
(1397)
(1507)
(1619)
(1732)
(1847)
(1963)
(2080)
(2197)
(2316)
(2435)
(2554)
(2673)
(2793)
(2912)
(3031)
(3150)
(3268)
(3385)
(3501)
(3616)
(3730)
(3842)
(3953)
(4061)
(4168)
(4272)
(4374)
(4474)
(4570)
(4663)
(4753)
(4839)
(4921)

Concentrate
gal.
___
1
8
19
32
47
64
83
103
125
148
172
197
224
251
279
307
337
367
398
429
460
493
525
558
591
624
658
692
725
759
793
827
861
894
928
961
994
1027
1059
1091
1122
1153
1183
1213
1242
1270
1297
1324
1349
1374
1397

in Tank
(L)
___
(4)
(31)
(71)
(120)
(178)
(243)
(314)
(391)
(473)
(560)
(652)
(747)
(846)
(949)
(1055)
(1163)
(1275)
(1389)
(1505)
(1623)
(1743)
(1864)
(1987)
(2112)
(2237)
(2363)
(2490)
(2618)
(2746)
(2874)
(3002)
(3130)
(3258)
(3385)
(3512)
(3637)
(3762)
(3886)
(4008)
(4128)
(4247)
(4364)
(4478)
(4591)
(4700)
(4807)
(4911)
(5011)
(5108)
(5201)
(5289)

HORIZONTAL BLADDER TANK MEASUREMENT TABLES


Page 36

1500 GALLONHORIZONTALBLADDERTANK

1600 GALLONHORIZONTALBLADDERTANK

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)

Concentrate
gal.
___
1
9
20
34
51
69
89
111
134
159
185
212
240
269
299
329
361
393
426
459
493
527
562
597
633
668
704
740
776
812
849
885
921
957
992
1028
1063
1098
1132
1166
1200
1233
1265
1297
1328
1358
1387
1416
1443
1469
1494

in Tank
(L)
___
(5)
(33)
(76)
(129)
(192)
(261)
(338)
(420)
(508)
(602)
(700)
(802)
(908)
(1018)
(1131)
(1247)
(1366)
(1488)
(1612)
(1738)
(1866)
(1996)
(2128)
(2260)
(2394)
(2529)
(2665)
(2801)
(2938)
(3075)
(3212)
(3348)
(3485)
(3621)
(3756)
(3890)
(4023)
(4155)
(4286)
(4415)
(4542)
(4666)
(4789)
(4909)
(5026)
(5140)
(5251)
(5359)
(5462)
(5562)
(5656)

Concentrate
gal.
___
1
10
22
37
55
74
96
120
145
171
199
228
258
289
321
354
388
422
457
493
529
566
603
641
679
717
755
794
833
871
910
949
987
1026
1064
1102
1140
1177
1214
1250
1286
1322
1356
1390
1424
1456
1487
1518
1547
1575

in Tank
(L)
___
(5)
(36)
(82)
(140)
(207)
(282)
(364)
(453)
(547)
(648)
(753)
(862)
(976)
(1094)
(1215)
(1340)
(1468)
(1598)
(1731)
(1866)
(2004)
(2143)
(2284)
(2426)
(2569)
(2714)
(2859)
(3005)
(3151)
(3298)
(3444)
(3591)
(3737)
(3882)
(4027)
(4171)
(4314)
(4455)
(4595)
(4733)
(4869)
(5003)
(5134)
(5263)
(5388)
(5511)
(5630)
(5745)
(5856)
(5963)

HORIZONTAL BLADDER TANK MEASUREMENT TABLES


Page 37

1700 GALLONHORIZONTALBLADDERTANK

1800 GALLONHORIZONTALBLADDERTANK

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)

Concentrate
gal.
___
1
10
23
39
58
79
102
127
154
182
211
242
274
307
341
376
412
448
486
524
562
601
640
680
720
761
802
842
883
924
965
1006
1047
1088
1128
1169
1209
1248
1287
1326
1364
1402
1438
1474
1510
1544
1577
1610
1641
1671
1699

in Tank
(L)
___
(5)
(38)
(88)
(149)
(220)
(300)
(387)
(482)
(583)
(689)
(800)
(917)
(1038)
(1163)
(1291)
(1424)
(1559)
(1697)
(1838)
(1982)
(2127)
(2275)
(2424)
(2575)
(2727)
(2880)
(3034)
(3188)
(3343)
(3499)
(3654)
(3809)
(3964)
(4118)
(4271)
(4424)
(4575)
(4725)
(4873)
(5019)
(5163)
(5305)
(5444)
(5581)
(5714)
(5844)
(5970)
(6093)
(6211)
(6324)
(6432)

Concentrate
gal.
___
2
11
25
42
62
84
109
135
163
193
224
257
290
325
361
398
436
475
514
554
595
636
678
720
762
805
848
891
934
977
1021
1064
1107
1150
1193
1236
1278
1320
1361
1402
1442
1482
1520
1559
1596
1632
1667
1702
1734
1766
1796

in Tank
(L)
___
(6)
(41)
(93)
(158)
(234)
(318)
(411)
(511)
(618)
(730)
(848)
(971)
(1099)
(1231)
(1368)
(1507)
(1650)
(1797)
(1946)
(2097)
(2251)
(2407)
(2564)
(2724)
(2884)
(3046)
(3209)
(3372)
(3535)
(3699)
(3863)
(4027)
(4191)
(4354)
(4516)
(4677)
(4836)
(4994)
(5151)
(5305)
(5458)
(5608)
(5755)
(5899)
(6040)
(6177)
(6311)
(6440)
(6565)
(6685)
(6799)

HORIZONTAL BLADDER TANK MEASUREMENT TABLES


Page 38

1900 GALLONHORIZONTALBLADDERTANK

2000 GALLONHORIZONTALBLADDERTANK

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)

Concentrate
gal.
___
2
11
26
44
65
89
115
143
172
204
237
271
307
344
381
420
460
501
542
585
627
671
715
759
804
849
894
939
985
1030
1076
1122
1167
1212
1258
1302
1347
1391
1434
1477
1520
1561
1602
1643
1682
1720
1757
1793
1828
1862
1893

in Tank
(L)
___
(6)
(43)
(99)
(167)
(247)
(337)
(435)
(540)
(653)
(771)
(896)
(1026)
(1161)
(1300)
(1444)
(1591)
(1742)
(1896)
(2053)
(2213)
(2375)
(2539)
(2705)
(2873)
(3042)
(3212)
(3383)
(3555)
(3728)
(3900)
(4073)
(4245)
(4418)
(4589)
(4760)
(4929)
(5097)
(5264)
(5429)
(5592)
(5752)
(5910)
(6065)
(6217)
(6366)
(6511)
(6651)
(6788)
(6920)
(7046)
(7167)

Concentrate
gal.
___
2
10
21
35
52
70
90
112
136
161
187
214
243
272
303
335
367
400
434
469
504
540
577
614
652
690
728
767
806
846
885
925
965
1005
1045
1085
1126
1166
1206
1246
1286
1325
1364
1404
1442
1481
1519
1556
1593
1630
1666
1701
1736
1770
1803
1835
1867
1897
1927
1955
1982

in Tank
(L)
___
(7)
(37)
(80)
(134)
(196)
(266)
(342)
(425)
(514)
(608)
(707)
(811)
(919)
(1031)
(1147)
(1266)
(1389)
(1515)
(1644)
(1775)
(1909)
(2046)
(2184)
(2325)
(2467)
(2611)
(2757)
(2903)
(3052)
(3201)
(3351)
(3501)
(3652)
(3804)
(3956)
(4108)
(4260)
(4412)
(4564)
(4715)
(4866)
(5016)
(5165)
(5312)
(5459)
(5604)
(5748)
(5890)
(6031)
(6169)
(6305)
(6439)
(6570)
(6698)
(6824)
(6946)
(7065)
(7181)
(7292)
(7400)
(7503)

HORIZONTAL BLADDER TANK MEASUREMENT TABLES


Page 39

2200 GALLONHORIZONTALBLADDERTANK

2400 GALLONHORIZONTALBLADDERTANK

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)

Concentrate
gal.
___
2
11
24
39
58
78
101
125
151
178
207
238
269
302
336
371
406
443
480
519
558
597
638
679
720
762
804
847
890
933
977
1020
1064
1108
1153
1197
1241
1285
1329
1373
1417
1460
1504
1547
1589
1631
1673
1715
1755
1796
1835
1874
1912
1950
1986
2022
2057
2090
2123
2154
2184

in Tank
(L)
___
(8)
(41)
(90)
(149)
(218)
(296)
(381)
(473)
(571)
(675)
(785)
(900)
(1019)
(1143)
(1271)
(1402)
(1538)
(1677)
(1819)
(1963)
(2111)
(2261)
(2414)
(2568)
(2725)
(2883)
(3044)
(3205)
(3368)
(3532)
(3697)
(3862)
(4029)
(4195)
(4362)
(4530)
(4697)
(4864)
(5031)
(5197)
(5362)
(5527)
(5691)
(5854)
(6015)
(6175)
(6333)
(6489)
(6644)
(6796)
(6946)
(7093)
(7238)
(7379)
(7518)
(7653)
(7784)
(7911)
(8035)
(8154)
(8268)

Concentrate
gal.
___
2
12
26
43
64
86
111
138
166
196
228
261
296
331
368
406
446
486
527
568
611
654
698
743
788
834
880
926
973
1021
1068
1116
1164
1212
1260
1308
1356
1404
1452
1500
1548
1595
1643
1690
1736
1782
1828
1873
1917
1961
2004
2047
2089
2130
2169
2208
2246
2283
2319
2353
2386

in Tank
(L)
___
(9)
(46)
(99)
(165)
(241)
(326)
(420)
(521)
(628)
(743)
(863)
(988)
(1119)
(1255)
(1394)
(1539)
(1687)
(1838)
(1993)
(2152)
(2313)
(2477)
(2643)
(2812)
(2983)
(3156)
(3330)
(3507)
(3684)
(3863)
(4043)
(4223)
(4405)
(4587)
(4769)
(4951)
(5133)
(5315)
(5497)
(5678)
(5859)
(6039)
(6217)
(6395)
(6571)
(6745)
(6918)
(7089)
(7257)
(7423)
(7587)
(7748)
(7906)
(8060)
(8212)
(8359)
(8503)
(8642)
(8777)
(8907)
(9032)

HORIZONTAL BLADDER TANK MEASUREMENT TABLES


Page 40

2600 GALLONHORIZONTALBLADDERTANK

2800 GALLONHORIZONTALBLADDERTANK

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)

Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)

Concentrate
gal.
___
3
13
29
48
70
94
121
150
181
214
248
285
322
361
401
442
485
528
573
618
664
711
759
807
856
906
956
1006
1057
1108
1160
1211
1263
1315
1367
1419
1472
1524
1576
1628
1679
1731
1782
1832
1883
1933
1982
2031
2079
2127
2174
2220
2265
2309
2353
2395
2436
2476
2515
2552
2588

in Tank
(L)
___
(10)
(50)
(108)
(180)
(263)
(356)
(458)
(568)
(686)
(810)
(941)
(1077)
(1219)
(1366)
(1518)
(1675)
(1835)
(2000)
(2168)
(2340)
(2515)
(2692)
(2873)
(3056)
(3241)
(3428)
(3617)
(3808)
(4001)
(4194)
(4389)
(4585)
(4781)
(4978)
(5175)
(5372)
(5570)
(5767)
(5964)
(6160)
(6356)
(6550)
(6744)
(6936)
(7127)
(7316)
(7503)
(7688)
(7870)
(8050)
(8228)
(8402)
(8573)
(8741)
(8905)
(9066)
(9221)
(9373)
(9519)
(9661)
(9797)

Concentrate in Tank
gal.
(L)
___
___
3
(11)
14
(54)
31
(117)
51
(194)
75
(284)
101
(384)
130
(494)
162
(612)
195
(738)
230
(872)
267
(1012)
306
(1159)
346
(1311)
388
(1469)
431
(1632)
476
(1800)
521
(1973)
568
(2149)
615
(2329)
664
(2513)
714
(2701)
764
(2891)
815
(3085)
867
(3281)
919
(3479)
972
(3680)
1026
(3882)
1080
(4087)
1134
(4293)
1189
(4500)
1244
(4708)
1299
(4918)
1355
(5128)
1411
(5339)
1466
(5550)
1522
(5761)
1578
(5973)
1634
(6184)
1689
(6395)
1745
(6605)
1800
(6814)
1855
(7022)
1910
(7230)
1964
(7435)
2018
(7640)
2072
(7842)
2125
(8042)
2177
(8241)
2229
(8436)
2280
(8629)
2330
(8819)
2379
(9006)
2428
(9190)
2476
(9370)
2522
(9546)
2567
(9718)
2612
(9885)
2655
(10047)
2696
(10205)
2736
(10356)
2775
(10502)

HORIZONTAL BLADDER TANK MEASUREMENT TABLES


Page 41

3000 GALLONHORIZONTALBLADDERTANK
Depth of Concentrate
in.
(cm)
__
____
2
(5.1)
3
(7.6)
4
(10.2)
5
(12.7)
6
(15.2)
7
(17.8)
8
(20.3)
9
(22.9)
10
(25.4)
11
(27.9)
12
(30.5)
13
(33.0)
14
(35.6)
15
(38.1)
16
(40.6)
17
(43.2)
18
(45.7)
19
(48.3)
20
(50.8)
21
(53.3)
22
(55.9)
23
(58.4)
24
(61.0)
25
(63.5)
26
(66.0)
27
(68.6)
28
(71.1)
29
(73.7)
30
(76.2)
31
(78.7)
32
(81.3)
33
(83.8)
34
(86.4)
35
(88.9)
36
(91.4)
37
(94.0)
38
(96.5)
39
(99.1)
40
(101.6)
41
(104.1)
42
(106.7)
43
(109.2)
44
(111.8)
45
(114.3)
46
(116.8)
47
(119.4)
48
(121.9)
49
(124.5)
50
(127.0)
51
(129.5)
52
(132.1)
53
(134.6)
54
(137.2)
55
(139.7)
56
(142.2)
57
(144.8)
58
(147.3)
59
(149.9)
60
(152.4)
61
(154.9)
62
(157.5)

Concentrate in Tank
gal.
(L)
___
___
3
(11)
16
(59)
33
(126)
55
(210)
81
(306)
109
(414)
141
(532)
174
(660)
210
(796)
248
(939)
288
(1090)
330
(1248)
373
(1411)
418
(1581)
464
(1756)
512
(1936)
560
(2121)
610
(2311)
662
(2504)
714
(2702)
767
(2902)
821
(3107)
876
(3314)
931
(3524)
987
(3737)
1044
(3952)
1101
(4169)
1159
(4388)
1218
(4609)
1276
(4831)
1335
(5055)
1395
(5279)
1454
(5504)
1514
(5730)
1574
(5956)
1633
(6183)
1693
(6409)
1753
(6635)
1813
(6861)
1872
(7086)
1932
(7311)
1990
(7534)
2049
(7756)
2107
(7977)
2165
(8195)
2223
(8412)
2279
(8627)
2335
(8840)
2391
(9049)
2446
(9256)
2499
(9460)
2552
(9661)
2604
(9858)
2655
(10051)
2705
(10240)
2754
(10424)
2801
(10604)
2848
(10778)
2892
(10947)
2935
(11110)
2977
(11267)

Part No. 71676-02

Copyright 2011 Tyco Fire Protection Products. All rights reserved.

TYCO FIRE PROTECTION PRODUCTS


ONE STANTON STREET
MARINETTE, WI 54143-2542

Page 1

001330

FOAM CONCENTRATES AND


FOAM PRE-MIX SOLUTIONS
Field Inspection Manual

INTRODUCTION
Page 1

INTRODUCTION
This manual is designed to serve as a guide to inspection
procedures for ANSUL Foam Concentrates and Pre-mix
Solutions.
As Tyco Fire Protection Products manufactures many types
of foam concentrates, locate the product data sheet for the
specific concentrate to be tested. Product Data Sheets can
be accessed at www.ansul.com.
The designated inspector should be a responsible, experienced person with sound, basic knowledge of fire equipment hardware and extinguishing agents. A thorough
briefing on the procedures to be followed should include the
need for precise execution of each analysis step.
See Field Inspection Record at the end of this manual to
record proportioning results.
Form Part No. 428680, Foam Analysis Request, is for use
in recording the information required when sending in
samples to the Tyco Fire Protection Products Agents
Laboratory. This form also outlines the correct procedure
for submitting samples. Review and complete the form as
thoroughly as possible. This form is included in the Foam
Agent Test Kit, Part No. 428679. It is also available on
www.ansul.com under Foam Products. (Note: There is a
charge for this testing service.)
FReqUeNCy aND aCCURaCy OF TesTs
Tyco Fire Protection Products recommends that proportioning tests be done at system commissioning and every three
(3) years minimum thereafter.
exception: Pre-primed foam-water sprinkler systems
should be flushed, drained and pre-primed with fresh solution annually. During this process correct proportioning
should be verified.
Tyco Fire Protection Products recommends that Standard
Quality Analysis Testing be done annually by the Tyco Fire
Protection Products Agents Laboratory which not only tests
the chemical properties of the sample, but also does lab
scale fire testing to assure the products performance.
Packages of two (2) sample containers with labels can be
purchased under Part No. 428679.
sTORage CONDITIONs
Tyco Fire Protection Products recommends that its concentrates be stored at the temperatures indicated on the
specific product data sheet.
Accelerated aging studies have been conducted with the
concentrate and pre-mix solutions stored at 150 F
(65.5 C) with no adverse effect. However, Underwriters
Laboratory Standard No. 162 requires that the maximum
storage temperature be listed at 120 F (48.9 C).

Storage of concentrates below the minimum temperature


listed on the product data sheets could result in freezing. If
the agent freezes, it should be thawed at or near room
temperature and agitated or stirred to ensure a homogenous mixture. If previous freezing is suspect, agitation will
again ensure a homogenous mixture.
To maximize life of concentrates stored in atmospheric
storage tanks, ANSUL recommends that a 1/4 in. (6 mm)
layer of mineral oil be added to the air-exposed surface of
the concentrate. This is critical for Alcohol Resistant
Concentrates.
RelaTeD INFORmaTION
The following is a list of Technical Bulletins that can be
found at the ANSUL internet home page www.ansul.com.
Technical Bulletin Number 52
(Environmental Impact of ANSULITE AFFF Products)
Technical Bulletin Number 54
(Shelf Life of ANSULITE AFFF Concentrates and Their
Pre-mixed Solutions)
Technical Bulletin Number 55
(Aspirated Versus Nonaspirated AFFF)
Technical Bulletin Number 59
(Acceptable Materials of Construction For Use With
ANSUL Foam Concentrates)
Technical Bulletin Number 60
(Foam and The Environment)
Technical Bulletin Number 64
(Compatibility of AFFF/Alcohol-Resistant AFFF
Concentrates)
ReFRaCTIve INDex vs. CONDUCTIvITy
Tyco Fire Protection Products recommends refractive index
testing instead of conductivity testing in the field because
there is less chance of results being skewed by water
quality or temperature. Also, continuous stirring is required
during conductivity testing to obtain stable results.

FOamsOlUTIONCONCeNTRaTIONDeTeRmINaTION
Page 2

FOam sOlUTION CONCeNTRaTION DeTeRmINaTION


ReFRaCTIve INDex OR CONDUCTIvITy
This test is used to determine the percent concentrate of a
foam concentrate in the water being used to generate foam.
It is typically used as a means to determine the accuracy of
the systems proportioning equipment.
This method is based upon comparing foam solution test
sample to pre-measured solutions (Calibration Standard)
that are plotted on a baseline graph of percent concentration versus instrument reading.
A hand-held refractometer is used to measure the refractive
index of the foam solution sample. Scales on refractometers vary, but what is actually being used to determine
concentration is a change in reading from one premeasured solution to another (Calibration Standards
Curve vs. Discharge Samples Reading). The philosophy
applies when using a conductivity meter which is measuring
the changes in the solutions conductivity. (Refer to
Proportioning Test Instruments Data Sheet, F-2007003, for
more detailed information about the specific meters.)
A base curve is prepared by using the following apparatus:
1. Four 100 ml or larger plastic bottles with leak-resistant
screw caps
2. One 10 ml (10 cc) measuring syringe
3. One 100 ml graduated cylinder
4. Four or more eye droppers
5. One Test Meter Model PA 202, 10419, 1500-32
6. Graph paper
7. Ruler or straight edge
Using water and foam concentrate from the system to be
tested, make up three 100 ml calibration standard solutions.
For a 6% concentrate, typically a 4%, 6% and 8% samples;
for a 3% concentrate, typically a 2%, 3% and 4% samples;
and for a 1% concentrate, typically a 0.5%, 1% and 1.5%
samples are made.
Label bottles with percent sample calibration solution that
will be utilized, i.e. 2%, 3% and 4% for a 3% concentrate.
As an example, for the 2% calibration solution sample,
measure 98 ml of system water in the graduate cylinder,
then pour into the bottle labeled 2%. Then with the measuring syringe, transfer 2 ml (2 cc) of the concentrate into the
labeled bottle. Secure the cap on the bottle and shake to
thoroughly mix the solution. Repeat for the 3% calibration
sample (97 ml water and 3 ml concentrate) and for the 4%
calibration sample (96 ml water and 4 ml concentrate).
Increasing sample sizes will increase accuracy relative
to the measurement instrument. After thoroughly mixing
the foam sample, a meter reading is taken of each percentage foam solution sample. It is important that temperatures
between discharge samples and calibration standards have
normalized with temperatures above 50 F (10 C) working
best. Each instrument has specific instructions for its
correct operation.

Using the graph paper, plot the meter reading on the X axis
and the percent concentrate reading on the Y axis. This
plotted curve will serve as the known baseline for the
proportioning test. Meters may have different scales and
the plotted resolution should be as large as possible with
the complete range of the calibration solutions known. The
scale you set must be linear.
Collect foam solution sample(s) from the proportioning
system, using care to ensure that each sample is taken at
an adequate distance downstream from the proportioner
being tested. (Usually any place downstream of the first
change in direction is adequate if samples are taken in the
riser room.) Stabilize a water flow through your discharge
device within the known acceptable range for the proportioner and open the concentrate control valve. Take the
sample about 30 to 60 seconds after foam appears from
the test connection. Take meter readings of the sample(s)
and compare readings to the plotted curve to determine the
percentage for each sample.
Per NFPA 11, Standard for Low-, Medium-, and HighExpansion Foam, acceptable ranges of proportioning
systems are not less than the rated concentration and not
more than 30% above the rated concentration or one
percentage point above the rated concentration, whichever
is less. For example, the acceptable range for a 3%
concentrate is from 3 to 3.9%.
Note: There is some variability dependent on the accuracy
of the meter, the accuracy to which the calibration samples
were made, and if temperatures between calibration standards and discharge samples have not normalized.
Conductivity is especially susceptible to reading fluctuation,
thus the sample should be continuously stirred until a stabilized reading can be estimated. Care should be taken to
not bump the sides or bottom of the sample container or
contaminate the sample with salts or solids, i.e. dirty fingers
while stirring. The conductivity of water stored in or for
systems can vary throughout a discharge which may affect
results. Conductivity should not be used for sea, salt, or
brackish water supplies. Although conductivity can be the
most accurate means of measuring foam solution in clean
water supplies under ideal conditions, the refractive index
method is best for most real world testing.
If discharge samples are sent to the Tyco Fire Protection
Products Test Lab for analysis, they should be packaged
per the instructions with the Test Kit and sent in for immediate processing. Largely dependent on water quality and the
type of concentrate used, foam solutions may start to
biodegrade in a short period of time which can affect results
(possibly as little as three to five days with nutrient-rich
water and detergent-based foam concentrates).
The following graphs are examples of typical refractive
index values for various concentrate pre-mixes. Results
may vary depending on the concentrate pre-mix type, site
water supply, and actual concentrate lot number. Therefore,
it is important that a new calibration curve be developed on
each date a proportioning test is required.

TypICal CalIbRaTION CURve ResUlTs WheN UsINg paRT NO. 405713 haNDhelD ReFRaCTOmeTeR
Page 3

006876

NOTes
Page 4

NOTes:

FIelD INspeCTION ReCORD


Page 5
CUSTOMER/LOCATION: ____________________________________________________________ FILE NO.: ____________
DATE: __________________________________________ TESTED BY: __________________________________________
FOAM CONCENTRATE TYPE / LOT NO.:______________________________________________________________________
METER TYPE:________ CONDUCTIVITY:________ REFRACTOMETER MODEL: __________________________________
CALIBRATION STANDARDS

METER READING

FOAM CONCENTRATE
WATER
PRE-MIX #1
PRE-MIX #2
PRE-MIX #3

PERCENT FOAM SOLUTION

CalIbRaTION CURve

METER READING

SYSTEM DISCHARGE SAMPLE

METER READING

PERCENT FOAM SOLUTION

Part No. 31274-07

Copyright 2011 Tyco Fire Protection0 Products

All rights reserved.

TYCO FIRE PROTECTION PRODUCTS


ONE STANTON STREET
MARINETTE, WI 54143-2542

TYCO FIRE PROTECTION PRODUCTS


MARINETTE, WI 54143-2542

Copyright 2011 Tyco Fire Protection Products. All rights reserved.

VerTICal
blaDDer TaNKS

Form No. F-8579-02

FOAM SYSTEMS
PARTS LIST

VerTICalblaDDerTaNKS

FIGure
NO.

ParT
NO.

DeSCrIPTION

ParTS COmmON TO mODelS 50 GallONS


ThrOuGh 1500 GallONS
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
22
23

Ball Valve 1 in.


Short Nipple 1 in.
Elbow 1 in. x 90
Pipe 1 in.
Tee 1 in.
Reducing Bushing
1 in. x 1/2 in.
Pipe Plug 1/2 in.
Bracket Nameplate
Bracket Nameplate
Bracket Nameplate
Bracket Nameplate
Machine Screw
Ring Pin
Chain
Pop Rivet
Visual Seal
Nameplate
Center Tube
Bladder

68338
19841
26039
19875
19872
19873
16450
68335
68826
68779
68777
70150
598
2367
25423
25940
63421
See Table 1
See Table 1

19
20
21

Reducing Bushing
2 1/2 in. x 1 in.
Tee 2 1/2 in.
Pipe Plug 2 1/2 in.
Short Nipple 2 1/2 in.

19
20
21

Reducing Bushing
3 in. x 1 in.
Tee 3 in.
Pipe Plug 3 in.
Short Nipple 3 in.

24080
23555
71181
16526

ParT
NO.

31
31
31
31
31
31
31

31
31
31

7 11 4 4

32

19974
16085
19825

32

SIze
ParT NO. ParT NO. ParT NO.
ParT NO.
GallONS ePOxy
eNamel CeNTer Tube blaDDer
50
70501
70502
70514
70504
100
69000
69001
69040
69030
150
70516
70517
70519
70505
200
69002
69003
69041
69031
300
69004
69005
69042
69032
400
419153
419154
419173
419168
500
419155
419156
419174
419169
600
69010
69011
69045
69035
700
69012
69013
69046
69036
800
419157
419158
419175
419170
900
419159
419160
419176
419171
1000
419161
419162
419177
419172
1100
71118
71119
71128
70970
1200
71120
71121
71129
70971
1300
71122
71123
71130
70972
1400
71124
71125
71131
70973
1500
71126
71127
71132
70974

Short Nipple 1/2 in.


Ball Valve 1/2 in.
Tube Connector
Tubing (Length as Required)
Mounting Bracket
Caplug
Nameplate

19836
68425
68424
68423
68422
68421
68426

NamePlaTeS aND maNual

Table 1

002552

24
25
26
27
28
29
30

31

ParTS COmmON TO mODelS 1100 GallONS


ThrOuGh 1500 GallONS
18

DeSCrIPTION

SIGhT GauGe OPTIONal

ParTS COmmON TO mODelS 50 GallONS


ThrOuGh 1000 GallONS
18

FIGure
NO.

ANSULITE 1% AFFF Concentrate


ANSULITE 3% AFFF Concentrate
ANSULITE 6% AFFF Concentrate
ANSULITE AFFF Freeze Protected
3% Concentrate
ANSULITE 3x3 Low Viscosity
(Alcohol Resistant Concentrate)
3%
ANSULITE ARC (Alcohol
Resistant Concentrate) 3%
ANSULITE ARC (Alcohol
Resistant Concentrate) 6%
ANSUL 3% Fluoroprotein
Concentrate
ANSUL 3% Protein Concentrate
JET-X 2% High-Expansion
Foam Concentrate
JET-X 2 3/4% High-Expansion
Foam Concentrate
Manual, Operation and
Maintenance
Nameplate, 20 x 12 in.
(508 x 305 mm)
Nameplate, 30 x 18 in.
(762 x 457 mm)

67691
67690
67692
67693
435627
67694
67695
72418
72616
436887
72765
74177
438812
438813

VerTICalblaDDerTaNKS

FIGure
NO.

ParT
NO.

DeSCrIPTION

ParTS COmmON TO mODelS 50 GallONS


ThrOuGh 1500 GallONS
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
22
23

Ball Valve 1 in.


Short Nipple 1 in.
Elbow 1 in. x 90
Pipe 1 in.
Tee 1 in.
Reducing Bushing
1 in. x 1/2 in.
Pipe Plug 1/2 in.
Bracket Nameplate
Bracket Nameplate
Bracket Nameplate
Bracket Nameplate
Machine Screw
Ring Pin
Chain
Pop Rivet
Visual Seal
Nameplate
Center Tube
Bladder

68338
19841
26039
19875
19872
19873
16450
68335
68826
68779
68777
70150
598
2367
25423
25940
63421
See Table 1
See Table 1

19
20
21

Reducing Bushing
2 1/2 in. x 1 in.
Tee 2 1/2 in.
Pipe Plug 2 1/2 in.
Short Nipple 2 1/2 in.

19
20
21

Reducing Bushing
3 in. x 1 in.
Tee 3 in.
Pipe Plug 3 in.
Short Nipple 3 in.

24080
23555
71181
16526

ParT
NO.

31
31
31
31
31
31
31

31
31
31

7 11 4 4

32

19974
16085
19825

32

SIze
ParT NO. ParT NO. ParT NO.
ParT NO.
GallONS ePOxy
eNamel CeNTer Tube blaDDer
50
70501
70502
70514
70504
100
69000
69001
69040
69030
150
70516
70517
70519
70505
200
69002
69003
69041
69031
300
69004
69005
69042
69032
400
419153
419154
419173
419168
500
419155
419156
419174
419169
600
69010
69011
69045
69035
700
69012
69013
69046
69036
800
419157
419158
419175
419170
900
419159
419160
419176
419171
1000
419161
419162
419177
419172
1100
71118
71119
71128
70970
1200
71120
71121
71129
70971
1300
71122
71123
71130
70972
1400
71124
71125
71131
70973
1500
71126
71127
71132
70974

Short Nipple 1/2 in.


Ball Valve 1/2 in.
Tube Connector
Tubing (Length as Required)
Mounting Bracket
Caplug
Nameplate

19836
68425
68424
68423
68422
68421
68426

NamePlaTeS aND maNual

Table 1

002552

24
25
26
27
28
29
30

31

ParTS COmmON TO mODelS 1100 GallONS


ThrOuGh 1500 GallONS
18

DeSCrIPTION

SIGhT GauGe OPTIONal

ParTS COmmON TO mODelS 50 GallONS


ThrOuGh 1000 GallONS
18

FIGure
NO.

ANSULITE 1% AFFF Concentrate


ANSULITE 3% AFFF Concentrate
ANSULITE 6% AFFF Concentrate
ANSULITE AFFF Freeze Protected
3% Concentrate
ANSULITE 3x3 Low Viscosity
(Alcohol Resistant Concentrate)
3%
ANSULITE ARC (Alcohol
Resistant Concentrate) 3%
ANSULITE ARC (Alcohol
Resistant Concentrate) 6%
ANSUL 3% Fluoroprotein
Concentrate
ANSUL 3% Protein Concentrate
JET-X 2% High-Expansion
Foam Concentrate
JET-X 2 3/4% High-Expansion
Foam Concentrate
Manual, Operation and
Maintenance
Nameplate, 20 x 12 in.
(508 x 305 mm)
Nameplate, 30 x 18 in.
(762 x 457 mm)

67691
67690
67692
67693
435627
67694
67695
72418
72616
436887
72765
74177
438812
438813

TYCO FIRE PROTECTION PRODUCTS


MARINETTE, WI 54143-2542

Copyright 2011 Tyco Fire Protection Products. All rights reserved.

VerTICal
blaDDer TaNKS

Form No. F-8579-02

FOAM SYSTEMS
PARTS LIST

TYCO FIRE PROTECTION PRODUCTS


MARINETTE, WI 54143-2542

Copyright 2011 Tyco Fire Protection Products. All rights reserved.

hOrIzONTAl
blADDer TANKS

Form No. F-85114-02

FOAM SYSTEMS
PARTS LIST

hOrIzONTAlblADDerTANKS

FIGure
NO.

DeSCrIPTION

PArT
NO.

PArTS COmmON TO mODelS 100 GAllONS


ThrOuGh 3000 GAllONS
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
25
26
27

Ball Valve 1 in.


Short Nipple 1 in.
Elbow 1 in. x 90
Pipe 1 in.
Tee 1 in.
Reducing Bushing
1 in. x 1/2 in.
Pipe Plug 1/2 in.
Bracket Nameplate
Bracket Nameplate
Bracket Nameplate
Bracket Nameplate
Machine Screw
Ring Pin
Chain
Pop Rivet
Visual Seal
Nameplate
U-Bolt 1/4-20
Lockwasher 1/4 in.
Hex Nut 1/4-20
Center Tube Vertical
Center Tube Horizontal
Bladder

68338
19841
26039
19875
19872
19873
16450
68335
68826
68779
68777
70150
598
2367
25423
25940
63421
17249
1133
18107
See Table 1
See Table 1
See Table 1

22
23
24

Reducing Bushing
2 1/2 in. x 1 in.
Tee 2 1/2 in.
Pipe Plug 2 1/2 in.
Short Nipple 2 1/2 in.

Reducing Bushing 3 in. x 1 in.


Tee 3 in.
Pipe Plug 3 in.
Short Nipple 3 in.

28
29
30
31
32
33
34

PArT
NO.

35
35
35
35
35
35
35
35
35
35
35

23555
71181
16526

Short Nipple 1/2 in.


Ball Valve 1/2 in.
Tube Connector
Tubing (Length as Required)
Mounting Bracket
Caplug
Nameplate

19836
68425
68424
68423
68422
68421
68426

NAmePlATeS AND mANuAl

24080

36
36

PArTS COmmON TO mODelS 1100 GAllON


ThrOuGh 3000 GAllON
21
22
23
24

DeSCrIPTION

SIGhT GAuGe OPTIONAl

PArTS COmmON TO mODelS 100 GAllONS


ThrOuGh 1000 GAllONS
21

FIGure
NO.

71144
19974
16085
19825

TAble 1
PArT NO.
PArT NO.
SIze
PArT NO. PArT NO. CeNTer Tube CeNTer Tube PArT NO.
GAllONS ePOxy
eNAmel VerTICAl
hOrIzONTAl blADDer
100
69090
69091
69140
69130
69120
150
70521
70522
69141
70534
70525
200
69092
69093
69141
69131
69121
300
69094
69095
69142
69132
69122
400
419178
419179
69144
419198
419193
500
419180
419181
69144
419199
419194
600
69100
69101
69144
69135
69125
700
69102
69103
69144
69136
69126
800
419182
419183
69144
419200
419195
900
419184
419185
69144
419201
419196
1000
419186
419187
69144
419202
419197
1100
71100
71101
71142
71133
70975
1200
71102
71103
71142
71134
70976
1300
71104
71105
71142
71135
70977
1400
71106
71107
71142
71136
70978
1500
71108
71109
71142
71137
70979
1600
71110
71111
71142
71138
70980
1700
71112
71113
71142
71139
70981
1800
71114
71115
71142
71140
70982
1900
71116
71117
71142
71141
70983
2000
71150
71151
71143
71162
70984
2200
71152
71153
71143
71163
70985
2400
71154
71155
71143
71164
70986
2600
71156
71157
71143
71165
70987
2800
71158
71159
71143
71166
70988
3000
71160
71161
71143
71167
70989

ANSULITE 1% AFFF Concentrate


ANSULITE 3% AFFF Concentrate
ANSULITE 6% AFFF Concentrate
ANSULITE AFFF Freeze
Protected 3% Concentrate
ANSULITE 3x3 Low Viscosity
(Alcohol Resistant Concentrate)
3%
ANSULITE ARC (Alcohol
Resistant Concentrate) 3%
ANSULITE ARC (Alcohol
Resistant Concentrate) 6%
ANSUL 3% Fluoroprotein
Concentrate
ANSUL 3% Protein Concentrate
JET-X 2% High-Expansion
Foam Concentrate
JET-X 2 3/4% High-Expansion
Foam Concentrate
Manual, Operation and
Maintenance
Nameplate, 20 x 12 in.
(508 x 305 mm)
Nameplate, 30 x 18 in.
(762 x 457 mm)

67691
67690
67692
67693
435627
67694
67695
72418
72616
436887
72765
74177
438812
438813

hOrIzONTAlblADDerTANKS

FIGure
NO.

DeSCrIPTION

PArT
NO.

PArTS COmmON TO mODelS 100 GAllONS


ThrOuGh 3000 GAllONS
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
25
26
27

Ball Valve 1 in.


Short Nipple 1 in.
Elbow 1 in. x 90
Pipe 1 in.
Tee 1 in.
Reducing Bushing
1 in. x 1/2 in.
Pipe Plug 1/2 in.
Bracket Nameplate
Bracket Nameplate
Bracket Nameplate
Bracket Nameplate
Machine Screw
Ring Pin
Chain
Pop Rivet
Visual Seal
Nameplate
U-Bolt 1/4-20
Lockwasher 1/4 in.
Hex Nut 1/4-20
Center Tube Vertical
Center Tube Horizontal
Bladder

68338
19841
26039
19875
19872
19873
16450
68335
68826
68779
68777
70150
598
2367
25423
25940
63421
17249
1133
18107
See Table 1
See Table 1
See Table 1

22
23
24

Reducing Bushing
2 1/2 in. x 1 in.
Tee 2 1/2 in.
Pipe Plug 2 1/2 in.
Short Nipple 2 1/2 in.

Reducing Bushing 3 in. x 1 in.


Tee 3 in.
Pipe Plug 3 in.
Short Nipple 3 in.

28
29
30
31
32
33
34

PArT
NO.

35
35
35
35
35
35
35
35
35
35
35

23555
71181
16526

Short Nipple 1/2 in.


Ball Valve 1/2 in.
Tube Connector
Tubing (Length as Required)
Mounting Bracket
Caplug
Nameplate

19836
68425
68424
68423
68422
68421
68426

NAmePlATeS AND mANuAl

24080

36
36

PArTS COmmON TO mODelS 1100 GAllON


ThrOuGh 3000 GAllON
21
22
23
24

DeSCrIPTION

SIGhT GAuGe OPTIONAl

PArTS COmmON TO mODelS 100 GAllONS


ThrOuGh 1000 GAllONS
21

FIGure
NO.

71144
19974
16085
19825

TAble 1
PArT NO.
PArT NO.
SIze
PArT NO. PArT NO. CeNTer Tube CeNTer Tube PArT NO.
GAllONS ePOxy
eNAmel VerTICAl
hOrIzONTAl blADDer
100
69090
69091
69140
69130
69120
150
70521
70522
69141
70534
70525
200
69092
69093
69141
69131
69121
300
69094
69095
69142
69132
69122
400
419178
419179
69144
419198
419193
500
419180
419181
69144
419199
419194
600
69100
69101
69144
69135
69125
700
69102
69103
69144
69136
69126
800
419182
419183
69144
419200
419195
900
419184
419185
69144
419201
419196
1000
419186
419187
69144
419202
419197
1100
71100
71101
71142
71133
70975
1200
71102
71103
71142
71134
70976
1300
71104
71105
71142
71135
70977
1400
71106
71107
71142
71136
70978
1500
71108
71109
71142
71137
70979
1600
71110
71111
71142
71138
70980
1700
71112
71113
71142
71139
70981
1800
71114
71115
71142
71140
70982
1900
71116
71117
71142
71141
70983
2000
71150
71151
71143
71162
70984
2200
71152
71153
71143
71163
70985
2400
71154
71155
71143
71164
70986
2600
71156
71157
71143
71165
70987
2800
71158
71159
71143
71166
70988
3000
71160
71161
71143
71167
70989

ANSULITE 1% AFFF Concentrate


ANSULITE 3% AFFF Concentrate
ANSULITE 6% AFFF Concentrate
ANSULITE AFFF Freeze
Protected 3% Concentrate
ANSULITE 3x3 Low Viscosity
(Alcohol Resistant Concentrate)
3%
ANSULITE ARC (Alcohol
Resistant Concentrate) 3%
ANSULITE ARC (Alcohol
Resistant Concentrate) 6%
ANSUL 3% Fluoroprotein
Concentrate
ANSUL 3% Protein Concentrate
JET-X 2% High-Expansion
Foam Concentrate
JET-X 2 3/4% High-Expansion
Foam Concentrate
Manual, Operation and
Maintenance
Nameplate, 20 x 12 in.
(508 x 305 mm)
Nameplate, 30 x 18 in.
(762 x 457 mm)

67691
67690
67692
67693
435627
67694
67695
72418
72616
436887
72765
74177
438812
438813

TYCO FIRE PROTECTION PRODUCTS


MARINETTE, WI 54143-2542

Copyright 2011 Tyco Fire Protection Products. All rights reserved.

hOrIzONTAl
blADDer TANKS

Form No. F-85114-02

FOAM SYSTEMS
PARTS LIST