TPO 7x.xx
Outdoor current transformers
The TPO 7x.xx transformers are cast in epoxy resin,
capable of withstanding outdoor environmental
conditions, and designed for insulation voltages
to 40.5 kV.
Description
The TPO 7x.xx transformers are designed as single-or-multiple turn
transformers, with one transformer ratio, and, if necessary, with the
possibility to be reconnectable on the primary or secondary side.
The number of secondary windings ranges from 1 to 4 (usually 2) depending on parameters (such as the accuracy class,
short-circuit current, overcurrent factor, burden).
Parameters
[A]
10 3000
[A]
20-40 600-1200
[A]
5; 1
1)
2)
Rated frequency
[Hz]
50; 60
[kV]
up to 40.5
[kV]
up to 90
[kV]
up to 200
[kA]
100
The secondary windings are used for measurement or protection purposes, or for special use (testing windings, PX
class). One terminal of each secondary winding used, and
one terminal of the unused, short-circuited, winding must be
earthed during the transformer operation.
voltage (peak)
Rated short time thermal current,
1 sec.
Max. rated burden/classes
3)
Temperature class
Ambient temperature
Reconnectable
1)
2)
The secondary winding is led out into a cast secondary terminal board covered with a sealable cover.
The transformers are designed and manufactured to conform
with the requirements and recommendations of the following
standards: IEC, VDE, ANSI, BS, GOST, SN and PN-EN.
E
[C]
3)
-60...+55
primary or secondary
Dimensions
TPO 70.11
TPO 70.12
2 TPO 7x.xx
weight: approx. 90 kg
creepage distance: 1600 mm
weight: approx. 90 kg
creepage distance: 1600 mm
TPO 71.11-76.11
weight: approx. 90 kg
creepage distance: 1600 mm
Basic marking
36/70/170 kV
38.5/80/180 kV
40.5/95/200 kV
... design
P2 (L)
S1
(k)
S2
(l)
a) Single-core design
P1 (K)
S1
(k)
P1 (K)
1S1
(1k)
S3
(l2)
d) S
ingle-core design, reconnectable
on the secondary side
1S2 2S1
(1l) (2k)
P1 (K)
1S1
(1k)
P2 (L)
P1 (K)
2S2
(2l)
b) Double-core design
P2 (L)
S2
(l1)
P2 (L)
1S1
(1k)
1S2 2S1
(1l) (2k)
2S2 3S1
(2l) (3k)
3S2
(3l)
c) Three-core design
P1
(Ka)
P2 (L)
2S2 2S3
(2l1) (2l2)
e) D
ouble-core design, reconnectable
on the secondary side
1S1
(1k)
C1 C2
(Kb) (La)
1S2 2S1
(1l) (2k)
P2
(Lb)
2S2
(2l)
f) D
ouble-core design, reconnectable
on the primary side
TPO 7x.xx 3
Wereserve the right tomake technical changes or modify the contents of this
document without prior notice. With regard topurchase orders, the agreed
particulars shall prevail. ABB Sp. zo.o. does not accept any responsibility
whatsoever for potential errors or possible lack of information in this document.
Wereserve all rights in this document and in the subject matter and illustrations
contained therein. Any reproduction, disclosure tothird parties or utilization of its
contents in whole or in parts is forbidden without prior written consent of
ABB Sp. zo.o.
Copyright 2011 ABB
All rights reserved