Beruflich Dokumente
Kultur Dokumente
Extent of
damage
Fault level
Duration of
fault
Winding failures
Voltage
regulating load
changers
Transformer
faults
Transformer
bushing failure
Transformer core
problem
Miscellaneous
failures
Insulation
breakdown
Time
Improve cooling
system of
possible
Ageing of
insulation
Temperature
Condition
leading to faults
Over heating
due to excitation
Oil
contamination%
& oil leakage
Reduced cooling
Reduced load
FAULT OF TRANSFORMER
Differential relay
Percentage biased
Transformer
differential relay
Overall percentage
biased differential
relay
L.H&H.V Connection
circulating protection
Percentage biased
Transformer
differential relay
High REF impedance
Circulating current
differential
protection
HV side over current
and earth fault
relay
LV side over current
and earth fault
relay
Over excitation
relay
500/220KV AUTO
TRANSFORMER
Overall percentage
biased differential
relay
L.H&H.V Connection
circulating
protection
Tertiary over
current protection
Transformer
buchhloz relay
Tap changer
buchhloz relay
MECHANICAL
PROTECTION:
Winding
Temperature
0IL
temperature
Pressure
relieve valve
Factors:
The shape, magnitude and duration of the inrush
current depend on the factors:
Size of power transformer
Source Impendence
The magnetic properties of the core i.e.
saturation density
The remanence of core
Resistance in power system from source to
transformer.
The moment when transformer is switch on.
Yy0d5
51
51
HV2
HV1
LV
HV1
HV2
Time
LV
IF(LV)
IF(HV)
1.2IF(LV)
Current
LV
50
51
Differential Protection
Overall differential protection may be justified for larger
transformers (generally > 5MVA).
Measuring principle:
Based on the same circulating current principle as the
restricted earth fault protection
However, it employs the biasing technique, to maintain stability
for heavy thro fault current
Biasing allows mismatch between CT outputs.
It is essential for transformers with tap changing facility.
Another important requirement of transformer differential
Protection is immunity to magnetizing inrush current.
PROTECTED ZONE
HV
LV
BIAS I2
I1 - I2
OPERATE
RESTRAIN
I 1 - I2
I1 + I2
2
Bias =
Mean Thro
Current
LV restricted E/F
protection trips
both HV and LV breaker
Recommended setting : 10% rated
Protected zone
REF
A2
A1
P1
P2
a1
S1
S2
a2
REF
P1
S1
P2
S2
P2
P1
S1
S2
To differential relay
Ratio
correction
Vectorial
correction
Virtual interposing CT
Differential
element
Virtual interposing CT
P2
a2
a1
A1
A2
S2
S1 T2
T1
P1
P2
P2
P1
S2
S1
300/5
25MVA
11KV
1600/5
50MVA
33KV
1000/5
4.59
5.51
10.33
2.88
2.88
Transformer Magnetising
Characteristic
Twice
Normal
Flux
Normal
Flux
Normal
No
Load
Current
No Load
Current at
Twice Normal
Flux
Parallel Transformers
T1
T2
NABC
Inter-Turn Fault
E
CT
Load
Shorted
turn
Nominal turns ratio
Fault turns ratio
Current ratio
- 11,000 / 240
- 11,000 / 1
- 1 / 11,000
Conservator
5 x internal pipe
diameter (minimum)
Oil conservator
3 minimum
Transformer
Buchholz Relay
Petcock
Counter balance
weight
Alarm bucket
Mercury switch
Oil level
To oil
conservator
Trip bucket
From transformer
Aperture adjuster
Drain plug
Deflector plate
2m
Low frequency
High voltage
Geomagnetic disturbances
Ie
Effects
Tripping of differential element (Transient overfluxing)
Damage to transformers (Prolonged overfluxing)
V/H CHARACTERISTIC:
Over-fluxing Relay
Ex
VT
AVR
RL
THERMAL OVERLOAD:
EFFECT OF OVER LOAD ON TRANSFORMER
INSULATION LIFE:
Overheating Protection
Trip
I load
TD
setting
Top oil of
power
transformer
Alarm
On
Fan
control
I load
Off
On
Pump
control
Off
Temp. indication
Heater
Local
Thermal
replica
Temperature
sensing resistor
Remote
Overload Protection
Overcurrent protection designed for fault
condition
Thermal replica provides better protection
for overload
Time
Current based
Flexible characteristics
Single or dual time constant
Reset facility
Non-volatile
Current
Single
characteristic:
= 120 mins
1000
Dual characteristic
100
10
1
ZA
2
3
4
5
6
Current (multiple of thermal setting)
Single
characteristic:
= 5 mins