Greensboro, North Carolina Product Overview


Overhead Distribution Cutouts, Overhead Disconnect
Switches and Capacitor Fuses

greensboro overview.qxp

1/5/2005

11:16 AM

Page 2

Overhead Distribution Cutouts


Product

Description
Distribution cutout for use on
overhead distribution system to
provide overcurrent protection
Fuse tube interchangeable with
S&C Type XS, Cooper Type L,
and AB Chance Type C cutouts
ICX

15 kV 38 kV, up to 16 kA
Outdoor loadbreak switch that
can be used as a fused cutout
for distribution systems
Loadbreak interruption is
accomplished by means of a
self contained loadbreak arc
chute which confines the arc
and provides a deionizing action
15 kV 27 kV, up to 16 kA

LBU

Distribution cutout for overcurrent protection on overhead distribution systems


15 kV 38 kV, up to 20 kA

Application

Options

Enclosed cutouts in porcelain


housing
Designed for either dropout or
non-dropout operation

Product

Description

Application

Provides visible indication of


fuse operation and a visible
break sectionalizing point for
maintenance personnel

Silicone rubber insulator (110 180 kV BIL) or polymer concrete insulator (110 & 125 kV
BIL)

Single insulator disconnect with


a double blade door and two 2hole extended NEMA pad terminals

Single-phase disconnect on
overhead distribution feeders
and in outdoor distribution substations.

Can function as a loadbreak


switch when used in conjunction
with a portable loadbreak tool

Stainless steel seacoast design

15 kV 38 kV, 600 or 900 A


continuous loads with a 40 kA
momentary rating

Provides overcurrent protection


for capacitor banks and gives
visible indication that the equipment is energized

Silicone rubber insulator (110 180 kV BIL) or polymer concrete insulator (110 & 125 kV
BIL)

Can be mounted like a standard


cutout: underhung, mounted
directly on a pole for use as a
disconnect between overhead
and underground lines, or as a
visible disconnect for maintenance of line equipment

Used for switching the magnetizing currents of single and threephase transformer banks and to
switch capacitive currents associated with underground feeder
cable at the riser pole

Cutout/arrester combination

Loadbreak single insulator disconnect with self-contained


loadbreak capabilities, a double
blade door, and two 2-hole
NEMA pad terminals

Single-phase disconnect on
overhead distribution feeders
and in outdoor distribution substations

Provides visible indication of


fuse operation and a visible
break sectionalizing point for
maintenance personnel

Polymer concrete insulator


(110 & 125 kV BIL)

Cutout/arrester combination
Emission Control Device (ECD)

Used in replacement applications in close spaces where


there are increased safety
needs

SID

ECD

15.5 kV 15/27 kV, 600 A continuous and loadbreak

LSID
Double insulator single-phase
disconnect switch
Rated at 600 or 900 A, available
in nominal ratings of 14.4 kV
(110 BIL) or 25 kV (125 BIL)

N/A

DCD

For outdoor use only

Single-phase bypass disconnect


switch
Rated at 600 or 900 A, available
in nominal ratings of 14.4 kV
(110 BIL) or 25 kV (125 BIL)

Hookstick operated switch used


for sectionalizing or isolating
equipment on electrical distribution systems up to 38 kV
Can be mounted vertical or
underhung, or on a single or
double crossarm
Provides a means for bypassing
and disconnecting reclosers or
voltage regulators, allowing
maintenance on equipment without service interruption
Can be mounted in the following
configurations: vertical or underhung, pole-mounted, or single or
double crossarm

RBD
Single-phase, non-loadbreak,
inline tension disconnect switch
with silicone insulator
Maximum voltage ratings: 15 kV
(150 BIL) or 27 kV (150 BIL)
Continuous current rating of 600
or 900 A
ITD

-2-

Self-contained loadbreak
enables lineman to interrupt load
current with a hookstick
Can be mounted underhung like
a standard cutout or mounted
directly on a pole used as a disconnect between overhead and
underground lines

Cutout/arrester combination

Can function as a loadbreak


switch when used in conjunction
with a portable loadbreak tool

NCX

EU

Overhead Disconnect Switches

Used for manual switching of


de-energized or parallel circuits
of overhead distribution lines
rated 15-38 kV
Loadbreak hooks allow for operation with a portable loadbuster
tool

-3-

Options
Polymer concrete insulator
(110 & 125 kV BIL)
Optional mounting kit allows
the following mounting scenarios: single or double crossarm
underhung, directly on a pole,
directly on a pole vertically,
and crossarm vertically

Polymer concrete insulator


(110 & 125 kV BIL)
Optional mounting kit allows
the following mounting scenarios: single or double crossarm
underhung, directly on a pole,
directly on a pole vertically,
and crossarm vertically

Insulators available in 2.25


bolt circle porcelain or epoxy
Bypass studs available for
bypassing reclosers, voltage
regulators, capacitor banks, or
metering devices
Insulators available in 2.25
bolt circle porcelain or epoxy
Mounting options: back bracket
for vertical or underhung, 30degree pole-mount bracket, or
package of three switches premounted on crossarm

N/A

greensboro overview.qxp

1/5/2005

11:17 AM

Page 4

Capacitor Fuses
Indoor
600 V Current Limiting
Continuous amperes: 25, 50, 75, 100, 125, 150, 175, 200, 225
CLN

Primary application is individual unit fusing of low voltage single and three phase capacitors in metal
enclosed equipment
1.2-4.3 kV Current Limiting
The 1200, 1800 and 3000 volt ratings are current limiting, indicating and non disconnecting
The 2500 volt and 4.3/2.5 kV ratings are current limiting, non-indicating and non-disconnecting
Primary application is individual unit fusing of low voltage single and three phase capacitors in metal
enclosed equipment

CLC

5.5-15.5 kV Current Limiting & Expulsion


Two part design:
- the high current section interrupts high 60Hz fault currents and/or high frequency discharge current
from parallel capacitors
- the low voltage sections consist of a standard NEMA type K fuse link mounted in a fiber tube
CIL

Outdoor
9.7-26.2 kV Expulsion
Primary application is individual capacitor unit fusing in outdoor capacitor equipment
CXP

Applications: in all ungrounded wye applications, in all grounded wye applications when the capacitor
units are connected in two or more series group
2.8-23 kV Current Limiting & Expulsion
Two part design:
- the high current section interrupts high 60Hz fault currents and/or high frequency discharge current
from parallel capacitors
- the low voltage sections consists of a standard NEMA type K fuse link mounted in a fiber tube

COL

2.5-25 kV Current Limiting & Expulsion

1VAG0001-DB Rev. A October 2004


Copyright 2004 ABB. All rights reserved.

CLXP

A very high energy capability individual capacitor fuse used in outdoor banks with many parallel