Beruflich Dokumente
Kultur Dokumente
Flowrite
SKB/C/D
Valve Actuator
Section 1 Overview
Introduction 1-1
The Siemens Differential Pressure Feedwater Control (DPFC) is an integrated system based on
a highly accurate Differential Pressure (DP) transducer(s) coupled to a RWF40 universal
controller. The RWF40 controls the Feedwater valve actuator directly (electro-hydraulic
actuator), or through an I to P converter (Pneumatic valve actuator). Many different actuators
and feedwater valves are offered to accommodate different feedwater pressures and flows.
The DPFC may be used on Firetube and Watertube Boilers, as well as Deareators. It can be set
up as a single or a dual element level control, depending upon which sensors are connected.
ModBus communications are also available via the RWF40, allowing the DPFC to interface with
a building management system or a HMI (touch screen). These features make the DPFC
extremely flexible, and ideally suited for use on most steam boilers and Deareators.
Figure 1-1.1 Typical Single Element DPFC
-06
Page 1
Section 1
RWF40.002B97
7MF4433-NODISP
7MF4433-DISP
7MF4433-DISPR2
7MF94115BA
6-14-06
Page 2
Section 1
15965-659
SKC62UA
SKB62UA
6-14-06
Page 3
Section 1
599-10048
599-10049
599-10071
599-10065
ASC1.6
599-03xxx
599-06xxx
6-14-06
Page 4
Section 1
283-03xxx
545-208
201-1000
142-279
2 Pressure Guage
0 -100 PSIG
908-051
6-14-06
Page 5
Section 1
Universal Controller
7MF4433-DISP
7MF94115BA
SK(D,C,B)62UA
599-10048
599-10049
599-03xxx
Feedwater Valve
Installer
Supplied
7MF94115BA
Installer
Supplied
6-14-06
Page 6
Section 1
Protection against electrical shock hazard on all connected electrical components must be
ensured through good wiring and grounding practices.
The system must be cool and depressurized before any work is performed on the water /
steam side of the control. Failure to do this could result in severe injury or death.
Condensation and the entry of water into the electronics compartment of any component
must be avoided.
Approvals 1- 5
Table 1- 5.1 Standards and certificates
6-14-06
Page 7
Section 1
Section 2 Mounting
RWF40 Mounting 2-1
The RWF40 should be mounted inside an enclosure that will protect the RWF40 from dirt and
moisture. The unit is mounted through the face of an enclosure, and uses a lead screw on each
side of the casing to clamp the RWF40 to the panel face. It should be noted that the enclosure
cutout must be accurate, or the RWF40 will not mount correctly. Figure 2-1.1 Illustrates the
proper size cutout for the RWF40, and the overall dimensions of the RWF 40.
After the cutout has been made, RWF40 can be inserted through the cutout back first. The lead
screws can be clipped in either the top and bottom or the left and right sides. Figure 2-1.2
illustrates the lead screws clipped in the left and right sides. After this is done, tighten the lead
screws, clamping the RWF40 to the face of the enclosure. Figure 2-1.2 illustrates this
procedure, as well as RWF40 module removal.
Please see Section 6 for specifications.
Figure 2-1.1 RWF40 Enclosure Cutout and Overall Dimensions (Inches)
6-14-06
Page 1
Section 2
The Differential Pressure Transducer (DPT) can be used for two different types of sensing duty.
In a typical single element DPFC, the DPT functions as a level sensing device that can
accurately detect the difference in the level of two water columns. In a dual element DPFC, two
DPT are used, one to sense level and the other to sense differential pressure across a flow
element (orifice). This flow element is typically piped into the vessel outlet.
The DPT is supplied with hardware and brackets that permit many different mounting
orientations. The DPT is typically oriented right side up (transducer head above process
connections, process connections horizontal) but it may also be oriented so that the process
connections are vertical with the transducer head to the side. The DPT must not be oriented
upside down (transducer head below process connections). Acceptable orientations are shown
in Figure 2-2.1.
After the DPT has been mounted in one of the permissible mounting orientations, accessories
such as the 3-valve manifold or the flange kit may be mounted to the DPT. All necessary
hardware and gaskets are provided with the 3-valve manifold and the flange kit.
6-14-06
Page 2
Section 2
When mounting and tubing the DPT for level sensing, a few important points must be observed.
These points are as follows:
1. The DPT must be mounted on cold legs (drip legs) so that the water that the DPT is
exposed to is less than 200 o F.
6-14-06
Page 3
Section 2
2. The DPT must be mounted lower than the lowest measured level. This could be the bottom
of the vessel (possibly in a deareator), or this could be halfway up the side of a vessel (as is
done on a typical firetube boiler). The DPT can be mounted at any practical distance below
the vessel.
3. The reference leg (-) of the DPT must remain full and at a constant level during operation.
This is assured by using a Condensate Pot which is less than saturation temperature. The
reference leg and the Condensate Pot must be filled with clean water during the initial Startup. When used on steaming vessels (boilers and deaerators) the Condensate Pot will
remain completely full due to the steam condensing in the below saturation temperature
Condensate Pot.
4. The colder and larger the Condensate Pot, the better. For example, if the vessel is at
saturation at 100 PSIG steam pressure, the water in the vessel is about 338 oF. If the
Condensate Pot is distanced from the vessel (on a un-insulated pipe) the water in the
Condensate Pot will be less than 338 oF, and will have a much lower likelihood to flashing in
the event of rapid de-pressurization of the vessel. If the Condensate Pot is distanced
enough to be less than 212 oF, Condensate Pot flashing will never take place. Achieving a
temperature of 212 oF at the condensate pot is not always practical, so the effects of a rapid
de-pressurization event severe enough to cause Condensate Pot flashing can be minimized
by using a larger diameter, larger volume condensate pot.
5. Provisions should be made so that the DPT can be bled of air during start-up. This is
typically done by loosening the plugs on the DPT opposite the process connection when the
vessel is cold and under little or no pressure.
Figure 2-2.2 illustrates the preferred method of mounting a DPT and Condensate Pot to a
typical deaerator vessel. Figure 2-2.3 illustrates another acceptable method that can be used to
mount a DPT to a typical deaerator vessel. Figure 2-2.4 and 2-2.5 illustrate the preferred and
acceptable methods (respectively) for mounting a DPT and Condensate Pot to a typical firetube
boiler.
Figure 2-2.3 Preferred Mounting (Deaerator Vessel)
6-14-06
Page 4
Section 2
6-14-06
Page 5
Section 2
The difference between the preferred and the acceptable methods of mounting is the water
column. The water column with blowndown valve is preferred since it provides a container for
solids precipitation / separation, and also a means to flush these solids. This serves to keep the
working leg of the transducer more debris free. The water column also serves to dampen
turbulence that may be occurring in the vessel. Last but not least, the water column serves as
an additional thermal barrier for the Condensate Pot. Typically, water columns are constructed
from pressure rated 1 pipe.
The Condensate Pot is the most important part of the reference leg, and necessary for almost
all installations. This piece serves as a condensate reservoir that will not vary in level any great
degree even if condensate flashing (due to depressurization) takes place. As was previously
mentioned, the larger the Condensate Pot, the better. Specifically, it is best to make the
Condensate Pot internal diameter as large as practical, while maintaining a 6 to 10 inch overall
height. Figure 2-2.6 illustrates typical Condensate Pots.
6-14-06
Page 6
Section 2
Connection of the Condensate Pot to the DPT is usually accomplished with 3/8 Stainless Steel
tubing, but other tubing / pipe of different material and / or larger diameter will also perform
adequately.
If a second DPT is used to measure the DP across an orifice (as would be done in a two
element DPFC) the second DPT should be mounted and tubing installed according to Figure 22.8. The DPT is installed below the steam flow orifice for thermal isolation. The two pieces of
tubing going to the DPT (or legs) will fill up with water as the steam is cooled and condensed in
the metal tubing. Care should be taken to ensure the water legs going to the DPT are installed
so that the accumulated water in each leg is equal in height.
Figure 2-2.8 DPT Mounting for Steam Flow Orifice
6-14-06
Page 7
Section 2
6-14-06
Page 8
Section 2
6-14-06
Page 9
Section 2
6-14-06
Page 10
Section 2
6-14-06
Page 11
Section 2
If positive 0% stroke indication is desired, a limit switch can be added to the SKB/C/D. This
switch is an ASC1.6, and it features a SPDT design. This switch is mounted under the cover of
the SKB/C/D with small machine screws. The switch can be moved up and down slightly before
fully tightening the machine screws so that the activation point can be fine tuned.
6-14-06
Page 12
Section 2
6-14-06
Page 13
Section 2
The Pneumatic Feedwater Valve Actuator, when combined with the positioning relay offers
much improved control compared to the Pneumatic Feedwater Valve alone. The reason for this
is that the positioning relay is designed to achieve a given actuator position (actuator stroke) for
a given pneumatic signal. The positioning relay varies the air pressure to the diaphragm in the
feedwater valve actuator to achieve a certain actuator position which is monitored by the
feedback arm. The air pressure delivered to the actuator diaphragm can be greater or less than
the original pneumatic signal. The end result of the positioning relay is that the actuator and
therefore feewater valve position are largely unaffected by the differential pressure across the
feedwater valve.
If the positioning relay is not used, the differential pressure across the feedwater valve will
influence the actuator position, since the differential pressure causes pushing or pulling forces
on the valve stem. With these variable pushing or pulling forces present on the actuator stem, a
certain pneumatic signal will not always position the feedwater valve in the same place. For this
reason, the use of the positioning relay is recommended on deaerators (small to medium
variance in DP across the feedwater valve) and is highly recommended on boilers (medium to
large variance in DP across the feedwater valve).
The Pneumatic Valve Actuator, Feedwater valve, and Positioning relay are assembled and the
positioning relay calibrated prior to shipment. The positioning relay generally does not need to
be recalibrated in the field. However, if recalibration or replacement is necessary, calibration
instructions for the positioning relay can be found in a document entitled RL147 Positioning
Relay (Document Number 155-038P25).
Figure 2-5.1 Jumper Settings, Output of the Electric to Pneumatic Transducer (AO-P)
6-14-06
Page 14
Section 2
6-14-06
Page 15
Section 2