Sie sind auf Seite 1von 3

EWG 01.

1, RWG 4020, potentiometer


Technical data Electronic position transmitters/potentiometer
EWG 01.1
Contactless and wear-free sensing of the valve position by means of Hall sensors for signalling the valve position.
Data

3-wire or 4-wire system

2-wire system

Output current IA

0 20 mA, 4 20 mA

4 20 mA

Power supply UV1)

24 V DC (18 32 V)

24 V DC (18 32 V)

Max. current consumption

LED off = 26 mA, LED on = 27 mA

20 mA

Max. load RB

600

(UV 12 V)/20 mA

Impact of power supply

0.1 %

Load inuence

0.1 %

Temperature impact

< 0.1 /K
60 C to +80 C2)/+90 C2)

Ambient temperature

Notes on table
1) Power supply

Power supply possible via: AC, AM controls or external power supply

2) Ambient temperature

Depending on temperature range of the actuator: Refer to name plate

Wiring
3-wire system

2-wire system

EWG 01.1

EWG 01.1

EWG 01.1

4-wire system

Plug/socket connector XK
for customer connection

Plug/socket connector XK
for customer connection

20 21 22 23 24

21 22 23 24

2 3

Plug/socket connector XK
for customer connection

20 21 22 23 24

0 20 mA
4 20 mA

+24 V 0 V

4 20 mA

+24 V 0 V

0 20 mA
4 20 mA

LED
S1 (0/4 mA)

S2 (20 mA)

Measuring point 1 (+)


2-wire system
Measuring point 2 () 0/4 20 mA
3-wire and 4-wire system

Setting:

Setting is performed via push buttons S1 (0/4 mA) and S2 (20 mA). Refer to operation instructions relating to actuator.

Inverse operation: Observe inversed assignment of push buttons S1 and S2 during setting.
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.388/001/en

Issue 1.15

Page 1/3

EWG 01.1, RWG 4020, potentiometer


Technical data Electronic position transmitters/potentiometer
RWG 4020
On the basis of the actual potentiometer value, the RWG generates a current signal for signalling the valve position.
Data

3-wire or 4-wire system

2-wire system

Output current IA

0 20 mA, 4 20 mA

4 20 mA

24 V DC (18 32 V)

14 V DC + (I x RB), max. 30 V

1)

Power supply UV

Max. current consumption

24 mA at 20 mA output current

20 mA

Max. load RB

600

(UV 14 V)/20 mA

Impact of power supply

0.1 %/V

0.1 %/V

Load inuence

0.1 %/(0 600 )

0.1 %/100

Temperature impact

< 0.3 /K
60 C to +80 C2)/+90 C2)

Ambient temperature
Transmitter potentiometer

5 k

Notes on table
1) Power supply

Power supply possible via: AC, AM controls or external power supply

2) Ambient temperature

Depending on temperature range of the actuator: Refer to name plate

Wiring
2-wire system

3-wire system

4-wire system

RWG 4020

RWG 4020

RWG 4020

Plug/socket connector XK
for customer connection

Plug/socket connector XK
for customer connection

20 21 22 23 24

21 22 23 24

0 20 mA
4 20 mA

+24 V 0 V

4 20 mA

Plug/socket connector XK
for customer connection
20 21 22 23 24

+24 V 0 V

(20 mA)

(0/4 mA)
N

3-wire and 4-wire system

0 20 mA
4 20 mA

R2

Measuring point 1 (+)


Measuring point 2 () 0/4 20 mA

2-wire system

Setting:

Refer to the operation instructions relating to actuator.

Inverse operation: For inverse operation, exchange terminals 7 (red/RD) and 5 (black/BK) on position transmitter board.
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.388/001/en

Issue 1.15

Page 2/3

EWG 01.1, RWG 4020, potentiometer


Technical data Electronic position transmitters/potentiometer
Potentiometer
Travel sensor for recording the valve position.

Data

Precision wire
potentiometer

Precision lm
potentiometer

Precision wire
potentiometer
in tandem version

Precision lm
potentiometer
in tandem version

Recommended for

OPEN-CLOSE duty

Modulating duty

OPEN-CLOSE duty

Modulating duty

Independent linearity

1%

Resistance (standard)

0.2 k

5 k

0.2/0.2 k

1 k/5 k

Resistance (option)3)

0.1 k
0.5 k
1.0 k
2.0 k
5.0 k

1 k

0.5/0.5 k
1.0/1.0 k
0.1/5.0 k
0.2/5.0 k
1.0/5.0 k
5.0/5.0 k

1 k/1 k
5 k/5 k

Resistance tolerance

+/ 5 %

+/ 10 %

+/ 5 %

+/ 10 %

Rated power

1.5 W

0.5 W

1.5 W

0.5 W

Max. wiper current

30 mA

0.1 mA

30 mA

0.1 mA

Lifetime

100,000 cycles

5106 cycles

100,000 cycles

5106 cycles

+/ 1.5 %

+/ 2.0 %

60 to +120 C

60 to +90 C

60 to +120 C

60 to +90 C

Synchronous operation
2)

Ambient temperature

Notes on table
2) Ambient temperature

Depending on temperature range of the actuator: Refer to name plate

3) Resistance (option)

Further options on request

The position of the valve can be transmitted as a continuous signal by a potentiometer. The potentiometer is installed in the control unit of the actuator.
We recommend:
Using the potentiometer as voltage divider. Depending on the supply voltage, suitable series resistors are to be provided. Please observe max. rated
power.
For the tandem version, two signals can be evaluated by two potentiometers, e,g, one signal for external controls or one signal for AUMA AC integral
controls.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.388/001/en

Issue 1.15

Page 3/3

Das könnte Ihnen auch gefallen