Fixed-Mounted Circuit-Breaker Switchgear

Type NXPLUS C up to 24 kV, Gas-Insulated


Medium-Voltage Switchgear
Catalog HA 35.41 2007

Power Transmission and Distribution

Contents

Application
Types

Page

Types, typical uses,


ratings

2 to 4

R-HA35-105a eps

Application

Fixed-mounted circuitbreaker switchgear


NXPLUS C is a factoryassembled, type-tested,
metal-enclosed, metal-clad,
SF6-insulated switchgear
for single-busbar and
double-busbar applications
for indoor installation.

Requirements
Features, safety, technology

4 and 5

Technical Data
Electrical data
Room planning
Shipping data, classification

6 and 7
8
9

Dimensions
Front views, sections,
floor openings, fixing points

10 to 17

Product Range
Single-busbar panels
Double-busbar panels

18 to 20
21

Design
Basic panel design

22

Components
Vacuum circuit-breaker
Three-position switch
HV HRC fuse assembly
Vacuum contactor, motor protection
Busbars
Current and voltage transformers
Panel connection
Indicating and measuring equipment

23 and 24
25 and 26
27 and 28
29
30
31 to 33
34 to 39
40 to 43

Standards
Standards, specifications, guidelines

44 and 45

Notes
46
Invalid: Catalog HA 35.41 2005

Circuit-breaker panel (example)

The products and systems described in this catalog


are manufactured and sold according to a certified
quality and environmental management system
(acc. to ISO 9001 and ISO 14001).
(DQS Certificate Reg. No. DQS 003473 QM UM).
The certificate is accepted in all IQNet countries.

Siemens AG 2007
2 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

Application
R-HA35-122.tif

Typical uses
Application:
Public power supply system

R-HA35-106.eps

R-HA35-109.eps

Application:
Industry

R-HA35-107.eps

R-HA35-123.eps

NXPLUS C switchgear
20 kV (example)

Application:
Industry and offshore

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 3

Application

Requirements

Typical uses, ratings

Features

Fixed-mounted circuit-breaker switchgear


NXPLUS C is used in transformer
and switching substations, e.g., in:

Environmental independence

Innovations

Hermetically tight, welded


switchgear vessels made of
stainless steel make NXPLUS C
switchgear

The use of digital secondary systems and combined protection and


control devices ensures

Insensitive to aggressive

Clear integration in proc-

Power supply companies


Power stations
Cement industry
Automobile industry
Iron and steel works
Rolling mills
Mining industry
Textile, paper and food industries
Chemical industry
Petroleum industry
Pipeline installations
Offshore installations
Electrochemical plants
Petrochemical plants
Shipbuilding industry
Diesel power plants
Emergency power supply installations
Lignite open-cast mines
Traction power supply systems

ambient conditions, such as


Salt water
Air humidity
Dust
Temperature
Tight to ingress of foreign

bodies, such as
Dust
Pollution
Small animals
Independent of site altitude

Compact design
Thanks to the SF6 insulation,
compact dimensions are
possible
Thus,
Existing switchgear rooms

can be used effectively


New constructions cost little
Costly city-area space is saved

Electrical data (maximum values) and dimensions


Rated voltage
Rated frequency
Rated short-duration powerfrequency withstand voltage
Rated lightning impulse
withstand voltage
Rated peak withstand current
Rated short-circuit making
current
Rated short-time
withstand current 3 s
Rated short-circuit breaking
current
Rated normal current of busbar
Rated normal current of
feeders
Width
Depth without pressure
relief duct at the rear
with pressure
relief duct at the rear
Height

Maintenance-free design

kV
Hz
kV

7.2
12
15
17.5 24
50/60 50/60 50/60 50/60 50/60
20
28 1) 36
38
50

kV

60

75 1)

95

95

125

kA
kA

80
80

80
80

80
80

63
63

63
63

Personnel safety

kA

31.5

31.5

31.5

25

25

Sealed-for-life design accord-

kA

31.5

31.5

31.5

25

25

A
A

2500 2500 2500 2500 2500


2500 2500 2500 2000 2000

Switchgear vessels designed


as sealed pressure systems,
maintenance-free switching
devices and enclosed cable
plugs ensure
Maximized power supply

reliability

ing to IEC 62 271-200 (sealed


pressure system)
Installation, operation, exten-

sion and replacement without SF6 gas work


Reduced operating costs

mm 600 2) 600 2) 600 2) 600 2) 600 2)


mm 1100 1100 1100 1100 1100

Cost-efficient investment
No maintenance cycles

mm 1225 1225 1225 1225 1225


mm 2250 2250 2250 2250 2250

1) 42 kV/75 kV according to some


national requirements
2) 1200 mm for rated normal
feeder currents of 2000 A,
2300 A and 2500 A

4 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

ess control systems


Flexible and highly sim-

plified adaptation to new


system conditions and
thus to cost-efficient
operation

Requirements
Technology

Safety
Personal safety

Security of operation

General

Safe-to-touch and hermetical-

Hermetically sealed primary

Three-pole enclosure of the

ly sealed primary enclosure


Cable terminations, busbars

and voltage transformers are


surrounded by earthed layers
All high-voltage parts includ-

enclosure independent of
environmental effects (pollution, humidity and small
animals)
Maintenance-free in

ing the cable terminations,


busbars and voltage transformers are metal enclosed

an indoor environment
(IEC 62 271-1 and
VDE 0671-1)

Capacitive voltage detecting

Operating mechanisms of

system to verify safe isolation


from supply
Operating mechanisms and

auxiliary switches safely accessible outside the primary


enclosure (switchgear vessel)
Due to the system design,

operation is only possible


with closed switchgear enclosure
Standard degree of protec-

tion IP 65 for all high-voltage


parts of the primary circuit,
IP 3XD for the switchgear
enclosure according to
IEC 60 529 and VDE 0470-1
High resistance to internal

arcs by logical mechanical


interlocks and tested
switchgear enclosure
Panels tested for resistance to

internal faults up to 31.5 kA


Logical mechanical interlocks

prevent maloperation
Make-proof earthing by

means of the vacuum circuitbreaker

switching devices accessible


outside the primary enclosure (switchgear vessel)
Metal-coated, plug-in induc-

tive voltage transformers


mounted outside the SF6
switchgear vessel
Current transformers as

ring-core current transformers mounted outside the


SF6 switchgear vessel
Complete logical mechanical

interlocking system
Welded switchgear vessels,

sealed for life


Minimum fire load
Type and routine-tested
Standardized, NC production

processes
Quality assurance in accord-

ance with DIN EN ISO 9001


More than 500,000

switchgear panels of Siemens


in operation worldwide for
many years
Option: Aseismic design

Reliability
Type and routine-tested
Standardized, NC production

processes
Quality assurance in accord-

ance with DIN EN ISO 9001


More than 500,000

switchgear panels of Siemens


in operation worldwide for
many years

primary part consisting of a


switchgear vessel made of
stainless steel
Insulating gas SF6
Three-position switch as

busbar disconnector and


feeder earthing switch
Make-proof earthing by

means of the vacuum circuitbreaker


Compact dimensions due to

SF6 insulation
Hermetically tight, welded

switchgear vessel made of


stainless steel
Single-pole, solid-insulated,

screened busbars, plug-in


type
Cable connection with out-

side-cone plug-in system, or


for connection of solid-insulated bars
Wall-standing or free-stand-

ing arrangement
Cable connection access from

front
Option: Cable connection

access from rear (only circuitbreaker panel 1250 A)


Installation and extension of

existing switchgear on both


sides without gas work and
without modification of existing panels
Interlocks

Locking device for three-

position switch
Cable compartment cover

(access to HV HRC fuses)


always interlocked against
the three-position switchdisconnector in panels with
HV HRC fuses (switch-disconnector panel, metering panel
and contactor panel with
fuses)
Option: Cable compartment

cover interlocked against the


three-position switch (circuitbreaker panel, disconnector
panel, contactor panel without fuses, ring-main panel)
Option: Electromagnetic

interlocks
Option: Actuating openings

can be locked with padlocks


Option: Locking device for

feeder earthed
Modular design
Panel replacement possible

without SF6 gas work


Low-voltage compartment

can be removed, plug-in bus


wires
Transformers
Current transformers not

subjected to dielectric stress


Easy replacement of ring-core

current transformers
Metal-coated, plug-in and

disconnectable voltage transformers

According to IEC 62 271-200

and VDE 0671-200


Logical mechanical interlocks

prevent maloperation
Three-position disconnector

can only be operated with circuit-breaker in OPEN position


Circuit-breaker or contactor

can only be operated with


three-position switch in end
position and operating lever
removed
Switch-disconnector, contac-

tor, ring-main and metering


panels are not interlocked
due to their own switching
capacity
Three-position disconnector

interlocked against the circuit-breaker in circuit-breaker


panels and in bus sectionalizers with one panel width
Locking device for feeder

Vacuum circuit-breaker
Maintenance-free under

normal ambient conditions


according to IEC 62 271-1
and VDE 0671-1
No relubrication or readjust-

ment
Up to 10,000 operating

cycles
Vacuum-tight for life

Secondary systems
Numerical protection,

measuring and control


equipment
Option: Customary multi-

function protection relay with


integrated protection, control, communication, operating and monitoring functions
Can be integrated in process

control systems

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 5

Technical Data
Electrical data, filling pressure, temperature for single-busbar switchgear
Common
Rated insulation level
electrical data,
filling pressure
and
temperature

kV
Rated voltage Ur
Rated short-duration power-freq. withstand voltage Ud:
phase-to-phase, phase-to-earth, open contact gap kV
across the isolating distance
kV
Rated lightning impulse withstand voltage Up:
phase-to-phase, phase-to-earth, open contact gap kV
across the isolating distance
kV

Rated frequency fr
Rated normal current Ir 2) for the busbar
Rated filling level pre 3)
Minimum functional level pme 3)
Ambient air temperature

7.2

12

15

17.5

24

20
23

28 1)
32 1)

36
39

38
45

50
60

95
110

125
145

2500

2500

95
60
75 1)
85 1)
110
70
50/60 Hz
up to A 2500
2500
2500
150 kPa (absolute) at 20 C
130 kPa (absolute) at 20 C
5 C to +55 C

Panel data
Circuit-breaker Rated normal current Ir 2)
panel
for switchgear with tk = 1 s
Rated short-time
630 A
withstand current Ik
for switchgear with tk = 3 s
Rated peak withstand current Ip
Rated short-circuit making current Ima
Rated short-circuit breaking current Isc
Electrical endurance of at rated normal current
vacuum circuit-breakers at rated short-circuit breaking current

A
up to kA
up to kA
up to kA
up to kA
up to kA

630
630
630
20
25 20
25 20
20
20
20
50
63 50
63 50
50
63 50
63 50
20
25 20
25 20
10,000 operating cycles
50 breaking operations

Circuit-breaker Rated normal current Ir 2)


panel and bus
sectionalizer
1000 A 4)
1250 A 5)
2000 A
for switchgear with tk = 1 s
Rated short-time
2300 A
withstand current Ik
for switchgear with tk = 3 s
2500 A
Rated peak withstand current Ip
Rated short-circuit making current Ima
Rated short-circuit breaking current Isc
Electrical endurance of at rated normal current
vacuum circuit-breakers at rated short-circuit breaking current

A
A
A
A
A
up to kA
up to kA
up to kA
up to kA
up to kA

1000
1000
1000
1250
1250
1250
2000
2000
2000
2300
2300
2300
2500
2500
2500
31.5
31.5
31.5
31.5
31.5
31.5
80
80
80
80
80
80
31.5
31.5
31.5
10,000 operating cycles
50 breaking operations

25

63
63
25

630
20
20
50
50
20

25

63
63
25

630
20
20
50
50
20

1000
1250
2000

1000
1250
2000

25
25
63
63
25

25
25
63
63
25

200
25
25
63
63
442

200
25
25
63
63
442

Switchdisconnector
panel
(with HV HRC
fuses)

Rated normal current Ir 2) for feeder 6)


for switchgear with tk = 1 s
Rated short-time
withstand current Ik
for switchgear with tk = 3 s
Rated peak withstand current Ip 6)
Rated short-circuit making current Ima 6)
Dimension e of HV HRC fuse links

A
up to kA
up to kA
up to kA
up to kA
mm

200
31.5
31.5
80
80
292 7)

Ring-main
panel
(switchdisconnector
panel without
HV HRC fuses)

Rated normal current Ir 2) for feeder


for switchgear with tk = 1 s
Rated short-time
withstand current Ik
for switchgear with tk = 3 s
Rated peak withstand current Ip
Rated short-circuit making current Ima

A
up to kA
up to kA
up to kA
up to kA

630
630
630
630
630
20
25 20
25 20
25 20
25 20
20
20
20
20
20
50
63 50
63 50
63 50
63 50
50
63 50
63 50
63 50
63 50

Disconnector
panel
1000 A 4)
1250 A
2000 A
2300 A
2500 A

Rated normal current Ir 2)

A
A
A
A
A
up to kA
up to kA
up to kA

1000
1250
2000
2300
2500
31.5
31.5
80

for switchgear with tk = 1 s


for switchgear with tk = 3 s
Rated peak withstand current Ip
Rated short-time
withstand current Ik

Rated normal current Ir 2) for feeder 6)


for switchgear with tk = 1 s
Rated short-time
withstand current Ik
for switchgear with tk = 3 s
Rated peak withstand current Ip 6)
Rated short-circuit making current Ima 6)
Electrical endurance at rated normal current
Dimension e of HV HRC fuse links

A
up to kA
up to kA
up to kA
up to kA

for switchgear with tk = 1 s


Metering panel Rated short-time
(with HV HRC
withstand current Ik
for switchgear with tk = 3 s
fuses)
Rated peak withstand current Ip 6)
Dimension e of HV HRC fuse links

up to kA
up to kA
up to kA
mm

Contactor
panel
(with HV HRC
fuses)

200
31.5
31.5
80
80
292 7)

1000
1250
2000
2300
2500
31.5
31.5
80

200
31.5
31.5
80
80
442

1000
1250
2000
2300
2500
31.5
31.5
80

1000
1250
2000

1000
1250
2000

25
25
63

25
25
63

450
450
450
450
31.5 8)
31.5 8)
31.5 8)
25 8)
31.5 8)
31.5 8)
31.5 8)
25 8)
80
80
80
63
80
80
80
63
100,000 or 500,000 operating cycles
292 7)
442
442
mm 292 7)
31.5
31.5
80
292 7)

6 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

31.5
31.5
80
292 7)

31.5
31.5
80
442

25
25
63
442

450
25 8)
25 8)
63
63
442
25
25
63
442

25

63
63
25

Technical Data
Electrical data, filling pressure, temperature for double-busbar switchgear
Common
Rated insulation level
electrical data,
filling pressure
and
temperature

kV
Rated voltage Ur
Rated short-duration power-freq. withstand voltage Ud:
phase-to-phase, phase-to-earth, open contact gap kV
across the isolating distance
kV
Rated lightning impulse withstand voltage Up:
phase-to-phase, phase-to-earth, open contact gap kV
across the isolating distance
kV

7.2

12

15

17.5

24

20
23

28 1)
32 1)

36
39

38
45

50
60

95
110

125
145

2500

2500

95
60
75 1)
85 1)
110
70
50/60 Hz
up to A 2500
2500
2500
150 kPa (absolute) at 20 C
130 kPa (absolute) at 20 C
5 C to +55 C

Rated frequency fr
Rated normal current Ir 2) for the busbar
Rated filling level pre 3)
Minimum functional level pme 3)
Ambient air temperature

Panel data
Circuit-breaker Rated normal current Ir 2)
panel, bus
for switchgear with tk = 1 s
Rated short-time
coupler 9)
withstand current Ik
for switchgear with tk = 3 s
1000 A
Rated peak withstand current Ip
Rated short-circuit making current Ima
Rated short-circuit breaking current Isc
Electrical endurance of at rated normal current
vacuum circuit-breakers at rated short-circuit breaking current

A
up to kA
up to kA
up to kA
up to kA
up to kA

1000
1000
1000
25
25
25
25
25
25
63
63
63
63
63
63
25
25
25
10,000 operating cycles
50 breaking operations

1000
25
25
63
63
25

1000
25
25
63
63
25

Incoming
sectionalizer
1250 A

Rated normal current Ir 2)


for switchgear with tk = 1 s
Rated short-time
withstand current Ik
for switchgear with tk = 3 s
Rated peak withstand current Ip
Rated short-circuit making current Ima
Rated short-circuit breaking current Isc
Electrical endurance of at rated normal current
vacuum circuit-breakers at rated short-circuit breaking current

A
up to kA
up to kA
up to kA
up to kA
up to kA

1250
1250
1250
25
25
25
25
25
25
63
63
63
63
63
63
25
25
25
10,000 operating cycles
50 breaking operations

1250
25
25
63
63
25

1250
25
25
63
63
25

Further
panel types

The above-mentioned panel types can on request be combined


with panel types of the single-busbar range.

Footnotes for pages 6 and 7


1) Higher values of the rated shortduration power-frequency
withstand voltage available with:
42 kV for phase-to-phase,
phase-to-earth, open contact
gap as well as
48 kV across the isolating
distance
Higher values of the rated lightning
impulse withstand voltage:
95 kV for phase-to-phase, phase-toearth, open contact gap as well as
110 kV across the isolating distance
2) The rated normal currents apply
to ambient air temperatures of
max. 40 C. The 24-hour mean
value is max. 35 C
(acc. to IEC 62 271-1/ VDE 0671-1)
2300 A with natural ventilation
2500 A with forced ventilation
3) Pressure values for SF6 insulated
switchgear vessels

4) Bus sectionalizer panel 1000 A and


disconnector panel 1000 A only possible
with rated short-time withstand current Ik
25 kA, 1 s and 3 s, rated peak withstand current Ip 63 kA and rated shortcircuit breaking current ISC 25 kA
5) Bus sectionalizer panel 1250 A in
2 panel widths only possible with rated
short-time withstand current Ik 25 kA,
1 s and 3 s, rated peak withstand current Ip
63 kA and rated short-circuit breaking
current ISC 25 kA
6) Depending on the HV HRC fuse
link, observe max. permissible let-through
current ID of HV HRC fuse links
7) Extension tube (150 mm long)
required additionally
8) Applies to combination of vacuum
contactor with HV HRC fuses:
Vacuum contactor without HV HRC fuse
reaches rated short-time withstand
current Ik 8 kA, 1 s, and rated peak
withstand current Ip 20 kA (applies to
the complete switchgear)
9) Bus coupler 1250 A on request

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 7

Technical Data
Room planning
Switchgear arrangement
Room planning for single-busbar switchgear

B****

1100

B****

1100

B****

1225

125

tions:
Wall-standing arrangement
or
Free-standing arrangement
Face-to-face arrangement
accordingly

125*

50

For single-busbar applica-

Room dimensions
See opposite dimension
drawings

52
50***

Room height
2800 mm

52
50***

800**

tions:
Back-to-back arrangement
(free-standing arrangement)

HA35-2529e eps

For double-busbar applica-

Wall-standing arrangement (top view)


Panels without pressure relief duct

Wall-standing arrangement
(same as left side), but panels
with pressure relief duct

125*

Switchgear fastening

* 125-mm-deep pressure relief


duct at the rear
B****

For floor openings and fixing

1225

The door dimensions depend


on the dimensions of the
individual panels (see pages
10 to 17)

500

Door dimensions

B****

52
50***

Room height
2800 mm

52
50***

800**

Foundations:
Steel structure
Steel-reinforced concrete
with foundation rails,
welded or bolted on

HA35-2530c eps

points of the switchgear,


see pages 10 to 17

** Depending on national requirements; for extension/panel


replacement:
Control aisle 1400 mm
recommended
*** Lateral wall distances:
On the left or right W 500 mm
recommended
**** For panel width, see dimensions
on pages 10 to 17

Free-standing arrangement (top view)


Panels with pressure relief duct

Panel dimensions
See pages 10 to 17

Room planning for double-busbar switchgear

Weights
Single-busbar panels

800**

Panels for 1250 A:

Approx. 800 kg
Panels for > 1250 A:

Approx. 1400 kg
Double-busbar panels
Panels for 1250 A:
2370

Approx. 1600 kg

600

50***

Room height
2800 mm

52
500***

800**

HA35-2531b eps

** For panel replacement:


52

Free-standing arrangement (top view)

8 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

Control aisle W 1400 mm


necessary
*** Lateral wall distance
W 50 mm optionally
possible on the left or right

Technical Data
Shipping data, classification
Transport

Transport dimensions, transport weights 1)

NXPLUS C switchgear is delivered in form of individual panels.

Panel width

The following must be noted:

mm

Transport facilities on site


Transport dimensions and

weights
Size of door openings in

building
In case of double-busbar panels
the A and B sides are supplied
separately.
Packing
Place of destination inside
Germany or other European
countries
Means of transport:

Rail and truck

Transport dimensions
Width x Height x Depth

Transport weight
with packing

without packing

mm x mm x mm

approx. kg

approx. kg

Single-busbar switchgear
Transport inside Germany or to other European countries
1 x 600
1 x 1200
1 x 600 (cable connection top rear)

1100 x 2470 x 1450


1450 x 2470 x 1450
1100 x 2470 x 2100

900
1500
900

800
1400
800

1130 x 2650 x 1450


1480 x 2650 x 1450
1130 x 2650 x 2100

900
1500
900

800
1400
800

1100 x 2470 x 1450

900

800

1130 x 2650 x 1450

900

800

Transport overseas
1 x 600
1 x 1200
1 x 600 (cable connection top rear)

Double-busbar switchgear
Transport inside Germany or to other European countries
1 x 600

Type of packing:
Panels on open pallets
Open packing with PE
protective foil

Transport overseas

Place of destination overseas

Classification of the NXPLUS C switchgear according to IEC 62 271-200

Means of transport:

Ship
Type of packing:
Panels on open pallets
In closed crates with sealed
upper and lower PE
protective foil
With desiccant bags
With sealed wooden base
Max. storage time: 6 months

1 x 600

Design and construction


Partition class
Loss of service continuity category 2)
Panels
with HV HRC fuses
without HV HRC fuses
Accessibility to compartments (enclosure)
Busbar compartment
Switching-device compartment
Low-voltage compartment
Cable compartment
without HV HRC fuses
with HV HRC fuses

PM (metallic partition)

LSC 2A
LSC 2B
Tool-based
Non-accessible
Tool-based
Tool-based
Interlock-controlled and tool-based

Internal arc classification


Designation of internal arc classification IAC
IAC for
Wall-standing arrangement
Free-standing arrangement
Type of accessibility A
F
L
R
Arc test current
Test duration

7.2 kV, 12 kV, 15 kV


17.5 kV, 24 kV
IAC A FL 31.5 kA, 1 s
IAC A FL 25 kA, 1 s
IAC A FLR 31.5 kA, 1 s
IAC A FLR 25 kA, 1 s
Switchgear in closed electrical service location,
access for authorized personnel only (according to IEC 62 271-200)
Front
Lateral
Rear (for free-standing arrangement)
25 kA, 31.5 kA
1s

1) Average values depending on


the degree to which panels are
equipped
2) The loss of service continuity category is referred to the complete
switchgear, i.e. the panel with the
lowest category determines the
loss of service continuity category
of the complete switchgear.

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 9

Dimensions
Front views, sections, floor openings, fixing points for single-busbar switchgear

Circuit-breaker panels

409
761

50

100

25 3)

180

1100

1000 A

409
761

1726

2250 1)

702

HA35-2505e eps

732 2)
1100 4)

125
125

50

1200

4
5
4

180
25 3)

100

700

100

400

2000 A, 2300 A
and 2500 A
420

400

400

3
100

30

280
30
1200
920

46

1250 A

100

400

732 2)
1100 4)

100
600

100

125

700

1200
920

3
46

630 A

584
125

420

100

1100

30

280
30

125
125

584
600

702

1726
702

1726
702

HA35-2574a eps

1726

2250 1)

761

409

761

409

Legend and footnotes for


pages 10 and 11
1 Floor opening for
control cables
2 Option: Pressure
relief duct
3 Mounting hole
for M8 / M10
4 Mounting hole
for M8 / M10 (for
aseismic version only)
5 Floor opening for
high-voltage cables
6 Cable compartment /
pressure relief duct
1) 2650 mm for higher
low-voltage compartment
2) 752 mm for deeper
cable compartment cover
3) 45 mm for deeper
cable compartment cover
4) 1120 mm for deeper
cable compartment cover
5) When only one cable is
connected, the dimension
is reduced by 275 mm

1200

10 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

Dimensions
Front views, sections, floor openings, fixing points for single-busbar switchgear

Circuit-breaker panels (for top-rear cable connection)

409

702

HA35-2573a eps

1726

22501)

761

474 5)
750 5)

600

1100

100

100

25

100

1045 5)

30

700

46

180

920

1825 5)

30

905 5)

750 5)

500

1250 A

100

600

For legend and footnotes, see page 10

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 11

Dimensions
Front views, sections, floor openings, fixing points for single-busbar switchgear

Disconnector panels

702

1726
702

HA35-2506f eps

1726

22501)

761

409

761

409

732 2)

584
125

1100

180
25 3)

1250 A

700

1200
920

1000 A

100

3
46

1100

420

100

125

4
100
600

30

280
30

125

50

600

4)

100

409

1726

22501)

761

702

HA35-2507e eps

Legend and footnotes for


pages 12 and 13

732 2)
1100 4)

125
125

50

1200

25 3)

400

46

400
1200

400

100

30

100

1) 2650 mm for higher


low-voltage compartment

4
700

100

2000 A, 2300 A
and 2500 A
420

400

180

1200
920

280
30

100

1 Floor opening for


control cables
2 Option: Pressure
relief duct
3 Mounting hole
for M8 / M10
4 Mounting hole
for M8 / M10
(for aseismic version only)
5 Floor opening for
high-voltage cables

2) 752 mm for deeper


cable compartment cover
3) 45 mm for deeper
cable compartment cover
4) 1120 mm for deeper
cable compartment cover

12 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

Dimensions
Front views, sections, floor openings, fixing points for single-busbar switchgear

Bus sectionalizers with disconnector


on the left
on the left and on the right
of the circuit-breaker
409

409
761

761

1726

HA35-2575a eps

1726

2250

22501)

125

600

100

1250 A
1 panel width

30

100

409

22501)
HA35-2511e eps

1726

1726

22501)
HA35-2509e eps

700
400
1200

400

100

125

50
25

100

30

180

1100

400

400

100

46

100

1250 A
2 panel widths

700

46

100

180

100

2000 A, 2300 A
and 2500 A
1 panel width

280
30

400

420

400

1200
920

125

50
1200
920

280
30

100

125

1200

1100

420

125

1200

25

409

761

761

180

100
600

25

1100

700

46

1000 A
1 panel width

420

100

125

1100

400
1200

400

100

30

1200
920

280
30

125

50

600

For legend and footnotes, see page 12

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 13

Dimensions
Front views, sections, floor openings, fixing points for single-busbar switchgear

Switch-disconnector panel with HV HRC fuses

Ring-main panel
(switch-disconnector panel without HV HRC fuses)

409

409

1726

1726

22501)

22501)

761

761

702

HA35-2514f eps

450

HA35-2512d eps

584

584

1100

1200
920

420

100

Metering panel

409

409

1726

1726

22501)

22501)

761

100
600

Vacuum contactor panel with HV HRC fuses

100

700

280
30

420

100

1100

761

25

100
600

180

100

3
46

25

180

700

1200
920

3
46

100

30

280
30

100

125
125

50

600

30

125
125

50

600

7
HA35-2515d eps

450

600

100
600

100

1100

700

30

280
30
1200
920

100

46
180

180

700

46

25

100

420

100

100

30

280
30
1200
920
25

125
125

1100

125

50

125

50

584
600

420

HA35-2513e eps

100
600

100

14 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

For legend and footnotes, see page 15

Dimensions
Front views, sections, floor openings, fixing points for double-busbar switchgear

Circuit-breaker panels
Side B

Side B

340

Side A

43

Side A

761

409

702

HA35-2568c eps

1726

22501)

22501)

100

25 3)

180

920
860

100
100

5
4
100
600

700

30

2318

100

2370 6)

732 2)
1100 4)

30

1
4

1100

1000 A

100

46

600

3
100

30

30

100

920
860

25

600

Legend and footnotes


for pages 14 and 15
1 Floor opening for
control cables
2 Option: Pressure
relief duct
3 Mounting hole
for M8 / M10
4 Mounting hole
for M8 / M10
(for aseismic version only)
5 Floor opening for
high-voltage cables
7 Option:
HV HRC fuses
1) 2650 mm for higher
low-voltage compartment
2) 752 mm for deeper
cable compartment cover
3) 45 mm for deeper
cable compartment cover
4) 1120 mm for deeper
cable compartment cover
6) 2390 mm for deeper
cable compartment cover

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 15

Dimensions
Front views, sections, floor openings, fixing points for double-busbar switchgear

Side A

Side B

Side B

43

Incoming sectionalizer
Side A

761

409

340

30

100

2370 6)

732 2)
1100 4)

100

3
46
180

100
600

700

100
100

5
4

30

700

30

1
4

3
100

30

3
5

100

2318

1100

100

920
860

600

1250 A

920
860

25

600

25 3)

702

HA35-2569c eps

1726

22501)

22501)

Legend and footnotes


for pages 16 and 17
1 Floor opening for
control cables
2 Pressure relief duct
3 Mounting hole
for M8 / M10
4 Mounting hole
for M8 / M10
(for aseismic version only)
5 Floor opening for
high-voltage cables
1) 2650 mm for higher
low-voltage compartment
2) 752 mm for deeper
cable compartment cover
3) 45 mm for deeper
cable compartment cover
4) 1120 mm for deeper
cable compartment cover
6) 2390 mm for deeper
cable compartment cover

16 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

Dimensions
Front views, sections, floor openings, fixing points for double-busbar switchgear

Bus coupler
Side B

Side B

340

Side A

43

Side A

761

409

HA35-2570c eps

1726

22501)

22501)

600

600

1100

1100

100

1
4

30

100

100
100

46
180

700

2318

920
860

30

100

25

1000 A

100
600

30

30

100

920
860

25

2370

100

For legend and footnotes, see page 16

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 17

Product Range
Single-busbar panels

Circuit-breaker panels
Three-position
disconnector

Vacuum
circuit-breaker

HA35-2541b eps

Plug-in voltage
transformer

and/or

or

or

and/or

and/or

and/or

and/or

HA35-2490c eps

HA35-2488f eps

or

630 A

and/or

or

or

Disconnectable and
plug-in voltage transformer

Current transformer
Capacitive voltage
detecting system

Forced ventilation
at 2500 A

2000 A, 2300 A and 2500 A

Busbar earthing
switch

Surge arrester
or limiter

or

and/or

or

or

and/or

and/or

or

and/or

and/or

1000 A and 1250 A

HA35-2576 eps

HA35-2489d eps

1)

or

and/or

1250 A, top-rear cable connection

1) Only for 1250 A

18 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

Cable connection with


outside-cone plugs
(not included in the
scope of supply)

Cable connection with


outside-cone plugs
(not included in the
scope of supply)

Product Range
Single-busbar panels

Disconnector panels

Bus sectionalizers
Three-position
disconnector

Vacuum
circuit-breaker

or

and/or

and/or

or

HA35-2493c eps

1)

HA35-2541b eps

Plug-in voltage
transformer

Disconnectable and
plug-in voltage transformer

1250 A, 1 panel width

or

HA35-2491c eps

Current transformer
Capacitive voltage
detecting system

and/or

1000 A and 1250 A

Forced ventilation
at 2500 A

Surge arrester
or limiter

HA35-2494a eps

or

and/or

and/or

Cable connection with


outside-cone plugs
(not included in the
scope of supply)

or

or

and/or

or

and/or

Cable connection with


outside-cone plugs
(not included in the
scope of supply)

and/or

2000 A, 2300 A and 2500 A

HA35-2495a eps

HA35-2492c eps

1250 A, 2 panel widths

2000 A, 2300 A and 2500 A, 1 panel width


1) Only for 1250 A

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 19

Product Range
Single-busbar panels

Switch-disconnector panel

Ring-main panel
Three-position
switch-disconnector

Vacuum contactor

HV HRC fuses

or

or

and/or

and/or

and/or

and/or

HA35-2498d eps

HA35-2496b eps

or

Vacuum contactor panel

and/or

HA35-2541b eps

Plug-in voltage
transformer
or

Disconnectable and
plug-in voltage transformer

Current transformer
Capacitive voltage
detecting system

Metering panel
2nd earthing
switch for fuses

Surge arrester
or limiter

Cable connection with


outside-cone plugs
(not included in the
scope of supply)

12))

or

and/or

or

and/or

and/or

and/or

and/or

HA35-2499c eps

HA35-2497d eps

or

1) Only possible when vacuum contactor panel


is designed without fuse

20 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

Product Range
Double-busbar panels

Circuit-breaker panels

Incoming sectionalizer
Three-position
disconnector

SS1

SS1
SS2

SS2

Vacuum
circuit-breaker

HA35-2541b eps

Plug-in voltage
transformer

HA35-2500c eps

and/or

and/or

1000 A

and/or

or

or

or

or

or

or

and/or

and/or

or

and/or

and/or

and/or

HA35-2502e eps

or

Disconnectable and
plug-in voltage transformer

Plug-in voltage
transformer,
mounted separately

and/or

Current transformer

1250 A

Capacitive voltage
detecting system

Bus coupler

Panel bars

SS1
SS2

Surge arrester
or limiter

HA35-2503a eps

Cable connection with


outside-cone plugs
(not included in the
scope of supply)

or

or

and/or

and/or

and/or

and/or

1000 A
Abbreviations
SS1 = Busbar 1
SS2 = Busbar 2

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 21

Design
Basic panel design
Insulating system
Circuit-breaker panel (example)

Switchgear vessel filled with SF6 gas


Features of SF6 gas:
Non-toxic
Odourless and colourless
Non-inflammable
Inert
Heavier than air
Electronegative (high-quality
insulator)

1
2

16
17

Pressure of SF6 gas in the

switchgear vessel (absolute values):


Rated filling level: 150 kPa
Design pressure: 180 kPa
Design temperature
of SF6-gas: 80 C
Operating pressure of bursting
disk: 300 kPa
Bursting pressure: 550 kPa
Gas leakage rate: < 0.1 % per year
Panel design

18
Z

20
21

3
4
5
6
7

22

24

9
10
11

Make-proof earthing by means

14

arrangement
Installation and possible later exten-

sion of existing panels without gas


work
Replacement of switchgear vessel

without gas work


Replacement of instrument trans-

formers without gas work, as they


are located outside the gas
compartments
Enclosure made of galvanized sheet-

steel, front cover, rear cover and end


walls painted in colour light basic
(SN 700)
Low-voltage compartment remov-

Sectional view (cable connection from the front)

Detail Z:
8

12

Wall-standing or free-standing

35

Front view

disconnecting and earthing by


means of the circuit-breaker

outside-cone plug-in system


according to DIN EN 50 181

29

HA35-2516d eps

screened busbars, plug-in type

Cable connection with

34

28

Maintenance-free

Three-position switch-disconnector

36

27

Single-pole, solid-insulated,

of the vacuum circuit-breaker

33

26

switchgear vessel made of


stainless steel

Three-position disconnector for

32

25

Hermetically tight, welded

vacuum contactor

31

23

Metal-enclosed, metal-clad

Vacuum circuit-breaker or

30

19

Factory-assembled, type-tested

Degree of protection
IP 65 for all high-voltage parts
of the primary circuit
IP 3XD for the switchgear enclosure

15

13

10 Position indicator
for ready-to-earth
function of threeposition switch
11 Control gate and
locking device for
disconnecting/earthing
functions of threeposition switch
12 Interrogation lever
13 Actuating opening
for disconnecting
function of three-position
1 Low-voltage
switch
compartment
14 Actuating opening
2 Multifunction protection
for ready-to-earth
relay SIPROTEC 4 (example)
function of three-position
3 Position indicator
switch
for circuit-breaker
15 Option: Busbar voltage
4 Actuating opening for
transformer, plug-in type
charging the circuit16 Busbars, single-pole,
breaker springs
fully-insulated, plug-in
5 ON pushbutton for
type, earthed on the
circuit-breaker
outside
6 Spring charged
17 Option: Busbar current
indicator
transformer
7 Operations counter
18 Switchgear vessel,
for circuit-breaker
hermetically welded,
filled with SF6 gas
8 Position indicator
for disconnecting
19 Three-position
function of three-position
disconnector
switch
20 OFF pushbutton for
9 Ready-for-service
circuit-breaker
indicator

able, plug-in bus wires

22 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

21 Vacuum interrupter of
circuit-breaker
22 Pressure relief
(bursting disk)
23 Capacitive voltage
detecting system
24 Locking device for feeder
(suitable for padlocking)
25 Disconnecting facility for
feeder voltage transformer
26 Bushing for feeder voltage
transformer
27 Option: Feeder voltage
transformer
28 Option: Pressure relief duct
29 Cable compartment
30 Operating mechanism for
three-position switch
31 Operating mechanism for
circuit-breaker
32 Feeder current transformer
33 Cable connection with
outside-cone T-plug
34 Operation of disconnecting
facility of the feeder voltage
transformer
35 Earthing busbar with
earthing connection
36 Air guides for cable
connection

Components
Vacuum circuit-breaker
Features

Trip-free mechanism
The vacuum circuit-breaker
is fitted with a trip-free
mechanism according to
IEC 62 271 and VDE 0671.
Switching duties and
operating mechanisms
The switching duties of the
vacuum circuit-breaker are

Vacuum circuit-breaker
R-HA35-050 eps

dependent, among other


According to IEC 62 271-100 factors, on its type of
operating mechanism.
and VDE 0671-100 (for
standards refer to page 44)
Motor operating
Application in hermetically mechanism
welded switchgear vessel
in conformity with the sys- Motor operating storedenergy mechanism
tem
For auto-reclosing (K)
Climate-independent
For synchronization and
vacuum interrupter poles
rapid load transfer (U)
in the SF6-filled switchgear vessel
Further operating
mechanism features
Maintenance-free for
indoor installation accord Located outside the switching to IEC 62 271-1 and
gear vessel in the operating
VDE 0671-1
mechanism box and behind the control board
Individual secondary equipment
Stored-energy spring
mechanism for 10,000
A metal bellows is used for
operating cycles
gasketless separation of
the SF6 insulation and the
Operating mechanism
operating mechanism as
functions
already used with success
for over 1 million vacuum
Motor operating
interrupters
mechanism 1) (M1 *)

10
4

Vacuum circuit-breaker
(operating mechanism open)

In the case of motor operating mechanism, the closing


spring is charged by means
of a motor and latched
in the charged position
(spring charged indication
is visible). Closing is effected
either by means of an ON
pushbutton or a closing solenoid. The closing spring is
recharged automatically (for
auto-reclosing).

1 Gear with motor (M1 *)

Class Standard

E2

C2

option: 12NO+12NC
8 Position indicator
CLOSED/OPEN for circuit-breaker
9 Option: 2nd release (Y2 *)
10 1st release (Y1 *)
11 Locking device for feeder

12

13

14

15

16

17

18

Propery of NXPLUS C

IEC 62 271-100 10,000 times mechanically


without maintenance
IEC 62 271-100 10,000 times rated normal
current without maintenance
50 times rated short-circuit
breaking current without maintenance
IEC 62 271-100 Very low probability of restrikes

Operating times

19

HA35-2276d eps

BREAKING M2

7 Auxiliary switch 6NO+6NC (S1 *),

2 Position switch (S4 *)


3 Closing spring
4 Closing spring charged
indicator
5 Closing solenoid (Y9 *)
6 Operations counter

Endurance class of circuit-breaker


Function

11

Closing time

Closing solenoid

< 75 ms

Section through the vacuum circuit-breaker

Opening time

1st release
2nd release

< 65 ms
< 50 ms

12 Fixed terminal

17 Switchgear vessel,

13
14
15
16

SF6-insulated, with vacuum


interrupter
18 Operating mechanism box
(see figure above)
19 Operating kinematics

Arcing time at 50 Hz
Break time

< 15 ms
1st release
2nd release

< 80 ms
< 65 ms

Dead time

300 ms

Total charging time

< 15 s

Abbreviations for switching duties


and applications:
1) Motor rating at
U = Synchronization and
24 V to 220 V DC: 350 W
rapid load transfer
110 V and 220 V AC: 400 VA
(make time 90 ms)
* Item designation
K = Auto-reclosing

Pole support
Vacuum interrupter
Moving terminal
Metal bellows

For further technical data and description of typical applications,


please refer also to Catalog HG 11.05 3AH5 Vacuum Circuit-Breakers

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 23

Components
Vacuum circuit-breaker

Closing solenoid
Type 3AY15 10 (Y9 *)

Circuit-breaker tripping signal

For electrical closing

For electrical signalling

Shunt releases
Types:

Standard: 3AY15 10 (Y1 *)


Option: 3AX11 01 (Y2 *),
with energy store

(as pulse > 10 ms), e.g. to remote control systems, in the


case of automatic tripping
(e.g. protection)

Switching rate of the vacuum interrupter

Type 3AX11 02 (Y4*), 0.5 A


Type 3AX11 04 (Y6 *) for

tripping pulse W 0.1 Ws in


conjunction with suitable protection systems
Used where no external

auxiliary voltage is available,


tripping by protection device
Undervoltage release
Type 3AX11 03 (Y7 *)
Comprising:
Energy store and unlatching
mechanism
Electromagnetic system,
which is permanently
connected to voltage while
the vacuum circuit-breaker is
closed; tripping is initiated
when this voltage drops
Connection to voltage trans-

formers possible

Function: If constant CLOSE

cut-out switch (S7 *)

500
200

10

Varistor module
To limit overvoltages to

approx. 500 V for protection


devices (when inductive
devices are mounted in the
vacuum circuit-breaker)

10

25

kA

Breaking current (r.m.s. value)


Electrical data
Rated voltage 24 kV
Rated short-circuit breaking current 25 kA
Rated normal current 2000 A

Auxiliary switch
Type 3SV9 (S1 *)

20000

Standard: 6NO+6NC, of which

3NO+4NC contacts are free 1)


Option: 12NO+12NC, of which

9NO+6NC contacts are free 1)


Position switch
Type 3SE4 (S4 *)
For signalling closing spring

charged

10000
5000
2000
1000
500
200
100

Mechanical interlocking

50

Mechanical interlocking

to the three-position
disconnector

20
10

three-position switch, the


vacuum circuit-breaker
cannot be operated

10

20

31,5

kA 50

Breaking current (r.m.s. value)


Electrical data
Rated voltage 15 kV
Rated short-circuit breaking current 31.5 kA
Rated normal current 2500 A

Release combination

shunt release type 3AY15 10

2nd shunt release type 3AX11 01

Current-transformer operated release type


3AX11 02, 0.5 A or type 3AX11 04, 0.1 Ws

Undervoltage release type 3AX11 03

Rated operating sequences


Rapid load transfer (U):
O-t-CO-t'-CO (t, t' 3 min)
Auto-reclosing (K):
O-t-CO-t'-CO (t 0.3 s, t' 3 min)
Multiple-shot reclosing: O-t-CO-t'-CO-t'-CO-t'-CO (t 0.3 s, t' 15 s)

1 unit of each release; max. 2 releases can be combined

* Item
designation

50

W 60 V DC

Release

1) For utilization
by the
customer

20

For auxiliary voltages

5 combination possibilities of the releases

1st

1000

20

Via limit switch (S6 *) and

During operation of the

Anti-pumping
(mechanical and electrical)

2000

50

Permissible operating cycles

Current-transformer operated
release

5000

100

Tripping by protection device

or electrical actuation

HA35-2539 eps

20000
10000

HA35-2540 eps

The scope of the secondary


equipment of the vacuum
circuit-breaker depends on the
type of application and offers a
wide range of variations, thus
allowing even the highest
requirements to be satisfied:

and OPEN commands are


present at the vacuum circuitbreaker, the vacuum circuitbreaker will return to the
OPEN position after closing.
It remains in this position until
a new CLOSE command is
given. In this manner continuous closing and opening
(= pumping) is avoided.

Permissible operating cycles

Secondary equipment

Abbreviations:
NO = normally-open contact
NC = normally-closed contact

O = OPEN operation
CO = CLOSE operation with subsequent OPEN
operation at the shortest internal closeopen time of the vacuum circuit-breaker

24 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

Components
Three-position switch

cally welded switchgear


vessel in conformity with
the system
Climate-independent

contacts in the SF6 filled


switchgear vessel
Maintenance-free for

indoor installation
according to IEC 62 271-1
and VDE 0671-1
Individual secondary

equipment
A metal bellows is used

for gasketless separation


of the SF6 insulation and
the operating mechanism as already used
with success for over
1 million vacuum interrupters
Compact design due to

short contact gaps in


SF6 gas
Operation via gas-tight

welded-in metal bellows


at the front of the switchgear vessel
Reliable switch position

up to the operating front


of the panel

Circuit-breaker panel from


1000 A to 2500 A (with
interlock against the
circuit-breaker)
Disconnector panel from
1000 A to 2500 A
Bus sectionalizer from
1000 A to 2500 A

HA35-2518 eps

Application in hermeti-

Switch positions of the three-position switches

Application in
1

CLOSED

2
3

OPEN

1000 mechanical operat-

ing cycles for CLOSED /


OPEN / READY-TO-EARTH
Feeder
EARTHED

Three-position
switch-disconnector
Application in
Circuit-breaker panel 630 A
(as disconnector with
interlock against the
circuit-breaker)
Switch-disconnector panel
Ring-main panel
Contactor panel
Metering panel

Switch positions
Three-position disconnector
(in OPEN position)
with vacuum circuit-breaker arranged below
(view into the switchgear vessel opened at the rear)
1
2
3
4

1000 mechanical operat-

ing cycles for CLOSED /


OPEN / EARTHED

Fixed contact at the busbar


Swivel-mounted contact blade
Fixed contact for feeder EARTHED
Operating shaft

Switching functions as

general-purpose switchdisconnector according to


IEC 60 265-1
VDE 0670-301
IEC 62 271-102
VDE 0671-102

9
HA35-2519 eps

IEC 62 271-102 and


VDE 0671-102 (for
standards refer to page 44)

R-HA35-040a eps

According to

Three-position
disconnector

(for standards refer to


page 44)
Designed as a multi-cham-

ber switch incorporating


the functions
Switch-disconnector and
Make-proof earthing
switch

R-HA35-047 eps

Common features

CLOSED

OPEN

Feeder
EARTHED

Three-position switch-disconnector
(exploded view)
5
6
7
8
9

Switch positions

Fixed contacts to earth


Rotary contact blade
Operating shaft
Fixed contact to the feeder
Fixed contact to the busbar

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 25

Components
Three-position switch
Operating mechanism

Selection of permissible

Spring-operated mecha-

nism operated via operating lever at the operating


front of the panel
Separate operating shafts

Option: Motor operating

mechanism for the functions DISCONNECTING and


EARTHING or READY-TOEARTH

Operating lever cannot

be removed until switching operation has been


completed

energy mechanism for the


switch-disconnector function with fuses:
Opening spring precharged (after closing)

closed until control gate is


in neutral position again
Switchgear interlocking

Maintenance-free due to

non-rusting design of
parts subjected to
mechanical stress

1 Gas-filled switchgear vessel


2 Gas-tight welded-in metal bellows

lubrication

Switch positions
CLOSED, OPEN,

Transmission of operating

power from outside into


the gas-filled switchgear
vessel by means of a metal
bellows

In circuit-breaker panels,

the cable connection is


earthed and shortcircuited by closing the
vacuum circuit-breaker

Three-position
disconnector

Bearings which require no

Transmission principle for


operating mechanisms
(see opposite drawings)

EARTHED or
READY-TO-EARTH

Spring-operated/stored-

Circuit-breaker cannot be

system also possible with


electromechanical interlocks if switchgear is
equipped with motor
operating mechanisms
(mechanical interlocking
for manual operation remains)

for the functions


DISCONNECTING and
EARTHING or READY-TOEARTH

Corresponding operating

shafts are not released


at the operating front
until they have been preselected with the control
gate

Transmission principle for operating mechanisms

HA35-2521 eps

switching operations by
means of a control gate
with mechanically interlocked vacuum circuitbreaker

HA35-2520 eps

Interlocks

Gas-tight
Maintenance-free

Endurance class of three-position disconnector


Function

Class

DISCONNECTING M0

Standard

Property of NXPLUS C

IEC 62 271
-102

1000 times mechanically


without maintenance

READY-TOEARTH
EARTHING

1000 times mechanically


without maintenance
E2 1)

IEC 62 271
-102

50 times rated short-circuit


making current Ima
without maintenance

Endurance class of three-position switch-disconnector


Function

Standard

Porperty of NXPLUS C

DISCONNECTING M0

IEC 62 271
-102

1000 times mechanically


without maintenance

LOAD
BREAKING

IEC 60 265-1 1000 times mechanically


without maintenance
IEC 60 265-1 100 times rated mainly active load breaking current I1
without maintenance
5 times rated short-circuit
making current Ima
without maintenance

Class

M1
E3

EARTHING

E2

IEC 62 271
-102

Three-position
switch-disconnector
1 Gas-filled switchgear vessel
2 Gas-tight welded-in metal bellows

5 times rated short-circuit


making current Ima
without maintenance

1) By closing the circuit-breaker

26 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

Components
HV HRC fuse assembly
Mode of operation

Application in
Switch-disconnector
panel
Contactor panel
Metering panel

In the event that an HV HRC


fuse link has tripped, the
switch is tripped via an articulation which is integrated
into the cover of the fuse
box (see figure).

according to DIN 43 625


(main dimensions) with
striker in medium
version acc. to IEC 60 282 /
VDE 0670-4
As short-circuit protection
before transformers in
the switch-disconnector
panel
As short-circuit protection
before motors in the
contactor panel
As short-circuit protection
before voltage transformers in the metering
panel
With selectivity
(depending on correct
selection) to upstream
and downstream
connected equipment
Single-phase insulated
Requirements according

to IEC 62 271-105 and


VDE 0671-105 fulfilled
by combination of HV
HRC fuses with the
three-position switchdisconnector
Climate-independent and

maintenance-free, with
fuse boxes made of cast
resin
Fuse assembly connected

to the three-position
switch-disconnector via
welded bushings and
connecting bars
Arrangement of fuse as-

sembly below the switchgear vessel


Fuse can only be replaced

if feeder is earthed

In the event that the fuse


tripping fails, e.g. if the fuse
has been inserted incorrectly, the fuse box is protected
by thermal protection. The
overpressure generated by
overheating trips the switch
via the diaphragm in the
cover of the fuse box and via
an articulation. This breaks
the current before the fuse
box incurs irreparable
damage.

Basic design

1
2
3
4

Bushing
Switchgear vessel
Sealing cover with seal
Tripping pin for spring-operated/
stored-energy mechanism
5 Fuse box
6 HV HRC fuse link
7 Striker of the HV HRC fuse link and
articulation for tripping of the
spring-operated/stored-energy mechanism

The above thermal protection works independently of


the type and design of the
HV HRC fuse used. Like the
fuse itself, it is maintenancefree and independent of any
outside climatic effects.
Furthermore, the Siemens
HV HRC fuses release the
striker independently of the
temperature and trip the
three-position switch-disconnector as early as in the
fuse overload range. Impermissible heating of the fuse
box can be avoided in this
way.

Fuse link
in service condition

HA35-2523 eps

HV HRC fuse links

HV HRC fuse assembly

HA35-2522 eps

Features

Replacement
of HV HRC fuse links
Fuse tripped
by striker

Isolating and earthing the

transformer feeder
Subsequent manual re-

placement of the HV HRC


fuse link after removing
the cable compartment
cover

Fuse tripped by overpressure,


e.g. if HV HRC fuse link
has been inserted incorrectly
Schematic sketches
for fuse tripping

Option:

Fuse tripped indication


for remote electrical indication with one normallyopen contact (1NO)

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 27

Components
Allocation of three-position switch-disconnector with HV HRC fuses, transformer ratings
The opposite table shows the
recommended HV HRC fuse
links 3GD (electrical data valid
for ambient air temperatures of
up to 40 C) for fuse protection
of transformers.

Operating
voltage
kV
6.0 to 7.2

Recommendation
The three-position switch-disconnector in the transformer
feeder (transformer switch)
was combined with Siemens
HV HRC fuse links of type 3GD
and tested in accordance with
IEC 62 271-105.
Higher transformer ratings on
request.

10 to 12

Standards
HV HRC fuse links medium
version with striker
according to
IEC 60 282
VDE 0670-4 and 402
DIN 43 625

main dimensions

13.2/13.8

15 to 17.5

22 to 24

Transformer
Relative impedance
Rating SN
voltage uk
kVA
%
50
4
75
4
100
4
125
4
160
4
200
4
250
4
315
4
400
4
500
4
630
4
50
4
75
4
100
4
125
4
160
4
200
4
250
4
315
4
400
4
500
4
630
4
800
5 to 6
1000
5 to 6
50
4
75
4
100
4
125
4
160
4
200
4
250
4
315
4
400
4
500
4
630
4
800
5 to 6
1000
5 to 6
1250
5 to 6
50
4
75
4
100
4
125
4
160
4
200
4
250
4
315
4
400
4
500
4
630
4
800
5 to 6
1000
5 to 6
1250
5 to 6
50
4
75
4
100
4
125
4
160
4
200
4
250
4
315
4
400
4
500
4
630
4
800
5 to 6
1000
5 to 6
1250
5 to 6
1600
5 to 6
2000
5 to 6

Rated normal current of the HV HRC fuse


Rated
current I1
A
4.8
7.2
9.6
12.0
15.4
19.2
24.0
30.3
38.4
48.0
61.0
2.9
4.3
5.8
7.2
9.3
11.5
14.5
18.3
23.1
29.0
36.4
46.2
58.0
2.1
3.2
4.2
5.3
6.7
8.4
10.5
13.2
16.8
21.0
26.4
33.5
41.9
52.4
1.9
2.9
3.9
4.8
6.2
7.7
9.7
12.2
15.5
19.3
24.3
30.9
38.5
48.2
1.5
2.2
2.9
3.6
4.7
5.8
7.3
9.2
11.6
14.5
18.2
23.1
29.0
36.0
46.5
58.0

Lowest
value
A
16
16
20
25
32
40
50
50
63
63
100
10
10
16
16
20
25
25
32
40
50
63
63
80
6
10
10
16
16
16
20
25
32
40
50
50
63
80
6
10
10
10
16
16
20
25
32
32
40
50
63
63
6
6
10
10
10
16
16
20
20
25
32
32
40
50
63
100

28 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

Highest
value
A
16
20
25
32
40
50
63
80
100
100
100
10
10
16
20
25
32
40
50
63
80
100
100
100
6
10
10
16
20
25
25
32
50
50
63
63
80
100
6
10
10
10
16
25
25
32
40
50
63
50
80
100
6
6
10
10
10
16
20
25
32
40
50
40
50
63
100
100

Components
Vacuum contactor, motor protection
Features
Vacuum contactor

According to IEC 60 470 and

VDE 0670-501 (for standards


refer to page 44)
Application in hermetically

Climate-independent vacuum

interrupter poles in the


SF6-filled switchgear vessel
Maintenance-free for indoor

R-HA35-110 eps

welded switchgear vessel in


conformity with the system

installation according to
IEC 62 271-1 and
VDE 0671-1

2
3
4

Individual secondary equip-

ment
A metal bellows is used for

gasketless separation of the


SF6 insulation and the operating mechanism as already used with success for
over 1 million vacuum interrupters
Magnet coil for operation

located outside the switchgear vessel

Vacuum contactor
(operating mechanism open)
1 Metal bellows
2 Pole support
3 Vacuum interrupter

4 Operating mechanism box with magnet coil


5 Base plate (welded into the switchgear vessel)

100,000 or 500,000 operat-

ing cycles at rated normal


current

10

11

12

13

6
7
8
9
10

Fixed terminal
Pole support
Vacuum interrupter
Moving terminal
Switchgear vessel,
SF6-insulated, with vacuum
interrupter
11 Metal bellows
12 Operating mechanism box
(see figure above)
13 Operating kinematics

The max. stress for HV HRC


fuses arises during motor
starting (starting currents,
starting times and starting
frequency).
Fuses must not operate or be
pre-damaged during motor
starting.
The opposite table shows the
permissible motor starting currents according to the starting
time and starting frequency
of downstream connected HV
motors with the associated
HV HRC fuses.

Section through the vacuum contactor

Motor protection table


HA35-2525 eps

In circuits subjected to shortcircuit currents, HV HRC fuse


links protect switching devices
without short-circuit breaking
capacity (e.g. vacuum contactors).

HA35-2524a eps

Short-circuit and overload


protection in connection with
motors

M
3~

HV motors
with starting times
up to 5 s

HV motors
with starting times
up to 15 s

HV motors
with starting times
up to 30 s

Number
of starts
per hour
2
4
8
16
2
4
8
16
2
4
8
16

Maximum permissible motor starting current in A


at rated normal current of fuse
40 A
63 A
100 A
125 A

160 A

250 A

90
80
75
65
85
75
70
60
80
70
65
55

480
440
400
360
430
400
360
325
420
370
320
280

740
675
615
550
635
580
530
475
600
530
460
400

135
120
110
100
120
110
100
90
120
105
90
80

255
235
215
190
225
205
185
165
215
190
165
145

360
330
300
270
310
285
260
235
300
265
230
200

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 29

Components
Busbars
Features

Busbars (example)
R-HA35-051 eps

Single-pole, plug-in and

bolted design
Consisting of round-bar

copper, insulated by means


of silicone rubber
Busbar joints with cross and

end adapters, insulated by


means of silicone rubber
Field control by means of

electrically conductive layers


on the silicone-rubber insulation (both inside and outside)
Safe-to-touch by earthing

the external layers with the


switchgear vessel
Insensitive to pollution and

condensation
Busbars 1250 A, plug-in type, fully insulated
(as front view of three panels, without low-voltage compartments)

Safe-to-touch as a result of

use of metallic covers


Switchgear extension or pa-

nel replacement is possible


without gas work
Possible fittings

Current transformers
Voltage transformers
Surge arresters
Cables with

Straight plug or
T-plug
Fully-insulated bars

(e.g. make Duresca)

3
4
11

5
7

10
HA35-2595a eps

Section of busbar 1250 A (basic design)


(panel width 600 mm)

2
3

1 Cap
2 Busbar insulation made of
silicone rubber
3 Clamps
4 Busbar (round-bar copper)
5 End adapter or coupling end
adapter
6 Connection bolt
7 Switchgear vessel
8 Metal cover of busbars
9 Cross adapter or coupling cross
adapter
10 Bushing
11 Earthing connection

4
5
6
2

3
4
10

11

7
HA35-2517a eps

Legend

Section of busbar 1600 A, 2000 A or 2500 A (basic design)


(panel width 600 mm)

30 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

Components
Current transformers
Features
Current transformers

According to IEC 60 044-1

R-HA35-052a eps

and VDE 0414-1


Designed as ring-core current

transformers, single-pole
Free of dielectrically stressed

1 Busbar current transformer


2 Feeder current transformer
at the panel connection
3 Cable-type current transformer
4 Bus-type current transformer

cast-resin parts (due to


design)
Insulation class E

Side views:

Inductive type
Certifiable
Climate-independent

means of a terminal strip in


the low-voltage compartment of the panel

Busbar current transformers


Example 1250 A

Panel with busbar


1250 A

Front views:

Installation

HA35-25277 eps

Secondary connection by

Arranged outside the primary

enclosure (switchgear vessel)


Mounting locations

At the busbar (1)


At the panel connection (2)
Around the cable (3)

Busbar current transformer (1):


Inside diameter of
transformer
56 mm / 1250 A and
56 x 300 mm / > 1250 A
Max. usable height 170 mm
Feeder current transformer (2):
Inside diameter of
transformer
106 mm / 1250 A and
106 x 240 mm / > 1250 A
Max. usable height 205 mm
Cable-type current trans-

former (3) for shielded cables:


Inside diameter of
transformer 55 mm
Max. usable height 170 mm
Bus-type current transformer

(4) underneath the panels


(included in the scope of
supply); on-site installation

630 A, 1000 A
and 1250 A

2000 A, 2300 A and 2500 A

HA35-25278 eps

Current transformer types

Panel with busbar


2500 A

Current transformer installation (basic design)

Electrical data
Designation

Type 4MC

Designation

Type 4MC

Operating voltage

max. 0.8 kV

Multiratio (secondary)

Rated short-duration
power-frequency withstand
voltage (winding test)

3 kV

200 100 A to
2500 1250 A
max. 3 cores

Rated frequency

50/60 Hz

Rated continuous thermal


current

max. 1.2 x
rated current
(primary)

Core data according to


rated primary current:
Measuring
Rating
core
Class
Overcurrent
factor
Protection
Rating
core
Class
Overcurrent
factor

Rated thermal
max. 31.5 kA
short-time withstand current,
max. 3 s
Rated current

dynamic
primary
secondary

unlimited
40 A to
2500 A
1 A and 5 A

2.5 VA to 30 VA
0.2 to 1
FS 5, FS 10
2.5 VA to 30 VA
5 P or 10 P
10 to 30

Permissible ambient air


temperature

max. 60 C

Insulation class

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 31

Components
Voltage transformers
Features
Voltage transformers

According to IEC 60 044-2 and


Single-pole, plug-in design
Connection system with

plug-in contact

R-HA35-120 eps

VDE 0414-2

Inductive type
Safe-to-touch as a result of

use of metallic covers


Certifiable
Climate-independent
Secondary connection by

means of plugs inside the


panel
Cast-resin insulated

Feeder voltage transformer (metal-coated)

Arranged outside the primary

enclosure (switchgear vessel)


Mounting locations:

At the busbar
At the panel connection
Voltage transformer types
Busbar voltage transformer

4MT3 at the panel connection:


Switchable through an
SF6-insulated disconnecting
facility in the switchgear
vessel
Switch positions: CLOSED
and Transformer bushing
EARTHED
Operation of the disconnecting facility from outside
through a metal bellows
welded in the switchgear
vessel
Voltage testing of switchgear
and cables possible with
mounted and earthed voltage
transformer

Side view:
4

CLOSED
1

OPEN and EARTHED


Z
5
2

2
3

Voltage transformer installation (basic design)

32 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

HA35-2528b eps

Feeder voltage transformer

Front view:

HA35-2527b eps

4MT2:
Pluggable in the cross adapters of the busbar 1250 A
using additional adapters
(> 1250 A on request)
No separate metering panel
required
Suitable for 80 % of the
rated short-duration powerfrequency withstand voltage
at rated frequency
Repeat test at 80 % of the
rated short-duration powerfrequency withstand voltage
possible with mounted
voltage transformer (also valid
for higher insulation ratings
according to GOST and GB
standards)

Disconnecting facility
for feeder voltage transformer
(details Z)

1 Busbar voltage transformer


2 Feeder voltage transformer
at the panel connection
3 Operating lever for
disconnecting facility
4 Panel connection
5 Switchgear vessel wall
(earthed)

Components
Voltage transformers

Electrical data
Primary data
For types 4MT3 and 4MT2
For operating voltages from 3.3 to 23 kV, rated voltage factor Un/8h = 1.9 ; Un /continuous = 1.2
Rated voltage

Rated short-duration
power-frequency
withstand voltage

Rated lightning impulse


withstand voltage

kV

kV

kV

3.6

10

7.2

12

Standard

Operating voltage

20

IEC

3.3/ 3

20

60

IEC

3.6/ 3; 4.8/ 3; 5.0/ 3;


6.0/ 3; 6.3 / 3; 6.6/ 3

32

60

GOST

6.0/ 3; 6.3/ 3; 6.6/ 3

28

75

IEC

7.2/ 3; 10/ 3; 11/ 3

42

75

GOST

10/ 3; 11/ 3

GB

10/ 3; 11/ 3

kV

42

75

17.5

38

95

IEC

13.2/ 3; 13.8/ 3; 15/ 3

24

50

125

IEC

17,5/ 3; 20/ 3; 23/ 3

Secondary data
For
type

4MT3

Operating
voltage

Auxiliary
winding

Thermal limit
current (measuring winding)

Rated long-time Rating at accuracy class


current,
8h
0.2
0.5

VA

VA

VA

100/ 3;
110/ 3;
120/ 3

100/3;
110/3;
120/3

IEC

VA

10,15, 20, 25, 10, 15, 20, 25, 10, 15, 20, 25,
30
30, 45, 50, 60, 30, 45, 50, 60,
75, 90
75, 90, 100,
120, 150, 180

10, 15, 20, 25,


30, 45, 50, 60,
75, 90, 100,
120, 150, 180

GOST 32/60 kV
10, 15, 20, 25, 10, 15, 20, 25, 10, 15, 20, 25,
30
30, 45, 50, 60, 30, 45, 50, 60,
75, 90
75, 90, 100,
120, 150, 180

10, 15, 20, 25,


30, 45, 50, 60,
75, 90, 100,
120, 150, 180

GOST 42/75 kV, GB 42/75 kV


10, 15, 20, 25 10, 15, 20, 25, 10, 15, 20, 25,
30, 45, 50, 60, 30, 45, 50, 60,
75
75, 90, 100,
120, 150
4MT2

100/ 3;
110/ 3;
120/ 3

100/3;
110/3;
120/3

10, 15, 20, 25,


30, 45, 50, 60,
75, 90, 100,
120, 150

IEC
5, 10,15, 20,
25

10, 15, 20, 25, 10, 15, 20, 25, 10, 15, 20, 25,
30, 45
30, 45, 50, 60, 30, 45, 50, 60,
75
75

GOST 32/60 kV
5

10, 15

10, 15, 20, 25, 10, 15, 20, 25,


30
30

GOST 42/75 kV, GB 42/75 kV


5, 10

10, 15, 20, 25, 10, 15, 20, 25, 10, 15, 20, 25,
30
30, 45, 50, 60 30, 45, 50, 60

GOST: Russian standard


GB: Chinese standard

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 33

Components
Panel connection
Features
Bushings with outside cone

Cable compartment

With bolted contact (M16) as

interface type C according


to EN 50 180 / EN 50 181

584 mm or 732 mm with


standard cable compartment
cover, 752 mm with deeper
cable compartment cover

L1
105

L2
195

L3
195

702
HA35-2598 eps

Max. connection depth:

HA35-2597 eps

702 mm (for switch-disconnector panels and contactor


panels with HV HRC fuses:
450 mm)

702 (450*)

Cable connection height:

105

Panel width 600 mm

L1
175

130

L2
230

130

L3
230

Panel width 1200 mm

With cable bracket, e.g. type

C40 accord. to DIN EN 50 024


Option: Access to the cable

Connectable cables

compartment only if the


feeder has been isolated and
earthed

Legend

For thermoplastic-insulated

1 Cable T-plug
2 Coupling T-plug
3 Screwed coupling
insert

cables
For cable T-plugs or cable

For connection cross-sections

up to 630 mm2
Cable routing downwards,

cable connection from the


front

* Cable connection height of


450 mm for switch-disconnector panels and contactor
panels with HV HRC fuses

HA35-2599 eps

elbow plugs with bolted contact

Connection with 1 cable per phase


connection with 2 cables per phase

Option: Cable routing to the

top at the rear, cable connection from the rear (only for
circuit-breaker panel 1250 A)

For rated normal currents

up to 2500 A

Surge arresters
Can be plugged into the

cable T-plug

HA35-2601 eps

ends and cable clamps are


not included in the scope of
supply

HA35-2600 eps

Cable plugs, cable sealing

Connection with 2 cables per phase


connection with 4 cables per phase

Surge arresters are recom-

Can be plugged into the

cable T-plug
Surge limiters are recom-

mended if motors with


starting currents < 600 A are
connected

HA35-2602 eps

Surge limiters

HA35-2603 eps

mended if, at the same time,


The cable system is directly
connected to the overhead
line,
The protective range of the
arrester at the terminal tower
of the overhead line does not
cover the switchgear

Connection with 3 cables per phase


connection with 6 cables per phase

34 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

130

175

Components
Installation possibilities for cable connections and surge arresters
Number of
cables per
panel and
phase

Make

Insulation Cable T-plugs


Conductor
cross-section 1)
bolted
12 kV
24 kV

mm2

Coupling inserts/
coupling plugs

Surge arresters with coupling inserts


Arresters
Coupling inserts

bolted
12 kV
24 kV

additionally

Circuit-breaker panel 630 A, 1000 A Switch-disconnector panel 630 A Disconnector panel 1000 A Ring-main panel 630 A
Contactor panel Circuit-breaker panel with top-rear cable connection 1250 A 2)
1

Euromold

Sdkabel

nkt cables

Tyco Electronics

2 3)

Euromold

Sdkabel

nkt cables

Tyco Electronics

35 to 300

EPDM

1x 400TB/G
1x K400TB/G

400PB-5(10)-SA-xxx

35 to 300

EPDM

1x 430TB-630A
1x K430TB-630A

300SA-5(10)SA

400 to 630

EPDM

1x 440TB/G
1x K440TB/G

400PB-5(10)-SA-xxx

50 to 300
25 to 240

Silicone

1x SET 12
1x SET 24

MUT 23

400 to 500
300 to 500

Silicone

1x SEHDT 13
1x SEHDT 23

MUT 23

25 to300

Silicone

1x CB 12-630
1x CB 24-630

CSA 12-x
CSA 24-x

400 to 630

Silicone

1x CB 36-630(1250)
1x CB 36-630(1250)

CSA 12-x
CSA 24-x

25 to 300

Silicone

1x RSTI-L56xx
1x RSTI-L56xx

RSTI-CC-L56SAxxxx
RSTI-CC-66SAxxxx

25 to 300

Silicone

1x RSTI-58xx
1x RSTI-58xx

RSTI-CC-58SAxxxx

400 to 630

Silicone

1x RSTI-36Lxx
1x RSTI-56Lxx

RSTI-L56SAxxxx
RSTI-66SAxxxx

RSTI-66CP-M16
RSTI-66CP-M16

35 to 300

EPDM

2x 400TB/G
2x K400TB/G

1x 400CP
1x K400CP

35 to 300

EPDM

1x 430TB-630A
1x K430TB-630A

1x 300PB-630A
1x K300PB-630A

400 to 630

EPDM

2x 440TB/G
2x K440TB/G

1x 440CP
1x K440CP

50 to 300
25 to 240

Silicone

1x SET 12
1x SET 24

1x SEHDK 13.1
1x SEHDK 23.1

50 to 300
25 to 240

Silicone

2x SET 12
2x SET 24

1x KU 23.2
1x KU 23.2

400 to 500
300 to 500

Silicone

2x SEHDT 13
2x SEHDT 23

1x KU 23
1x KU 23

25 to 300

Silicone

1x CB 12-630
1x CB 24-630

1x CC 12-630
1x CC 24-630

CSA 12-x
CSA 24-x

25 to 300

Silicone

2x CB 12-630
2x CB 24-630

1x CP 630-C
1x CP 630-C

CSA 12-x
CSA 24-x

400 to 630

Silicone

1x CB 36-630(1250)
1x CB 36-630(1250)

1x CC 36-630(1250)
1x CC 36-630(1250)

CSA 12-x
CSA 24-x

25 to 300

Silicone

1x RSTI-L56xx
1x RSTI-L56xx

1x RSTI-CC-L56xx
1x RSTI-CC-L56xx

RSTI-CC-L56SAxxxx
RSTI-CC-66SAxxxx

25 to 300

Silicone

1x RSTI-58xx
1x RSTI-58xx

1x RSTI-CC-58xx
1x RSTI-CC-58xx

RSTI-CC-58SAxxxx

400 to 630

Silicone

2x RSTI-36Lxx
2x RSTI-56Lxx

1x RSTI-66CP-M16
1x RSTI-66CP-M16

RSTI-L56SAxxxx
RSTI-66SAxxxx

RSTI-66CP-M16
RSTI-66CP-M16

1) Observe the actual current and short-circuit current carrying capacity of the cables and sealing ends.
2) For the 1250 A version, only sealing ends with silver-plated or nickel-plated cable lugs are permissible.
3) The use of arresters is not possible for cable connection panels 1250 A with top-rear cable connection.

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 35

Components
Installation possibilities for cable connections and surge arresters
Number of
cables per
panel and
phase

Make

Insulation Cable T-plugs


Conductor
cross-section 1)
bolted
12 kV
24 kV

mm2

Coupling inserts/
coupling plugs

Surge arresters with coupling inserts


Arresters
Coupling inserts

bolted
12 kV
24 kV

additionally

Circuit-breaker panel 1250 A 2) Disconnector panel 1250 A 2)


1

Same combination options as in the previous table

Euromold

Sdkabel

nkt cables

Tyco Electronics

Euromold

nkt cables

Tyco Electronics

35 to 300

EPDM

2x 400TB/G
2x K400TB/G

1x 400CP
1x K400CP

400PB-5(10)-SA-xxx

35 to 300

EPDM

1x 430TB-630A
1x K430TB-630A

1x 300PB-630A
1x K300PB-630A

300SA-5(10)SA

400 to 630

EPDM

2x 440TB/G
2x K440TB/G

1x 440CP
1x K440CP

400PB-5(10)-SA-xxx

50 to 300
25 to 240

Silicone

1x SET 12
1x SET 24

1x SEHDK 13.1
1x SEHDK 23.1

50 to 300
25 to 240

Silicone

2x SET 12
2x SET 24

1x KU 23.2
1x KU 23.2

400 to 500
300 to 500

Silicone

2x SEHDT 13
2x SEHDT 23

1x KU 23
1x KU 23

25 to 300

Silicone

1x CB 12-630
1x CB 24-630

1x CC 12-630
1x CC 24-630

CSA 12-x
CSA 24-x

25 to 300

Silicone

2x CB 12-630
2x CB 24-630

1x CP 630-C
1x CP 630-C

CSA 12-x
CSA 24-x

400 to 630

Silicone

1x CB 36-630(1250)
1x CB 36-630(1250)

1x CC 36-630(1250)
1x CC 36-630(1250)

CSA 12-x
CSA 24-x

25 to 300

Silicone

1x RSTI-L56xx
1x RSTI-L56xx

1x RSTI-CC-L56xx
1x RSTI-CC-L56xx

RSTI-CC-L56SAxxxx
RSTI-CC-66SAxxxx

25 to 300

Silicone

1x RSTI-58xx
1x RSTI-58xx

1x RSTI-CC-58xx
1x RSTI-CC-58xx

RSTI-CC-58SAxxxx

400 to 630

Silicone

2x RSTI-36Lxx
2x RSTI-56Lxx

1x RSTI-66CP-M16
1x RSTI-66CP-M16

RSTI-L56SAxxxx
RSTI-66SAxxxx

RSTI-66CP-M16
RSTI-66CP-M16

35 to 300 3)

EPDM

3x 400TB/G
3x K400TB/G

2x 400CP
2x K400CP

35 to 300

EPDM

1x 430TB-630A
1x K430TB-630A

2x 300PB-630A
2x K300PB-630A

400 to 630 3)

EPDM

3x 440TB/G
3x K440TB/G

2x 440CP
2x K440CP

25 to 300

Silicone

1x CB 12-630
1x CB 24-630

2x CC 12-630
2x CC 24-630

CSA 12-x
CSA 24-x

400 to 630

Silicone

1x CB 36-630(1250)
1x CB 36-630(1250)

2x CC 36-630(1250)
2x CC 36-630(1250)

CSA 12-x
CSA 24-x

25 to 300

Silicone

1x RSTI-L56xx
1x RSTI-L56xx

2x RSTI-CC-L56xx
2x RSTI-CC-L56xx

RSTI-CC-L56SAxxxx
RSTI-CC-66SAxxxx

25 to 300

Silicone

1x RSTI-58xx
1x RSTI-58xx

2x RSTI-CC-58xx
2x RSTI-CC-58xx

RSTI-CC-58SAxxxx

400 to 630

Silicone

3x RSTI-36Lxx
3x RSTI-56Lxx

2x RSTI-66CP-M16
2x RSTI-66CP-M16

RSTI-L56SAxxxx
RSTI-66SAxxxx

RSTI-66CP-M16
RSTI-66CP-M16

1) Observe the actual current and short-circuit current carrying capacity of the cables and sealing ends.
2) For the 1250 A version, only sealing ends with silver-plated or nickel-plated cable lugs are permissible.
3) Only possible with deeper cable compartment cover.

36 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

Components
Installation possibilities for cable connections and surge arresters
Number of
cables per
panel and
phase

Make

Insulation Cable T-plugs


Conductor
cross-section 1)
bolted
12 kV
24 kV

mm2

Coupling inserts/
coupling plugs

Surge arresters with coupling inserts


Arresters
Coupling inserts

bolted
12 kV
24 kV

additionally

Circuit-breaker panel and disconnector panel 2000 A, 2300 A, 2500 A 2)


2

Euromold

Sdkabel

nkt cables

Tyco Electronics

Euromold

Sdkabel

nkt cables

Tyco Electronics

35 to 300

EPDM

2x 400TB/G
2x K400TB/G

400PB-5(10)-SA-xxx

35 to 300

EPDM

2x 430TB-630A
2x K430TB-630A

300SA-5(10)SA

400 to 630

EPDM

2x 440TB/G
2x K440TB/G

400PB-5(10)-SA-xxx

50 to 300
25 to 240

Silicone

2x SET 12
2x SET 24

MUT 23

400 to 500
300 to 500

Silicone

2x SEHDT 13
2x SEHDT 23

MUT 23

25 to 300

Silicone

2x CB 12-630
2x CB 24-630

CSA 12-x
CSA 24-x

400 to 630

Silicone

2x CB 36-630(1250)
2x CB 36-630(1250)

CSA 12-x
CSA 24-x

25 to 300

Silicone

2x RSTI-L56xx
2x RSTI-L56xx

RSTI-CC-L56SAxxxx
RSTI-CC-66SAxxxx

25 to 300

Silicone

2x RSTI-58xx
2x RSTI-58xx

RSTI-CC-58SAxxxx

400 to 630

Silicone

2x RSTI-36Lxx
2x RSTI-56Lxx

RSTI-L56SAxxxx
RSTI-66SAxxxx

RSTI-66CP-M16
RSTI-66CP-M16

35 to 300

EPDM

4x 400TB/G
4x K400TB/G

2x 400CP
2x K400CP

400PB-5(10)-SA-xxx

35 to 300

EPDM

2x 430TB-630A
2x K430TB-630A

2x 300PB-630A
2x K300PB-630A

300SA-5(10)SA

400 to 630

EPDM

4x 440TB/G
4x K440TB/G

2x 440CP
2x K440CP

400PB-5(10)-SA-xxx

50 to 300
25 to 240

Silicone

2x SET 12
2x SET 24

2x SEHDK 13.1
2x SEHDK 23.1

MUT 23

50 to 300
25 to 240

Silicone

4x SET 12
4x SET 24

2x KU 23.2
2x KU 23.2

MUT 23

400 to 500
300 to 500

Silicone

4x SEHDT 13
4x SEHDT 23

2x KU 23
2x KU 23

MUT 23

25 to 300

Silicone

2x CB 12-630
2x CB 24-630

2x CC 12-630
2x CC 24-630

CSA 12-x
CSA 24-x

25 to 300

Silicone

4x CB 12-630
4x CB 24-630

2x CP 630-C
2x CP 630-C

CSA 12-x
CSA 24-x

400 to 630

Silicone

2x CB 36-630(1250)
2x CB 36-630(1250)

2x CC 36-630(1250)
2x CC 36-630(1250)

CSA 12-x
CSA 24-x

25 to 300

Silicone

2x RSTI-L56xx
2x RSTI-L56xx

2x RSTI-CC-L56xx
2x RSTI-CC-L56xx

RSTI-CC-L56SAxxxx
RSTI-CC-66SAxxxx

25 to 300

Silicone

2x RSTI-58xx
2x RSTI-58xx

2x RSTI-CC-58xx
2x RSTI-CC-58xx

RSTI-CC-58SAxxxx

400 to 630

Silicone

4x RSTI-36Lxx
4x RSTI-56Lxx

2x RSTI-66CP-M16
2x RSTI-66CP-M16

RSTI-CC-L56SAxxxx
RSTI-CC-66SAxxxx

RSTI-66CP-M16
RSTI-66CP-M16

1) Observe the actual current and short-circuit current carrying capacity of the cables and sealing ends.
2) For the 2000 A, 2300 A and 2500 A versions, only sealing ends with silver-plated or nickel-plated cable lugs are permissible.

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 37

Components
Installation possibilities for cable connections and surge arresters
Number of
cables per
panel and
phase

Make

Insulation Cable T-plugs


Conductor
cross-section 1)
bolted
12 kV
24 kV

mm2

Coupling inserts/
coupling plugs

Surge arresters with coupling inserts


Arresters
Coupling inserts

bolted
12 kV
24 kV

additionally

Circuit-breaker panel and disconnector panel 2000 A, 2300 A, 2500 A 2)


6

Euromold

nkt cables

Tyco Electronics

35 to 300 3)

EPDM

6x 400TB/G
6x K400TB/G

4x 400CP
4x K400CP

35 to 300

EPDM

2x 430TB-630A
2x K430TB-630A

4x 300PB-630A
4x K300PB-630A

400 to 630 3)

EPDM

6x 440TB/G
6x K440TB/G

4x 440CP
4x K440CP

25 to 300

Silicone

2x CB 12-630
2x CB 24-630

4x CC 12-630
4x CC 24-630

CSA 12-x
CSA 24-x

400 to 630

Silicone

2x CB 36-630(1250)
2x CB 36-630(1250)

4x CC 36-630(1250)
4x CC 36-630(1250)

CSA 12-x
CSA 24-x

25 to 300

Silicone

2x RSTI-L56xx
2x RSTI-L56xx

4x RSTI-CC-L56xx
4x RSTI-CC-L56xx

RSTI-CC-L56SAxxxx
RSTI-CC-66SAxxxx

25 to 300

Silicone

2x RSTI-58xx
2x RSTI-58xx

4x RSTI-CC-58xx
4x RSTI-CC-58xx

RSTI-CC-58SAxxxx

400 to 630

Silicone

6x RSTI-36Lxx
6x RSTI-56Lxx

4x RSTI-66CP-M16
4x RSTI-66CP-M16

RSTI-L56SAxxxx
RSTI-66SAxxxx

RSTI-66CP-M16
RSTI-66CP-M16

1) Observe the actual current and short-circuit current carrying capacity of the cables and sealing ends.
2) For the 2000 A, 2300 A and 2500 A versions, only sealing ends with silver-plated or nickel-plated cable lugs are permissible.
3) Only possible with deeper cable compartment cover.

38 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

Components
Panel connection (commercially available cable sealing ends)
Cable type

Cable sealing ends


Make

Thermoplastic insulated cables


1-core cable, PE and XLPE-insulated

Comment
Type

Cross-section
mm2

12 kV according to IEC 60 502-2 and VDE 0276-620


400 TB/G

35 to 300

N2YSY (Cu) and N2XSY (Cu)

430TB-630A

35 to 300

EPDM with semi-conductive layer

or

440 TB/G

400 to 630

EPDM with semi-conductive layer

CB 12-630

25 to 300

Silicone with semi-conductive layer


(optionally with metal housing)

NA2YSY (AI) and NA2XSY (AI)

Euromold

nkt cables

Sdkabel

Tyco Electronics

EPDM with semi-conductive layer

CB 36-630(1250)

400 to 630

Silicone with semi-conductive layer

SET 12

50 to 300

Silicone with semi-conductive layer


(optionally with metal housing)

SEHDT 13

400 to 500

Silicone with semi-conductive layer


(optionally with metal housing)

RSTI-L56xx

25 to 300

Silicone with semi-conductive layer, with capacitive


measuring point

RSTI-58xx

25 to 300

Silicone with semi-conductive layer, with capacitive


measuring point

RSTI-36Lxx

400 to 630

Silicone with semi-conductive layer, with capacitive


measuring point

Thermoplastic insulated cables 15/17.5/24 kV according to IEC 60 502-2 and VDE 0276-620
K400TB/G

35 to 300

N2YSY (Cu) and N2XSY (Cu)

K430TB-630A

35 to 300

EPDM with semi-conductive layer

or

K440TB/G

400 to 630

EPDM with semi-conductive layer

CB 24-630

25 to 300

Silicone with semi-conductive layer


(optionally with metal housing)

1-core cable, PE and XLPE-insulated

NA2YSY (AI) and NA2XSY (AI)

Euromold

nkt cables

Sdkabel

Tyco Electronics

Paper-insulated belted cables

EPDM with semi-conductive layer

CB 36-630(1250)

400 to 630

Silicone with semi-conductive layer

SET 24

50 to 300

Silicone with semi-conductive layer


(optionally with metal housing)

SEHDT 23

400 to 500

Silicone with semi-conductive layer


(optionally with metal housing)

RSTI-L56xx

25 to 300

Silicone with semi-conductive layer, with capacitive


measuring point

RSTI-58xx

25 to 300

Silicone with semi-conductive layer, with capacitive


measuring point

RSTI-56Lxx

400 to 630

Silicone with semi-conductive layer, with capacitive


measuring point

12 kV according to IEC 60 055 and VDE 0255

3-core cable, paper-insulated

nkt cables

CB 24-630

25 to 240

NKBA (Cu), NKBY (Cu),


NKRA (Cu) and NKFA (Cu)

Silicone with semi-conductive layer,


in combination with transition sealing end type SEV 10

Tyco Electronics

RSTI-58xx

25 to 300

Silicone with semi-conductive layer, with capacitive


measuring point, in combination with transition sealing
end type SMOE

or
NAKBA (AI), NAKBY (AI),
NAKRA (AI) and NAKFA (AI)

Paper-insulated belted cables


3-core cable, paper-insulated

12 kV according to GOST 18410-73


nkt cables

CB 24-630

25 to 240

Silicone with semi-conductive layer,


in combination with transition sealing end type SEV 10

Tyco Electronics

RSTI-58xx

25 to 300

Silicone with semi-conductive layer, with capacitive


measuring point, in combination with transition sealing
end type SMOE

ASB and ASBL

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 39

Components
Indicating and measuring equipment
Voltage detecting systems
acc. to IEC 61243-5 or
VDE 0682-415

LRM system

R-HA40-103 eps

L1 L2 L3

A2
A3
A4
A5

Integrated voltage indicator


VOIS+, VOIS R+

A6
ERROR

A0 CAPDIS-S2+: Operating voltage


not present
A1 Operating voltage present
A2 Operating voltage not present
For CAPDIS-S2+:
Auxiliary power not present

Integrated voltage detecting system


CAPDIS-S1+, -S2+

Routine-tested
Measuring system and volt-

age indicator can be tested

HA35-2537 eps

continuous operation

C1

U LE

A3 Failure in phase L1, operating voltage


at L2 and L3 (for CAPDIS-Sx+ also
earth-fault indication)

L1
L2
L3

C2

A4 Voltage (not operating voltage)


present
A5 Indication Device-Function-Test
passed

U2

Voltage indicator flashes

when high voltage is present


VOIS+, VOIS R+
Integrated display, without

L1 L2 L3

A1

Indicator suitable for


Safe-to-touch

CAPDIS-S2+

A0

Verification of safe isolation

from supply phase by phase


through insertion in each
socket pair

L1 L2 L3

HA35-25279 eps

Detecting systems
LRM system with plug-in
indicator
LRM system with integrated
indicator type VOIS+, VOIS R+
LRM system with integrated
indicator, with integrated
repeat test of the interface,
with integrated function test
type CAPDIS-S1+
LRM system with integrated
indicator, with integrated
repeat test of the interface,
with integrated function test,
with integrated signalling
relay type CAPDIS-S2+

VOIS+, VOIS R+ CAPDIS-S1+


Plug-in voltage indicator
per phase at
the panel front

R-HA40-104 eps

supply

Symbols shown

R-HA40-102a eps

To verify safe isolation from

Indicators and detecting systems

LRM system
plugged in

A6 Indication ERROR, e.g. in case of


missing auxiliary voltage
(see: error indication M4)

CAPDIS/VOIS
installed

Voltage indication
via capacitive voltage divider (principle)

auxiliary power
With indication A1 to A3,

(see legend)
Maintenance-free, repeat test

C1 Capacity integrated into bushing


C2 Capacity of the connection leads and
of the voltage indicator to earth

required
With integrated three-phase

test socket for phase comparison (also suitable for plug-in


voltage indicator)
Degree of protection IP 67,

temperature range -25 C to


+55 C
With integrated signalling

relays (only VOIS R+)


M1: Voltage present at one
phase L1, L2 or L3 as a
minimum
M2: Voltage not present
at L1, L2 and L3

ULE = UN / 3 during rated operation


in the three-phase system

U2 = UA = Voltage at the capacitive interface


of the switchgear or at the voltage indicator

CAPDIS-Sx+

Features of CAPDIS-S1+

Common features

Without auxiliary power

Maintenance-free

With indication A1 to A5

Integrated display, without

auxiliary power
Integrated repeat test of the

(see legend)
Without ready-for-service

monitoring

interfaces (self-monitoring)

Without signalling relay (thus

With integrated function test

without auxiliary contacts)

(without auxiliary power) by


pressing the Device-Function-Test pushbutton

With indication A0 to A6

With integrated three-phase

test socket for phase comparison (also suitable for plug-in


voltage indicator)
Degree of protection IP 54,

temperature range 25 C to
+55 C

Features of CAPDIS-S2+
(see legend)
Only by pressing the

Device-Function-Test
pushbutton: ERROR indication (A6), e.g. in case of
missing auxiliary voltage

With circuit capacity

40 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

With ready-for-service

monitoring (external auxiliary


power required)
With integrated signalling re-

lay for signalling M1 to M4


(auxiliary power required):
M1: Voltage present at
phases L1, L2, L3
M2: Voltage not present at
L1, L2 and L3 (= active zero
indication)
M3: Earth fault or voltage
failure, e.g. in one phase
M4: External auxiliary
power missing (operating
voltage present or not)

Components
Indicating and measuring equipment
Verification of correct
terminal-phase connections

Phase comparison test units


R-HA40-089 eps

nal-phase connections possible by means of a phase


comparison test unit
(can be ordered separately)

R-HA40-059 eps

Verification of correct termi-

Safe-to-touch handling of the

phase comparison test unit


by inserting it into the capacitive taps (socket pairs) of the
switchgear

Phase comparison test unit


Make: Horstmann, type ORION 3.0
as combined test unit for:
Phase comparison
Interface testing at switchgear
Voltage detection for LRM system

R-HA35-124.eps

Phase comparison test unit


Make: Pfisterer, type EPV

Phase comparison test unit


Make: Kries, type CAP-Phase
as combined test unit (HR and LRM)
for:
Voltage detection
Repeat test
Phase comparison
Phase sequence test
Self-test
The unit does not require a battery

or other makes

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 41

Components
Indicating and measuring equipment
Ready-for-service indicator
Gas monitoring

Low-voltage compartment

R-HA35-112b eps

R-HA35-105 eps

Features
Self-monitoring; easy to read
Independent of temperature

and pressure variations


Independent of site altitude
Only responds to changes in

gas density
Option: Alarm switch 1NO +

1NC for remote electrical indication


Mode of operation
For the ready-for-service indicator, a gas-tight measurement
box is installed inside the
switchgear vessel.

While changes in the gas density during the loss of gas, which
are decisive for the insulating
capacity, are displayed, temperature-dependent changes in
the gas pressure are not. The
gas in the measurement box
has the same temperature as
that in the switchgear.
The temperature effect is compensated via the same pressure
change in both gas volumes.
Low-voltage compartment

Control board (detail)


with red/green ready-for-service
indicator

HA35-2538 eps

A coupling magnet, which is


fitted to the bottom end of the
measurement box, transmits its
position to an outside armature
through the non-magnetizable
stainless-steel switchgear
vessel. This armature moves
the ready-for-service indicator
of the switchgear.

Low-voltage compartment with


multifunction protection relay SIPROTEC 4 7SJ61
(example)

2
3

Description
of the SIPROTEC 4 multifunction protection relays,
see page 43.

Stainless-steel vessel
filled with SF6 gas,
relative pressure
50 kPa at 20 C

Ready-forservice
indicator

Principle of operation
of gas monitoring
with ready-for-service indicator

For accomodation of protec-

tion, control, measuring and


metering equipment
Partitioned safe-to-touch

from the high-voltage part of


the panel
Low-voltage compartment

can be removed, bus wires


and control cables are
plugged in

1
2
3
4

Ready-for-service indicator
Measurement box
Magnetic coupling
Red indication:
Not ready for service
5 Green indication:
Ready for service

Option: High low-voltage

compartment (1161 mm
instead of 761 mm) possible

42 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

Components
Protection, control, indicating and measuring equipment
The low-voltage compartment can accommodate all
customary protection, control, measuring and monitoring equipment available
on the market.

Multifunction protection
relay SIPROTEC 4 7SJ63

Examples:

Functions: control,

program DIGSI 4 for configuration and analysis


Communications and bus

capability
Functions: control,

protection, indicating,
communications and
measuring
LCD (2 text lines) and key-

board for local operation,


configuration and display
Four user-programmable

LEDs for displaying any


desired data
Operation and fault indi-

cation memory
Fault recorder
Circuit-breaker control

Multifunction protection
relay SIPROTEC 4
7SJ61/7SJ62
For stand-alone or master

operation
Communications and bus

capability
Functions: control,

protection, indicating,
communications and
measuring

Communications and bus

capability
protection, indicating,
communications and
measuring

2
7

LCD for process and

equipment data, in the


form of a feeder mimic
diagram and as text, e.g.
for
Measuring and metering
values
Information on status of
switchgear and switching
device
Protection data
General indications
Alarms

R-HA35-104 eps

User-friendly operating

operation

Multifunction protection relay


SIPROTEC 4 7SJ600/7SJ602

Four user-programmable

function keys for frequently performed actions


Fourteen user-program-

mable LEDs for displaying


any desired data

Two key-operated

switches to switch between local and remote


control and interlocked
and non-interlocked
operation

4
2

Keys for navigation in

menus and for entering


values

R-HA35-103 eps

Multifunction protection
relay SIPROTEC 4
7SJ600/7SJ602

Multifunction protection relays SIPROTEC 4

For stand-alone or master

Integrated motor control

by special relays with


enhanced performance

Multifunction protection relay


SIPROTEC 4 7SJ61/7SJ62

Fault recorder

LCD (4 text lines) for pro-

cess and equipment data,


as text, e.g. for
Measuring and metering
values
Information on status of
switchgear and switching
device
Protection data
General indications
Alarms

4
2

Four user-programmable
5

function keys for frequently performed actions


ble LEDs for displaying
any desired data
Keys for navigation in me-

nus and for entering values


Fault recorder

Legend
1 LCD
2 LEDs
3 Key-operated switches
4 Navigation keys
5 Control keys
6 Function keys
7 LCD (text display)

R-HA35-102 eps

Seven user-programma-

3
6

Multifunction
protection relay
SIPROTEC 4 7SJ63

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 43

Standards
Standards, specifications, guidelines
Standards

Overview of standards (October 2007)

The NXPLUS C switchgear


complies with the relevant
standards and specifications
applicable at the time of type
tests.

IEC standard

VDE standard

EN standard

Switchgear

NXPLUS C

IEC 62 271-1

VDE 0671-1

EN 62 271-1

IEC 62 271-200

VDE 0671-200

EN 62 271-200

Devices

Circuit-breaker

IEC 62 271-100

VDE 0671-100

EN 62 271-100

Vacuum contactor

IEC 60 470

VDE 0670-501

EN 60 470

Disconnector and earthing


switch

IEC 62 271-102

VDE 0671-102

EN 62 271-102

Switch-disconnector

IEC 60 265-1

VDE 0670-301

EN 60 265-1

Switch-disconnector /
fuse combination

IEC 62 271-105

VDE 0671-105

EN 62 271-105

In accordance with the harmonization agreement reached by


the EU countries, their national
specifications conform to the
IEC standard.

Degree of
protection

Type of service location


NXPLUS C switchgear can be
used as indoor installation in
accordance with IEC 61 936
(Power installations exceeding
1 kV AC) and VDE 0101:

HV HRC fuses

IEC 60 282

VDE 0670-4

EN 60 282

Voltage detecting systems

IEC 61 243-5

VDE 0682-415

EN 61 243-5

IEC 60 529

VDE 0470-1

EN 60 529

Insulation

IEC 60 071

VDE 0111

EN 60 071

Instrument
transformers

Current transformers

IEC 60 044-1

VDE 0414-1

EN 60 044-1

Voltage transformers

IEC 60 044-2

VDE 0414-2

EN 60 044-2

Installation

IEC 61 936-1

VDE 0101

Table Dielectric strength


Rated voltage (r.m.s. value)

Dielectric strength
kV

7.2

12

15

17.5

24

Rated short-duration power-frequency withstand voltage (r.m.s. value)


Across isolating distances

kV

23

32

39

45

60

Between phases and to earth

kV

20

28

35

38

50

Outside lockable electrical

service locations. A lockable


electrical service location is a
place outdoors or indoors
that is reserved exclusively
for housing electrical equipment and which is kept under lock and key. Access is
restricted to authorized personnel and persons who
have been properly instructed in electrical engineering.
Untrained or unskilled persons
may only enter under the supervision of authorized personnel or properly instructed
persons

Across isolating distances

kV

70

85

105

110 145

Between phases and to earth

kV

60

75

95

95 125

Altitude correction factor Ka


For site altitudes
above 1000 m,
the altitude correction factor Ka
is recommended,
depending on the
actual site altitude
above sea level.

Ka
1.50

m=1

A
1.40

HA40-2037a en eps

Inside lockable electrical

Rated lightning impulse withstand voltage (peak value)

Altitude correction factor

service locations at places


which are not accessible to
the public. Enclosures of
switchgear can only be
removed with tools.

1.30
1.20
1.10
1.00
1000

1500

2000

2500

3000

3500

4000

Site altitude in m above sea level

Terms

Rated short-dur. power-frequ. withstand volt. to be selected for site altitudes > 1000 m

Make-proof earthing switches


are earthing switches with
short-circuit making capacity
according to
IEC 62 271-102 and
VDE 0671-102/
EN 62 271-102

W Rated short-duration power-frequency withstand voltage up to w 1000 m Ka


Rated lightning impulse withstand voltage to be selected for site altitudes > 1000 m
W Rated lightning impulse withstand voltage up to w 1000 m Ka
Example:

Result:

3000 m site altitude above sea level


17.5 kV switchgear rated voltage
95 kV rated lightning impulse withstand voltage

According to the above table,


a switchgear for a rated voltage of 24 kV with a rated
lightning impulse withstand
voltage of 125 kV is to be
selected.

Rated lightning impulse withstand


voltage to be selected
95 kV 1.28 = 122 kV

44 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

The dielectric strength is

verified by testing the switchgear with rated values of


short-duration powerfrequency withstand voltage
and lightning impulse withstand voltage according to
IEC 62 271-1/ VDE 0671-1 (see
table Dielectric strength).
The rated values are referred

to sea level and to normal


atmospheric conditions
(1013 hPa, 20 C, 11 g/m3
humidity in accordance with
IEC 60 071 and VDE 0111).
The gas insulation at a relative
pressure of 50 kPa (= 500 h Pa)
permits switchgear installation
at any desired altitude above
sea level, without the dielectric
strength being adversely affected. This also applies to the
cable connection when cable
plugs are used.
A decrease (reduction) of the
dielectric strength with increasing site altitude must only be
considered for panels with
HV HRC fuses.
This reduction is permitted up
to a site altitude of 1000 m
according to IEC and VDE.
For site altitudes above
1000 m, a higher insulation
level must be selected. It results
from the multiplication of the
rated insulation level for 0 to
1000 m with the altitude
correction factor Ka.

Standards
Standards, specifications, guidelines
Current-carrying capacity
According to IEC 62 271-200 /

VDE 0671-200 or
IEC 62 271-1/ VDE 0671-1,
the rated normal current refers to the following ambient
air temperatures:
Maximum of
24-hour mean
+ 35 C
Maximum
+ 40 C
The current-carrying capacity

of the panels and busbars


depends on the ambient air
temperature outside the enclosure.

Short-circuit-proof feeder

earthing by means of the


circuit-breaker or the
three-position switchdisconnector
In the unlikely event of a fault
within the switchgear vessel,
the energy conversion in the
case of an internal arc fault is
minor thanks to the gas-insulation, i.e. approximately only 1/3
compared to air. The escaping
gases are discharged upwards
through a pressure relief duct
(option).
Aseismic capacity (optional)

Protection of operating per-

NXPLUS C switchgear can be


upgraded for regions at risk
from earthquakes.

Internal arcing tests must be

performed in accordance with


IEC 62 271-200 and
VDE 0671-200
Definitions of criteria:
Criterion 1
Correctly secured doors and
covers do not open. Limited
deformations are accepted.
Criterion 2
No fragmentation of the
enclosure. Projection of small
parts up to an individual mass
of 60 g, are accepted.
Criterion 3
Arcing does not cause holes
in the accessible sides up to
a height of 2 m.
Criterion 4
Horizontal and vertical
indicators do no ignite due
to the effect of hot gases.
Criterion 5
The enclosure remains
connected to its earthing
point.

Resistance to internal faults


Due to the single-pole enclosure
of external components and the
SF6 insulation of switching devices, the possibility of faults in
gas-insulated switchgear is improbable and a mere fraction of
that typical of earlier switchgear
types, as

NXPLUS C switchgear is completely enclosed and insensitive


to climatic influences.
All medium-voltage devices

(except for HV HRC fuses) are


installed in a gas-tight, welded stainless-steel switchgear
vessel which is filled with
SF6 gas
Live parts outside the switch-

Type approval
NXPLUS C switchgear has been
type-approved by the following
classification societies:
Lloyds Register of Shipping

(LRS)
Det Norske Veritas (DNV)
German Lloyd (GL)

The switchgear is therefore also


approved for application on
ships and platforms.

gear vessel are provided with


single-pole enclosure
At no point can creepage cur-

Internal arc classification


sonnel by means of tests for
verifying the internal arc
classification

Climate and environmental


influences

For upgrading, earthquake


qualification testing has been
carried out in accordance with
the following standards:
IEC 60 068-3-3, 1993
IEC 60 068-2-6, 1995
IABG TA13-TM-002/98

(guide)
Within the range of the prevailing earthquake frequencies
from 1 Hz to 35 Hz, the category 1 required response spectrum to IABG TA13-TM-002/98
covers the following response
spectra:
Uniform Building

rents flow from high-voltage


potentials to earth
Operating mechanism parts

which are functionally important are made of corrosionresistant materials


Bearings in operating me-

chanisms are designed as


dry-type bearings and do not
require lubrication
Protection against solid
foreign objects, electric shock
and water
NXPLUS C switchgear fulfills
according to the standards
IEC 62 271-1

VDE 0671-1,
EN 62 271-1
IEC 62 271-200 VDE 0671-200
IEC 60 529

EN 60 529

Code zone 3
Seismic Requirements

Spec. 9067; Department of


Water & Power, Los Angeles

the following degrees of


protection:

GTS 1.013 ENDESA, Chile

Degree of
protection

Type of
protection

VDE 0670-111

IP 65

for live parts of


the primary
circuit under high
voltage

IP 3XD

for switchgear
enclosure
for switchgear
enclosure (option)
for switchgear
enclosure (option)

Colour of the panel front


Siemens standard (SN)
47 030 G1,
colour No. 700 / light basic
(similar to RAL 7047 / grey)

IP 31D
IP 34D

There are no effects due to

external influences, such as


Pollution layers
Moisture
Small animals and foreign
bodies
Maloperation is practically

excluded by logical arrangement of the operating


mechanism elements

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007 45

Notes
Notes
If not stated otherwise on the
individual pages of this catalog,
we reserve the right to include
modifications, especially
regarding the stated values,
dimensions and weights.
Drawings are not binding
All product designations used
are trademarks or product
names of Siemens AG or other
suppliers.
If not stated otherwise, all
dimensions in this catalog are
given in mm.

Responsible for
Technical contents:
Oliver Nldner
Siemens AG, Dept. PTD M 2 PPM
Erlangen
General editing:
Gabriele Pollok
Siemens AG, Dept. PTD CC M
Erlangen
46 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2007

Siemens AG
Power Transmission and Distribution
Medium Voltage Division
Postfach 32 40
91050 Erlangen
Germany
www.siemens.com/
medium-voltage-switchgear

For questions concerning Power


Transmission and Distribution:
You can contact our Customer Support
Center 24 hours a day, 365 days a year.
Tel.: +49 180/524 70 00
Fax: +49 180/524 24 71
(Charges depending on provider)
E-Mail: support.energy@siemens.com
www.siemens.com/energy-support

Subject to change without notice


Order No.: E50001-K1435-A401-A8-7600
Printed in Germany
Dispo 31606
KG 11.07 9.0 44 En