Beruflich Dokumente
Kultur Dokumente
I. INTRODUCTION
Is back feed
limit exceeded? ( for
DG case)
Yes
Curtail plant capacity to avoid
the reverse power flow
No
Solve for load flows
and fault levels (for
DG case)
Finish
I ij I ij m a x
(2 )
The three phase fault current in each line must be less than
the fault design rating of the switchgear on that line.
IFij IFijdesign
( 3)
ij
loss ( noDG )
i =1
PLi
i =1
Are
constraints breached ?
(Loss, line flow, voltage,
fault current )
Curtail DG size at
marked DG by unit
size.
Yes
+ Ploss %
i =1
No
Technically
constrained DG
sizes
Detect the DG
nearest to that line Yes
and mark it.
No
Run VSI program .
The DG with
Yes
highest VSI is
marked.
No
Detect the DG
nearest to the fault
and mark it.
Yes
(4)
ij
PGi
Enter
(1)
V i min V i V i max
a feeder group are more than the load (plus loss) for the feeder
group, the surplus plant capacity is shed at the plant with
largest biomass production cost (/kWh).
A Voltage Sensitivity Index (VSI) is used to identify the
plant that may have caused the voltage flag to set. Voltage
sensitivity index is defined as
V
V
VSI = w
+ (1 w)
(6)
P
Q
Where w, is the weighting factor depending on, line
reactance to resistance (X/R) ratio. The voltage sensitivity to
real power is greater than its sensitivity to reactive power for
low X/R lines found in low voltage distribution. Voltage
sensitivity is important in understanding the effect of the DG
capacity on the voltage of lines. This index is used in the
current study to identify the most sensitive DG bus location.
(5)
C. Economic optimization
In this section, the economic assessment of a biomass
power plant is discussed in detail. Economic assessment is
performed by the evaluation of economic performance
indicators such as Net Present Value (NPV) and Profitability
Index (PI). In this study, the radius of the biomass fuel
and
(8)
P CI
(9)
Y = r2 d
(11)
(14 )
E = e LHV Y
(1 + i )n 1
n
i (1 + i )
(17 )
(19 )
11 BB
BSP
March 132 BB
Chatteris 11 BB
Whittlesey 11 BB
Whittlesey
T1
Whittlesey T2
NOP
To Peterborough
Central Grid BSP
NOP
Whitt 33 BB
Chatteris T2
Chatteris T1
March T1
March 11 BB
March T2
March local
Grid 33 BB
Littleport T1
Littleport T2
Upwell 11 BB
Upwell 33 BB
Upwell T2
To Swaffham
Grid BSP
NOP
Southery T1
Southery 11 BB
Southery 33 BB
t r opel tti L
33 BB
t r opel tti L
With DG
@bus
None
March
Local
Upwell
Littleport
BSP
import
(MW)
Constrained
& Safe DG
(MW)
76.20
Constraints activated
Active
loss
(MW)
Bac
k
feed
Lin
e
Los
s
No
No
No
2.56
20.94
55.26
No
No
Yes
2.56
42.57
33.62
No
Yes
Yes
2.55
45.96
30.20
No
Yes
Yes
2.52
Whittelesey
Chatteris
52.40
23.72
No
Yes
Yes
2.48
44.18
32.00
No
Yes
Yes
2.54
31.83
44.32
No
Yes
Yes
2.51
(MW)
%
loss
red.
Loss
Constraints activated
Back
Lin
feed
e
Loss
1.61
33.43
20
10
0.91
43
No
No
No
33.43
20
10
0.91
43
No
No
No
Case
B
8.43
20
35
1.34
17
No
No
No
8.43
20
35
1.34
17
No
No
No
Case
C
21
21
21
0.87
46
No
No
No
21
21
21
0.87
46
No
No
No
TABLE III
SAFE MAXIMUM DG (GROUP OF 3) CAPACITY LEVELS (E: ECONOMICALLY
OPTIMAL SIZE AND T: TECHNICALLY CONSTRAINED SIZE OF DG)
DG Planned at buses in MW
LittleSout
Whittleport
h-ery
sey
No DG
case
Case
D
Case
E
Case
F
(MW)
%
loss
red.
Loss
Constraints activated
Back
feed
Line
Loss
2.56
32
22
22
6.45
No
Yes
Yes
12
17
22
2.13
16
No
No
No
22
22
32
4.66
No
No
Yes
12
17
32
2.44
No
No
No
22
32
22
7.11
No
Yes
Yes
12
17
22
2.14
16
No
No
No
200
150
% active power loss
Southery
100
50
0
Case A
Case B
Case C
Case D
Case E
Case F
-50
-100
Siting combinations
TABLE V
LOSS BASED APPROACH LEAST LOSS DETERMINATION
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
VII. BIOGRAPHIES
Sree L Payyala received her B.Tech. and M.Tech.
degrees in electrical and electronic engineering from
J.N.T. University, Ananthapur, Andhra Pradesh, India
in 1996 and 2002 respectively. She is currently
working for her Ph.D in the control and power
research group at Imperial College London, London,
UK. Her interests are in the area of distributed
generation planning, integration of renewables into the
distribution network and power systems economics.