Beruflich Dokumente
Kultur Dokumente
Technical Information GB
6.1.2.8 Edition 05.10
AGA
www.kromschroeder.com
Contents
Burner control units BCU 480 . . . . . . . . . . . . . . . . . . . . . . . . 1
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 Examples of application . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1 Stage-controlled main burner with alternating pilot
burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Stage-controlled main burner with permanent pilot
burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3 Two-stage-controlled main burner with permanent
pilot burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.4 Modulating-controlled burner . . . . . . . . . . . . . . . . . . . . 10
2.5 BCU 480..B1 for PROFIBUS-DP . . . . . . . . . . . . . . . . . . . . 11
2.6 BCU 480..D:
High temperature equipment . . . . . . . . . . . . . . . . . . . . . . . 11
3 Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.1 EC type-tested and certified . . . . . . . . . . . . . . . . . . . . . . 12
3.2 AGA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.3 CSA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.4 FM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.5 PROFIBUS User Organisation . . . . . . . . . . . . . . . . . . . . 13
3.6 Approval for Russia . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.1 Connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.1.1 BCU 480 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.1.2 BCU 480..B1 with Profibus . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.1.3 BCU 480..P with 16-pin industrial plug connector . . . . . . . 16
24
24
24
25
28
33
34
34
35
5.7.1 Purge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.7.2 Cooling in start-up position/standby . . . . . . . . . . . . . . . . . 41
5.7.3 Burner start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.7.4 Air valve opens in the case of external activation
(not during start-up) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.7.5 Air valve opens in the case of external activation
(even during start-up) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.7.6 Air valve opens with valve V2 . . . . . . . . . . . . . . . . . . . . . . 44
5.7.7 Air valve opens with operating signal . . . . . . . . . . . . . . . . 45
5.7.8 Low fire over run time tKN after a normal shut-down . . . . 46
5.7.9 Behaviour of the air valve in the event of a fault lock-out 47
= To be continued
3
6 Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.1 Safety time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.1.1 Calculating the safety time tSA . . . . . . . . . . . . . . . . . . . . . . 49
7.7 Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.7.1 Parallel reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.7.2 Permanent remote reset . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.7.3 Automatic remote reset (PLC) . . . . . . . . . . . . . . . . . . . . . . .
7.7.4 Burner start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.7.5 Restart and start-up attempts . . . . . . . . . . . . . . . . . . . . . .
53
53
53
53
53
= To be continued
= To be continued
1 Application
The burner control units BCU 480 control, ignite and monitor
gas burners for intermittent or continuous operation. As a result of their fully electronic design they react quickly to various
process requirements and are therefore suitable for frequent
cycling operation.
They can be used for industrial burners of unlimited capacity
which are ignited by pilot burners. Pilot and main burners may
be modulating or stage-controlled. The BCU 480 monitors pilot
and main burners independently. The pilot burner can burn
permanently or be switched off. The BCU is installed near to
the burner to be monitored.
On industrial furnaces, the BCU reduces the load on the central furnace control by taking over tasks that only relate to the
burner, for example it ensures that the burner always ignites
in a safe condition when it is restarted.
BCU 480 Edition 05.10
The air valve control assists the furnace control for cooling,
purging and capacity control tasks.
The program status, the unit parameters and the level of the
flame signal can be read directly from the unit. The burner
can be controlled manually for commissioning and diagnostic
purposes.
If the local requirements on the burner control unit change, the
PC software BCSoft can be adjusted to the unit parameters
of the application by using the optical interface.
The service personnel is supported by a convenient visualisation system of the input and output signals and the error
history.
Application
6
To reduce the installation and wiring costs, Elster Kromschrder
offers an optional PROFIBUS-DP interface to transfer the activation signals and feedbacks so as to expand the remote
servicing and diagnostics facilities.
Intermittent shuttle
kiln in the ceramics
industry
Walking beam
furnace with overhead firing
BCU 480 Edition 05.10
2 Examples of application
2.1 Stage-controlled main burner
with alternating pilot burner
Control:
Main burner ON/OFF.
The main burner can be started with reduced capacity after the operating signal
from the pilot burner has been detected.
The pilot burner is switched off automatically after the main burner has started
up. When the main burner is switched off,
the pilot burner automatically switches
on again. This reduces the main burner
start-up time.
A UV sensor monitors the flame signal
from pilot and main burners. UV sensor
UVD 1 is used for continuous operation,
UV sensor UVS for intermittent operation.
The BCU provides the cooling and purging processes.
L1, N, PE
P
DI
SPS
PLC
API
BCU 480
DI
23
22
21
18
19
26 14
12
24
16
17
28
29
VBY
UV
VAG
0204 0608
VR..L
0204 0608
1
1
2
Examples of application
L1, N, PE
P
DI
SPS
PLC
API
BCU 480
DI
23
22
21
18
19
26 14
12
24
16
17
28
29
VBY
VAG
0204 0608
VR..R
04
0608
04
1
1
2
Examples of application
L1, N, PE
Control:
Main burner ON/OFF with ignition via
bypass.
The main burner can be started at lowfire rate after the operating signal from
the pilot burner has been detected. When
the operating state is reached, the BCU
issues the Enable signal for the maximum burner capacity. Pilot and main
burners can be operated simultaneously.
This reduces the time required by the
main burner for starting up.
The BCU provides the cooling and purging processes.
DI
SPS
PLC
API
BCU 480
DI
23
22
21
18
19
50 51 26
14
12
24
16
17
28
29
VBY
VAS
VAG
0204 0608
M IC 40
BV
04
0608
04
1
1
2
Examples of application
10
L1, N, PE
P
DI
SPS
PLC
API
mA
DI
BCU 480
14
24
12
VBY
VAG
M
BV+IC
21
18
19
16
17
28
29
Control:
Main burner continuous
The butterfly valve for air is moved to ignition position in order to start the main
burner. The main burner can be started
at low-fire rate after the operating signal
from the pilot burner has been detected.
The control system controls the burner
capacity via the butterfly valve for air
after the operating state has been signalled. Pilot and main burners can be
operated simultaneously. This reduces
the time required by the main burner
for starting up.
Examples of application
11
L1, N, PE
P
DI
BUS
SPS
PLC
API
PROFIBUS-DP
BCU 480..B
BCU 480..B
BCU 480..B
16
16
16
BUS
BUS
BUS
BCU 480..D
C
L1
DI 6
STW >750 C
DI 6
24
24
Indirect flame control using the temperature. During the start-up process, as long
as the wall temperature is below auto
ignition temperature the flame must be
controlled by conventional methods.
When the working temperature has exceeded 750C, the safety temperature
monitor (STW) takes over the indirect
flame control.
12
3 Certification
3.3 CSA
pursuant to
Gas Appliances Directive (90/396/EEC) in conjunction with
EN 298:1993 and GAD-AC N 316E,
Low Voltage Directive (2006/95/EC) in conjunction with
EN60730,
Electromagnetic Compatibility Directive (2004/108/EC) in
conjunction with the relevant standards relating to radiation.
3.2 AGA
AGA
3.4 FM
13
14
s1
F1
V1
V2
O
I
(BCU 480..C)
F3
c2 N c1
1 2 3 4
40 41 42 43 44 45 46 47
88
230V~
BCU 480
v1 N
v2 N
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 50 51
PE
max. 2 A,
253 V
A
1
V1
DI
V2
L1 (L1)
N (L2)
PE
PE
7 8 9
24
PE
7 8 9 10
24 25
1
UVS 2
3
4 Function
4.1 Connection diagrams
For cable selection and wiring, see Project planning information.
15
s1
F1
V1
V2
O
I
(BCU 480..C..B1)
F3
c2 N c1
1 2
PE
40 41 42 43 44 45 46 47
88
230V~
BCU 480..B1
v1 N
v2 N
7 8 9 10 11 12 13 14 15
18 19 20
22
24 25 26 27
30 31 32 33 34 35 36 37 38 50 51
max. 2 A,
253 V
V1
DI
V2
L1 (L1)
N (L2)
PE
PE
7 8 9
24
PE
7 8 9 10
24 25
BCU 480..B1/1
2B 2A 1B 1A
ON
OFF
I
Z
1
UVS 2
3
PROFIBUS-DP
ON
OFF
16
4.1.3 BCU 480..P with 16-pin industrial plug connector
The burner control unit BCU 480..P can be supplied with an
industrial chassis plug (pursuant to VDE 0627). This 16-pin
plug connector ensures fast connecting or disconnecting of
units without any additional wiring required. This simplifies
replacing units and reduces standstill times.
All signals to the higher-level control system, the mains supply
and the safety interlocks are routed via this plug.
See Accessories.
17
s1
F1
V1
V2
O
I
(BCU 480..P..C)
c2 N c1
1 2 3 4
16 15 14 8
PE
7 8 9
PE
v1 N
v2 N
F3
max. 2 A,
253 V
s
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 50 51
V1
24
40 41 42 43 44 45 46 47
88
230V~
BCU 480..P
PE
V2
7 8 9 10
12 11 10 9
24 25
5 4 3
2 1
DI
16
15
14
12
11
10
PE
I
Z
1
UVS 2
3
L1 (L1)
N (L2)
Function
18
Switch on BCU 480
In the event of fault signal:
reset
BCU 480
If the air valve control is used,
the unit offers the following additional functions:
Start-up position/standby
If parameter P15 = 1:
flame simulation check
01
If parameter P15 = 0:
flame simulation check
02
19
Operating signal
Pilot burner closes
05
Wait until
min. burner pause time tBP
has elapsed (P21)
If parameter P15 = 0:
flame simulation check
06
The BCU coordinates the correct program run for the pilot and main burners. The main burner can be started via
the signal input Start-up signal 2 (terminal 21) if required. Once the start-up
signal 2 has been applied (terminal 21),
the BCU 480 opens valve V2. The main
burner is ignited by the pilot burner. If a
flame is detected during the safety time
tSA2, the flame proving period tFS2 starts
after the safety time tSA2 has elapsed. If
the main burner has been started successfully and its flame has stabilised, the
operation signalling contact (terminals
28/29) closes.
Start-up of the pilot burner without
flame signal
If no flame is detected during the safety
time tSA1, either a fault lock-out occurs
or up to three further start-up attempts
occur. The required functions and, if
applicable, the number of start-up attempts must be specified when ordering. (Parameter 10, Pilot burner start-up
attempts).
07
08
Operating signal
Main burner closes
08
Normal shut-down
via signal for
pilot and main burners
00
20
Function
21
DISPLAY
00
Cooling
A0
Purge
P0
Air valve
AX
X.X.
* In Manual mode, two dots will blink on the display in program status 0108 .
** Optionally available.
22
5 Parameters
Description
Flame signal, pilot burner
Flame signal, main burner
Program status when the most recent fault occurred
Switch-off threshold, pilot burner
Switch-off threshold, main burner
Start-up attempts, pilot burner**
Start-up attempts, main burner**
Restart, pilot burner
Restart, main burner
Safety time during operation for V1 and V2 tSB
Flame simulation check in start-up position/standby
Permanent pilot burner
Minimum combustion time tB
Minimum burner pause time tBP
Pilot burner safety time on start-up tSA1**
Pilot burner flame proving period tFS1
Main burner safety time on start-up tSA2**
Main burner flame proving period tFS2
Air valve control
Air valve can be activated externally on start-up
Air valve closed/can be activated in the event of malfunction
Parameter
Value range
01
02
03
04
05
10
11
12
13
14
15
16
20
21
22
23
24
25
30
31
32
099 A
099 A
x0x8
120 A
120 A
14
14
0; 1
0; 1
1; 2 s
0; 1
0; 1
25 s
0250 s
3; 5; 10 s
025 s
3; 5 s
025 s
0; 1; 2; 3
0; 1
0; 1
Factory
default setting
Adjustable*
1 A
1 A
1
1
0
0
1s
1
1
tSA
0s
0s
0s
0
0
1
Parameters
Description
High temperature operation**
Manual mode limited to 5 minutes
UVS check (1 x in 24 hours)
Low fire over run time**
* Adjustable using BCSoft software and a PC opto-adapter
** Please quote in your order.
0 = Function inactive,
1 = Function active.
23
Parameter
Value range
33
34
35
36
2; 3
0; 1
0; 1
0; 5; 15; 25 s
Factory
default setting
1
0
0s
Adjustable*
Parameters
24
5.2.4 Switch-off threshold of the flame amplifier
Parameter 04, pilot burner switch-off threshold
Parameter 05, main burner switch-off threshold
The sensitivity at which the burner control unit still detects a
flame can be set between 1 and 20 A.
Example: In the case of UV control with the UV sensor UVS,
the signal of the burner to be monitored is influenced by other
burners.
The set value can be incremented in parameter 04 so that only
the flame of the systems own burner is detected.
The measured flame signal of the systems own burner should
be at least 3 A (empirical value) higher than the set switchoff threshold.
25
The voltage may be applied to the DI input (terminal 6) so as
to activate High temperature operation only when the temperature at the furnace wall has exceeded 750C. The BCU
starts the burner as usual, without monitoring the presence
of the flame.
00
02
03
tZ
tFS
04
88
1
5
4 1
6 DI
7
9
12 V1
14 V2
16-17 1
18-19
t
tSA
Parameters > Flame control > High temperature operation in the case of BCU..D2 or BCU..D3
The BCU then responds, depending on setting:
Parameter 33 = 2 (BCU..D2)
08
01 02
03
tZ
tW
tFS1
04
06
07
tSA2
tFS2
08
Parameter 33 = 3 (BCU..D3)
08
88
1
5
4 1
7
6 DI
12 V1
1
9
16-17 1
21 2
14 V2
24 2
28-29 2
18-19
t
tSA1
The BCU switches off the burner once the DI input has been
disconnected from the electrical power supply and restarts
with flame simulation check (recommended in the case of UV
control with UVS).
26
08
88
30a
26e
10e 1
28c
22a DI
16c V1
26a 1
2c4c 1
14a 2
18e V2
2
18a
6a6e 2
2e4e
t
Parameters > Flame control > High temperature operation in the case of BCU..D2 or BCU..D3
If no flame signal is present when High temperature operation
is deactivated, the burner control unit performs a fault lock-out,
regardless of parameter 33.
Fault, pilot burner
04
04
88
1
5
4 1
7
6 DI
12 V1
1
9
16-17 1
21 2
14 V2
24 2
28-29 2
18-19
t
08
88
1
5
4 1
7
6 DI
12 V1
1
9
16-17 1
21 2
14 V2
24 2
28-29 2
18-19
t
27
28
Parameters
29
Automatic burner control unit BCU 480 for pilot and main
burner combination of unlimited capacity.
Pilot burner: single-stage-controlled.
Main burner: modulating or stage-controlled.
The burner control unit BCU 480 has separate start-up signal
inputs for the pilot burner (terminal 4) and the main burner
(terminal 21). The burner control unit coordinates the program
run (the interplay) of both burners. If required, the main burner
can be started once the pilot burner has reached its operating
position. Benefit: The time for starting up the main burner can
be reduced as low as its safety time. By using two flame amplifiers, the pilot and main burners can be monitored separately.
The BCU 480 can also be used on indirectly ignited surface
burners with end point monitoring.
Permanent pilot burner
0204 0608
04
0608
04 88
1
1
2
2
0204 0608
00
0204 0608
00 88
Pilot and main burners are controlled with one start-up signal (terminals 4 and 21 in parallel). The main burner starts
automatically after the operating signal from the pilot burner
has been detected. Operation is terminated simultaneously
for both burners.
Interrupted pilot burner
0204 0608
0204 0608
88
1
1
2
2
The pilot burner is switched off during the main burner safety
time tSA2. This type of flame monitoring is required if no distinction can be made between the flame signals of the pilot and
main burners (e.g. if both burners can be monitored with a
single UV sensor). If the start-up signal for the pilot burner is
applied continually, the pilot burner restarts immediately after
the main burner has been switched off.
30
03
tZ
tFS1
04
06
07
tSA2
tFS2
08
00
88
tSA1
02
03
04
06
07
2
5
1
4
7
V1
12
1
9
16-17 1
2
21
14
V2
2
24
28-29 2
18-19
tZ
tFS1
tSA2
tFS2
08
88
2
5
1
4
7
V1
12
1
9
1
16-17
2
21
14
V2
2
24
28-29 2
18-19
tSA1
Parameters
31
00
tLV
00 02
06
88
1
V1
88
1
5
4 1
7
9
12 V1
14 V2
16-17
18-19
V2
Parameter 15 = 0, parameter 16 = 1
00 01 02
05 06
If the BCU notices an extraneous signal during the flame simulation check, it starts the flame simulation delay time t LV (25
s). If the extraneous signal is discontinued during this period,
the burner can start up. Otherwise, a fault lock-out occurs.
1 blinks on the display if an extraneous signal is detected
by the pilot burner and 5 blinks if an extraneous signal is
detected by the main burner.
Parameter 15 = 0: The flame simulation check is conducted
after applying the start-up signal () during the waiting time
tW.
Parameter 15 = 1: The flame simulation check is conducted
provided no start-up signal () is applied (during the so-called
start-up position/standby). This allows fast start-up of the
burner since there is no waiting time tW.
The burner must have been switched off for at least 4 s before start-up in order for the flame simulation check to be
conducted correctly.
88
1
V1
V2
tW1
tW2
Parameter 15 = 1, parameter 16 = 0
00 02
06
88
1
V1
V2
Parameter 15 = 0, parameter 16 = 0
00 01 02
05 06
88
1
V1
V2
tW1
tW2
tBP
07
tSA2
tFS2
08
The time should be set such that the system can be moved to
ignition position, i.e. butterfly valves can be closed and, possibly, gas can be flared off, before a restart occurs.
See examples of application Stage-controlled main burner
with alternating pilot burner and Stage-controlled main burner
with permanent pilot burner.
The pause time has an effect on the behaviour of the main
burner only. Reason: The pilot burner is only used in singlestage operation.
88
1
5
4 1
7
1
9
12 V1
16-17 1
21 2
2
9
14 V2
28-29 2
18-19
t
32
Parameters
33
Main burner
Parameter 24
02
03
tZ
tFS
00 02
04
88
1
5
4 1
7
9 1
12 V1
14 V2
16-17 1
18-19
t
tSA1
This indicates the safety time on start-up tSA for the pilot
burner.
03
tZ
tFS1
04
06
07
tSA2
tFS2
08
88
2
5
1
4
7
V1
12
1
9
1
16-17
2
21
14
V2
2
24
2
28-29
18-19
tSA1
This indicates the safety time on start-up tSA for the main
burner.
34
02
03
tZ
04
88
1
5
4 1
7
9 1
12 V1
14 V2
16-17 1
18-19
04
06
07
tFS
tSA1
Main burner
Parameter 25
00 02
03
tZ
tFS1
04
06
07
tSA2
tFS2
08
88
2
5
1
4
7
V1
12
1
9
16-17 1
2
21
14
V2
2
24
28-29 2
18-19
tSA1
tSA2
tB
88
2
5
1
4
V1
12
1
9
16-17 1
2
21
14
V2
2
24
28-29 2
18-19
35
02
02
88
1
5
4 1
7
9
12 V1
14 V2
16-17
18-19
t
tZ
t SA
2 or 3 start-up attempts
Parameter 10 = 2, 3
00
02
88
1
5
4 1
7
9
12 V1
14 V2
16-17
18-19
tZ
tZ
tSA1
tSA1
02
04
06
06
88
1
5
4
7
12
9
tZ
2 or 3 start-up attempts
Parameter 11 = 2, 3
00 02
03
tFS1
tSA2
V1
1
16-17 1
21 2
14 V2
24 2
28-29 2
18-19
t
tSA1
04
06
05 06
05 06
06
88
1
5
4
7
12
9
tZ
tSA1
03
36
tFS1
V1
1
16-17 1
21 2
14 V2
24 2
28-29 2
18-19
t
If several start-up attempts are set at the works and if the BCU
does not detect a flame signal during start-up, it closes valve
V2 after the safety time tSA2 has expired and attempts to start
up again. After the last programmed start-up attempt has been
completed, the burner control unit conducts a fault lock-out.
The display blinks and shows the cause of the fault.
Parameters
37
5.6.2 Fault lock-out or restart, pilot burner
Parameter 12
This parameter determines whether the BCU starts a one-off
restart or performs an immediate fault lock-out for the burner
after an installation fault such as a flame failure or failure of
air flow (see also Project planning information).
5.6.3 Immediate fault lock-out following flame failure
Parameter 12 = 0: Pilot burner fault lock-out.
04
04
tSB
88
1
5
4 1
7
9
1
12 V1
14 V2
16-17 1
18-19
t
Parameters > Behaviour during operation > Immediate fault lock-out following flame failure
Restart following flame failure
Parameter 12 = 1: Restart following flame failure.
1x
04
01
03
>2 s
tSB
tFS1
tZ
tW
04
88
1
5
4 1
7
9 1
12 V1
16-17 1
18-19
t
tSA1
38
39
08
88
1
5
4
7
12
9
V1
1
16-17 1
21 2
14 V2
24 2
28-29 2
18-19
tSB
Parameters > Behaviour during operation > Fault lock-out or restart, main burner
Restart following flame failure
Parameter 13 = 1: Restart following flame failure.
1x
08
05 06
07
08
88
1
5
4
7
12
9
V1
1
16-17 1
21 2
14 V2
24 2
28-29 2
18-19
>2 s
tSA2
tSB
tFS2
tW2
40
Parameters
41
5.7.1 Purge
In the case of multiple burner applications, burners with mechanical combustion air supply are used. The air for combustion and pre-purge is supplied by a central fan controlled by
a separate logic. This logic determines the purging time.
The BCU..L supports centrally-controlled pre-purge or postpurge. The BCU..L is informed that purging is currently being
performed by input 22. It then opens the air valve, regardless
of the status of the other inputs (purging has priority). The
display indicates P0 .
For purging, the safety interlock (limits) must activate input 5
and input 22 of the BCU.
5.7.2 Cooling in start-up position/standby
The air valve can be activated externally via input 23 for cooling in the start-up position. During activation of the air valve
the display shows A0 , indicating that cooling is currently
being carried out.
5.7.3 Burner start
Parameters 30 and 31 determine the behaviour of the air valve
during burner start.
42
07
tSA2
L1
A8
88
2
5
4 1
7
12 V1
1
9
16-17 1
21 2
14 V2
24 2
28-29 2
23 A
26
18-19
tFS2
BCU 480..L
SPS
PLC
CPE
VAS 1
UV
VAG
VR..R
Parameter 30 = 0: The air valve opens if it is activated externally via input 23.
Parameter 31 = 0: The air valve remains closed during startup even if it is activated externally.
These settings are required on burners on which the gas/air
ratio is controlled via a pneumatic link and which also need
to be started at low fire, e.g. on two-stage-controlled burners.
In this case, activation of the air valve during burner start via
input 23 must be prevented.
External control allows switchover between low fire and high
fire during operation.
43
00 A0 00 A0 A2
tZ
A6
A7 A8
tSA2
tFS1
tFS2
tSA1
L1
BCU 480..L
VAS 1
UV
VAS..L
VAS
88
2
5
4 1
7
12 V1
1
9
16-17 1
21 2
14 V2
24 2
28-29 2
23 A
26
18-19
Parameter 30 = 0: The air valve opens if it is activated externally via input 23.
Parameter 31 = 1: The air valve can be activated even during start-up.
These settings may be selected only if the burner can start
with full air capacity.
44
03 04
00 A0 00 02
tZ
A7 A8
tSA2
tFS1
tFS2
tSA1
L1
BCU 480..L
SPS
PLC
CPE
VAS 1
1
VAS
VR..R
88
2
5
4 1
7
12 V1
1
9
16-17 1
21 2
14 V2
24 2
28-29 2
23 A
26
18-19
45
07
tSA
L1
A8
BCU 480..L
SPS
PLC
CPE
VAS 1
1
VR..R
88
2
5
4 1
7
12 V1
1
9
16-17 1
21 2
14 V2
24 2
28-29 2
23 A
26
18-19
tFS
VAS
46
5.7.8 Low fire over run time tKN after a normal shut-down
A8
00
88
1
5
4 1
7
12 V1
1
9
16-17 1
21 2
14 V2
24 2
28-29 2
23 A
26
18-19
tKN
L1
BCU 480..L
SPS
PLC
CPE
VAS 1
GIK..B
VG..N
VR..R
Parameter 36
Settings: 0; 5; 15 or 25 (low fire over run time in seconds)
This parameter is applicable to systems with a pneumatic link
between gas and air and On/Off control.
Parameter 36 = 0 (low fire over run time tKN = 0 s): Without low
fire over run, the gas side is closed immediately owing to the
quick-closing gas valve in the case of On/Off control. The air
side closes more slowly. The air flowing in during the closing
time increases the O2 content in the combustion chamber.
Parameter 36 = 5; 15 or 25 (low fire over run time
tKN = 5, 15 or 25 s):
The air valve closes slowly after the activation signal has
been switched off. The gas valve remains open for tKN. This
means that the burner, after deactivation of the start-up
signal (), is initially adjusted down to low fire and then
switched off completely.
Using the low fire over run function reduces the O2 content in
the furnace atmosphere.
Flame control is still operational. Can be used only in the case
of pneumatic link and On/Off control. Its must be ensured that
no excess gas occurs.
The low fire over run time has an effect on the behaviour of
the main burner only.
Background: The pilot burner is only used in single-stage
operation.
47
Parameters
48
5.8.1 Manual mode limited to 5 minutes
Parameter 34
Parameter 34 determines when Manual mode is terminated.
Parameter 34 = 0: Manual mode is not limited in time. If this
function has been selected, operation of the furnace may
be continued manually in the event of failure of the central
control system.
Parameter 34 = 1: Manual mode ends automatically five minutes after the last time the button was pressed. The BCU then
moves abruptly back to start-up position/standby.
49
6 Selection
6.1 Safety time
Please quote the safety time t SA when ordering.
EN 746-2
tSA
PN
70 kW
5s
> 70 kW*
3s
350 kW
> 350 kW**
10 s
5s
10 s
tSA = 3 s, 5 s or 10 s
PN = Rated heat output
PZ = Ignition capacity
The safety time of the automatic burner control unit depends
on the burner type, the burner capacity and the respective
application.
4.00 kW
5 s
Selection
50
1)
1)
Type = BCU
1st safety time on start-up:
tSA1 [s] = 3; 5; 10
2nd safety time on start-up:
tSA2 [s] = 3; 5
Safety time during operation:
tSB [s] = 1; 2
Air valve control = L
Low fire over run time [s] = 5*; 15*; 25*
Mains voltage
230 V AC, -15/+10%, 50/60 Hz = W
115 V AC, -15/+10%, 50/60 Hz = R
Ignition transformer
TZI 5-15/100 = 1*
TZI 7-25/20 = 2*
TZI 7,5-12/100 = 3*
TZI 7,5-20/33 = 8*
Front film in English (with additional stickers in D, F, I, NL, E) = GB
Industrial plug connector = P*
Digital input to interrupt the flame monitoring...
... for intermittent operation = D2*
... for continuous operation = D3*
Number of pilot burner start-up attempts = S2, 3**
Number of main burner start-up attempts = /2, /3**
Preparation for UV sensor for continuous operation UVD 1 = U*
Additional signal distribution
= C*
For PROFIBUS-DP = B1*
9-pin D-Sub bus plug connector, IP 54 = /1*
* If none, this specification is omitted.
** If 1 start-up attempt, this specification is omitted.
1) Not in conjunction with PROFIBUS-DP = B1.
= standard, = available.
C* B1* /1*
51
7.1.3 UV cable
Cable length: max. 50 m. Avoid external electrical interference.
Install as far as possible from mains and ignition cables and
interference from electro-magnetic sources. If possible, do
not lay in a metal conduit. Several UV cables can be routed
together.
52
06
07
tSA2
tB
88
2
5
1
4
V1
12
1
9
1
16-17
2
21
14
V2
2
24
28-29 2
18-19
7.7 Reset
7.7.1 Parallel reset
Several automatic burner control units can be reset in parallel
using the external button. The BCU cannot be reset by mains
failure.
7.7.2 Permanent remote reset
Permanent remote reset gives rise to a malfunction. If a remote
reset signal is permanently applied to terminal 3, 52 flashes
on the display to indicate a fault.
Reset with a pulse < 1 s.
7.7.3 Automatic remote reset (PLC)
In the case of automatic remote reset (PLC), the reset pulse
duration should not exceed 1 second. Check compliance with
standards.
If a fault is acknowledged by remote reset too often, error
10 (Too many remote resets) is displayed. The error can only
be acknowledged with the Reset/Information button on the
unit.
The burner malfunction must be remedied. The malfunction
can not be remedied by changing the method of activation.
53
7.7.4 Burner start
A furnace start may only be initiated, if it has been ensured
using an appropriate procedure that there is no combustible
mixture in the combustion/processing chamber, in the connected areas or in the exhaust gas system (heat exchanger,
dust collector). This can be achieved by pre-purge, which occurs immediately before ignition or within the period specified
in the operating instructions.
In the case of multiple burner applications, pre-purge is not
necessary after a normal burner shut-down.
Note the requirements of the Standards. For exceptions, see
Standards.
7.7.5 Restart and start-up attempts
The precondition for a restart/start-up attempt is that activation of the restart allows the burner to restart as intended (in
all operating phases). In this case, it must be ensured that
the program sequence started by the BCU matches the application.
Note the requirements of the Standards. For exceptions, see
Standards.
54
55
7.10 Installation
7.11 Wiring
From inside
Open BCU and screw on with four screws ( 4 mm, min. length
15 mm).
From outside
163 mm
6.42"
m
185 m "
7.28
56
Third gas valve (can be shut down) on
BCU..L
Units with an air valve control have an
additional contact (terminal), which closes at the same time as the air valve.
This can be used to activate a third gas
valve (V3). To do this the output of valve
V1 or V2 must be used as auxiliary energy (as a result of the required flame
monitoring).
L1, N, PE
P
DI
SPS
PLC
API
BCU 480
DI
23
22
21
18
19
16
17
50 51 26
14
12
28
29
24
25 26 27
50 51
VBY
V3
VAS
VAG
0204 0608
M IC 40
BV
04
0608
04
1
1
2
57
In general, the BCU cannot be activated when no mains voltage is applied or the burner control unit is switched off. The
fault signalling contact is only closed when the unit is supplied
with voltage and switched on.
If the unit is switched off, an immediate program abort with
switch-off of all outputs occurs (even during the safety time).
When the unit is switched on, the program run is restarted
in standby.
The mains switch in the unit isolates the BCU on two poles
from the mains. It does not meet the requirements of EN
50156-1:2004 (5.2.2 Switch disconnectors) set out in chapter
5 for a device to disconnect the power supply.
Although the mains switch cannot be used for disconnecting
from the electrical power supply in accordance with EN 50156,
it does allow the burner to be isolated functionally from the
central control system. This function is required for manual
operation and, in the case of PROFIBUS units, to switch off the
unit without causing BUS errors.
Disconnection for electrical maintenance work is to be implemented with an external switch per unit or group only, in
accordance with Standard EN 50156.
58
59
8 Flame control
8.1 With ionisation sensor
The BCU generates an alternating voltage (230 V AC) between
the sensing electrode and burner earth. The flame rectifies
this voltage. Only the DC signal (> 1 A) is detected by the
burner control unit.
A flame cannot be simulated. Ignition and monitoring with a
single electrode is possible.
60
9 Accessories
9.3 BCSoft
Accessories
61
m
174 m
5
6.8 "
230 mm
9.1"
212 mm
8.35"
m
185 m "
7.28
45
1.77mm
"
4 mm
0.16"
Order No.: 74960422
62
10 Technical data
Mains voltage:
230 V AC, -15/+10%, 50/60 Hz,
115 V AC, -15/+10%, 50/60 Hz,
for grounded and ungrounded mains.
Voltage to inputs and valves = mains voltage.
Signal and control line: max. 2.5 mm2 (AWG 14).
Cable for burner earth/PE wire: 4 mm2 (AWG 12).
Cable gland:
5 cable glands with multiple seal inserts for cable diameters of up to 7 mm,
BCU..P: with 2 cable glands and an industrial chassis plug.
Each BCU is supplied for two cable glands with one seal
insert each for cable diameters between 7 and 12 mm.
Input voltage of signal inputs:
Rated value
115 V AC
230 V AC
Signal 1
80126,5
160253
Signal 0
020
040
Frequency
50/60 Hz
50/60 Hz
Inherent current:
Signal 1
typ. 2 mA
Output current:
max. 1 A, cos = 1, for the valve outputs (or SRC outputs),
but total current for valves and ignition transformer:
max. 2.5 A
Fail-safe inputs and outputs:
All the inputs and outputs marked (see connection diagrams) may be used for safety tasks.
Technical data
Flame control:
sensor voltage approx. 230 V AC,
sensor current > 1 A.
Length of sensor cable: max. 5 m (16.4 ft).
Fuses in unit:
Fuse for protecting the air output (26):
F1: 5 A, slow-acting, H pursuant to IEC 127-2/5.
Fuse for protecting the safety-relevant ignition, valve 1 and
valve 2 outputs (terminals 7, 12 and 14):
3.15 A, slow-acting, not replaceable.
F3 (only for BCU.. A and C):
3.15 A, slow-acting, H pursuant to IEC 127-2/5.
Operation and fault signalling contacts:
Signalling contact for mains voltage, max. 2 A, 253 V,
not internally fused.
Ambient temperature: -20 to +60C (-4 to +140F),
Climate: no condensation permitted.
Enclosure: IP 54 pursuant to IEC 529.
Number of operating cycles:
Relay outputs: 250,000 pursuant to EN 298,
Mains switch: 1,000,
Reset/Information button: 1,000.
Weight: approx. 5 kg (11 lb) depending on version.
BCU..B1
External fuse: 12 A per zone.
63
Technical data
64
87")
m (7.
200 m
200 mm (7.87")
88
5
mm0 5
m5
(1.9
7") m
(2.1
7")
4,5 mm
0.177"
163 mm
6.42"
185 m
7.28"
A: Optical interface.
B: Labelling field for individual labelling of the system components.
C: 2-digit 7-segment display.
D: Mains switch to isolate the BCU on two poles from the
mains.
E: Reset/Information button to reset the system after a fault
or to scan parameters on the display.
65
11 Legend
88 Display
88 Blinking display
Ready
Safety interlocks (Limits)
1
2
DI
P
A
Purge
Ext. air valve control
Flame signal
Operating signal, pilot burner
2
Operating signal, main burner
Fault signal
Reset
Input signal
Output signal
Flame simulation check
tW Waiting time 2 s
tSA Safety time on start-up 3 s, 5 s or 10 s
tSB Safety time during operation < 1 s or < 2 s
tZ Ignition time 2 s, 3 s or 6 s
tLV Flame simulation delay time 25 s
tFS Flame proving period 025 s
1
66
12 Glossary
tW
01
01
02
1
14
4
5
9
6
22-23
24-25
tZ
88
L1
V1
V2
tW
t
tSA
Once the start-up signal has been applied, the waiting time
tW starts to elapse. During this time, a self-test is conducted
to detect errors in internal and external circuit components. If
no malfunction is detected, the burner will start up.
L1
V1
V2
04
tSB
1
14
4
5
9
6
22-23
24-25
88
L1
V1
V2
If the flame fails during operation, the valve outputs are disconnected within the safety time tSB.
t
BCU 480 Edition 05.10
88
tLV
1
14
4
5
9
6
22-23
24-25
Glossary
67
s1
c2 N c1
PE
230V~
TheF1start fuel flow rate for the main burner is released by main
V2 C V2.
N ItS opens when the safety time on start-up t
gasV1 valve
SA2
starts to elapse. It remains open until the burner is switched
off again byCa normal
88 shut-down or fault lock-out.
v1 N
v2 N
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
max. 2 A,
253 V
DI
V1
V2
68
Feedback
Finally, we are offering you the opportunity to assess this Technical Information (TI) and to give us your opinion, so that we
can improve our documents further and suit them to your needs.
Clarity
Found information quickly
Searched for a long time
Didnt find information
What is missing? sdvsdvsd
No answer
Comprehension
Coherent
Too complicated
No answer
Scope
Too little
Sufficient
Too wide
No answer
Use
To get to know the product
To choose a product
Planning
To look for information
Navigation
I can find my way around
I got lost
No answer
My scope of functions
Technical department
Sales
No answer
Remarks
sdvsdvsdv
Kromschrder AG
Michael Rehkamp
m.rehkamp@kromschroeder.com
Osnabrck
www.kromschroeder.com Sales
Kromschrder, a product
brand of the Elster Group
We reserve the right to make technical
modifications in the interests of progress.
Copyright 2007 Elster Group
All rights reserved.
03250692
Contact