Beruflich Dokumente
Kultur Dokumente
Angel
Yale University Optical Arc Flash fiber optic runs and relay
layout
Each master unit monitored the three phase currents from one
of the incoming source; and its high speed output contact was
wired to the incoming source breaker. The extension units
high speed output contact was wired to the tie breaker.
When the arc flash occurred in cubicle 19 the overcurrent and
light signals were activated and the master and extension units
open their prospective breaker thereby isolating and
extinguishing the arc flash immediately (2.5 ms + 3 cycle
breaker speed approx. 48 ms) resulting in minimal damage to
the switchgear and no injuries to personnel.
U.I.
1528
1536
Tie
11
13.8 kV Bus A
13.8 kV Bus B
13.8 kV Bus C
13.8 kV Bus D
GT-1
GT-2
19
1527
21 22
First
30 cycle UI Fault
Second
SPP was in low load configuration at the time of the fault, with
B-Bus UI feeders in service and the Tie breaker closed.
When the tie was closed an arc flash was immediately detected by
the newly installed arc flash system which opened the Tie breaker
and did not allow the arc flash to evolve into a catastrophic event.
(Bus Differential protection never detected the fault due to fast
response of the Arc Flash protection system.)
Detected
Fault
Current
Breaker
Provides
High
ROI
In Summary
Yale has installed the same Arc Flash protection system in its
Sterling and the Central substations 13.8 KV switchgear.