Beruflich Dokumente
Kultur Dokumente
041020
P
N
M
T
ASOLINK
ETWORK
Operation Manual
(for MIU)
ANAGEMENT
ERMINAL
NEC Corporation
Copyright 2004
ROI-S04075
Table of Contents
DOCUMENT WARRANTY........................................................................................................ 1
1
1.1
1.2
1.3
INTRODUCTION .................................................................................................................2
CONVENTIONS USED IN THIS MANUAL .............................................................................2
PNMT COMMUNICATION INTERFACES .............................................................................3
1.3.1
Communications .......................................................................................................3
2.1
2.2
2.3
2.3.1
2.4
2.5
2.6
LOGOUT ..........................................................................................................................10
SHUTTING DOWN THE PNMT .........................................................................................10
SEARCHING FOR NETWORK ELEMENTS AND CONNECTING TO SELECTED NETWORK
ELEMENT ..................................................................................................................................11
2.7 CHANGE PASSWORD ........................................................................................................12
2.8 ALARM BUZZER SETTING ................................................................................................13
2.9 REFRESH .........................................................................................................................14
2.10 VIEWING PNMT MAIN WINDOW .................................................................................15
2.11
2.12
2.13
2.14
2.15
2.16
2.17
2.18
CONFIGURATION..........................................................................................................31
2.19
2.20
-i-
ROI-S04075
Document Warranty
1. The information contained in this document is subject to change without prior notice.
2. The PNMS/PNMT screen figures in this manual are only examples. Screens will vary
according to equipment configurations, equipment operation modes, setting
parameters, PNMS/PNMT application program version, etc. Screens contained in this
manual are the latest one at the moment of publishing, however, they may differ from
actual screens on your PNMS/PNMT.
3. This manual is written on the assumption that you have already understood about the
restrictions, limitations and cautions to operate the equipment properly. Refer to the
equipment manual to operate the equipment properly.
- 1-
ROI-S04075
Getting Started
1.1
Introduction
The PASOLINK Network Management Terminal (PNMT) is developed by NEC for
management of NECs PASOLINK radio transmission network and associated plan. The
PNMT is a scaled down version of PASOLINK Network Management System (PNMS) that
is designed as a maintenance tool for field engineers to locally and remotely monitor alarms,
control points, generate reports, and archive data, all within a familiar graphical user
interface, and all in real time. The PNMT is a mobile laptop computer fitted with NEC PNMT
software package that interfaces and controls NEC PASOLINK series short haul radio
equipment. Moreover, PNMT can control and monitor the other types of NEC radio
equipment (2500S/2600S/2000S/3000S/3500S) and other manufactures equipment by
using Management Interface Unit (MIU).
This software package remote monitors and controls the status and configuration of an
entire radio transmission network with associated equipment as well as the performance of
the actual microwave links.
1.2
Font
Italic
Hostname
Bold
Example
Please refer to PASOLINK
Operation Manual for details.
The Overall window
Menu Items
<username>
Keycap
Keyboard keys.
- 2-
Login/Logout
ROI-S04075
1.3
1.3.1
Communications
Communications between the PNMT and the managed equipment can be via the PNMT
port of the MIU equipment or via the digital service channel to a remote node in the network.
1.3.1.1
The PNMT port is located on the front of the MIU equipment as shown in the following front
view drawings of MIU.
CONT/ANALOG/PMON1
ALM/STATUS1
MIU
EXP2
RESET1 ALM1
PWR
SEL V
SV11
PNMS1
PNMT1
EXP1
FUSE(7.5A)
PWR -
ALM/STATUS1
MIU
EXP2
RESET1 ALM1
PWR
SEL V
SV11
SV12
PNMS1
PNMT1
EXP1
FUSE(7.5A)
PWR -
(b) G8003B, H: For 1 System (Equipment) Monitor and Control with G.703 interface
CONT/ANALOG/PMON1
ALM/STATUS1
EXP2
RESET1 ALM1
CONT/ANALOG/PMON2
MIU
ALM/STATUS2
RESET2 ALM2 PWR
SEL V
SV11
PNMS1
PNMT1
EXP1
SV21
PNMS2
PNMT2
FUSE(7.5A)
PWR -
ALM/STATUS1
EXP2
RESET1 ALM1
CONT/ANALOG/PMON2
MIU
ALM/STATUS2
RESET2 ALM2 PWR
SEL V
SV11
SV12
PNMS1
PNMT1
EXP1
SV21
SV22
PNMS2
PNMT2
FUSE(7.5A)
PWR -
(d) G8003D, K: For 2 System (Equipment) Monitor and Control with G.703 interface
CONT/ANALOG/PMON1
ALM/STATUS1
MIU
EXP2
RESET1 ALM1
PWR
SEL V
SV11
PNMS1
PNMT1
EXP1
LAN
FUSE(7.5A)
PWR -
(e) G8003E, L: For 1 System (Equipment) Monitor and Control with LAN interface
CONT/ANALOG/PMON1
ALM/STATUS1
MIU
EXP2
RESET1 ALM1
PWR
SEL V
SV11
SV12
PNMS1
PNMT1
EXP1
LAN
FUSE(7.5A)
PW
R
(f) G8003F, M: For 1 System (Equipment) Monitor and Control with G.703 and LAN interface
- 3-
ROI-S04075
The PNMT port consists of a subminiature DB15 connector and connects to PM Card
installed in the MIU via the PNMT cable to the relevant communications port of the PNMT
PC.
The PNMT port has the following properties:
Connector type:
Stop bits:
Parity:
no parity.
The following table is given cabling pin assignment of the connection between PNMT Port
and PNMT PC.
15-pin (M)
9-pin (F)
MIU
PNMT port
Connector
PNMT PC
Serial port
RS-232C
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
GND
PNMT-CTS
PNMT-RTS
PNMT-RXD
GND
PNMT-TXD
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
CD
RD
TD
DTR
GND
DSR
RTS
CTS
RI
PNMT PC
- 4-
ROI-S04075
2.1
PNMT Screen
The PNMT window is comprised of the following main parts as shown in the following
screen example.
Title Bar
The title bar of the window is used to indicate the title of the window.
Block Diagram
The block diagram illustrates the equipments of the managed NE. Its main purpose in the
window is to display the current summary alarm state of the equipment. You can click on a
specific block to display the status of equipment in the data window.
Data window
This window displays in detail the status and alarm items of a specific part of the NE. You
can select the tab or the block of the specific part, which you want to monitor in the data
window.
Tab
To view the status and alarms in the specific part of the NE, click on the tab at the bottom
of the Data window.
Command Button
The command button is used to execute the specified operation on the pop-up window.
Login User
This indicates the current user who has logged-in the PNMT.
- 5-
ROI-S04075
Title Bar
Common
Menu Bar
Common
Tool Bar
Block
Diagram
Data
window
Tab
Login User
Pop-up window
Command Button
- 6-
ROI-S04075
2.2
2.
3.
Click on Start
Programs
Pnmt
Pnmt, then following PNMT system
logo, the PNMT main window appears. (See figure below.)
- 7-
ROI-S04075
2.3
Login
Users are registered by means of login name and password.
To protect the network and network management system from unauthorized access or
unauthorized modifications, five levels (refer to the table shown in section 2.3.1 User Level
Privilege) of users are defined with different privileges. The functions that are available
depend on the users access level. Therefore, some of the functions may or may not be
carried out.
The highest level or administrator level has full access to the network and network
management system.
To login:
1. Click on System
2. Select Login.
3. Enter the <user name>.
4. Enter the valid <password> for the specific User.
5. Click on the [OK] button.
- 8-
ROI-S04075
2.3.1
Category
Item
Menu-System
Alarm Buzzer
Equipment Type
Event Log
Save to disk
Threshold
Save to disk
Input Item
Output Item
Date/Time
Reset
Configuration File
Program File
Configuration
Equipment
PMC
Parallel I/O
Control
Download (PC PMC)
Upload (PMC PC)
Monitor
User
Local
*Admin:
*Remote:
Remote
Admin
*User:
*Monitor:
- 9-
ROI-S04075
2.4
Logout
To logout from PNMT:
2.5
1.
Click on System
2.
Select Logout.
3.
2. Click on [YES] button on the confirmation message window to close the application.
- 10-
ROI-S04075
2.6
NOTE
Initially only the current Network Element physically
connected to the PNMT and its opposite Network
Element will be shown on the Network Element List.
- 11-
ROI-S04075
2.7
Change Password
To change the password:
1. Click on System
window.
- 12-
ROI-S04075
2.8
2. Select the Wave file radio button to activate the buzzer. No sound is the factory
setting of the PNMT.
3. If you select the Wave file radio button, enter the location of the sound file
(*.wav) Otherwise; click on browse [] button to locate the desired file. You can
also preview the *.wav file by click on the arrow [] button next to the browse
button. If you select the Beep radio button, click on [Edit] button to edit the
beep with its frequency and duration. You can also preview the beep sound by
click on the arrow [] button next to the edit button.
4. Click on [OK] button to activate the new setting.
NOTE
Beep function is not available on Windows 98.
- 13-
ROI-S04075
2.9
Refresh
This function is supported only by PNMT. This function enables PNMT to acquire all status
manually and to update equipment information
To Refresh:
1. Click on Refresh
Refresh in the menu bar or click on the refresh icon in the
tool bar on the PNMT main window.
NOTE
Metering items such as TX power, RX level, power supply
and BER are automatically refreshed every 15 seconds.
This function is used when the immediate refreshing of
these metering items is necessary or confirmation of all
current status is immediately required.
- 14-
ROI-S04075
- 15-
ROI-S04075
2.10.1
Monitored Item
Following items can be monitored in the Equipment tab on the PNMT main window.
MONITOR PARAMETER
RX LEVEL No.1 CH
RX LEVEL No.2 CH
MONITOR STATUS
Parallel Input (Alarm/Status)
Parallel Output (Control)
Following items can be monitored in the PMC tab on the PNMT main window.
CONTROL BUTTON
Date/Time
PMC Reset
Configuration (Download)
Program File (Download)
Configuration (Upload)
PMC Version
- 16-
ROI-S04075
NOTE
To set the value of the Date and
Time field to the same value as that
of the PNMT PC, check on the
Display PC Time check box.
- 17-
ROI-S04075
Click on [Program File] button in the Download (PC >> PMC) section in the
PMC tab on the PNMT main window.
2.
Enter the appropriate location of the program file (*.pof) in the File field.
Otherwise, click [Browse] button to locate the file.
WARNING!!!
Make sure that the correct program file is downloaded
to the PM Card. Incorrect program file will lead to PM
Card failure.
3.
4.
A message window will appear displaying the status of the operation. Do Not
click [Cancel] button, otherwise you would have to repeat the operation. The
message window will close automatically once the download is completed.
NOTE
This operation may take several minutes depending on
the program file size.
- 18-
ROI-S04075
- 19-
ROI-S04075
Click on [Configuration File] button in the Download (PC >> PMC) section in
the PMC tab on the PNMT main window.
2.
- 20-
ROI-S04075
3. Enter the location of the configuration file in the File field, or click [Browse] to
locate the file on the local hard disk or diskette.
WARNING!!!
Make sure that the correct configuration file is downloaded
to the correct PM Card. Incorrect configuration file will lead
to PM Card or network failure.
4.
5.
A message window indicating the status of the operation will appear. It will close
automatically once the operation is finished. Click [Cancel] button to abort the
operation.
WARNING
Make sure that you have successfully downloaded the
configuration file before doing Update. Otherwise the PM
Card will switch to an empty ROM that may cause PM Card
failure.
6.
7.
Select the appropriate box for the type of configuration file that will be updated.
One or more configuration file can be updated by checking the box opposite to
the configuration file name. Click on [Execute] button to start the operation.
NOTE
When updating configuration file, PMC to PMC
communication will be lost when the PMC re-initializes to
the new configuration. This WILL NOT affect the radio link.
During this time PNMT connection to the Network Element
will be lost but will automatically be reconnected after the
PMC resets.
8.
- 21-
ROI-S04075
Click on [Configuration File] button in the Upload (PMC >> PC) section in the
PMC tab on the PNMT main window.
2.
3. Enter the location of the configuration file in the File field, or click [Browse]
button to locate the file on the local hard disk or diskette.
4. Click on [Execute] button to start the operation.
5. A message window indicating the status of the operation will appear. It will close
automatically once the operation is completed.
6. After the upload is finished click on [Close] button.
7. Verify that the file was uploaded on the specified directory.
- 22-
ROI-S04075
Click on [PMC Reset] button in the PMC tab on the PNMT main window.
2.
3.
- 23-
ROI-S04075
Version Monitor
To display the version of PMC:
1. Click on the PMC tab on the PNMT main window.
Version of PMC
- 24-
ROI-S04075
- 25-
ROI-S04075
2.17.1
Monitored Item
Following items are monitored.
1. Sixteen (16) inputs (Input-1 to Input-16)
2. Four (4) relay outputs. (Output-1 to Output-4)
2.17.2
(2)
(3)
(4)
(5)
(6)
(7)
(8)
- 26-
ROI-S04075
NOTE
PMON Ach indicates first PMON input information of the
CONT/ANALOG/PMON connector on MIU. PMON Bch
indicates second PMON input information.
4. Select the desired condition (Alarm when Event ON or Alarm when Event OFF
or Status) in the Condition field when Status (Not Maint) is selected in Maint
Mode field. In case that Maint for item is selected in Maint Mode field,
option items in Condition field change from Alarm to Maint. Select the
desired condition (Maint when Event ON or Maint when Event OFF) in the
Condition field when Maint for item is selected in Maint Mode field.
5. Enter the desired name on the Status Strings field for Event ON and Event
OFF states. A maximum of 32 characters can be used.
6. Select the desired item (Severity or Alarm Type or Probable Cause) that is to
be configured in the list on the corresponding combo box. ITU-T X.733
recommendation establishes user requirements for the alarm reporting function.
7. Select the HDLC Relay state (Enable or Disable) in the HDLC Relay (High
BER) field.
NOTE
HDLC Relay control action when High BER Alarm occurred
on Network Equipment can guard that the MIU sends bad
data (error data) to upper other MIU.
8. Click on [Execute] button to activate the new values set.
(2)
(3)
(4)
(5)
(8)
In Case of Maint Setting
- 27-
ROI-S04075
(2)
(3)
(4)
(5)
(8)
In Case of Status Setting
CAUTION:
Photocoupler Intput
Event OFF (low): The status that input is closed.
Event ON (high): The status that input is opened.
- 28-
ROI-S04075
2.17.3
2.17.3.1
(2)
(4)
(3)
(5)
In Case of 1 Port Control Setting
1. Click Output (1-4) button in Equipment tab on the PNMT main window.
2. Enter the desired name on the Name field. A maximum of 32 characters can be
used.
3. To set Event ON or Event OFF, the output selects the appropriate item (Event
ON or Event OFF).
4. Enter the desired strings for the open and close states of the Relay in the
appropriate Even ON and Event OFF fields in the Control field. A maximum of
32 characters can be used.
5. Click on [Execute] button to activate the new values set.
CAUTION:
Relay output (Form-C)
Event OFF (low): The status that Common and NC
(Normal Close) points are closed.
Event ON (high): The status that Common and NO
(Normal Open) points are closed.
- 29-
ROI-S04075
2.17.3.2
Event ON (Open)
Pattern 1
Pattern 2
Event ON (Open)
Pattern 3
Pattern 4
4. Enter the desired strings for the open and close states of the Relay in the
appropriate [Status Strings] fields in the Control field. A maximum of 32
characters can be used.
CAUTION:
Please refer to your Network Element Operation Manual for
detailed control method of parallel output data. Switch
made of NEC (2500S, 2600S, 2300S, and 3500S) is executed
by using 2 Port Control.
5. Check the desired item in the [Inhibit] box in case of control inhibition pattern.
6. Click on [Execute] button to activate the new values set.
- 30-
ROI-S04075
2.18 Configuration
PM Card portion and Parallel Input/Output usage can be monitored and controlled in this
window.
CAUTION:
Please refer to your Network Element Operation Manual for
detailed explanation of the configurable items mentioned
below.
2.18.1
Configuration Monitor
To open the Configuration Monitor:
1. Click on [Configuration] button in PNMT main window.
2.18.1.1
- 31-
ROI-S04075
2.18.1.2
2. Enter the optional description for the specific Network Element in the Note dialog
box. A maximum of 80 characters can be used in this field.
3. Click on [Execute] button when finished.
4. Click on [Close] button when finished.
2.18.1.3
- 32-
ROI-S04075
2.18.1.4
2. Select the desired Bit Rate ID (Other or 32M or 17M or 8M) in the Bit Rate ID
(PM) field. Setting data is used in Block Error Counter for Performance Monitor.
CAUTION:
Please refer to your Network Element Operation Manual for
detailed traffic capacity of the Performance Monitor.
3. Click on [Execute] button to change to new Bit Rate ID (PM).
4. Click on [Close] button when finished
- 33-
ROI-S04075
2.18.1.6
2. Select the desired option button (Low Active or High Active) in the FASYNC
Alarm Active (PM) field. Setting data is used in UAS Error for Performance
Monitor.
CAUTION:
Please refer to your Network Element Operation Manual for
detailed FASYNC output information. Existence of FASYNC
information depends on your Network Element. FASYNC
information is used in Performance Monitor only when
your Network Element has it.
3. Click on [Execute] button to change to new FASYNC Alarm Active (PM).
4. Click on [Close] button when finished.
2.18.1.7
2. Select the desired option button (Not Convert or 1 Item Convert or 2 Item
Convert) in the A/D Convert Type field. Setting data is reflected in Analog (RX
LEV No.1 CH/No.2 CH) indication on PNMT main window.
CAUTION:
Please refer to your Network Element Operation Manual for
detailed output number of analog data.
3. Click on [Execute] button to change to new A/D Convert Type.
4. Click on [Close] button when finished.
- 34-
ROI-S04075
2.18.1.8
2. Select the desired Parallel Output Port Usage (Single or Pair) in the Parallel
Output Port Usage field. In case of 2 Port Control, a set of even and odd port is
used. Setting data is reflected in Control indication (Parallel Output) in the
Equipment tab on the PNMT main Window.
CAUTION
Please refer to your Network Element Operation Manual for
detailed control method of parallel output data. Switch
made of NEC (2500S, 2600S, 2300S, and 3500S) is executed
by using 2 Port Control.
3. Click on [Execute] button to change to new A/D Convert Type.
4. Click on [Close] button when finished.
- 35-
ROI-S04075
- 36-
ROI-S04075
Threshold setting
To set the threshold values:
1. Click on [Threshold] button in the Summary Link Performance Monitor window.
2. Set the value when the Occur and when the Recover in the appropriate item
(ES/SES/UAS/BBE).
3. Click on [Execute] button to activate the new settings.
4. Click on [Close] button when finished
- 37-
ROI-S04075
2.19.3
- 38-
ROI-S04075
2.19.5
WARNING!!!
Make sure that the current data has been saved. This
operation will delete all the performance data in the current
week.
2. Click on [Execute] button to reset all the data.
- 39-
ROI-S04075
3. The Event Log View window will be displayed after uploading the data.
- 40-