OUTDOOR CABINET

LITESPAN-1540

01

02/12/2009

ED

DATE

CHANGE NOTE

FGM
AND / LITESPAN
EXCELLENCE CENTER

MGM
AND / LITESPAN
EXCELLENCE CENTER

APPRAISAL AUTHORITY

ORIGINATOR

SAD-OUTDOOR INSTAL. MANUAL


LITESPAN 1540 FR3 I/T
INSTALLATION GUIDE

01

PD 08

3AM 20060 0001 RJZZA

1/164

PEIC: (position 1-right)


One of these boards provides power input and PDH transport interfaces (16xE1) connections. Its
equipped in position 1 of the subrack and it should be always present in all shelves.
POW3-A/B: (position 1-right)
One of these boards provides power input. Its equipped in position 1 of the subrack and it should be
always present in all shelves.
In particular, POW3-B will be equipped when LINA (ADM) is equipped.

For details on ANIT-A and PEIC-POW3-A/B position and switches configuration se document 3AM 20059
0001 RJZZA, Indoor Installations Manual for Litespan 1540 FR3.1.

Regarding POW3-A/B or PEIC PCBs, it should be noted that before extracting it from the
subrack ALL other PCBs must be REMOVED.
In particular, if POW3-A/B or PEIC are extracted with NEHC equipped in the subrack, the
NEHC could be damaged.

LITESPAN-1540 FR3.2 OUTDOOR CONFIGURATIONS

There are several available configurations for the Outdoor Cabinet, depending on the cooling system, on the
number of MLS used and on the inclusion or not of an ISAM equipment for Broadband.
4.1

Outdoor Cabinets Cooling System

With Filtered External Air Exchange:

The cool air gets into the cabinet through some openings provided with filters on the lower part of the
Electronics door and moves through the MLS-3F.
This air flux is enhanced by a Fans Tray with 4 axial non stop DC fans over the subrack, which forces it
inside the double roof and then to the outside environment. The output has also filters
This fan tray can be the Litespan 3AM 20071 BGAA or else another fan tray with similar functionality, with
4 axial non stop fans.
The filters and the non-stop fans warrant the IP-55 condition in the inside of the Electronics. Compartment.
Adequate baffles are located inside the cabinet for guiding the air fluxes and thus enhancing the global
thermal performance.
A thermostat is provided in each fans tray for activating the alarms in the case of excessive temperature or
fans failure.
Fans stop when heaters are on, until working temperature reaches the minimum required for electronics (+
5 C).
In battery area, no specific cooling actions are required.

01

PD 08

3AM 20060 0001 RJZZA

17/164

4.2

Types of Cabinets

4.2.1

1 MLS Outdoor Cabinet configuration

Cabinet code

Cooling System

MLS Type

Line Card

Ner of Subscribers

3AM 20190 AA

Filtered External
Air Exchange

MLS_3F

20 LC / 48 Subscr.

960

Table 2.
4.2.2

2 MLS Outdoor Cabinet configurations


Cabinet code

Cooling System

3AM 20185 AA

Filtered External
Air Exchange

3AM 20185 BA

Filtered External
Air Exchange

Table 3.

1 MLS Outdoor Cabinet configuration

MLS Type

Line Card

Ner of
Subscribers

MLS_3F + MLS_3F 40 LC / 48 Subscr.

MLS_3F + ISAM
7330 FD

20 LC / 48 Subscr.
+ 10 LC 48 Subscr.

1920

1440

2 MLS Outdoor Cabinet configurations

1 MLS OUTDOOR CABINET: FILTERED EXTERNAL AIR EXCHANGE

It's an outdoor IP-55 cabinet, except in battery area, equipped with an MLS_3F subrack with up to 960
subscribers, grouped in 48 subscribers per slot, along with its Powering System, Transmission System, MDF,
ODF and batteries.
The ODF is prepared for up to 12 fibers with connectors type SC/XXX or E2000/APC or 24 fibers with
connectors type LC.
The MDF has Reichle & De Massari disconnection strips in Primary side and connection strips in Secondary
side, both for 960 subscribers.
The Powering System can be Xcend, Aspiro 1U or 2U from Power-One.
The maximum external dimensions of the cabinet are, roof included: 1465 x 1605 x 600 (W x H x D). (Roof
included). And the weight of the cabinet, equipped, is roughly 180 Kg.
5.1

Internal Distribution

The cabinet includes three areas to house the following equipment:


I. Electronics area
MLS_3F
AC power subsystem, from Mains to -48V, including:
-

AC/DC converter, including cold start control, battery controller and batteries temperature sensor:
Power-One Aspiro 1U or 2U Power shelf, 3AM 20191 XA with up to 4 converters 3AM 20202 AX or
Xcend 3AM 19867 AAAA.

Electrical Protections Frame, protections and other control equipment.

01

PD 08

3AM 20060 0001 RJZZA

18/164

The AC/DC is designed to be powered from Mains AC (230 Vac), providing secondary power to the MLS,
as well as to the heating and cooling control equipment which are also required in the cabinet.
See Chapter 0.
The Electrical Protections Frame includes the elements listed below:
- 2 Overvoltage protection devices class C, with auxiliary contacts, between line and neutral and
between neutral and ground. (VmaxAC/DC=320/420V, In=20 kA, Imax=40kA, tA<25ns, short circuit
25kA/50Hz)
-

1 relay 230 V, providing an alarm, upstream the differential breaker,

- 1 differential breaker class A for the complete equipment (40 A) (with 2P and a sensitivity of
30mA)
-

1 breaker for the AC/DCs (32 A) (C curve type, 6kA, 2P)

1 breaker for auxiliary socket (6 A) (C curve type, 6kA, 2P)

1 socket for powering auxiliary equipment (16A)

Cooling equipment
Fans tray 4 fans: 535 x 195 x 50 mm (WxDxH). ETSI fixing.
This fan tray can be the Litespan 3AM 20071 BGAA or else another fan tray with similar functionality with 4
axial non stop fans.
- Optional elements in Electronics area:
Heating equipment, code: 3AM 20211 AAAA
High temperature sensor, code: 3AM 20241 AAAA
Litespan 1540 items included in electronic area are specified for a working temperature above 10C. In order
to comply with environmental condition classes, optionally, especially for class 4.1E, the use of heaters inside
the electronic area is required.
These heaters will be activated below +10C in the electronics area and disconnected over +10C, by means
of an adequate thermostat.
A thermostat adjusted at 20C guarantees the disconnection of the AC/DC below that temperature.
Humidity sensor, Code: 3AM 20204 AAAA.
II. Interconnection area
In this area the MLS connectors are connected via cabling to the MDF - primary side, while the external
cabling is connected to the MDF - secondary.
MDF with Primary and Secondary sides
Connection strips are mounted on a fixed system, to overcome the problem of moving a big amount of cabling.
Room has been foreseen in the cabinet for several types of connection strips: R&M, Alcatel-Lucent, 3M SID-C,
3M STG type, Krone-LSA PLUS, Krone PROFIL.
For each RSA code its particular MDF kit contains the connections strips and their support.
Primary side: It has a capacity of 960 subscribers, equipped in disconnecting type strips. These ones are
prepared for receiving overvoltage protections.
Secondary side: The relation between subscribers in Primary and Secondary is normally 1:1, and up to 1:1,3
when possible, depending on the volume of the strips equipped. Strips in this side can be connection type
only.
ODF
ODF device is capable of handling a minimum of 12 fibers.
The ODF is prepared for receiving SC/APC, SC-PC (for up to 12 fibers) or LC adaptors (for up to 24 fibers.
01

PD 08

3AM 20060 0001 RJZZA

19/164

The possibility of E2000 or FC-PC adaptors (not included) will be on customer request.
Cables entry
- Optional elements:
Flooding sensor, Code: 3AM 20205 AAAA.
Smoke sensor, Code: 3AM 20203 AAAA.
No specific heating actions are required under normal operating conditions, provided that suitable equipment
for specified environmental class is used.
III. Battery area
Battery pack
Batteries will provide a minimum of 10 hours of backup. For the maximum configuration expected in the
cabinet, the requirement for the batteries is at least 78 A/h.
They will be AGM type.
Depending on the allocation of the batteries in the dedicated area, two configurations are possible:
Configuration A: 4 batteries on each tray (1 removable tray+ 1 fixed tray) (8 units)
Configuration B: 2 lain batteries on each tray (3 removable + 1 fixed) (8 units)
Configuration C: 8 batteries on one fixed tray (8 units)

01

PD 08

3AM 20060 0001 RJZZA

20/164

DIN-6798 M4 Inox

WASHER

MCD-080422-170

PBA-CONV. 48Vdc 12Vdc 15A

MCD-080422-172

PBA SUPPORT

DIN-7985 M3x8 Inox

SCREW

DIN-6798 M3 Inox

WASHER

MCD-080422-174

COVER

L=0,80m CABLE 2X1.5 MM2 SECTION

10

L=0,80m CABLE 2X0.22 MM2 SECTION ALARM DETECTOR TO CONN. STRIPS

11

L=3,0 m

12

CABLE 2X1.5 MM2 SECTION

POWER CONN. CONV. TO MAINS (48Vdc)

MCD-980907-63

LABEL ENERGY HAZARD

Table 13.
Figure 11.

POWER DETECTOR TO COVERTER

1 & 2 MLS Outdoor Cabinet: Smoke Detection elements (Optional)


1 MLS Outdoor Cabinet: Smoke Detection Elements (Optional)

2 MLS OUTDOOR CABINET: FILTERED EXTERNAL AIR EXCHANGE

It's an outdoor IP-55 cabinet, except in battery area, equipped with two possible configurations:

Configuration 1:

Litespan MAIN:

MLS-3F, 960 subscribers

Litespan EXTENSION:

MLS-3F, 960 subscribers

with up to 1920 subscribers in MDF - Primary, grouped in 48 subscribers per subrack slot, along with its
Powering System, Transmission System, MDF, ODF and batteries.

Configuration 2:

Litespan MAIN:

MLS-3F, 960 subscribers

ISAM:

7330 FD

with up to 1920 subscribers in MDF - Primary, grouped in 48 subscribers per Litespan subrack slot,
along with its Powering System, Transmission System, MDF, ODF and batteries.
The ODF is prepared for receiving SC/APC, SC-PC (for up to 12 fibers) or LC adaptors (for up to 24 fibers.
The MDF has Reichle & De Massari disconnection strips in Primary side and connection strips in Secondary
side, both for 1920 subscribers.
The Powering System can be Xscend, Aspiro 1U or 2U from Power-One.
The maximum external dimensions of the cabinet are, roof included: 2520 x 1550x 600 (W x H x D). (Roof
included). See Figure 12.
And the weight of the cabinet, equipped, is roughly 450 Kg.
Depending on the batteries area distribution, configurations type A and B exist. See Chapter 6.2.1.

01

PD 08

3AM 20060 0001 RJZZA

27/164

Figure 12. 2 MLS Cabinet Main Dimensions


01

PD 08

3AM 20060 0001 RJZZA

28/164

MLS-MAIN

MLS-EXT
OR
ISAM
7330

AC/DC

ELECTRICAL

ADM

SWITCHES

THIRD PARTY ODF

MDF

PROTECTIONS
FRAME

Figure 13. 2 MLS Cabinet


6.1

Power Requirements

Maximum power consumption and dissipation foreseen, located in electronics area:

DC Power consumption (incl. Fans and 3rd party equipment), @ 48Vdc <1450W

AC Power consumption, @ 230Vac <1600W

In each particular installation, the Max DC and Max AC should be calculated as a function of the foreseen
configuration.
The DC Power Supply unit is designed as N+1 redundancy. N is the number of rectifier modules whose total
capacity is enough for powering all DC loads and to charge the batteries. See chapter 7.
Power dissipation for thermal management <1500W, distributed in the two electronics areas (max 750W each)
Voltage fluctuation in Mains: 230 V 10% according to standard EN50160 Power Quality Standard.
6.2

Internal Distribution

6.2.1 Litespan MLS-3F + MLS-3F Configuration


See Figure 13.
The cabinet includes three areas to house the following equipment:

01

PD 08

3AM 20060 0001 RJZZA

29/164

I. Electronics area (left & central doors)

2 x Litespan MLS_3F

AC power subsystem, from Mains to -48V, including:

AC/DC converter, including cold start control, battery controller and batteries temperature
sensor: Power-One Aspiro 1U or 2U Power shelf, 3AM 20191 XA with up to 3 converters
3AM 20202 AX or Xcend 3AM 19867 AAAA. See Chapter 0.

Electrical Protections Frame, with protections and other control equipment. See chapter
6.2.2.

ADM 1642 EM

Cooling equipment
Fans tray 4 fans: 535 x 195 x 50 mm (WxDxH). ETSI fixing.
This fan tray can be the Litespan 3AM 20071 BGAA or else another fan tray with similar functionality
with 4 axial non stop fans.

Optional elements in Electronics area:

Heating equipment, code: 3AM 20211 ABAA

Litespan 1540 items included in electronic area are specified for a working temperature above 10C. In order
to comply with environmental condition classes, optionally, especially for class 4.1E, the use of heaters inside
the electronic area is required.
These heaters will be activated below +10C in the electronics area and disconnected over +10C, by means
of an adequate thermostat.
A thermostat adjusted at 20C guarantees the disconnection of the AC/DC below that temperature.

Humidity sensor, Code: 3AM 20204 AAAA

Ethernet Switch from 3rd Party

ODF from 3rd Party

II. Interconnection area (right door)


In this area the MLS connectors are connected via cabling to the MDF - primary side, while the external
cabling is connected to the MDF - secondary.
MDF with Primary and Secondary sides
Connection strips are mounted on a fixed system, to overcome the problem of moving a big amount of cabling.
Room has been foreseen in the cabinet for several types of connection strips: R&M, Alcatel-Lucent, 3M SID-C,
3M STG type, Krone-LSA PLUS, Krone PROFIL.
For each RSA code its particular MDF kit contains the connections strips and their support.
Primary side: It has a capacity of 1920 subscribers, equipped in disconnecting type strips. These ones are
prepared for receiving overvoltage protections.
Secondary side: The relation between subscribers in Primary and Secondary is normally 1:1, and up to 1:1,3
when possible, depending on the volume of the strips equipped. Strips in this side can be connection type
only.
ODF supplied with the cabinet
The ODF is prepared for receiving SC/APC, SC-PC (for up to 12 fibers) or LC adaptors (for up to 24 fibers.
The possibility of E2000 or FC-PC adaptors (not included) will be on customer request.
According to the selected model, there are several available kits with their respective connections from the
equipment to the ODF device:

01

PD 08

3AM 20060 0001 RJZZA

30/164

KITS

ADM

ODF

DESCRIPTION

3EC 40406 ABAA LC/PC

SC/PC

SET (ADM ODF):

3 CABLES & 5 TRANSITIONS

3EC 40406 BBAA LC/PC

SC/PC

SET (ADM ODF):

1 CABLES & 2 TRANSITIONS

3EC 40407 ABAA LC/PC SC/APC SET (ADM ODF):

3 CABLES & 5 TRANSITIONS

3EC 40407 BBAA LC/PC SC/APC SET (ADM ODF):

1 CABLES & 2 TRANSITIONS

3EC 41492 ABAA LC/PC

FC/PC

SET (ADM ODF):

3 CABLES & 5 TRANSITIONS

3AM 20253 AAAA

LC/PC

SET (ODF):

1 DOUBLE TRANSITION

3AM 20253 ABAA

SC/PC

SET (ODF):

2 TRANSITIONS

3AM 20253 ACAA

SC/APC SET (ODF):

2 TRANSITIONS

Table 14.

Optical Cables & Transitions Kits

Other optical kits could be developed on customer request.


DDF 75 (up to 8 coaxial cables) (optional), code 3AM 20224 AAAA
DC Powered Lamps code 3AM 20226 AAAA
Cables entry
External Generator Socket
It is a MALE connector 32 A - 230 V. Number of contacts: 2P+Ground.
The access to this socket is permitted only when the cabinet is open but, a system is provided for the outlet of
the power cable with the cabinet closed, for operation in emergency conditions.
For switching between normal powering system and emergency powering system a mechanical switch is
provided. This switch is a bipolar selector, type ABB E222-4-2 or similar.
Optional elements in Interconnection area:

Flooding sensor, Code: 3AM 20205 AAAA

Smoke sensor, Code: 3AM 20203 AAAA

No specific heating actions are required under normal operating conditions, provided that suitable equipment
for specified environmental class is used.
III. Battery area (left door)

2 strings x 4x12V Battery pack

Batteries will provide a minimum of 10 hours of backup. They are batteries of 12V and a capacity of 125 A/h
up to 170 A/h, AGM type.
The AC/DC system always works providing the required power for equipment, and giving the remaining
available power to recharge the batteries, assuring the proper charging process.
The frame for the batteries (columns + trays) has two possible configurations, depending on the trays height
and the corresponding batteries position, as can be seen hereafter:
2 batteries on the bottom fixed tray and 2 batteries on the removal tray.
Batteries area configuration A:
3 batteries on the bottom fixed tray & 1 horizontal battery on the removable tray that can be fixed at
2/3 height position.
Batteries area configuration B:
2 batteries on the bottom fixed tray & 2 batteries on the removable tray that can be fixed at 1/2 height
position.
Batteries which fit with the requirements of the different configurations are listed hereafter:

01

PD 08

3AM 20060 0001 RJZZA

31/164

10 Installation of Outdoor Cabinet


This chapter explains the installation procedure for the Litespan-1540 FR3.2 Outdoor Cabinets:
1 MLS code:

3AM 20190 AX equipped with a MLS-3F

2 MLS code:

3AM 20185 XX equipped with 2 x MLS-3F or MLS-3F + ISAM 7330 FD

The installation procedure consists of the following steps:

Unpacking and Warehousing: See chapter 10.1.3

Mechanical Installation: See chapter 10.3

Electrical Connections: See chapter 10.5

Safety ground connection: See chapter 10.5

Power supply connection: See chapter 10.5

Transport signals connection: See chapter 10.5

External synchronism signals connection: See chapter 10.5

Subscriber lines connection: See chapter 10.5

Optical Connections: See chapter 10.6

Alarms: See chapter 10.8

Local Management with MLS-3F Subrack: See chapter 10.9

Optional Equipment management: See chapter 10.10

10.1 Necessary Infrastructure


The cabinet installation requires specific previous works to be executed:

Specific basement for anchoring

Mains 230 Vac connection

Optic Fibers connection on the lower part (if necessary)

Safety ground bar

Secondary network cable pairs connection for the external connections towards subscriber lines

10.1.1 Basement 1 MLS Outdoor Cabinet


The cabinet is installed over a concrete basement through a metal base where it is fixed.
The location of the cabinet basement must consider some features related to the ventilation:
- The minimum distance between the rear of the cabinet and any possible obstacle, usually a wall, will be
275 mm
- Don't locate it under trees
According to the floor conditions, the basement shall be built with the masonry traditional methods. Next
figures show in detail how to make the concrete basement. Over the basement, a metal base will be placed,
for fixing the cabinet unto it. See Figure 50.
For warranting the IP-55 of the cabinet, a sealing of the metal base with the cabinet itself is needed. This
sealing will be made by means of polyurethane.
For building the basement, see Figure 51, Figure 52 & Figure 53, as an orientation.

01

PD 08

3AM 20060 0001 RJZZA

76/164

Figure 50. 1 MLS Outdoor Cabinet: Metal Base

01

PD 08

3AM 20060 0001 RJZZA

77/164

Figure 51. 1 MLS Outdoor Cabinet: Basement (I)

01

PD 08

3AM 20060 0001 RJZZA

78/164

Figure 52. 1 MLS Outdoor Cabinet: Basement (II)


01

PD 08

3AM 20060 0001 RJZZA

79/164

Figure 53. 1 MLS Outdoor Cabinet: Basement (III)


01

PD 08

3AM 20060 0001 RJZZA

80/164

10.1.2 Basement 2 MLS Outdoor Cabinet


The cabinet is installed over a concrete basement through a metal base where it is fixed.
The location of the cabinet basement must consider some features related to the ventilation:
- The minimum distance between the rear of the cabinet and any possible obstacle, usually a wall, will be
275 mm
- Don't locate it under trees
According to the floor conditions, the basement shall be built with the masonry traditional methods.
Next figures show in detail how to make the concrete basement.
Over the basement, a metal base will be placed, for fixing the cabinet unto it. See Figure 54 & Figure 55.
Two variants of bases can be installed, 3AN 48772 ABAA and BBAA.

Variant ABAA will be mounted on a Basement TYPE A

Variant BBAA will be mounted on a Basement TYPE B

The only difference between them, and thus, between the two types of basements, is the hole for the cables
entry, as can be seen in next figure.
For the details on the fixing bolts and corrugated rods of the two bases, Figure 55 has been included.

Figure 54. Metal Bases


For warranting the IP-55 of the cabinet, a sealing of the metal base with the cabinet itself is needed. This
sealing will be made by means of polyurethane.
For building the basement, see Figure 56, Figure 57, Figure 58, Figure 59 & Figure 60, as an orientation.

01

PD 08

3AM 20060 0001 RJZZA

81/164

Figure 55. 2 MLS Outdoor Cabinet: Metal Base Variant ABAA


01

PD 08

3AM 20060 0001 RJZZA

82/164

Figure 56. 2 MLS Outdoor Cabinet: Basement TYPE A (I)

01

PD 08

3AM 20060 0001 RJZZA

83/164

Figure 57. 2 MLS Outdoor Cabinet: Basement TYPE A (II)


01

PD 08

3AM 20060 0001 RJZZA

84/164

Figure 58. 2 MLS Outdoor Cabinet: Basement TYPES A & B (III)

01

PD 08

3AM 20060 0001 RJZZA

85/164

Figure 59. 2 MLS Outdoor Cabinet: Basement TYPE B (IV)


01

PD 08

3AM 20060 0001 RJZZA

86/164

Figure 60. 2 MLS Outdoor Cabinet: Basement TYPE B (V)

01

PD 08

3AM 20060 0001 RJZZA

87/164

10.1.3 Cables Tubes Arrangement: 2 MLS cabinet


For the placement of the tubes inside the basement, next recommendations should be followed, in order to
prevent interferences between cables tubes and the cable entry edge of the cabinet, and to facilitate the
routing of the cables at the inlet plate of the cabinet:

Respect the forbidden area for tubes indicated in Figure 61 (20 / 20 / 25mm) (only for basement TYPE A)

Locate Power / Fibers / Ground cables tubes on the left of the cable entry; preferably, ground at the front

Locate Subscribers cables tubes distributed in the rest of the surface of the cable entry. The number of
these tubes will depend on the tubes size and the cables size decided for each installation.

As an example, see Figure 62.

Figure 61. Forbidden Area for Cables Tubes in Basement TYPE A

Figure 62. Example of Tubes Layout


10.1.4 Grounding System
The required Grounding System Resistance to Ground must have a low value, i. e. less than 10 Ohms
according to BS 6651 or BS EN 62305, preferably 8 Ohms or less.
10.2 Instructions for Unpacking and Warehousing
10.2.1 Generalities
The unpacking of the equipment must strictly follow the operations described below. As for the packing
procedure, if needed, proceed reciprocally. In both cases, the use of the original wrapping materials is
preferred.
The external packing frames used for equipment protection will depend on the mechanical and climatic
conditions. There can be three types of packing frames:

WOODEN BOXES: used for ship, plane or road transportation for a period of time more than 60
days

PLYWOOD BOXES: used for ship, plane or road transportation for a period of time between 30 and
60 days

CARDBOARD BOXES: used for ship, plane or road transportation for a period of time less than 30
days

01

PD 08

3AM 20060 0001 RJZZA

88/164

10.2.2 Unpacking
The package must have the following information on the outside:

International symbols:

This side up

Keep in a dry place

Fragile

Trademark and address of the manufacturer

Labels (or other) that must state the consignee and the address of destination

Packing list

Once the package has been received, the following must be checked:

The actual address of destination is the same as indicated on the address label

The package shows no external signs of damage.

For Unpacking procedure follow the steps below:

Make sure the package was correctly placed during transportation, as indicated by the symbol

Unwrap the package

Take out the contents from the box

Remove the wrapping, bags and other protection stuff

Remove the dehydrating bags

Check that the material shows no visible damage and that it is the same as indicated on the annexed
shipping list

Note: Any damage shall invalidate the receipt of the package.


10.2.3 Warehousing
The following requirements shall apply to store the material:

Cardboard boxes shall be placed in ventilated areas

Wooden or plywood boxes can be stored outdoor, whenever they are protected from rain or direct
sunlight

10.3 Batteries Operation & Maintenance


For the correct operation and maintenance of the VRLA AGM batteries follow the instructions included
hereafter.
10.3.1 Transport
Cells and blocs must be transported in an upright position.

01

PD 08

3AM 20060 0001 RJZZA

89/164

Batteries without any visible damage are not defined as dangerous goods under the regulations for transport
of dangerous goods by road (ADR) or by railway (RID).
They must be protected against short circuits, slipping, upsetting or damaging.
Cells/blocs may be suitable stacked and secured on pallets (ADR and RID, special provision 598). Stapling
pallets is prohibited.
No dangerous traces of acid shall be found on the exterior of the packing unit.
Cells/blocs whose containers leak or are damaged must be packed and transported as class 8 dangerous
goods under UN no. 2794.
10.3.2 Maintenance and Control
For a correct maintenance and control of the batteries, next instructions should be taken into account:
Keep the battery clean and dry to avoid creeping currents.
Plastic parts of the battery, especially containers, must be cleaned with pure water without additives. Never
use any additives, acids and/or scourers.
At least every 6 months, measure and record next parameters:

Battery voltage

Voltage of several cells/blocs (See Note)

Surface temperature of several cells/blocs

Battery-room temperature

Note: If the cell voltage differs from the average float charge voltage by more than +/- 0,5V, or if the surface
temperature difference between cells / mono-blocs exceeds 5C, service agent should be contacted.
Annual measurement and recording should be made:

Voltage of all cells / blocs

Surface temperature of all cells/blocs

Battery-room temperature

Annual visual check should be made:

Screw connections

Screw -connections without locking devices have to be checked for tightness

Battery installation and arrangement

Ventilation

Call a batteries service representative immediately if faults in the battery or the battery charger are found.
Recorded data as described in this chapter must be made available to the service representative.
10.3.3 Storage and Taking Out of Operation
To store or decommission cells/blocs for a longer period of time they should be fully charged and stored in a
dry frost-free room.
a) The storage location should provide the following functions:

Shelter the cells / mono-blocs from harsh weather and risk of flooding

Protect the batteries against any overheating risk induced by direct exposure to the sun radiation or by
their amplification through glass walls

Protect the batteries from any risk of electric shock resulting from short-circuiting by a conductive
object or from a building-up of conductive dust

01

PD 08

3AM 20060 0001 RJZZA

90/164

Avoid any risk of mechanical shock caused by dropping objects onto the cell / mono-bloc or by
dropping the cell / mono-bloc itself

Avoid contamination of the lids by dust etc.

b) During storage period, checking the batteries voltage and applying maintenance charges to them is
mandatory.
The average storage temperature determines the test and charges intervals:

20C: 6 months first time. Then, each 3 months.

30C: 4 months first time. Then, each 2 months.

Higher temperatures storage is not recommended.


In any case, if OCV (Open Circuit Voltage) measurement < 2,07 Vpc, consider a maintenance charge.
To avoid damage, the following general charging methods can be chosen. It is recommended to check for
special instructions for each particular battery model.
Equalizing-charge as follows:

2.40Vpc

Max. 20-30A / 100Ah depending on batteries model.

24 < t < 48h


The cells / bloc temperature must never exceed 45C . If it does, stop charging.
Float charging, typically:

2,27Vpc. / 25C

t > 48h

10.4 Mechanical Installation


The Outdoor Cabinet can be shipped in the following equipping stage:

Subrack without equipped units

Without batteries

All internal cabling and Primary Network pre-connected

The procedure for anchoring the cabinet is as indicated hereafter:

Open the doors of the cabinet for giving access to the cabinet bottom holes where the studs in the
metal plate must be inserted.

Lift the roof for giving access to the lifting eyes located on the internal part of the roof.

Lift up the cabinet by means of those eyes on the internal part of the roof, and align the bottom holes
with the threaded studs in the metal plate located on the basement.

Lifting Eyes

Figure 63. Outdoor Cabinet: Cabinet Lifting Eyes

01

PD 08

3AM 20060 0001 RJZZA

91/164

Once the cabinet has been anchored to the threaded studs:

Check the proper leveling of the structure, both horizontal and vertical, with a level or plumb line.

Enter the grounding and power supply cables, the Secondary Network subscribers cables and the
fiber optic cables towards the cables entry area, guiding them through the corresponding cable ducts,
and fasten them properly.

10.5 Electrical Connections

The equipment has been designed to be directly powered from the external Mains supply
(230 Vac).
Whenever any door of an area which contains a part which operates with a harmful
voltage or which can be exposed to harmful voltages in the case of failure is open by the
user, that potentially harmful part is protected from an eventual contact. The dangerous
areas are labeled with an ENERGY HAZARD label.

The connection procedure must follow the sequential steps indicated below:

Safety ground connection. See chapter 10.5.1

Power supply connection. See chapter 10.5.4

Transport signals connection. See chapter 10.5.6

Subscriber lines connection. See chapter 10.5.7

10.5.1 General Cabling Inlet Rules


Cables which are coming inside the cabinet must be led in according to Figure 64.
For keeping the IP Protection degree of the cabinet once the cables are passed through the cones, the cables
must be tightly inserted through the plastic cones.
For that, and for each cone,

the surface of the cone to be cut out must be smaller than the section of the cable to be inserted in it

if more than one cable are to be inserted through one cone, this tightly insertion must be achieved by
using silicone around the cables, for closing the gaps

01

PD 08

3AM 20060 0001 RJZZA

92/164

Figure 64. Cabinet Inlet Plate Cables Distribution

01

PD 08

3AM 20060 0001 RJZZA

93/164

10.5.2 General Cables Routing Rules


As a general rule, the cabling will be guided without obstructing the handling or the viewing of the different
cards or devices of the electronics equipment mounted in the cabinet.
The cabling will be also neatly arranged and fixed, so as to minimize the risk of a non-desired disconnection
during the normal operation within the cabinet.
The cabinet is provided with several holes for the guiding of the cables between the different areas,
Electronics, MDF, ODF, Batteries areas.

Figure 65. Cabling Holes Distribution


Next table shows the suggested allocation of the holes for the different cables which are susceptible of being
connected during the installations process.

01

PD 08

3AM 20060 0001 RJZZA

94/164

Example:
The Power 230 Vac cable going between outside AC Power Supply and the Power Selector located in the
Electrical Protections Frame comes through hole 11 into the MDF area, then comes into Electronics area
through hole 23 to the Power Selector.

HOLES DISTRIBUTION IN Figure 65


CABLES

START - END

START AREA

MEDIUM
AREA

END AREA

HOLE

POWER 230 Vac

OUTSIDE AC POWER SUPPLY TO


POWER SELECTOR

OUTSIDE

MDF

ELECTRONICS

11 & 23

GENERAL
GROUND

OUTSIDE TO GENERAL GROUND


STRIP

OUTSIDE

MDF

13

OTHER GROUND
CABLES

EQUIPMENT TO GENERAL
GROUND STRIP

ELECTRONICS

MDF

22

BATTERIES -48Vdc

BATTERIES TO AC/DC

BATTERIES

ELECTRONICS

24

BATTERIES +0 Vdc

BATTERIES TO AC/DC

BATTERIES

ELECTRONICS

24

POWER MLS-1

MLS-1 TO POWER STRIPS IN


ELECTRICAL PROTECTIONS
FRAME

ELECTRONICS

ELECTRONICS

POWER MLS-2 OR
7330

MLS-1 OR 7330 TO POWER STRIPS


IN ELECTRICAL PROTECTIONS
FRAME

ELECTRONICS

ELECTRONICS

POWER (-A) ADM

ADM (A) TO POWER STRIPS IN


ELECTRICAL PROTECTIONS
FRAME

ELECTRONICS

ELECTRONICS

POWER (-B) ADM

ADM (-B) TO BREAKERS BOX


(RIGHT ETSI COLUMN)

ELECTRONICS

ELECTRONICS

POWER
SWITCHES

SWITCHES TO BREAKERS BOX


(RIGHT ETSI COLUMN)

ELECTRONICS

ELECTRONICS

TRANSPORT
CABLING

MLS-1 OR 7330 TO ADM

ELECTRONICS

ELECTRONICS

INTERNAL FIBERS

BETWEEN ELECTRONIC
EQUIPMENT

ELECTRONICS

ELECTRONICS

MDF DOOR
ALARM

MLS-1 TO MDF DOOR SWITCH

ELECTRONICS

MDF

16

BATTERIES
DOORS ALARMS

MLS-1 TO BATTERIES DOORS


SWITCHES

ELECTRONICS

BATTERIES

26

EXTERNAL
ALARMS

MLS-1 TO ALARMS AUXILIARY


CONN. STRIPS

ELECTRONICS

MDF

16

SUBSCRIBERS

OUTSIDE TO MDF

OUTSIDE

MDF

1 to 10

SUBSCRIBERSMLS-1

MLS-1 TO MDF

ELECTRONICS

MDF

20

SUBSCRIBERSMLS-2 OR 7330

MLS-2 OR 7330 TO MDF

ELECTRONICS

MDF

20

FIBERS CABLE

OUTSIDE TO ODF

OUTSIDE

ODF

12

FIBERS

ODF TO OPTICAL EQUIPMENT

ODF

ELECTRONICS

17

01

PD 08

3AM 20060 0001 RJZZA

95/164

DDF CABLE

MLS-1 TO DDF

ELECTRONICS

MDF

18

BATTERIES
HEATERS

BATTERIES HEATERS TO BATT.


STRIPS IN ELECTRICAL
PROTECTION FRAMES

ELECTRONICS

BATTERIES

25

SMOKE
DETECTOR

SMOKE DETECTOR TO POWER


STRIPS IN ELECTRICAL
PROTECTIONS FRAME

MDF

ELECTRONICS

16

HUMIDITY
DETECTOR

HUMIDITY DETECTOR TO ALARMS


AUXILIARY CONN. STRIPS

MDF

MDF

FLOODING
DETECTOR

FLOODING DETECTOR TO
ALARMS AUXILIARY CONN.
STRIPS

MDF

MDF

MDF LAMP

MDF LAMP TO POWER STRIPS IN


ELECTRICAL PROTECTIONS
FRAME

MDF

ELECTRONICS

19

ELECTRONICS
LAMP

ELECTRONICS LAMP TO POWER


STRIPS IN ELECTRICAL
PROTECTIONS FRAME

ELECTRONICS

ELECTRONICS

Table 29.

Cabling Holes Allocation

Holes 14, 15, 19 & 21 in the cabinet are spare.


When the holes are provided with cones for the keeping of the IP-55 protection level, the same rules as in
previous chapter apply.
10.5.3 Safety Ground Connection
This is the first connection to be made, before any other connection, just after having anchored the cabinet.
Both 1 and 2 MLS outdoor cabinets have a safety ground cable which connects the Power Distribution Frame
to the Safety Ground Terminal, located in the MDF area of the cabinet. See Figure 23.
Besides, the outdoor cabinets have another 10 mm2 cable which is connected to the Safety Ground Terminal
on one end, and whose other end is to be connected to the Ground Stake located on the concrete basement,
or close to it.
10.5.4 Power Supply Connection
There are two main parts:

230 Vac Mains Power Supply Connection. See chapter 10.5.4.1.

Batteries Connection. See chapter 10.5.4.2.

10.5.4.1 230 Vac Mains Power Supply Connection


According to EN 50160 Power Quality Standard, the voltage fluctuation in Mains is 230 V 10%.
Proceed as follows:
Let in the 230 Vac Power Supply cable through the appropriate hole in the base (see Table 29) of the
cabinet and guide it to the Electronics area, to be connected to the terminals next to the Power Selector, which
switches between the normal power and the Emergency Power.
Remove the protection cover from the breakers box, located in the electronics area, in order to access
the two terminals for power supply cable connection. The safety ground cable coming with the 230 Vac Power
Supply cable should be connected to the Safety Ground Terminal in the MDF area of the cabinets.
See Figure 23 & Figure 24.

01

PD 08

3AM 20060 0001 RJZZA

96/164

10.5.4.2 Batteries Connection


For the battery pack installation, proceed as follows:

Put the batteries on its support in the battery area of the cabinet

Connect the cables coming from the Rectifier Unit to the batteries

As an example, document 3EC 44319 0020 BCZZA shows the recommended operation system for batteries
3AM 20221 AMAA in the 2 MLS cabinet.
See Figure 23 & Figure 24.
10.5.5 Insertion Procedure of a Board with a Big Amount of Rear Connectors
Due to the big amount of connectors, and thus a lot of connection pins at the rear of
some boards, to be connected at the back panel, special care should be taken during the
insertion process of GEB-3B and/or other cards with similar amount of rear connectors.
It is highly recommended to do the process in three steps:

Do a first insertion of the card with a correct positioning of the extractors in the subrack profiles,

Press once more over the front face of the extractors

Check the position of the board

To see whether the board is correctly inserted, check that:

the leds of the front plate are light,

the internal face of the front plate is in contact with the front face of the subrack front profiles; see
Figure 66

for the bottom part, the top of the subrack profile must be inserted in the groove of the extractor; see
Figure 66

for the top part, similar situation

the front face of the extractor is located at right angles with the top face of the cables guide of the front
plate, and parallel to the front plate itself; see Figure 66.
CARD
FRONT PLATE

CARD
EXTRACTOR

SUBRACK
LOWER PROFILE

90

GROOVE

FRONT PLATE
&
PROFILE
MUST BE IN
CONTACT

Figure 66. Insertion Procedure of a Board with a Big Amount of Rear Connectors

01

PD 08

3AM 20060 0001 RJZZA

97/164

10.5.6 Transport Signals Connection


In Alcatel-Lucent Litespan 1540 FR3.2 the 2 Mbit external connections are provided by:
Narrow Band PDH, provided by PEIC: 16 x 2Mb/s Electrical G.703
Drop & Insert from SHDSL line form SLT3: 4 x 2Mb/s G.703
Additional interfaces for PRA, TDM LL or transport: 8 x 2Mb/s G.703
IMA interfaces from ANITA: 8 x 2Mb/s G.703
LINA (Integrated ADM): Gigabit Ethernet (2 channels from/to front panel) and STM-1 (1 channel from/to front
panel SFP) tributaries onto two front panel line/aggregate interfaces, each capable of STM-1/4/16.
The 16 x 2Mb/s G.703 from PEIC will be connected to an ADM, for example, the 1642 EMC, by using a
dedicated cable, 3AM 20033 CX.
For asynchronous E1 connections, cable 3AM 20033 DX allows to flexibly connect the ADM 8-14 ports to
PEIC and, through the DDF in the cabinet, to SLT3, as follows: 3xE1 to PEIC and 4xE1to SLT3.
At the PEIC front plate, four metral 24 way (6x4) connectors are used which contain, each of them 4
interfaces. Next figure shows Tx/Rx pin disposition on each metral connector.
Rx3N

Rx1P

Rx1N

Rx3P

EG

EG

EG

EG

Tx2N

Tx2P

Tx4N

Tx4P

RxnP: PEIC 2M Rx active wire


RxnN: PEIC 2M Rx ground wire
TxnP: PEIC 2M Tx active wire
TxnN: PEIC 2M Tx ground wire

Tx1P

Tx1N

Tx3P

Tx3N

EG

EG

EG

EG

Rx2N

Rx2P

Rx4N

Rx4P

EG: Backpannel ground

Figure 67. PEIC E1 (2Mb/s G.703 ) connector


A Digital Distribution Frame (DDF) is foreseen as an optional kit, code 3AM 20224 ABAA, to be mounted in the
MDF compartment. See Figure 14 & Figure 28.
10.5.6.1 SFP Modules

ETHERNET SFP MODULES


MODULE TYPE

CODE

DESCRIPTION

1000BT

3AM20070EA

SFP pluggable electrical GE 1000BT module

1000FX

3AM20070AA

GE

MM SX 850nm -40+85 LC-duplex 550m(7db)

3AM20070AB

GE

SM LX 1310nm -40+85 LC-duplex10km(11db)

3AM20070AC

GE

SM EX 1310nm -40+85 LC-duplex 40km(18db)

100FX

01

3AM20070AD

GE

SM ZX 1310nm -25+85 LC-duplex 80km(24db)

3AM20070CC

FE

SM LX 1310nm -with SGMII

3AM20070CA

FE

MM SX 850nm -40 +85 LC duplex

3AM20070CB

FE

SM LX 1310nm

-40 +85 LC duplex

PD 08

3AM 20060 0001 RJZZA

98/164

STM SFP MODULES


MODULE TYPE

CODE

DESCRIPTION

STM1 (ATM)
STM1 S1.1
STM1 L1.1
STM1 L1.2
STM4 S4.1
STM4 L4.1
STM4 L4.2
STM16 S16.1
STM16 L16.1
STM16 L16.2

3AM20070BA
3AM20070BC
3AM20070BD
3AM20070BH
3AM20070BJ
3AM20070BK
3AM20070BL
3AM20070BE
3AM20070BF
3AM20070BG

STM1 SM 1550nm, -25C to +85C, Duplex LC


connector, 80km
SFP STM1 SHORT S1.1 -40/+85
SFP STM1 LONG L1.1 -40/+85
SFP STM1 LONG L1.2 -40/+85
SFP STM4 SHORT S4.1 -40/+85
SFP STM4 LONG L4.1 -40/+85
SFP STM4 LONG L4.2 -40/+85
SFP STM16 SHORT S16.1 -40/+85
SFP STM16 LONG L16.1 -40/+85
SFP STM16 LONG L16.2 -40/+85
Table 30.

SFP Types

The correspondence between each type of SFP and the cards to be used with is shown in next tables:

CODE
3AM20070EA

GIO3
YES
(1)

GEB3-B GEB3-A GEBC


YES
(1)
NO

3AM20070AA

YES

YES

3AM20070AB

YES

3AM20070AC

NTIO-A
NTIO-A
ANIT(SFP ONLY) (COMBO) A

LINA

FESC-B

YES

YES

YES

--

YES

YES

YES

YES

YES

--

YES

YES

YES

YES

YES

YES

--

YES

YES

YES

YES

YES

YES

YES

--

YES

3AM20070AD

YES

YES

YES

YES

YES

YES

--

YES

3AM20070CC

NO

NO

YES (2)

NO

NO

NO

--

NO

3AM20070CA

NO

NO

YES

NO

NO

NO

--

NO

3AM20070CB

NO

NO

YES

NO

NO

NO

--

NO

(1) Only with ethernet cables codes: 3AM19841CX and 3AM20359AX


(2) From FR3.1.32 onwards
Table 31.

CODE

GIO3

SFP/Cards Correspondence (I)

GEB3-B GEB3-A GEBC

NTIO-A
(SFPonly)

NTIO-A
ANIT(COMBO) A

LINA

FESC-B

3AM20070BA

--

--

YES

--

--

YES

--

--

3AM20070BC

--

--

--

--

--

--

YES

--

3AM20070BD

--

--

--

--

--

--

YES

--

3AM20070BH

--

--

--

--

--

--

YES

--

3AM20070BJ

--

--

--

--

--

--

YES

--

3AM20070BK

--

--

--

--

--

--

YES

--

3AM20070BL

--

--

--

--

--

--

YES

--

3AM20070BE

--

--

--

--

--

--

YES

--

3AM20070BF

--

--

--

--

--

--

YES

--

01

PD 08

3AM 20060 0001 RJZZA

99/164

3AM20070BG

--

--

-Table 32.

--

--

--

YES

--

SFP/Cards Correspondence (II)

10.5.7 Craft Terminal Cabling


The Craft Terminal cables to be connected between Litespan and the serial port of a PC are:

For LIOC / GIO3-A:

3AM 19534 AA

For GEB3-B:

3AM 20012 AB

For GEBC, GEB3-A, ANIT-A & LINA: 3AM 20051 AA

10.5.8 Ethernet Cabling


The Ethernet cables available for Litespan are:

3AM 19841 BX (Shielded Point-to-point)

3AM 19841 CX (Shielded Point-to-point - Earthing prepared)

3AM 20359 AX (Shielded Swapped)

01

PD 08

3AM 20060 0001 RJZZA

100/164

10.5.9 External Synchronism


When an external clock signal is necessary for synchronizing the E1 links, use cables:

Between LIOC card and an external MDF or DDF:


3AM 20102 AX (120 Ohm) or 3AM 20368 AX (75 Ohm)

Between LIOC card and PRC3 card:


3AM 20376 AA

10.5.10 Subscribers Lines Connection


10.5.10.1 Subscriber Cables Inlet
The subscribers cables coming through the cabinet inlet plate (see Figure 64) must be fixed at the MDF inlet
by using the cable clamps as shown in Figure 68.
The clamps can be adjusted to the incoming cable by means of their screws.
For their screen to be connected with Ground, the cables must have a length without cover. In this way the
screen can be pressed by the clamps and then connected with Ground.

Figure 68. MDF Inlet Cables Distribution


10.5.10.2 Subscribers Cables between Litespan and the MDF
The whole cabling coming from the Electronics area towards the Main Distribution Frame (MDF) area is
provided already wired up from the factory, therefore the equipment is delivered with a fixed pre-set
configuration.
Note that the cabling is prepared for a Line card in each slot. So, if not all line cards are equipped, each one
must use its own dedicated cable.
The cables not used in a particular configuration must be left fixed at the front lateral parts of the subrack,
prepared for being used in a future, and not interfering with other cabling or with the air fluxes through the
subrack.
The MDF, located in the right part of the cabinet, is mounted on a fixed structure which allows an easy access
to all existing connection modules. The MDF has two parts: Primary (Upper part of the MDF) and Secondary
(Lower part of the MDF).
Each connection module has:

Primary Connection Module:

Secondary Connection Module: 20 positions (10 pairs)


01

32 positions (16 pairs)

PD 08

3AM 20060 0001 RJZZA

101/164

It is divided in two sections "a" (upper part) and "b" (lower part):

In section "a" (upper one) the signals coming from MLS (Primary Network) or Subscriber Lines
(Secondary Network) are connected

In section "b" (lower one) is used for the associative connections between Primary Network and
Secondary Network sides,

In any case, a special tool is required to connect/disconnect the wires in the module.

Figure 69. MDF Primary Connection Strip


The aspect of the Secondary side connection strip is similar to this figure, for 10 pairs instead of 16.
For meeting the ITU K.45 Recommendation, Resistibility of Telecommunication Equipment installed in Access
and Trunk Networks to overvoltages and overcurrents, it is required to install Overvoltage protections on each
subscriber line
They can be installed either on Primary side or in Secondary side (where the connection modules allow it), by
means of adequate cartridges provided with the protections mounted on the connection modules.
10.5.10.3 Subscribers Cable for (MLS-3F+MLS-3F) Configuration
The subscribers cable (included in 3AM 20213 ABAA), with 96 pairs, for connecting at the front plate of units
inserted in MLS_3F is 3AM 20002 BXXX:

01

PD 08

3AM 20060 0001 RJZZA