Sie sind auf Seite 1von 67

Model X40-08-N4X, Model X40-32-N4X

Model X40-32-N1P, Model X40-32-N7


Integrated Alarm & Control System

m
e
t
s
y
S
l
o
r
t
n
o
C
&

m
r
a
l
A
d
e
t
a
r
g
e
t
n
I

Operators Installation and Instruction Manual


Covers all Model X40 Control Systems

DETCON, Inc.
3200 Research Forest Dr.,
The Woodlands, Texas 77387
Ph.281.367.4100 / Fax 281.298.2868
www.detcon.com
April 02, 2012 Document #3672 Revision 2.1

Model X40

This page left intentionally blank

Shipping Address: 3200 A-1 Research Forest Dr., The Woodlands Texas 77381
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
Phone: 888.367.4286, 281.367.4100 Fax: 281.292.2860 www.detcon.com sales@detcon.com
Model X40 Instruction Manual

Rev. 2.1

ii

Model X40

Table of Contents
1.

Introduction............................................................................................................................................1
1.1
1.2

2.

Installation (N1P Enclosure).................................................................................................................3


2.1
2.2

3.

Mounting and Cable Installation .................................................................................................................... 6


Power and I/O Connections............................................................................................................................ 7

3.2.1
AC Power.................................................................................................................................7
3.2.2
DC Power ................................................................................................................................8
3.2.3
RS-485 connections..................................................................................................................8
Installation (N7 Enclosure) .................................................................................................................10
4.1
4.2

5.

Mounting and Cable Installation .................................................................................................................... 3


Power and I/O Connections............................................................................................................................ 3

2.2.1
AC Power.................................................................................................................................3
2.2.2
DC Power ................................................................................................................................4
2.2.3
RS-485 connections..................................................................................................................4
Installation (N4X Enclosure) ................................................................................................................6
3.1
3.2

4.

Description ..................................................................................................................................................... 1
System Operation ........................................................................................................................................... 2

Mounting and Cable Installation .................................................................................................................. 10


Power and I/O Connections.......................................................................................................................... 11

4.2.1
AC Power and I/O Connections.............................................................................................11
4.2.2
DC Power and I/O Connections ............................................................................................12
I/O Connections ...................................................................................................................................14
5.1
5.2
5.3
5.4

Analog 4-20mA Sensor Inputs (DA-4)......................................................................................................... 15


Dry Contact Inputs (DI-4) ............................................................................................................................ 17
Analog 4-20mA Outputs (AO-4).................................................................................................................. 18
Alarm Relay Outputs (RL-4)........................................................................................................................ 20

5.4.1
5.4.2
5.4.3
5.5
5.6
5.7

6.
7.

Energized or De-Energized ...................................................................................................22


Silenceable or Non-Silenceable .............................................................................................22
Latching or Non-Latching Relays..........................................................................................22

Serial Output Gas Sensors (RS-485) ............................................................................................................ 22


General Wiring Notes................................................................................................................................... 24
Initial Start-Up.............................................................................................................................................. 24

Secure Digital Card .............................................................................................................................25


System Operation and Configuration ................................................................................................26
7.1

Operator Interface......................................................................................................................................... 26

7.1.1
7.1.2
7.1.3
7.1.4
7.2
7.3

PROG Switch .........................................................................................................................26


u Up Arrow Switch............................................................................................................26
v Down Arrow Switch .......................................................................................................26
ENTER and RESET/ACK Switch ...........................................................................................26

Main Display Functions ............................................................................................................................... 27


Menu Functions............................................................................................................................................ 27

7.3.1
7.3.2
7.3.3
7.3.4
7.3.5
7.3.6
7.3.7
7.3.8
7.3.9

Auto Configure System...........................................................................................................29


Set # of Channels, AO-4s, RL-4s (Alarm Stations) ................................................................30
Set # of RXT-320s (Wireless Function Only).........................................................................30
Set RF Silence and RF Sleep (Wireless Function Only) ........................................................30
Set COMM Baud Rates ..........................................................................................................31
Set Modbus Timeouts .............................................................................................................31
Set Channel Data ...................................................................................................................32
Set Channel Alarms ...............................................................................................................33
Set Low Battery Alarms .........................................................................................................33

Model X40 Instruction Manual

Rev. 2.1

iii

Model X40

8.

7.3.10 Set Relay (Alarm) Functions..................................................................................................34


7.3.11 Flashing Blue LED Codes .....................................................................................................35
7.3.12 Set Modbus Address...............................................................................................................35
7.3.13 Inhibit & Alarm Test Mode ....................................................................................................35
7.3.14 RF Link Quality and Battery Status (Wireless Function Only)..............................................36
7.3.15 System Diagnostics ................................................................................................................36
7.3.16 Display Settings .....................................................................................................................37
7.3.17 Time and Date........................................................................................................................37
7.3.18 View TWA & Peak .................................................................................................................38
Modbus Communications ...............................................................................................................38
8.1

9.

Modbus Register Map...............................................................................................................................38

Options..................................................................................................................................................40
9.1
9.2

Optional Remote Alarm Reset/Acknowledge Switch...................................................................................40


Wireless Option (RXT-320) .........................................................................................................................40

9.2.1
RXT-320 Mounting ................................................................................................................41
9.2.2
RXT-320 Wiring.....................................................................................................................42
9.2.3
Model 100 Terminal Board....................................................................................................43
10.
Troubleshooting Guide....................................................................................................................46
11.
Warranty ..........................................................................................................................................47
12.
Specifications....................................................................................................................................47
12.1
12.2

Spare Parts ....................................................................................................................................................48


Revision Log.................................................................................................................................................49

Table of Figures
Figure 1 Model X40-N4X Controller ..............................................................................................................1
Figure 2 X40-32-N1P Controller Mounting and Dimensional View ..............................................................3
Figure 3 AC/DC Inputs....................................................................................................................................4
Figure 4 RS-485 port Connections ..................................................................................................................4
Figure 5 X40-08-N4X Controller Mounting and Dimensional View..............................................................6
Figure 6 X40-32-N4X Controller Mounting and Dimensional View..............................................................7
Figure 7 AC/DC Inputs....................................................................................................................................8
Figure 8 RS-485 Master Port Connections ......................................................................................................8
Figure 9 RS-485 Slave Port Connections ........................................................................................................9
Figure 10 X40-32-N7 Controller Mounting and Dimensional View.............................................................10
Figure 11 X40-32-N7 Controller Assembly w/Mounting Plate ....................................................................10
Figure 12 X40-32-N7 Controller PCA ..........................................................................................................11
Figure 13 AC/DC Converter Board Wiring...................................................................................................12
Figure 14 Transient Protection Module Wiring.............................................................................................13
Figure 15 I/O Module Installation .................................................................................................................14
Figure 16 Model DA-4 4-20mA Input Module and 4-20mA Gas Sensor Connections ................................15
Figure 17 Model DA-4 4-20mA Input Module and 4-20mA Gas Sensors....................................................15
Figure 18 Model DI-4 Contact Input Module................................................................................................17
Figure 19 Model AO-4 4-20mA Output Module...........................................................................................18
Figure 20 Model RL-4 Relay Output Module ...............................................................................................20
Figure 21 Modbus Gas Sensor Connections ..............................................................................................23
Figure 22 Magnetic Programming Tool ........................................................................................................26
Figure 23 Front Panel User Interface.............................................................................................................27
Model X40 Instruction Manual

Rev. 2.1

iv

Model X40

Figure 24 Menu Flow Chart ..........................................................................................................................29


Figure 25 N1P & N4X Remote Switch Input ................................................................................................40
Figure 26 N7 Remote Switch Input ...............................................................................................................40
Figure 27 RXT-320 Wireless Assembly for X40 Controller.........................................................................41
Figure 28 RXT-320 Wireless Assembly w/Mounting Plate Dimensions ......................................................42
Figure 29 Model 100 Terminal Board to X40 Controller Wiring .................................................................43
Figure 30 Model 100 Terminal Board ...........................................................................................................43
Figure 31 Model 100 Terminal Board Rotary Switches................................................................................44
Figure 32 Wiring Diagram to the Master.......................................................................................................45
Figure 32 Wiring Diagram to the Slave.........................................................................................................46

List of Tables
Table 1 AO-4 Modbus Addresses..............................................................................................................18
Table 2 RL-4 Relay Modbus Addresses ....................................................................................................21
Table 3 X40 Register Map.............................................................................................................................38
Table 4 Model 100 Terminal Board Jumper Settings.................................... Error! Bookmark not defined.

Model X40 Instruction Manual

Rev. 2.1

Model X40

This page left intentionally blank

Shipping Address: 3200 A-1 Research Forest Dr., The Woodlands Texas 77381
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
Phone: 888.367.4286, 281.367.4100 Fax: 281.292.2860 www.detcon.com sales@detcon.com

Model X40 Instruction Manual

Rev. 2.1

vi

Model X40

1.

Introduction

1.1 Description
The Detcon X40 controller is a multi-channel gas detection control system designed to serve as a host
monitor and controller for a network of gas detection sensors as well as a wide range of other field devices.
All X40 models are configurable for up to 32 channels and can be customized using Detcons selection of
I/O modules. The enclosure type will dictate the number of I/O modules that can be accommodated. These
modules communicate with the controller via Modbus and are available in four channel sets for 4-20mA
inputs, dry contact inputs, 4-20mA outputs and relay outputs. The modules are DIN rail mounted and
stackable allowing for seamless system expansion.
Remote mounted gas detection sensors can include any analog 4-20mA or RS-485 (Modbus) serial
output device such as toxic gas, combustible gas or oxygen deficiency sensors. Other remote field devices
can include contact closure inputs such as liquid level, temperature, pressure or smoke detection devices.
The analog sensors and field devices are interfaced to the I/O modules which communicate with the
controllers COMM1 Modbus master port. The serial sensors interface directly with the controllers
COMM1 port and do not require I/O modules. Thus, the types of sensors or field devices being interfaced
will dictate the I/O modules needed for the X40 controller. Also, all configuration inputs are completely
field-configurable which provides a distinctive combination of user configuration flexibility and expansion
customization.
The X40 controller utilizes a non-intrusive magnetic interface and displays the real time status of every
sensor on a backlit LCD. Typical sensor status includes channel number, gas concentration, device tag (gas
type) and alarm/fault status. Each channel provides three alarm levels (Alarm 1, Alarm 2 and Alarm 3) and
fault for which the present status can be shown via the front panel LED indicators. Additional features
include Alarm Inhibit, Alarm Reset and Alarm Silence (Acknowledge) functions.
The X40 controller is available in different enclosure types to accommodate various customer needs. The
NEMA 4 enclosures can also incorporate integral alarms such as a Strobe, or a horn or both. These
enclosure types are NEMA 1 (N1P), NEMA 4X (N4X) and NEMA 7 (N7). The N1P is an indoor use,
panel-mount enclosure. The N4X is an indoor/outdoor use, water/corrosion proof enclosure. The N7 is an
indoor/outdoor use, explosion proof enclosure. These enclosure types are discussed in more detail in their
perspective installation sections.

m
e
t
s
y
S
l
o
r
t
n
o
C
&

m
r
a
l
A
d
e
t
a
r
g
e
t
n
I

Figure 1 Model X40-N4X Controller


Model X40 Instruction Manual

Rev. 2.1

Page 1 of 50

Model X40

1.2 System Operation


The heart of the X40 controller is the non-intrusive magnetic interface with backlit LCD display. The
controller communicates with serial (RS-485) sensors and I/O modules using RS-485 Modbus RTU
protocol. The X40 includes a primary Modbus interface (COMM1 Master) and a secondary Modbus
interface (COMM2 Slave) that is used for communication with another controller or remote display. The
Modbus master interface is used to communicate directly with Modbus capable sensors and Detcons
I/O modules. The I/O modules are individually addressable and operate on 11.5-30VDC.
The number of I/O modules supported by the X40 controller will vary depending on the enclosure type
chosen due to physical space limitations. A maximum of 2 I/O modules will fit outside the X40-32-N1P
enclosure, a maximum of 6 I/O modules will fit inside the X40-08-N4X enclosure and a maximum of 12
I/O modules will fit inside the X40-32-N4X enclosure. I/O modules are normally factory installed unless
specifically instructed otherwise. The X40-32-N7 enclosure does not accommodate module installations.
Modules for the N7 enclosure or any additional modules for the other enclosure types will have to be
mounted in a separate enclosure by the customer. I/O modules are purchased separately.
The available Detcon I/O modules include:
Model DA-4 Four Channel 4-20mA Input Module
Model DI-4 Four Channel Dry Contact Input Module
Model AO-4 Four Channel 4-20mA Output Module
Model RL-4 Four Alarm Relay Output Module
Alarm values and fault condition can be field-configurable via the magnetic user interface to cause an
assigned relay output or bank of relay outputs to fire, thus triggering external alarm devices. As gas alarm
or fault conditions clear, the assigned relay outputs return to their normal states. Relays can be set-up as
Energized/De-Energized, Latching/Non-Latching and Silenceable/Non-Silenceable. The X40 also allows
for wiring of an external manual switch to act as an Acknowledge/Reset switch.
The X40 controller can be configured for various I/O combinations at the Detcon factory based on
application specific information provided by the customer on the Configuration Form. It must be verified
that the correct quantity and type of I/O modules have been purchased to support the customers
configuration requirements. On the Configuration Form, the customer should supply all site-specific
information:
1)
2)
3)
4)
5)
6)
7)

Number of gas channels


Detcon sensor model number and I/O type (Modbus or 4-20mA) for each channel
Range, units, and gas type for each channel
Alarm level(s) for each gas channel
Device Tag for each channel
Assignment and set-up information for each relay contact
Analog output requirements for each channel

NOTE: The set-up configuration is fully field-configurable and can be executed by the user in
the field. Refer to section 7 System Operation and Configuration. Modifications to the set-up
configuration are expected to take place at the customers site due to requirement changes
and/or system expansions.

Model X40 Instruction Manual

Rev. 2.1

Page 2 of 50

Model X40

2.

Installation (N1P Enclosure)

2.1 Mounting and Cable Installation


The Model X40-32-N1P controller is housed in a NEMA 1 panel mount enclosure for indoor use. Securely
mount the Model X40-32-N1P per the mounting dimensions provided in Figure 2. The enclosure is
designed to fit a panel opening of 9.25 wide by 7.5 high. Keep AC power separate from DC power and
signals within conduit runs.
10.5"

1.69"

9.75"

12"
7"

3.5" 8"

7"

I/O Modules
(Qty. of 2 Max)

0.375"

R0.109"
Slot Detail

0.218"

Figure 2 X40-32-N1P Controller Mounting and Dimensional View

2.2 Power and I/O Connections


The Model X40-32-N1P controller can be powered by either 110/220VAC or 11.5-30VDC. An internal
power supply is available for the X40-32-N1P that converts 110/220VAC to 24VDC (up to 7.5 Amps) and
can power up to 32 sensors and any associated I/O modules. Optionally, the X40 controller can be
powered by an external DC source that meets the input requirements of the unit if AC power is not
available or desired.
NOTE: The X40-32-N1P controller can power up to a maximum of 32 sensors and any
associated I/O modules, but only 2 I/O modules can be installed on the controller. Any
additional modules required will need to be mounted separately by the customer.

2.2.1

AC Power

Connect 110/220VAC input wiring to the terminals labeled VAC (L1), NEU (L2), and GROUND
(See Figure 3). The power supply for the X40-32-N1P is capable of handling AC inputs from 100240VAC, 50-60Hz without degradation.

Model X40 Instruction Manual

Rev. 2.1

Page 3 of 50

Model X40

C3A

C3A

WMS1C03
240V10000

WMS1C03
240V10000

5A
I ON

I ON

24VDC

NEU (L2)

VAC (L1)

GROUND

Figure 3 AC/DC Inputs

NOTE: The input voltage range must be between 110-240VAC.

2.2.2

DC Power

For optional external DC power input, connect 11.5-30VDC to the terminals of the DIN rail mounted
terminal block labeled 24VDC and DC Comm (See Figure 3). This input can be used for primary
power or back-up power in the event of an AC power failure. The DC input voltage should be capable of
delivering at least 8 Amps of current to the load (200 Watts @ 24VDC).
NOTE: The supply of power should be from an isolated source with over-current protection
as applicable. The input voltage range must be between 11.5-30VDC.

2.2.3

RS-485 connections

A
B

RS-485 and power out are provided for connection to sensors attached to the unit. The RS-485
connections for external sensors are labeled RS-485 Master; A, B, and Shld. Connections to
external sensors should be made here.

A B

RS-485 VDC RS-485


Out SLAVE

Figure 4 RS-485 port Connections

Model X40 Instruction Manual

Rev. 2.1

Page 4 of 50

Model X40

24VDC is also provided for external sensors, this power out is found directly adjacent to the RS-485
connections and is labeled 24VDC Out; +, and -. If 24VDC is needed to power external sensors
connect the sensors to these power connections.
NOTE: The X32-N1P units can power a maximum of 32 sensors. Care should be taken that
the number of sensors does not exceed the maximum number of sensors allowed, as damage to
the power supply may result.
The NEMA-4 units also provide a set of terminal blocks for the RS-485 Slave Port. The Slave Port is used
t connect the X40 unit to a Remove Display Unit. The Terminals are labeled RS-485 Slave; A, B,
Shld.

Model X40 Instruction Manual

Rev. 2.1

Page 5 of 50

Model X40

3.

Installation (N4X Enclosure)

3.1 Mounting and Cable Installation


The X40 controller is available in two different size models for the N4X enclosure type. Both the Model
X40-08-N4X and X40-32-N4X controllers are housed in a NEMA 4X water/corrosion proof enclosure for
indoor/outdoor use. Securely mount the Model X40-N4X enclosure per the mounting dimensions provided
in Figure 5 or Figure 7. Provide for suitable conduit/cable entries in the bottom, top or sides of the
enclosure and use required cable glands to maintain enclosure rating. Keep AC power separate from DC
power and signals within conduit runs.
NOTE: It is recommended to make conduit and cable entries to the bottom of the enclosure
whenever possible to prevent water leaking into the unit.
11.85"
9"
8"

6.79"

0.31"

6.5"

Mounting
Bracket

13.75" 10.9"

12.75"

Figure 5 X40-08-N4X Controller Mounting and Dimensional View


Figure 6

Detcon also provides an X40-08-N4X model with integral Alarm Strobe. The unit uses the same enclosure
as the X40-08-N4X, but has an 8 inch strobe mounted on the top of the enclosure. Extra clearance above
the enclosure may be needed for the added strobe.

Model X40 Instruction Manual

Rev. 2.1

Page 6 of 50

Model X40
16"
13"
12"

0.31"

8.80"
8.5"

Mounting
Bracket

17.85" 14.9"

16.75"

Figure 7 X40-32-N4X Controller Mounting and Dimensional View

3.2 Power and I/O Connections


The X40-N4X controller can be powered by either 110/220VAC or 11.5-30VDC. An internal power
supply is available for the X40-08-N4X that converts 110/220VAC to 24VDC (up to 2.5 Amps) and can
power up to 8 sensors and any associated I/O modules. The X40-32-N4X has an internal power supply that
converts 110/220VAC to 24VDC (up to 7.5 Amps) and can power up to 32 sensors and any associated I/O
modules. Optionally, the X40 controller can be powered by an external DC source that meets the input
requirements of the unit if AC power is not available or desired.
NOTE: The power supply for the X40-08-N4X controller can power up to a maximum of 8
sensors even though the controller is capable of communicating with up to 32 devices. An
additional power supply will be required if powering more than 8 sensors or an upgrade to
Model X40-32-N4X is needed which can power up to a maximum of 32 sensors.

3.2.1

AC Power

Connect 110/220VAC input wiring to the terminals labeled VAC (L1), NEU (L2), and GROUND
(See Figure 8). The power supplies for both the X40-08-N4X and the X40-32-N4X are capable of handling
AC inputs from 100-240VAC, 50-60Hz without degradation.

Model X40 Instruction Manual

Rev. 2.1

Page 7 of 50

I ON
I ON

WMS1C03
240V10000
WMS1C03
240V10000
WMS1C03
240V10000

24VDC

NEU (L2)

I ON

C3A
C3A
C3A

Model X40

VAC (L1)
GROUND

TB1

Figure 8 AC/DC Inputs

3.2.2

DC Power

For optional external DC power input, connect 11.5-30VDC to the terminals of the TB1 DIN rail mounted
terminal block labeled 24VDC and DC Comm (See Figure 8). This input can be used for primary
power or back-up power in the event of an AC power failure. The DC input voltage should be capable of
delivering at least 2.5 Amps of current to the load (60 Watts @ 24VDC) for the X40-08-N4X. The DC
input voltage should be capable of delivering at least 7.5 Amps of current to the load (200 Watts @
24VDC) for the X40-32-N4X.
NOTE: The supply of power should be from an isolated source with over-current protection
as applicable. The input voltage range must be between 11.5-30VDC.

3.2.3

RS-485 connections

RS-485 and power out are provided for connection to sensors attached to the unit. The RS-485 connections
for external sensors are labeled RS-485 Master; A, B, and Shld. Connections to external sensors
should be made here.
24VDC is also provided for external sensors, this power out is found directly adjacent to the RS-485
connections and is labeled 24VDC Out; +, and -. If 24VDC is needed to power external sensors
connect the sensors to these power connections.

A
B

NOTE: The X32-N4 units can power a maximum of 32 sensors, while the X08-N4X can
power only a maximum of 8 sensors. Care should be taken that the number of sensors does not
exceed the maximum number of sensors allowed, as damage to the power supply may result.

RS-485 VDC
Out

Figure 9 RS-485 Master Port Connections


Model X40 Instruction Manual

Rev. 2.1

Page 8 of 50

Model X40

A
B

The NEMA-4 units also provide a set of terminal blocks for the RS-485 Slave Port. The Slave Port is used
to connect the X40 unit to a RD-64X Remove Display Unit. The Terminals are labeled RS-485 Slave;
A, B, Shld.

RS-485
SLAVE

Figure 10 RS-485 Slave Port Connections

Model X40 Instruction Manual

Rev. 2.1

Page 9 of 50

Model X40

4.

Installation (N7 Enclosure)

4.1 Mounting and Cable Installation


The Model X40-32-N7 controller is housed in an explosion proof NEMA 7 enclosure for indoor/outdoor
use. Securely mount the Model X40-32-N7 per the mounting dimensions provided in Figure 11. Use an
appropriate cable gland to maintain enclosure rating. Keep AC power separate from DC power and signals
within conduit runs.
11.05"

2.78"

MODEL X40-32-N7
Controller

9.15"

Figure 11 X40-32-N7 Controller Mounting and Dimensional View

Detcon offers an optional mounting plate that can be used for mounting the Model X40-32-N7 controller to
a pole. If ordered with this option, secure the controller assembly and J-Box to the mounting plate (if not
already done so from the factory) per Error! Reference source not found.. The mounting plate can then
be mounted to a pole with two U-Bolts secured through the rectangle holes of the mounting plate.

RD-32X-N7
J-Box w/ Transient
Protection Module

If an Alarm reset switch is installed, the switch should


be mounted in the bottom port of the J-Box.
If no reset switch is installed, install a 3 4" NPT Plug.

Place Spacers between N7 Enclosure


and Mounting Plate.

Figure 12 X40-32-N7 Controller Assembly w/Mounting Plate


Model X40 Instruction Manual

Rev. 2.1

Page 10 of 50

Model X40

4.2 Power and I/O Connections


The X40-32-N7 controller can be powered by either AC or DC. An optional AC/DC converter board is
available from Detcon that converts 90-264VAC to 24VDC (up to 167mA) to power the controller only.
Any sensors and associated I/O modules will need to be powered separately by the customer. The X40
controller can also be powered directly by an external DC source that meets the input requirements of the
unit if AC power is not available or desired.
Power and I/O connections to the X40-32-N7 controller are made on connector J7 of its PCA (Printed
Circuit Assembly). A plug-in male connector is provided for input wiring terminations. This connector
style provides for quick disconnect convenience during replacement or servicing. To access connector J7,
remove the faceplate from the controller enclosure to reveal the PCA.

SW4

SW3

SW2

SW1

R8

J5

J7
D3

D4

D5

D6

PWR
GND

J2

B2

A2
B2
A1
B1

A1

MAIN

J7

A2

J6

SW

SECONDARY

GND

PWR

B1
SW

Figure 13 X40-32-N7 Controller PCA

PWR/GND:
A2/B2:
A1/B1:
SW:

DC power connection to power X40-32-N7 controller


Secondary Modbus connection (COMM2 Slave)
Primary Modbus connection (COMM1 Master)
External switch connection for RESET/ACK function (Normally Open)

NOTE: The X40-32-N7 controller can support up to a maximum of 32 sensors and any
associated I/O modules, but no I/O modules can be installed in the controller. All I/O modules
required will need to be mounted separately by the customer.

4.2.1

AC Power and I/O Connections

An optional AC/DC converter board is available from Detcon to power the X40-32-N7 controller with an
AC voltage source. The AC/DC converter is provided inside a condulet/J-Box (See Error! Reference
source not found.). This converter takes AC inputs from 90-264VAC and provides a 24VDC output.
Connect 90-264VAC input wiring to the J3 connector of the converter board labeled AC IN. The
terminals on the J3 connector are labeled N for neutral, L for line power and E for earth ground.
Power and I/O connections to the controller can be made by interfacing the J1 connector of the AC/DC
converter board to the J7 connector of the controller. I/O modules and sensors can then be interfaced to the
X40 controller through the J2 connector of the AC/DC converter board (See Figure 14).
Model X40 Instruction Manual

Rev. 2.1

Page 11 of 50

Model X40
Wiring to
X40-32-N7 Controller
J7 Connector

Customer Supplied Modbus Wiring to


I/O Modules and Sensors

U1

PWR(+)
GND(-)
A2(+)
B2(-)
A1(+)
B1(-)

+24V

GND

GND

+24V

J1

B1(-)
A1(+)
B2(-)
A2(+)
Not Used
Not Used
J2

E
J3

Power to I/O Modules


and Sensors must be
provided separately.

VAC(N) Wht
VAC(L) Blk
Grn
GND

AC IN

AC Power from
External Voltage Source
Customer Supplied Wiring
(In)

Figure 14 AC/DC Converter Board Wiring

NOTE: The AC/DC converter board should be used to power the X40 controller only. Power
to any I/O modules or sensors will have to be provided separately by the customer. The AC
input voltage range must be between 90-264VAC.

4.2.2

DC Power and I/O Connections

The X40-32-N7 controller can also be powered directly through a DC voltage source provided by the
customer. The controller requires 11.5-30VDC to the PWR and GND terminals of connector J7. The
wiring for a DC power input is shown in Figure 15.
NOTE: The supply of DC power should be from an isolated source with over-current
protection as applicable. The input voltage range must be between 11.5-30VDC.

Model X40 Instruction Manual

Rev. 2.1

Page 12 of 50

Model X40

Blu A1(+)
Wht B1(-)
A1(+)
B1(-)

VDC(+)
VDC(-)

Red VDC(+)
Blk VDC(-)

Wiring to
X40-32-N7 Controller
J7 Connector

11.5~30VDC / RS-485
Customer Supplied Wiring

Figure 15 DC Power Wiring

Model X40 Instruction Manual

Rev. 2.1

Page 13 of 50

Model X40

5.

I/O Connections

The quantity of I/O modules supported by the X40 controller will vary depending on the enclosure type
chosen due to physical space limitations. A maximum of 2 I/O modules may be installed on the Model
X40-32-N1P enclosure, a maximum of 6 I/O modules may be installed in the Model X40-08-N4X
enclosure and a maximum of 12 I/O modules may be installed in the Model X40-32-N4X enclosure.
Modules can be installed on the enclosures DIN rail.
NOTE: The X40-32-N7 enclosure does not accommodate module installations. Modules for
the N7 enclosure or any additional modules for the other enclosure types will have to be
mounted in a separate enclosure by the customer. Refer to Section 4.2.
NOTE: The X40-08-N4X enclosure with Alarm Strobe comes with at least one RL-4 module
installed. This module is used to power the Alarm Strobe, and should not be removed.
I/O modules are mounted on an industry-standard 37.5 x 7.5 mm DIN rail (See Figure 16). Install the first
I/O module at the end of the DIN rail nearest the male connector. Plug the male connector into the side of
the module. Slide it all the way to the end stop. Add additional modules next to the first module. When
installing additional I/O modules, make sure there is about 0.5 inch clearance on either side of the module
and snap the module onto the DIN rail (the 0.5 spacing is to allow for connector clearance). Once the I/O
module is snapped onto the DIN rail, slide it towards the adjacent module and assure that it firmly plugs
into it. Connect the RS-485 and power female connector to the last module installed on the DIN rail.
Secure the modules with an end stop.
Add additional modules
as needed.

Female
Connector
COMM

COMM

M
S
D

M
S
D

L
S
D

L
S
D

L
S
D

L
S
D

4-20mA
INPUT

4-20mA
INPUT

4-20mA
INPUT

End Stop

S BA

RS-485 and Power


Cable from Output
Terminal Blocks.

COMM
M
S
D

COMM
M
S
D

Male
Connector
-

RS-485 and
Power Cable

4-20mA
INPUT

End Stop

Figure 16 I/O Module Installation

NOTE: The male connector must be plugged into the I/O module at one end of the DIN rail
and the female connector must be plugged into the I/O module at the other end of the stack of
I/O modules. If these connectors are not properly installed, communication with other RS-485
devices will not be possible.
NOTE: If no I/O modules are installed in the controller, the male connector must be plugged
into the female connector for the RS-485 to communicate.
For addressable I/O modules or Modbus sensors that are being located remotely from the controller,
Belden P/N 1502P cable is recommended for serial and power connections. For serial only connections,
Belden P/N 9841 cable is recommended.

Model X40 Instruction Manual

Rev. 2.1

Page 14 of 50

Model X40

5.1 Analog 4-20mA Sensor Inputs (DA-4)


Connect 4-20mA type gas sensors to Model DA-4 4-20mA input modules. The DA-4 modules provide
power to any 2-wire or 3-wire field sensor and receive standard 4-20mA signal outputs from the sensors
(See Figure 17).
2-Wire 4-20mA Sensor

Sensor 4
Sensor 3

mA _

mA _

COMM
M
S
D
L
S
D

4-20mA
INPUT

Sensor 1
Sensor 2

_ mA

_ mA

3-Wire 4-20mA Sensor

Figure 17 Model DA-4 4-20mA Input Module and 4-20mA Gas Sensor Connections

There are four 4-20mA inputs in each DA-4 module to support up to four sensors (See Figure 18). DA-4
modules can be installed on the DIN rail of the controller.

Sensor 4
Sensor 3

COMM
M
S
D
L
S
D

4-20mA
INPUT

Sensor 1
Sensor 2
Figure 18 Model DA-4 4-20mA Input Module and 4-20mA Gas Sensors

The 4-20mA signals from the sensors are communicated by the DA-4 modules to the controller using RS485 Modbus RTU protocol therefore each DA-4 module must have a unique Modbus address.
Modules are serially addressed in hex using the two rotary switches on the modules front panel labeled
MSD (most significant digit) and LSD (least significant digit). All DA-4 modules must be setup on the
COMM1 (master) port of the controller. The DA-4 modules must be addressed within the range 01h-7Fh.
Model X40 Instruction Manual

Rev. 2.1

Page 15 of 50

Model X40

A DA-4 module connected properly to the controller will have a flashing DATA COMM LED when polled
to indicate a valid communication status and will provide the controller with a continuous reading of the
sensor attached.
NOTE: DA-4 modules must be connected to the COMM1 port, they must be addressed
correctly and only those channels associated with that DA-4 will be available.
After identifying the correct address for the DA-4 module, the channels to be used need to be defined and
configured
via
the
operator
interface
in
section
7

Model X40 Instruction Manual

Rev. 2.1

Page 16 of 50

Model X40

System Operation and Configuration (See sections 7.3.2 and 7.3.7). A properly addressed DA-4 that is
correctly connected and configured to the controller will respond to channel activation with a concentration
reading. If the controller does not detect a DA-4 module, the controller will display COMM ERR for the
corresponding channels.

5.2 Dry Contact Inputs (DI-4)


Relay contact outputs from field devices can be connected to Model DI-4 input modules. There are four
relay contact inputs in each Model DI-4 module (See Figure 19). DI-4 modules can be installed on the DIN
rail of the controller.
4mA Reading
NO NC

Input 4
Input 3
There are four relay
contact inputs on
each DI-4 module.

mA

mA

COM

Relay Contacts

COMM
M
S
D
L
S
D

CONTACT
INPUT

Input 1
Input 2

mA

mA

20mA Reading
NO NC

COM

Relay Contacts

Figure 19 Model DI-4 Contact Input Module

The state of the contact outputs from field devices are communicated by the DI-4 modules to the controller
using RS-485 Modbus RTU protocol therefore each DI-4 module must have a unique Modbus address.
Modules are serially addressed in hex using the two rotary switches on the modules front panel labeled
MSD (most significant digit) and LSD (least significant digit). All DI-4 modules must be setup on the
COMM1 (master) port of the controller. The DI-4 modules must be addressed within the range 01h-7Fh.
A DI-4 module connected properly to the controller will have a flashing DATA COMM LED when polled
to indicate a valid communication status and will provide the controller with a 4mA reading when the
contact from the field device is open and a 20mA reading when the contact is closed for the corresponding
channels.
NOTE: DI-4 modules must be connected to the COMM1 port, they must be addressed
correctly and only those channels associated with that DI-4 will be available.
After identifying the correct address for the DI-4 module, the channels to be used need to be defined and
configured
via
the
operator
interface
in
section
7

Model X40 Instruction Manual

Rev. 2.1

Page 17 of 50

Model X40

System Operation and Configuration (See sections 7.3.2 and 7.3.7). A properly addressed DI-4 that is
correctly connected and configured to the controller will respond to channel activation with either a 4mA or
a 20mA reading depending on the state of the contact output from the field device. If the controller does
not detect a DI-4 module, the controller will display COMM ERR for the corresponding channels.

5.3 Analog 4-20mA Outputs (AO-4)


There are four 4-20mA outputs in each Model AO-4 module (See Figure 20). These can be used as signal
inputs to other control devices. AO-4 modules can be installed on the DIN rail of the controller.
4-20 mA Signal

Output 4

mA _

Output 3

mA _

There are four


4-20mA outputs on
each AO-4 module.

4-20mA
Input

Control
System

COMM
M
S
D
L
S
D

4-20mA
Output

Output 1
Output 2

_ mA
_ mA

Figure 20 Model AO-4 4-20mA Output Module

AO-4 modules provide a 4-20mA output equal to the current concentration reading reported to the
controller for the associated channel. These concentration readings are communicated by the controller to
the AO-4 modules using RS-485 Modbus RTU protocol therefore each AO-4 module must have a unique
Modbus address. Modules are serially addressed in hex using the two rotary switches on the modules
front panel labeled MSD (most significant digit) and LSD (least significant digit). All AO-4 modules must
be setup on the COMM1 (master) port of the controller. The AO-4 modules must be addressed according
to Table 1 AO-4 Modbus Addresses.
Table 1 AO-4 Modbus Addresses

Module
1

Channel #
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Model X40 Instruction Manual

Decimal

Hex

Module

161

A1

162

A2

163

A3

164

A4

Rev. 2.1

Channel #
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

Decimal

Hex

165

A5

166

A6

167

A7

168

A8

Page 18 of 50

Model X40

An AO-4 module connected properly to the controller will have a flashing DATA COMM LED when
polled to indicate a valid communication status and will provide a 4-20mA output equal to the current
concentration reading reported to the controller for the associated channel.
NOTE: AO-4 modules must be connected to the COMM1 port, they must be addressed
correctly, and only those AO-4s associated with a channel will be available.
After identifying the correct address for the AO-4 module, the outputs to be used need to be defined and
configured
via
the
operator
interface
in
section
7

Model X40 Instruction Manual

Rev. 2.1

Page 19 of 50

Model X40

System Operation and Configuration (See section 7.3.2). A properly addressed AO-4 that is correctly
connected and configured to the controller will respond to channel activation with a 4-20mA concentration
reading corresponding to the associated channel. If the controller does not detect an AO-4 module, the blue
LED (Fault) will start flashing. Go to the FLASHING BLUE LED CODES menu to identify the problem
(See section 7.3.11).

5.4 Alarm Relay Outputs (RL-4)


There are four Form C, Single Pole Double Throw (SPDT), 5 Amp relay contacts in each Model RL-4
module. Each relay in the module is assigned specifically to one alarm. Relay 1 is assigned to Alarm 1,
relay 2 is assign to Alarm 2, relay 3 is assigned to Alarm 3, and relay 4 is assigned to Fault. These can be
used to control (fire) annunciating devices or as signal inputs to other control devices. Connections to the
relay contacts of the RL-4 module are shown in Figure 21 and are labeled C (Common), NO (Normally
Open) and NC (Normally Closed). Note that the 5 Amp rating of the relay contact should not be exceeded.
RL-4 modules can be installed on the DIN rail of the controller.
NOTE: The current ratings of the relay contacts should not be exceeded. (5A @ 30VDC, 5A
@ 250VAC)

Relay 4

NC NO C

Fault

Relay 3

NC NO C

Alarm 3

There are four relay


contact outputs on
each RL-4 module.

Fault
Device

COMM
M
S
D
L
S
D

RELAY

Relay 1
Relay 2

C NO NC

Alarm 1

C NO NC

Alarm 2

Alarm 2
Device

Figure 21 Model RL-4 Relay Output Module

RL-4 modules provide a contact output for the associated channel. These outputs are communicated by the
controller to the RL-4 modules using RS-485 Modbus RTU protocol therefore each RL-4 module must
have a unique Modbus address. Modules are serially addressed in hex using the two rotary switches on
the modules front panel labeled MSD (most significant digit) and LSD (least significant digit).
The X40 controller has been configured to have two separate relay banks (Bank1 and Bank2). Each bank
can hold up to four RL-4 modules and are defined by addresses 80h-83h for Bank1 and 84h-87h for Bank2.
Anytime a specific alarm is fired for a module in a bank, all corresponding alarms for all modules in that
particular bank are also triggered. For example, if alarm 3 of a particular module is triggered in Bank2,
then all alarm 3s for all the modules in Bank2 will also be fired. All RL-4 modules must be setup on the
COMM1 (master) port of the controller and be defined in Bank1 or Bank2 (See section 7.3.2). The RL-4
modules must be addressed according to Table 2 RL-4 Relay Modbus Addresses.
For NEMA 4 units that have an integral alarm strobe, the strobe is connected to the first RL-4 installed in
the enclosure, and is connected to Alarm 1 of the RL-4. The RL-4 is assigned to Bank1, Alarm1, but can
be reconfigured by the user.
Model X40 Instruction Manual

Rev. 2.1

Page 20 of 50

Model X40

Table 2 RL-4 Relay Modbus Addresses

Bank1
Module Decimal
1
128
2
129
3
130
4
131

Hex
80
81
82
83

Bank2
Module Decimal
5
132
6
133
7
134
8
135

Hex
84
85
86
87

An RL-4 module connected properly to the controller will have a flashing DATA COMM LED when
polled to indicate a valid communication status and will provide a relay output for the associated channel.
NOTE: RL-4 modules must be connected to the COMM1 port, they must be addressed
correctly, they must be defined in Bank1 or Bank2, and only those RL-4s associated with a
channel will be available.
After identifying the correct address for the RL-4 module, the alarms to be used need to be defined and
configured
via
the
operator
interface
in
section
7

Model X40 Instruction Manual

Rev. 2.1

Page 21 of 50

Model X40

System Operation and Configuration (See section 7.3.8). A properly addressed RL-4 that is correctly
connected and configured to the controller will respond to channel activation with an alarm output related
to the alarm set points of the associated channel. If the controller does not detect an RL-4 module, the blue
LED (Fault) will start flashing. Go to the FLASHING BLUE LED CODES menu to identify the problem
(See section 7.3.11).
Each relay within the bank can be set as Energized/De-Energized, Silenceable/Non-Silenceable, and
Latching/Non-Latching (See section 7.3.10).

5.4.1

Energized or De-Energized

All alarms relays - Alarm 1, Alarm 2, Alarm 3, and Fault - can be configured to operate in either energized
or de-energized mode. In de-energized mode, the normally open contact is open if the alarm level has not
been reached (alarm relays) or the sensor is not in fault (fault relay). In energized mode, the normally open
contact is closed if the alarm level has not been reached (alarm relays) or the sensor is not in fault (fault
relay). Energized mode provides for fail-safe operation since a loss of power or cable failure will cause the
contact to be open.

5.4.2

Silenceable or Non-Silenceable

All alarms - Alarm 1, Alarm 2, Alarm 3, and Fault - can be configured to operate as silenceable, or nonsilenceable. If an alarm or fault is configured as non-silenceable, the corresponding alarm LED and relay,
once activated, will stay activated until the cause of the alarm or fault has cleared. If an alarm or fault is
configured as silenceable, the corresponding alarm LED and relay, once activated, can be deactivated by
acknowledging the Alarm Silence function on the front panel of the X40 controller or by activating the
external acknowledge switch if one has been installed (See section 7.1.4 ENTER and RESET/ACK Switch
and section 9.1 Optional Remote Alarm Reset/Acknowledge Switch).

5.4.3

Latching or Non-Latching Relays

All alarms - Alarm 1, Alarm 2, Alarm 3, and Fault - can be configured as either latching or non-latching.
In non-latching mode, the relay is deactivated as soon as the sensor alarm (alarm relays) or fault (fault
relay) condition is cleared. In latching mode, the relay remains active even after the alarm or fault
condition has cleared. Once activated, the relay can only be deactivated by acknowledging the Alarm
Reset function on the front panel of the X40 controller or by activating the external reset switch if one has
been installed (See section 7.1.4 ENTER and RESET/ACK Switch and section 9.1 Optional Remote Alarm
Reset/Acknowledge Switch).

5.5 Serial Output Gas Sensors (RS-485)


Serial output gas sensors can be interfaced with the X40 controller without the need for I/O modules. This
is accomplished by connecting the sensors in series to the controllers primary RS-485 Modbus interface
(COMM1). Connect the five wires of a Modbus capable sensor (Detcon Model 100, Model 600 and
Model 700 series, typically) to the Modbus DIN rail mounted terminal block, labeled RS-485
MASTER and VDC Out (See Figure 22). For the X40-32-N7 controller, the serial sensors can be
connected directly to the J7 connector of the controllers PCA (See section 4.2).

Model X40 Instruction Manual

Rev. 2.1

Page 22 of 50

RS-485 VDC
Out

Model X40

B
A

Figure 22 Modbus Gas Sensor Connections

The serial sensors interface with the controller using RS-485 Modbus RTU protocol therefore each serial
sensor must have a unique Modbus address and be connected to the COMM1 (master) port for the
controller to communicate properly. The sensors must be connected in series (daisy-chained) to other RS485 sensors. The serial sensors must be addressed within the range 01h-7Fh.
A serial sensor connected properly to the controller will provide the controller with a continuous reading of
the sensor attached.
NOTE: Serial output sensors must be connected in series to the COMM1 port, they must be
addressed correctly and only those channels associated with the serial sensors will be available.
After identifying the correct address for the serial sensors, the channels to be used need to be defined and
configured
via
the
operator
interface
in
section
7

Model X40 Instruction Manual

Rev. 2.1

Page 23 of 50

Model X40

System Operation and Configuration (See sections 7.3.2 and 7.3.7). A properly addressed serial sensor that
is correctly connected and configured to the controller will respond to channel activation with a
concentration reading. If the controller does not detect a serial sensor, the controller will display COMM
ERR.

5.6 General Wiring Notes


Follow generally accepted guidelines for RS-485 serial networks. Do not wire I/O modules and/or
Modbus gas sensors in long-distance T-Tap configurations. Instead, use a daisy-chain wiring
scheme.
Use Detcon recommended cabling whenever possible.
Belden P/N 1502P cable is recommended for a single cable providing serial communications
and power.
Belden P/N 9841 cable is recommended for a single cable providing serial communications
only.
Ground the cable shielding at the X40 controller only. Other points of grounding may cause a ground
loop, and induce unwanted noise on the RS-485 line, which in turn may disrupt communications.

5.7 Initial Start-Up


The X40 controller will power up as soon as power is applied. There is no external power switch to the
unit.
NOTE: Before applying power, check to make sure that all the wiring connections and
external devices are installed correctly.
NOTE: Applying power with devices hooked up incorrectly may cause damage to the
equipment.
When power is applied to the unit, the unit will boot up and display the company name, model, firmware
version and COMM ports available. It will proceed to poll Modbus addresses of any attached devices.
The display will show up to 8 channels at one time. The LCD will then refresh and display the next 8
channels and so on until the LCD cycles back to the first 8 channels and repeats the process. This is
considered normal operation.
If a previous configuration does not exist, the user will need to manually configure the network from the
user-interface. After the unit has been configured, the unit will begin normal operation. If the unit has
been configured properly, the unit will display the current status of the devices that it is connected to.

Model X40 Instruction Manual

Rev. 2.1

Page 24 of 50

Model X40

6.

Secure Digital Card

The X40 controller has a feature that allows data logging when a secure digital (SD) memory card is
installed. The SD card must be installed in the SD slot (J9) on the back of the controllers PCA before the
controller is powered up. The controller will notify the user if a successful installation of the card was
achieved upon power up. The controller will automatically format the card and create the necessary files
for data logging. See section 7.3.18 for more information regarding the data logging feature.

Model X40 Instruction Manual

Rev. 2.1

Page 25 of 50

Model X40

System Operation and Configuration

7.

The setup of the controller is critical for proper operation. Modbus addresses must be correct on all the
devices connected to the controller before the controller will acknowledge them. The number of sensors
must be entered into the controller to allow it to communicate with them. Four basic areas need to be
configured:

The number of sensors must be determined before setup begins.


The sensors channel information must be configured to match the sensor connected.
If 4-20mA outputs are required, they must be set up and configured.
Relay modules and banks must be configured.

7.1 Operator Interface


The operator interface of the X40 controller is accomplished via four internal magnetic switches located
above the controllers backlit LCD display. The four switches offer a non-intrusive interface and allow for
complete configuration of the controller. These switches are labeled: PROG, u (Up Arrow), v (Down
Arrow) and ENTER. The ENTER switch also doubles as a RESET/ACK switch from the Main Display
only (Not in Menu Mode). With reference to the Menu Flow Chart (See Figure 25), it is easy to learn how
to navigate the menus and make changes.
The magnetic programming tool (See Figure 23) is used to operate the magnetic switches. Switch action is
defined as a momentary contact (hold) on a switch marker (). For momentary contact, the programming
magnet is briefly held on the switch marker () and then removed. This action will be referred to as a
swipe for the remainder of this manual.

Figure 23 Magnetic Programming Tool

7.1.1

PROG Switch

From the Main Display, the PROG switch enters into the Main Menu. Once inside the Main Menu, the
PROG switch acts as an Escape switch that moves backwards in the menu flow chart.
NOTE: While in Main Menu mode there are no updates to gas readings and hence no alarms
will take place.

7.1.2

u Up Arrow Switch

This switch moves the user up the Main Menu flow chart. It is also used to change selected entries
within menu selections in the upward direction.

7.1.3

v Down Arrow Switch

This switch moves the user down the Main Menu flow chart. It is also used to change selected entries
within menu selections in the downward direction.

7.1.4

ENTER and RESET/ACK Switch

This switch has multi-purpose use. The ENTER function is used to accept selections within all menu
screens. The switch is also used to execute the Reset and Acknowledge functions. The Reset function
releases all latched relays if they have cleared the alarm/fault condition. The Acknowledge function
will disengage any silenceable relays that are in a currently active state. This is typically used to
Model X40 Instruction Manual

Rev. 2.1

Page 26 of 50

Model X40

silence alarms once the end-user has assessed the alarm condition. The RESET/ACKNOWLEDGE
function of the switch is only applicable from the Main Display and not while in Main Menu mode.

m
e
t
s
y
S
l
o
r
t
n
o
C
&

m
r
a
l
A
d
e
t
a
r
g
e
t
n
I

Figure 24 Front Panel User Interface

NOTE: The controller automatically times out of Main Menu mode and returns to the Main
Display after 15 seconds of inactivity.
NOTE: The RESET/ACKNOWLEDGE function is applicable from the Main Display only.

7.2 Main Display Functions


The Main Display is a 1 x 6 backlit LCD that has 4 lines by 40 characters. In normal operation, the
configured channels will be displayed up to 8 channels at one time. The LCD then refreshes, displaying the
next 8 channel group and so on until the LCD cycles back to the first 8 channel group and repeats the
process. When the X40 is in alarm, the display will stay on the channel group with the channel in alarm. If
two or more channels in different groups are in alarm, then the display will cycle through all the groups
with alarms. The user can manually advance to the next channel group using the arrow switches. This is
considered normal operation and each channels information will be shown as:
XX>

YYY Device Tag

Where XX is the corresponding channel number followed by the gas concentration value YYY. If any
channel is in any gas alarm condition, XX> YYY IN ALARM# will be displayed for that channel. If
any gas channel is in fault, XX> YYY IN FAULT will be displayed for that channel. If any channel is
not communicating with its appropriate device, then that channel will display XX> 0 COMM ERR.
Four LED indicators on the front panel show alarm and fault alarm output status. The LEDs represent
ALM 1 (yellow), ALM 2 (yellow), ALM 3 (red) and FAULT (blue) and are labeled respectively.

7.3 Menu Functions


X40 controller setup is accomplished through the MAIN MENU. The MAIN MENU consists of 18 menu
items:
1) AUTO CONFIGURE SYSTEM
2) SET # OF CHANNELS/AO4S/RL4S/ALARM STATIONS
Model X40 Instruction Manual

Rev. 2.1

Page 27 of 50

Model X40

3) SET # OF RXT-320S
4) SET RF SILENCE AND RF SLEEP
5) SET COMM BAUD RATES
6) SET MODBUS TIMEOUTS
7) SETUP CHANNEL DATA
8) SET CHANNEL ALARMS
9) SET LOW BATTERY ALARMS
10) SET RELAY FUNCTION
11) FLASHING BLUE LED CODES
12) SET MODBUS ADDRESS
13) INHIBIT & ALARM TEST MODE
14) RF LINK QUALITY AND BATTERY STATUS
15) SYSTEM DIAGNOSTICS
16) DISPLAY SETTINGS
17) TIME AND DATE
18) VIEW TWA & PEAK
The PROG switch is used to enter the menu mode of the unit by swiping a programming magnet over the
corresponding marker . Once in the menus, all Modbus polling stops. Sensor values are not read
and alarm outputs are not updated. If the X40 is in alarm when the user enters the menu, it will stay in
alarm until they exit the menu. Upon entering the MAIN MENU, the LCD will display:
MAIN MENU
AUTO CONFIGURE SYSTEM
Use the down arrow v switch to move to the next menu item or use the up arrow u switch to move to
the previous menu item by swiping the programming magnet over the corresponding markers. Swiping the
PROG switch again will return the unit to normal operation. When the appropriate Menu Item is found, the
ENTER switch is used to enter that menu item by swiping the ENTER marker.
NOTE: The X40 automatically times out of Main Menu mode and returns to the Main Display
after 15 seconds of inactivity. While in Main Menu mode, there are no updates to gas readings.
NOTE: The LCD has a backlight that will automatically turn off after a user-defined amount
of inactivity. The LCD backlight will come on automatically as soon as any magnetic switch is
activated. This is a feature designed to save on power.
There are 18 Main Menu items and their functional descriptions are discussed in the following sections.

Model X40 Instruction Manual

Rev. 2.1

Page 28 of 50

Model X40

MAIN DISPLAY

MAIN MENU

NORMAL OPERATION

SET LOW BATTERY ALARMS

TTE(DD:HH:MM): ##:##:##
SOC(%): ###%
Multiple Relays
(Fault, Alm1, Alm2, Alm3)

MAIN MENU
AUTO CONFIGURE SYSTEM

MAIN MENU
SET # OF CHANNELS/AO4S/
RL4S/ALARM STATIONS

MAIN MENU

CHANNELS: ##
AO4S: #
RXT-320S:##
RL4/ALM BANK 1: #
RL4/ALM BANK 2: #

MAIN MENU
SET RELAY FUNCTION

CHANNELS: ##
AO4S: #
BANK 1: #
BANK 2: #

MAIN MENU
FLASHING BLUE LED CODES

RXT 320S: ##

SET # OF RXT-320S

MAIN MENU
SET RF SILENCE
AND RF SLEEP

RF SILENCE: ON/OFF
RF SLEEP: ##:##
RF SLEEP: ON/OFF

MAIN MENU

MAIN MENU

SET COMM BAUD RATES

Sensor Comm Errors


Sensor Faults
AO4 Comm Errors
RL4 Comm Errors
RXT-320 Comm Errors
RXT-320 Battery Fault
RXT-320 Low Battery Alarm
Inhibit Test Mode Status

MODBUS ADDRESS: ###

SET MODBUS ADDRESS

INHIBIT & ALARM TEST MODE

MAIN MENU

LATCHING (Bank1): Y/N


ENERGIZED (Bank1): Y/N
SILENCEABLE (Bank1): Y/N
LATCHING (Bank2): Y/N
ENERGIZED (Bank2): Y/N
SILENCEABLE (Bank2): Y/N

COMM1 BAUD RATE: ####


COMM2 BAUD RATE: ####

INHIBIT MODE: #:##


INHIBIT MODE: START/STOP
ALARM TEST MODE: ON/OFF
Multiple Transceivers

MAIN MENU
SET MODBUS TIMEOUTS

RESPONSE TIMEOUT: ####


INTERPOLL DELAY: ####

MAIN MENU
RF LINK QUALITY AND
BATTERY STATUS

Multiple Channels

MAIN MENU
SYSTEM DIAGNOSTICS

MAIN MENU
SETUP CHANNEL DATA

SLAVE ID: ## in hex


DEVICE TYPE: XXXXXX
ANALOG INPUT: #
DECIMAL POINT: #
RANGE: #####
TYPE: XXXXXXXXX
RL4 BANK: XXX

MAIN MENU
DISPLAY SETTINGS

Multiple Channels

MAIN MENU
SET CHANNEL ALARMS

ALM1 LEVEL: ##
ALM1 ASCENDING: Y/N
ALM2 LEVEL: ##
ALM2 ASCENDING: Y/N
ALM3 LEVEL: ##
ALM3 ASCENDING: Y/N

MAIN MENU
TIME AND DATE

MAIN MENU
VIEW TWA & PEAK

RF LINK: ###%
BATTERY: ##D ##H ##M

LCD DISPLAY TEST


LED DRIVER TEST
EXT RESET SWITCH TEST
RELAY DRIVER TEST
MODBUS DRIVER TEST

BRIGHTNESS: ###
BACKLIGHT TIMEOUT: #:##
CONTRAST: ###

TIME: HH:MM:SS
DATE: MM/DD/YY

DATE,TIME,CHANNEL,
TWA:######,PEAK: ######

Figure 25 Menu Flow Chart

7.3.1

Auto Configure System

The AUTO CONFIGURE SYSTEM menu is used to automatically configure the X40 controller when
other Detcon devices have been installed as part of the control system. When this feature is activated, the
controller will search for Detcon serial sensors, RL-4 modules, AO4 modules and RXT-320 transceivers by
polling the Modbus addresses of these particular device types. Upon entering this menu, the LCD will
display:
CONFIGURATION SUMMARY
CHANNELS:##
AO4S:##
RXT-320S:##
RL4/ALM ST BANK1:##
RL4/ALM ST BANK2:##
[RUN SYSTEM AUTO CONFIGURE]
Swipe the ENTER marker to initiate the search. The X40 controller will perform an incremental search for
available 700/100 and 600 serial sensors starting with Modbus address 01h. The search will continue
until Modbus address 7Fh is reached or until it is terminated by swiping the ENTER marker which will
save the serial sensors found up to that point and proceed to search for available RL4 modules starting with
Modbus address 80h. The search will continue until Modbus address 87h is reached or until it is
Model X40 Instruction Manual

Rev. 2.1

Page 29 of 50

Model X40

terminated by swiping the ENTER marker which will save the RL4 modules found up to that point and
proceed to search for available AO4 modules starting with Modbus address A1h. The search will
continue until Modbus address A8h is reached or until it is terminated by swiping the ENTER marker
which will save the AO4 modules found up to that point and proceed to search for available RXT-320
transceivers starting with Modbus address 01h. The search will continue until Modbus address 8Fh is
reached or until it is terminated by swiping the ENTER marker which will save the RXT-320 transceivers
found up to that point. A swipe of the PROG marker at any time while in search mode will cancel the
search and restore the default settings. Any devices found up to that point will not be saved.

7.3.2

Set # of Channels, AO-4s, RL-4s (Alarm Stations)

The SET # OF CHANNELS/AO4S/RL4S/ALARM STATIONS menu allows the user to set the number of
active channels (1-32), the number of AO-4 modules (0-8) and the number of RL-4 modules (0-4) each for
Bank1 and Bank2. The number of active channels should match the number of sensors being connected to
the controller. Upon entering this menu, the LCD will display:
SET # OF CHANNELS/AO4S/RL4S:
CHANNELS:##
AO4S:#
RL4 MODULES/ALARM STATIONS
BANK1:#
BANK2:#
These values can be changed by swiping the magnet over the markers of the up or down arrows to move
the arrow prompt to the desired function. A swipe over the ENTER marker will select the function
indicated by the arrow prompt and the value can be changed by swiping over the markers of the up or
down arrows. Another swipe over the ENTER marker will save the selected value.
NOTE: The number of activated channels can be less than (but not greater than) the
controllers maximum input capacity.

7.3.3

Set # of RXT-320s (Wireless Function Only)

The SET # OF RXT-320S menu is only applicable to X40 controllers that have the wireless option
installed. This menu is used to automatically search for all available RXT-320 transceivers in the network.
Upon entering this menu, the LCD will display:
SETUP RXT-320S:
RXT 320S IN NETWORK:##
[CONFIGURE]
Swipe the ENTER marker to initiate the search. The X40 controller will perform an incremental search for
available RXT-320s starting with Modbus address 1 (decimal). The search will continue until
Modbus address 143 is reached or until it is terminated by swiping the ENTER marker which will save
the RXT-320s found up to that point. A swipe of the PROG marker while in search mode will cancel the
search and will not save any RXT-320s found up to that point.

7.3.4

Set RF Silence and RF Sleep (Wireless Function Only)

The SET RF SILENCE AND RF SLEEP menu allows the user to initiate radio silence over the whole
network. Radio silence terminates communication between all the RXT-320 transceivers in the network.
This menu also allows the user to initiate RF sleep for a set amount of time. This sleep function lets the
X40 controller broadcast a sleep command to all the RXT-320 transceivers in the network and is used as a
power saving feature. Upon entering this menu, the LCD will display:
RF SILENCE AND SLEEP
Model X40 Instruction Manual

Rev. 2.1

Page 30 of 50

Model X40

RF SILENCE:
XXX

|
|
|

RF SLEEP:
##:##
SLEEP:XXX

Swipe the magnet over the markers of the up or down arrows to move the arrow prompt to the desired
location. A swipe over the ENTER marker for RF SILENCE and SLEEP will toggle the value between ON
and OFF. For the sleep timer, a swipe over the ENTER marker will select the function indicated by the
arrow prompt and the value can be changed by swiping over the markers of the up or down arrows.
Another swipe over the ENTER marker will save the selected value. The sleep timer has a range from 0
5 minutes and is set in minutes and seconds.
RF Silence is used to prevent the radios from possibly interfering with other RF devices on site (such as
remote detonators). Once set to ON, it will stay on until the user turns it OFF. In RF silence, the sensors
are not monitored and no alarms can be activated. When sleep is enabled, the sensors are each polled once,
and then the wireless transceivers are turned off for the sleep period. Once the sleep period expires, the
transceivers are turned back on and the sensors are polled once more. This cycle repeats indefinitely. The
sensors are not updated and the alarms are not activated while the wireless network is asleep. The longer
the sleep time, the longer the possible delay between alarm conditions occurring and the alarms being
activated. However, a longer sleep period will increase the battery run time.

7.3.5

Set COMM Baud Rates

The SET COMM BAUD RATES menu displays the current baud rate settings for COMM1 (master) and
COMM2 (slave). Upon entering this menu, the LCD will display:
SET COMM BAUD RATES:
COMM1 BAUD RATE:9600
COMM2 BAUD RATE:9600
NOTE: The value shown is pre-configured to 9600 and should not be altered unless directed
to do so by Detcon Factory Personnel.

7.3.6

Set Modbus Timeouts

The SET MODBUS TIMEOUTS menu allows the user to set the response timeout for Modbus
communications and the inter-poll delay. Upon entering this menu, the LCD will display:
SET MODBUS TIMEOUTS:
RESPONSE TIMEOUT:###
INTERPOLL DELAY:###
These values can be changed by swiping the magnet over the markers of the up or down arrows to move
the arrow prompt to the desired function. A swipe over the ENTER marker will select the function
indicated by the arrow prompt and the value can be changed by swiping over the markers of the up or
down arrows. Another swipe over the ENTER marker will save the selected value.
Response timeout is the amount of time in milliseconds the X40 controller will wait for a sensor to respond
to a poll request. Ten missed poll responses will result in the sensor being declared in COMM ERR. Interpoll delay is the amount of time in milliseconds the X40 will wait after receiving a poll response from one
sensor before it polls the next sensor. The range of values for the response timeout is 100-1000
milliseconds and 10-255 milliseconds for the inter-poll delay. The recommended value for the response
timeout is 500 and 150 for the inter-poll delay.
Model X40 Instruction Manual

Rev. 2.1

Page 31 of 50

Model X40

7.3.7

Set Channel Data

The SETUP CHANNEL DATA menu allows configuration of each channel represented by its assigned
sensor or device. When a sensor or device is being added to the controller, its information will need to be
added or modified in this menu. The information to be configured is the SLAVE ID, DEVICE TYPE,
ANALOG INPUT, DECIMAL POINT, RANGE, TYPE and RL4 BANK. Upon entering this menu, the
LCD will display:
CHANNEL 1 DATA:
SLAVE ID:##
DEVICE TYPE:XXX
ANALOG INPUT:#

DECIMAL POINT:#
RANGE:#####
TYPE:XXXXXXXXX
RL4 BANK:XXX

A flashing cursor will appear on SLAVE ID. Swiping the magnet over the markers of the up or down
arrows will move the flashing cursor to the desired function. A swipe over the ENTER marker will select
the function indicated by the flashing cursor and the value can be changed by swiping over the markers of
the up or down arrows. Another swipe over the ENTER marker will save the selected value and return to
the flashing cursor.
The SLAVE ID is the Modbus address in hex of the sensor or device being assigned to the indicated
channel. This will be a Modbus slave device to the X40 controller.
NOTE: For Detcon wireless DM-100 sensors only, the SLAVE ID will be the Modbus
address of its RXT-320 transceiver.
The DEVICE TYPE values available are 100, 700, 600, DA4/DI4 or RXT-320. The values of 100, 600 and
700 correspond to Detcon serial sensor models. The DA4/DI4 value represents analog sensors. The RXT320 value represents Detcons wireless transceiver when its analog inputs are used. Choose the appropriate
value corresponding the sensor or device being assigned to the indicated channel.
The ANALOG INPUT is only available for analog sensors and devices. Serial sensors do not use this field
and the field will only be active for DEVICE TYPE values of DA4/DI4 or RXT-320. For analog sensors
(DA4/DI4), the available value is 1, 2, 3 or 4 which corresponds to the input position on the DA-4/DI-4
module the sensor will be connected to (DA-4/DI-4 modules support up to four 4-20mA inputs). For
wireless transceivers (RXT-320), the available value is 1 or 2 which corresponds to the input position of the
transceiver the sensor will be connected to (RXT-320 transceivers support up to two 4-20mA inputs).
The DECIMAL POINT value can be 0, 1 or 2. It corresponds to the number of digits displayed to the right
of the decimal point of the gas concentration value displayed. Typically, if the sensor range is less than 10,
this value will be 2. If the sensor range is between 10 and 25, then this value will usually be 1. The
DECIMAL POINT value should be 0 if the sensor range is greater than 25.
The RANGE value can be selected from 1-10,000 and corresponds to the gas range value of the sensor.
NOTE: If the range is changed, the alarm levels will have to be reset!
The TYPE value is an alphanumeric string of nine characters and corresponds to the tag that is displayed
with the gas concentration value. This field is normally used to define the gas concentration units and the
gas type. When changing this value, the first alphanumeric character to be modified will be indicated by an
underscore and can be changed by swiping the magnet over the markers of the up or down arrows. A swipe
over the ENTER marker will select the displayed value and the next character to be changed will be
indicated by the underscore. Follow these same steps to input all nine characters. The last swipe over the
ENTER marker will return to the flashing cursor.

Model X40 Instruction Manual

Rev. 2.1

Page 32 of 50

Model X40

The RL4 BANK value can be 1, 2 or ALL and defines the bank that a channel is related to, whether its
associated with Bank1, Bank2 or both.
If there is more than one channel, a swipe of the down arrow marker while the flashing cursor is on RL4
BANK will scroll the display to the next channel allowing for its configuration. To return to the previous
channel, a swipe of the up arrow marker should be performed while the flashing cursor is on SENSOR
TYPE.

7.3.8

Set Channel Alarms

The SET CHANNEL ALARMS menu allows configuration of each channels alarms. The information to
be configured is the ALM1 LEVEL, ALM1 ASCENDING, ALM2 LEVEL, ALM2 ASCENDING, ALM3
LEVEL and ALM3 ASCENDING. Upon entering this menu, the LCD will display:
CHANNEL 1 ALARMS:

ALM2 LEVEL:
##
ALM2 ASCENDING: X
ALM3 LEVEL:
##
ALM3 ASCENDING: X

ALM1 LEVEL:
##
ALM1 ASCENDING: X

A flashing cursor will appear on ALM1 LEVEL. Swiping the magnet over the markers of the up or down
arrows will move the flashing cursor to the desired function. A swipe over the ENTER marker will select
the function indicated by the flashing cursor and the value can be changed by swiping over the markers of
the up or down arrows. Another swipe of the ENTER marker will save the selected value and return to the
flashing cursor.
All sensors have three alarm settings. These are labeled ALM1, ALM2, and ALM3 for Alarm 1,
Alarm 2, and Alarm 3 respectively. The alarm level values are pre-determined by the user and set for each
sensor depending on the range. These values represent the alarm level set points and can be entered in 5%
increments of the full-scale range selected for that channel.
The alarm relays can also be configured for ascending or descending mode. In ascending mode the relay
will be activated when the concentration is above the alarm threshold. The alarm relays can also be
activated in descending mode. In this mode, the alarm relays will activate when the concentration is below
the alarm threshold. Typically alarms are ascending, with the exception of oxygen sensors. The alarm
ascending level can be either Y (Yes) or N (No).
If there is more than one channel, a swipe of the down arrow marker while the flashing cursor is on ALM3
ASCENDING will scroll the display to the next channel allowing for its configuration. To return to the
previous channel, a swipe of the up arrow marker should be performed while the flashing cursor is on
ALM1 LEVEL.
NOTE: If there is no intention of using a gas alarm relay, a setting of 0 will make it inactive.
NOTE: Any channels that are in alarm or fault will not display the device tag on the Main
Display.
NOTE: If the channel range is changed, then the alarm set points must be re-entered!

7.3.9

Set Low Battery Alarms

The SET LOW BATTERY ALARMS menu allows the user to set low battery alarm thresholds for RXT320 transceivers using Detcons Smart Battery Pack that are interfaced to the controller. Upon entering this
menu, the LCD will display:
LOW BATTERY ALARM:
TTE(DD:HH:MM): |
SOC(%):
Model X40 Instruction Manual

Rev. 2.1

Page 33 of 50

Model X40

##:##:##

|
##%
| ALARM STATIONS ONLY

TTE represents the time to empty and will be displayed in days, hours and minutes. SOC represents the
state of charge and will be displayed as a percentage value. To change the TTE and/or SOC values, swipe
the magnet over the markers of the up or down arrows to move the cursor to the desired field. A swipe
over the ENTER marker will select the field indicated by the cursor and enclose the value in brackets.
While in brackets, the value can be changed by swiping over the markers of the up or down arrows.
Another swipe over the ENTER marker will save the selected value. A swipe of the PROG marker at any
time while setting the TTE or SOC will escape out of the current field with no changes saved.
The recommended value for the TTE should be set to 5 days and applies to all battery powered RXT-320s
other than alarm stations. The SOC value applies to alarm stations only and the recommended value
should be set to 25%. When any battery in the network falls below the set thresholds, the blue LED on the
controller will be activated and begin flashing. Refer to Section 7.3.11 to access the RXT-320 LOW
BATTERY ALARM fault code which will indicate the RXT-320s that have fallen below the thresholds by
displaying their corresponding hexadecimal Modbus address.

7.3.10 Set Relay (Alarm) Functions


The SET RELAY FUNCTION menu allows for configuration of the relays in Bank1 and Bank2 of the X40
controller. The information to be configured is LATCHING, ENERGIZED and SILENCEABLE for both
Bank1 and Bank2. Upon entering this menu, the LCD will display:
FAULT RELAY SETUP: BANK 1 & 2
LATCHING:X
LATCHING:X
ENERGIZED:X
ENERGIZED:X
SILENCEABLE:X
SILENCEABLE:X
The fields on the left side of the display correspond to Bank1 and the fields on the right side of the display
correspond to Bank2. Also, the first relay to be displayed will be the FAULT relay followed by ALARM1,
then ALARM2 and finally ALARM3. A flashing cursor will appear on LATCHING for Bank1. Swiping
the magnet over the markers of the up or down arrows will move the flashing cursor to the desired function.
A swipe over the ENTER marker will select the function indicated by the flashing cursor and the value can
be changed by swiping over the markers of the up or down arrows. Another swipe over the ENTER marker
will save the selected value and return to the flashing cursor. A swipe of the down arrow marker while the
flashing cursor is on SILENCEABLE for Bank2 will scroll the display to the next relay allowing for its
configuration. To return to the previous relay, a swipe of the up arrow marker should be performed while
the flashing cursor is on LATCHING for Bank1.
There are four relay outputs per bank. Three relay outputs are used for ALM1, ALM2 and ALM3 and the
fourth relay output is used for the FAULT condition. All four relays outputs in both banks must be set-up
to account for the following three settings: Latching or Non-Latching, Energized or De-Energized and
Silenceable or Non-Silenceable (See sections 5.4.1, 5.4.2 and 5.4.3). The values selected can be either Y
(Yes) or N (No).
NOTE: It is generally recommended to set the FAULT relay as energized so that it will trip
upon loss of power.
NOTE: The FAULT condition is assigned to the FAULT relay as a standard. It cannot be
disengaged in the configuration of the controller. The Main Display will show IN FAULT for
any channel that is in fault.

Model X40 Instruction Manual

Rev. 2.1

Page 34 of 50

Model X40

7.3.11 Flashing Blue LED Codes


The FLASHING BLUE LED CODES menu allows the user to interpret the fault status of the X40
controller when the blue fault LED is illuminated. Upon entering this menu, the LCD will display any fault
codes available. Perform a swipe of the down arrow marker to scroll the display to the next available code.
Perform a swipe of the up arrow marker to scroll the display to the previous code. To exit this menu, a
swipe over the PROG marker can be performed at anytime. If there are no fault codes, NO ERRORS
FOUND will be displayed. There are 8 fault codes available:
1. Sensor Comm Errors
2. Sensor Faults
3. AO4 Comm Errors
4. RL4 Comm Errors
5. RXT-320 Comm Errors
6. RXT-320 Battery Fault (The battery fault can be acknowledged by swiping the magnet over the
RESET/ACK marker)
7. RXT-320 Low Battery Alarm
8. Inhibit/Test Mode Status

7.3.12 Set Modbus Address


The SET MODBUS ADDRESS menu allows the user to set the serial address of the X40 controller when it
is to be polled by another master device via its RS-485 Modbus RTU slave port (COMM2). Upon
entering this menu, the LCD will display:
MODBUS ADDRESS:
###
This value can be changed by performing a swipe over the ENTER marker and then swiping over the
markers of the up or down arrows. Another swipe over the ENTER marker will save the selected value.
The range of values for the Modbus address is 1-127 in decimal value.

7.3.13 Inhibit & Alarm Test Mode


The INHIBIT & ALARM TEST MODE menu allows the user to inhibit functionality of alarms in the
network as well as simulate alarm conditions and verify relay contacts. Upon entering this menu, the LCD
will display:
INHIBIT & ALARM TEST MODE
INHIBIT MODE:
|
ALARM TEST MODE:
#:##
|
OFF
START
|
These values can be changed by swiping the magnet over the markers of the up or down arrows to move
the arrow prompt to the desired function. A swipe over the ENTER marker will select the function
indicated by the arrow prompt and the value can be changed by swiping over the markers of the up or
down arrows. Another swipe over the ENTER marker will save the selected value.
The INHIBIT MODE has a timer range from 0-60 minutes. Once the timer value has been entered in
minutes and seconds, select START and all relay outputs on the network will be disabled until the timer
reaches 0 or is manually stopped by the user.
When turned ON, the ALARM TEST MODE simulates alarm conditions by incrementing the gas readings
from 0 for all active gas channels at 5% full scale. When full scale is reached, the readings will decrement
back to 0 and the unit will exit the test mode. The test mode can also be terminated at any time during the
Model X40 Instruction Manual

Rev. 2.1

Page 35 of 50

Model X40

test cycle by turning OFF the alarm test mode. As the readings cross their respective alarm set points, the
relays will fire according to their configuration.

7.3.14 RF Link Quality and Battery Status (Wireless Function Only)


The RF LINK QUALITY AND BATTERY STATUS menu displays the network RF link quality between
the RXT-320 transceiver of the X40 controller and of the RXT-320 transceivers of the wireless sensors
configured to the X40 controller. This menu also displays the battery life of the Smart Battery Packs
powering the RXT-320s of the wireless sensors. Upon entering this menu, the LCD will display:
F0> -----------------01> RF LINK:##%

BATTERY:DC POWER
BATTERY:##D ##H ##M

The first line corresponds to the information of the X40 controllers RXT-320 transceiver (indicated by the
transceivers Modbus address F0) and will only show the BATTERY status since there is no link
quality available. The other lines correspond to the RXT-320 transceiver information of the slave devices
controlled by the X40 on the network. Each transceiver available will be identified by its Modbus
address followed by the RF LINK value and BATTERY status. The RF LINK value is a percentage
representing the RF link quality between the controllers RXT-320 transceiver and the slave device RXT320 transceiver. The BATTERY status will be either DC POWER or ##D ##H ##M where DC POWER
indicates the transceiver is powered by a DC power supply other than a Smart Battery Pack. The ##D ##H
##M value corresponds to the days, hours and minutes of life remaining for the Smart Battery Pack
connected to the slave devices transceiver. The battery life is only displayed in D/H/M when the
remaining life is less than 45 days. If it is more than 45 days, it is displayed as a percentage of battery life
remaining. Refer to Section 7.3.9 for setting thresholds that triggers a low battery fault and alerts the user
of a low battery state.

NOTE: While in the RF LINK QUALITY AND BATTERY STATUS menu, the controller
performs a complete Modbus poll cycle and automatically times out of the menu and returns
to Main Menu mode after 60 seconds of inactivity.

7.3.15 System Diagnostics


The SYSTEM DIAGNOSTICS menu performs function tests for the LCD display, the panel LEDs, the
external reset switch, the relays and Modbus interface. Upon entering this menu, the X40 controller will
automatically initiate a function test that displays every pixel of the 4 line, 40 character LCD display. The
controller then performs a function test of the LED drivers by activating all four LEDs. After the LED
test, the controller will initiate a test for the external reset switch which lets the user know when the reset
switch is pressed. The user will be prompted to press (swipe) enter key (marker) to continue which will
initiate the relay driver test and the controller will then reset all the relays and turn on the alarm 1 relay.
The user will be prompted to press (swipe) any key (marker) which will turn on the alarm 2 relay. The
user will be prompted again to press any key and the alarm 3 relay will be turned on. The user will be
prompted again to press any key and the fault relay will be turned on. The user will be prompted again to
press any key and all the relays will be reset. The user will then be prompted to connect COMM1
(master) to COMM2 (slave) for a Modbus loop back test and press any key to continue. This will
initiate test 1 of 4 which performs a Modbus communication test at 4800 baud rate. The test will
perform 127 iterations and indicate the number of errors received if any. The user has the option to abort
the test at any time by pressing any key. Once test 1 is complete or has been aborted by the user, test 2 of
4 will initiate automatically and perform 127 iterations of the Modbus communication test at 9600 baud
rate. Test 3 of 4 will follow at 19200 baud rate and finally test 4 of 4 will be performed at 38400 baud rate.
All four tests can be terminated at any time by the user. When these tests are completed the display will
revert back to the SYSTEM DIAGNOSTICS menu.
Model X40 Instruction Manual

Rev. 2.1

Page 36 of 50

Model X40

NOTE: When performing the Modbus loop back test, the loop back cable should be
installed between the COMM1 (Master) port and the COMM2 (Slave) port. Disconnect all
other external Modbus interfaces from the loop and bypass any installed modules.

7.3.16 Display Settings


The DISPLAY SETTINGS menu allows the user to customize the brightness, contrast and backlight
duration of the display. Upon entering this menu, the LCD will display:
DISPLAY SETTINGS
BRIGHTNESS: ###
BACKLIGHT TIMEOUT: #:##
CONTRAST: ###
These values can be changed by swiping the magnet over the markers of the up or down arrows to move
the arrow prompt to the desired function. A swipe over the ENTER marker will select the function
indicated by the arrow prompt and the value can be changed by swiping over the markers of the up or
down arrows. Another swipe over the ENTER marker will save the selected value. Values for brightness
and contrast can range between 0 and 100. Available values for the backlight timeout function are OFF, 10
seconds, 30 seconds and 1-5 minutes. The backlight timeout is the amount of time the user has before the
LCD backlight will turn off while in the Main Display due to inactivity.

7.3.17 Time and Date


The TIME AND DATE menu allows the user to set the time and date for the controller. Upon entering this
menu, the LCD will display:
TIME AND DATE:
##:##:##
|
##:##:##
|
[TIME]
DATE
The time will be displayed as military time (24hrs) in hours, minutes and seconds. The date will be
displayed as the month, day and two digit year. If the time and/or date are not correct, they can be changed
as follows. To set the time, verify TIME is selected (enclosed in brackets) and swipe the magnet over the
ENTER marker to enter the SET TIME menu. Swipe the magnet over the markers of the up or down
arrows to move the arrow prompt to the desired field. A swipe over the ENTER marker will select the
field indicated by the arrow prompt and the value can be changed by swiping over the markers of the
up or down arrows. Another swipe over the ENTER marker will save the selected value. Once the desired
values have been set, move the arrow prompt to Update Time and swipe the ENTER marker to update
the time with the changes entered. To set the date, swipe the magnet over the marker of the down arrow
and verify DATE is selected (enclosed in brackets). Swipe the magnet over the ENTER marker to enter the
SET DATE menu. Swipe the magnet over the markers of the up or down arrows to move the arrow prompt
to the desired field. A swipe over the ENTER marker will select the field indicated by the arrow prompt
and the value can be changed by swiping over the markers of the up or down arrows. Another swipe over
the ENTER marker will save the selected value. Once the desired values have been set, move the arrow
prompt to Change Date and swipe the ENTER marker to update the date with the changes entered. A
swipe of the PROG marker at any time while setting the time or date will escape out of the current menu
with no changes saved.

Model X40 Instruction Manual

Rev. 2.1

Page 37 of 50

Model X40

7.3.18 View TWA & Peak


The VIEW TWA & PEAK menu allows the user to view the recorded time weighted average (TWA) and
peak readings for each channel represented by its assigned gas sensor. To use this menu function, a secure
digital (SD) memory card must be installed in the SD slot of the X40 controller board (J9). The data is
recorded on the SD card with the date, time, channel number, TWA and peak readings every time the
controller polls a sensor. Upon entering this menu, the user can view the data recorded from the SD card
and is displayed as:
<File Name>:
MM/DD/YY, HH:MM:SS, Channel #, TWA #, PEAK #
Example:
TWA_P08.CSV:
05/17/11,23:00:09,17, 51, 100
The sensor readings are continuously logged to the SD card. This data can also be viewed by removing the
SD card and inserting it in a laptop using the Detcon Log File Viewer application. Refer to the Detcon Log
File Viewer instruction manual for more information.

8.

Modbus Communications

The X40 controller features a Modbus compatible communications protocol and is addressable by a
PLC, PC/HMI, DCS or other Modbus RTU master-polling devices. Communication is accomplished by
two wire half duplex RS-485, 9600 baud, 8 data bits, 1 stop bit, no parity, through the controllers primary
port (COMM1).
A Modbus RTU master device up to 4000 feet away can theoretically poll up to 64 different X40
controllers. This number may not be realistic in harsh environments where noise and/or wiring conditions
would make it impractical to place so many devices on the same pair of wires. If multiple controllers are
being used on a single Modbus network, each controller must be set to a different device address.

8.1 Modbus Register Map


Table 3 X40 Register Map

Channel #
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Model X40 Instruction Manual

Register
40000
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012

Description
Reading
Status
Reading
Status
Reading
Status
Reading
Status
Reading
Status
Reading
Status
Reading
Rev. 2.1

Channel #
Channel 17
Channel 18
Channel 19
Channel 20
Channel 21
Channel 22
Channel 23

Register
40032
40033
40034
40035
40036
40037
40038
40039
40040
40041
40042
40043
40044

Description
Reading
Status
Reading
Status
Reading
Status
Reading
Status
Reading
Status
Reading
Status
Reading
Page 38 of 50

Model X40

Channel 8
Channel 9
Channel 10
Channel 11
Channel 12
Channel 13
Channel 14
Channel 15
Channel 16

40013
40014
40015
40016
40017
40018
40019
40020
40021
40022
40023
40024
40025
40026
40027
40028
40029
40030
40031

Status
Reading
Status
Reading
Status
Reading
Status
Reading
Status
Reading
Status
Reading
Status
Reading
Status
Reading
Status
Reading
Status

Channel 24
Channel 25
Channel 26
Channel 27
Channel 28
Channel 29
Channel 30
Channel 31
Channel 32

40045
40046
40047
40048
40049
40050
40051
40052
40053
40054
40055
40056
40057
40058
40059
40060
40061
40062
40063

Status
Reading
Status
Reading
Status
Reading
Status
Reading
Status
Reading
Status
Reading
Status
Reading
Status
Reading
Status
Reading
Status

Reading Register
Current gas reading of the channel
Status Register
High Byte
Bit 7 NOT USED
Bit 6 NOT USED
Bit 5 NOT USED
Bit 4 NOT USED
Bit 3 NOT USED
Bit 2 NOT USED
Bit 1 NOT USED
Bit 0 NOT USED
Low Byte
Bit 7 1-Reading divisor is 100 (bit 6 read as 0)
Bit 6 1-Reading divisor is 10 (bit 7 read as 0)
Bit 5 1-Comm. Error
ON
Bit 4 1-Calibration
ON
Bit 3 1-Fault
ON
Bit 2 1-Alarm 3
ON
Bit 1 1-Alarm 2
ON
Bit 0 1-Alarm 1
ON

Model X40 Instruction Manual

Rev. 2.1

0-No reading divisor


0-No reading divisor
0- Comm. Error
0- Calibration
0- Fault
0- Alarm 3
0- Alarm 2
0- Alarm 1

OFF
OFF
OFF
OFF
OFF
OFF

Page 39 of 50

Model X40

9.

Options

9.1 Optional Remote Alarm Reset/Acknowledge Switch


Model X40 controllers are designed for an optional Remote Alarm Reset/Acknowledge Switch. This
enables the user to reset or acknowledge alarms without having to open the X40 enclosure. The Reset
Switch is a momentary normally open push button type switch and will typically be mounted on the bottom
or side of the NEMA 4X enclosure. For the other enclosure types, the switch will have to be mounted
externally such as in the bottom of a J-Box if one is available. Connect the switch to the terminals of the
terminal block labeled REMOTE RESET for the N1P and N4X controllers (See Figure 26) For the N7
controller, connect the switch to the terminals SW on connector J7 (See Figure 27) Once installed,
pushing the switch will execute the reset/acknowledge function.

RESET

Figure 26 N1P & N4X Remote Switch Input

J7

D3

D4

PWR
GND
A2
B2
A1

RESET SWITCH
1 SW1 2

B1
SW

Figure 27 N7 Remote Switch Input

9.2 Wireless Option (RXT-320)


The Model X40 controller offers a wireless option that is designed to take Modbus communication
between the controller and other devices to a wireless platform. This option takes local Modbus
communication, and using a wireless network of transceivers, broadcasts this information throughout a
wireless network platform, creating a seamless network of Modbus devices that need not be physically
connected in any way.
The wireless function of the X40 Controller is made possible by Detcons RXT-320 wireless transceiver.
This transceiver transmits signal data such as analog 4-20mA DC or serial Modbus and can support up to
32 devices. It operates at 2.4GHz and conforms to non-licensed radio frequency appliance usage around
the world. Wireless network integrity and security is accomplished using direct sequence spread spectrum
wireless mesh technology. Wireless applications can be as simple as a single field device communicating
with a host controller or any number of field devices forming a network of subscribers. Each device in the
network is assigned a Network ID and a Modbus address. Processing power is based in a designated
Modbus master while every slave device in the network is capable of functioning as a router and repeater
for all other devices in the network. This means that subscribers can hop through neighboring devices to
communicate with each other thereby widening network access points. This unique and innovative
technology is designed to create a robust network that automatically routes around congestion and line-ofModel X40 Instruction Manual

Rev. 2.1

Page 40 of 50

Model X40

sight obstacles while improving throughput as subscriber device density increases. Refer to the RXT-320s
instruction manual for more detailed information.
The Model X40 controller can communicate wirelessly with up to 32 gas detection sensors. This is
accomplished by connecting an RXT-320 to the Modbus master port on the X40. The Model X40 also
offers the option to wirelessly connect an RD-64X remote display. This is accomplished by connecting an
RXT-320 to the Modbus slave port of the X40 and a second RXT-320 to the RD-64X.

9.2.1

RXT-320 Mounting

The RXT-320 wireless transceiver for the X40 controller comes mounted on a J-Box (condulet) which can
be remotely mounted on a pole near the controller (See Figure 28). Remote separation distances of up to
15 feet are possible with the recommended cable.
RXT-320 Wireless
Transceiver

X40 Controller
Mounting Plate

ng
mi
XT m
R ra
og
Pr

J6

J8

J5

ed
Us
t
No

W/BU

V
W/
N
W/G

J3

ed
Us
t
No

SA

SB
A
W
B
W

1 2 3 4 5 6 7

mA

2
TP

ed
Us
t
No

ed
Us
t
No

J4

J7
N
G

BU

BK

J-Box w/
Model100
Terminal Board

BK

BU

W/BR

W/BK

rt
Po
T ng
mi
RX m
ra
og
Pr

te
ys
S
l
ro
nt
o
C

&
m
ar
Al
d
e
at
gr
te
In

r
ve
ei
sc
an
Tr
20
-3
XT
R

J1
ER SS
WI LE
1
TP

www.detcon.com

er
oll
ntr
Co
0
X4
J2

R/
SO MI
NH
SE

Power & Modbus


Cabling to/from
Remote RXT Transceiver
Up to 15' Length

Figure 28 RXT-320 Wireless Assembly for X40 Controller

NOTE: It is highly recommended to install the cable inside rigid metal conduit to eliminate
potential EMI and RFI interference and to maintain a Class I Division I rating.
NOTE: A 6-32 or 8-32 threaded exterior ground point is provided on most junction boxes for
an external ground. If the transceiver assembly is not mechanically grounded, an external
ground strap must be used to ensure that the transceiver is electrically grounded.
Detcon offers an optional mounting plate that can be used for mounting the RXT-320 wireless assembly to
the pole. If ordered with this option, secure the wireless transceiver assembly to the mounting plate using
two of the four 3/8 diameter holes located on the top face of the mounting plate (If not already done so
from the factory). The mounting plate can then be mounted to a pole with two U-Bolts secured through the
7/16 holes of the mounting plates base (See Figure 29).

Model X40 Instruction Manual

Rev. 2.1

Page 41 of 50

Model X40

r
e
v
i
e
c
s
n
a
r
T
s
s
e
l
e
r
i
W
0
2
3
T
X
R

e
r
ec
a
h
f
tr
o
u
rs
o
g
n
i
t
e
n
l
ou
Po
m

e
t
a
l
P
gl
na
i
t
n
n
o
ui
ot
p
MO
n
o
c
t
e
D

71

g
n4
i
t
x
n
s
ue
ol
mo
"6h
s
t
r
o
P
T
P
N
"
34

g
n
i4
x
t
n
s
ue
oo
l
mh
"
38

g
n2
i
x
t
n
s
ue
oo
l
mh
"
14
8-32 tapped
ground point

Figure 29 RXT-320 Wireless Assembly w/Mounting Plate Dimensions

NOTE: Proper electrical installation of the RXT-320 transceiver assembly is critical for
conformance to Electrical Codes and to avoid damage due to water leakage. A conduit seal is
typically required to be located within 18" of the transceiver assembly if a conduit run is
required. Crouse Hinds type EYS2, EYD2 or equivalent are suitable for this purpose.
NOTE: Any unused ports should be blocked with suitable male NPT plugs. Detcon
supplies one NPT male plug with each J-box enclosure. If connections are other than
NPT, use an appropriate male plug of like construction material.
NOTE: Use suitable cord connectors (cable glands) for cable entering the X40 controller or
the transceivers J-Box.
NOTE: The Detcon Warranty does not cover water damage resulting from water leaking into
the enclosure.

9.2.2

RXT-320 Wiring

If the RXT-320 transceiver does not come pre-wired from the Detcon factory, it will require four conductor
connections for the power supply and Modbus interface. DC power is provided to the transceiver by the
controllers 24VDC power supply or a Detcon SmartWireless battery pack. The RS-485 interface is
accomplished by connecting the transceiver assembly to the controllers master and/or slave RS-485
Modbus interface. Connect four wires of a power & Modbus capable cable (Belden P/N 1502P is
recommended) to the Modbus TB2 DIN rail mounted terminal block. Connect the other end of the cable
to the J2 connector of the Terminal Board located inside the J-Box of the transceiver (See Figure 30, Figure
31, Figure 33, and Figure 34).
Model X40 Instruction Manual

Rev. 2.1

Page 42 of 50

Model X40

NOTE: It is highly recommended to install the cable inside rigid metal conduit to eliminate
potential EMI and RFI interference and to maintain a Class I Division I rating.
Model 100 Terminal Board
S
S
E
L
E
R
I
W
N
G
/
W

V
/
W

D
N
G

V
4
2

2
N
I
A

A
M

D
N
G

R
W
P

D
N
G

7
J

V
4
2

D
N
G

2
W
S

1
J

N
I
R
RA
EL
WO
OS
P

2
J

8
J

T
US
OS
E
SL
UE
BR
DI
OW
M

U
B
/
W

SM
SA
ER
L
EG
RO
I
R
WP

K N
1 B
B
N
/
I /
W W
A

6
J

4
J
1
W
S

V
4
2

R
O
S
N
E
S

N
I
S
U
B
D
O
M

X40 Controller

5
J
A
D
S

1
P
S

2
P
S

Y
A
L
P
S
I
D

9
L

RS-485 VDC
Out

L
C
S

D
N
G

1
P
J

MM
RA
ER
TG
O
R
P

R
W
P

B
A

Figure 30 Model 100 Terminal Board to X40 Controller Wiring

9.2.3

Model 100 Terminal Board

If the RXT-320 connected to the Modbus master port is to be used with a Detcon SmartWireless battery
pack, then the Model 100 Terminal Board will be mounted in the condulet/J-Box (See Figure 31). The
terminal board includes connector plugs for the following:
J1 4-Pin Connector Modbus Out (Wireless Transceiver Option)
J2 6-Pin Header Wireless Transceiver Programming Header
J3 6-Beau Connector used for battery operation or display interface dependant on sensor configuration
J4 4-Pin Connector Modbus In
J5 6-Pin Connector used for Display interface with battery/wireless configurations
J6 4-Pin Connector Sensor connections
J7 4-Pin Connector Auxiliary power in and mA out.
J8 6-Pin Connector Wireless Transceiver
J9 5-Pin Header Terminal Board Programming
S
S
E
L
E
R
I
W
V
/
W

V
4
2

D
N
G

2 A D
N
N
I
A M G

R
W
P

7
J

V
4
2

2
W
S

D
A N
G

1
J

N
IR
RA
EL
WO
OS
P

2
J

8
J

T
US
OS
E
SL
UE
BR
DI
OW
M

U N
B
/ G
/
W W

SM
SA
E
LR
EG
RO
IR
WP

K N
1 B
N / B
/
I
A W W

6
J

4
J
1
W
S

V D
4 N
2 G

R
O
S
N
E
S

N
I
S
U
B
D
O
M
5
J
L A 1
C D P
S S S

2
P
S

1
P
J

MM
RA
ER
TG
O
R
P

R D
W N
P G

Y
A
L
P
S
I
D

9
L

Figure 31 Model 100 Terminal Board


Model X40 Instruction Manual

Rev. 2.1

Page 43 of 50

Model X40

The Model 100 Terminal Board also contains two rotary switches which are used to set the Modbus
address for the RXT-320 wireless transceiver of the X40 controller. If not already set from the Detcon
factory, set the address to F0h. Access the terminal board and locate the switches shown in Figure 32. The
MSD (most significant digit) F is represented by the top rotary switch (closest to the J1 connector) and
the LSD (least significant digit) 0 is represented by the bottom rotary switch (closest to the J2 connector).

Figure 32 Model 100 Terminal Board Rotary Switches

9.2.4

Transient Protection Board

If the RXT-320 connected to the Modbus master or slave port is to be powered using the 24VDC output
from the controller, then the Transient Protection Board will be mounted in the condulet/J-box. The wiring
for the master port is shown in Figure 33 and the wiring for the slave port is shown in Figure 34.
NOTE: If an RXT-320 is used on both the Modbus master and slave ports on the X40, they
must be on different RF channels. Refer to the RXT-320 Instruction Manual for more
information on setting the RF channel on the RXT-320.

Model X40 Instruction Manual

Rev. 2.1

Page 44 of 50

Model X40
RXT-300
Wireless
Transceiver

White/Black
Power (+) Red
Ground (-) Black
Modbus B (-) White
Modbus A (+) Blue

Transceiver

Transient
Protection Module
T
U
O

N
I

A
m

A
m

Power (+) Red


Ground (-) Black
White/Black

Modbus A (+) Blue


Modbus B (-) White

R
O
S
N
E
S

Modbus A (+) Blue


Modbus B (-) White

RS-485 VDC
Master Out

Power (+) Red


Ground (-) Black

A
m

X40 Enclosure

B
A

Black
Red
White
Blue

Figure 33 Wiring Diagram to the Master

Model X40 Instruction Manual

Rev. 2.1

Page 45 of 50

Model X40
RXT-300
Wireless
Transceiver

Transient
Protection Module
T
U
O

N
I

Power (+) Red

Ground (-) Black

A
m

A
m

Yellow
Yellow

RESET

White
Purple

Modbus A (+) Blue


Modbus B (-) White

X40 Enclosure

B
A

SLAVE

Power (+) Red


Ground (-) Black
Modbus B (-) White
Modbus A (+) Blue

Transceiver

R
O
S
N
E
S
B

A
m

Black
Black
Black

Black

Modbus A (+) Blue


Modbus B (-) White

Power (+) Red


Ground (-) Black

Red
Red
Red
Red

White
Blue

Red
Black

Figure 34 Wiring Diagram to the Slave

10.

Troubleshooting Guide

Problem
Unit will not Power Up
Relays are not firing
Alarms on constantly
Alarm Firing causes unit to LockUp

Potential Fix

Check for correct AC or DC voltage selection.


Check for correct VAC and VDC powering configuration.
Check that the alarm relays are configured properly
Insure that no channels are set to ascending or descending
incorrectly.
Check that Alarm Annunciators current draw does not
exceed the on-board Power Supply limitations. Replace with
external Power Supply if necessary.

Contact the Detcon Service Department for further troubleshooting assistance at 281-367-4100.

Model X40 Instruction Manual

Rev. 2.1

Page 46 of 50

Model X40

11.

Warranty

Detcon, Inc., as the manufacturer, warrants under intended normal use each new Model X40-N4X
controller to be free from defects in material and workmanship for a period of one year from the date of
shipment to the original purchaser. Should the controller fail to perform in accordance with published
specifications within the warranty period, return to Detcon, Inc., for necessary repairs or replacement. All
warranties and service policies are FOB the Detcon facility located in The Woodlands, Texas.

12.

Specifications

System Specifications
Capacity:
Sensor Inputs:
Outputs:
Warranty:

32 I/O Channels
Analog 4-20mA or RS-485 Modbus RTU
Analog 4-20mA or RS-485 Modbus RTU
One year

Electrical Specifications
N1P, N4X Input Voltage:
N7 Input Voltage:
Power Consumption:

Power Consumption:

Power Consumption:
RFI/EMI Protection:
Electrical Classification:

100-240VAC, 45-65Hz
11.5-30VDC
11.5-30VDC
X40-08-N4X - Total Power consumption is dependent on number of I/O
modules, number of gas sensors, and the type of gas sensors. Total power
of controller with I/O modules and gas sensors not to exceed 60 Watts
(2.5A at 24VDC).
X40-32-N1P, X40-32-N4X - Total Power consumption is dependent on
number of I/O modules, number of gas sensors, and the type of gas
sensors. Total power of controller with I/O modules and gas sensors not to
exceed 180 Watts (7.5A at 24VDC).
X40-32-N7 Less than 0.5W (with alarm LEDs and backlight inactive,
controller only)
Complies with EN61326
NEMA 1 (X40-32-N1P), NEMA 4X (X40-08-N4X, X40-32-N4X)
NEMA 7 (X40-32-N7)

Mechanical Specifications
Display:
Dimensions:

1 x 6 Backlit LCD
X40-32-N1P 10.5 W x 8 H x 12 D
X40-08-N4X 11.85 W x 13.75 H x 6.5 D
X40-32-N4X 16 W x 17.85 H x 8.5 D
X40-32-N7 11.05 W x 9.15 H x 2.78 D
Operating Temperature Range: -20C to +70C
Wireless Specifications
Frequency:
Range:
Model X40 Instruction Manual

ISM 2.4GHz
Indoor/No Line of Sight 1,000ft
Outdoor RF Line of Sight (with directional antenna) 3 Miles
Rev. 2.1

Page 47 of 50

Model X40

Spread Spectrum:
Modulation:
Sensitivity:
Inputs:
Outputs:

Digital-Sequence Spread Spectrum (DSSS)


0-QPSK
-102dBm (1% PER)
RS-485 Modbus RTU (9600bps)
Two 4-20mA inputs
RS-485 Modbus RTU (9600bps)

12.1 Spare Parts


3B

Part Number
360-STP060-024
360-DLP180-024
975-041402-000
976-041400-000
975-041401-000
975-041400-000
327-000000-000
800-003648-000
500-003087-100
500-005156-000
949-005142-200

Part Number
976-000320-316
500-005168-100
897-850800-010
897-850400-010
960-202200-000
800-004221-000
897-044400-34T
8522-750
898-52310
899-07550
899-150750-316
301-58205

Model X40 Instruction Manual

Spare Parts
Power Supply 2.5A
Power Supply 7.5A
DI-4 Input Module
DA-4 Input Module
AO-4 Output Module
RL-4 Output Module
Programming Magnet
Mounting Plate for N7 Enclosure
Transient Protection Module
AC/DC Converter 4W
X40 Drop-In Control Assembly

Wireless Accessories
RXT-320 Wireless Transceiver
Model 100 Terminal Board
NEMA 7 Aluminum Condulet Base
NEMA 7 Aluminum Condulet Solid Cover
Condensation prevention packet (For condulet, replace annually)
Mounting Plate
NPT T-Outlet Box w/Aluminum Cover
NPT Plug
NPT Drain
NPT to NPT Adapter
NPT x 1.5 Nipple
NPT Cord Connector

Rev. 2.1

Page 48 of 50

Model X40

12.2 Revision Log


34B

Revision
0.0
0.1

Date
02/07/2011
03/18/2011

1.0

07/29/2011

1.1

08/10/2011

2.0
2.1

11/14/11
04/02/12

Model X40 Instruction Manual

Changes made
Initial Release.
Corrected AO4 modbus address range. Corrected enclosure
dimensions for 32 channel enclosure and added drawing for 8
channel enclosure. Revised DC input voltage specs.
Updates and modifications made relating to addition of different
enclosure types for the X40. Added 4 new menus: Auto
Configure, Low Battery Alarms, Time and Date and TWA and
Peak. Added section relating to SD card.
Made minor clarifications to sections 5.4.2, 5.5, 7.3.4, 7.3.7,
7.3.13 and 7.3.15. Modified RL-4 Table 2.
Changed N4X enclosure to include the Drop-In Assembly
Updates to terminal boards used, verbiage on units with alarm

Rev. 2.1

Approval
LU
LU
LU

LU
LU
LU

Page 49 of 50

Model X40

Model X40 Instruction Manual

Rev. 2.1

Page 50 of 50

Das könnte Ihnen auch gefallen