where e=r-y
is the control error which is the difference between the reference signal, r, and output
of the system y. The control law implies that maximum corrective action is always is
used which explains the name of on-off control.
A system with on-off control will always oscillate, in many cases the amplitude of the
oscillations is so small that they can be tolerated.
QNET heating and ventilation trainer (HVACT) is the system consists of a plexiglass
duct, with a heater in one end and a blower in the other end. There is a thermistor
sensor placed inside the duct to measure the temperature of the chamber and another
thermistor sensor outside the chamber to measure the room temperature.
On-off control is one of the simplest control strategies. The heater is switched on
when the temperature is lower than the desired value, and the heater is switched off
when the temperature is higher than the desired value. To avoid rapid switches it is
common to introduce a hysteresis in the relay switch.
The on-off control input and the measured temperature output from the experiment
have an interesting property that makes it possible to find a simple model for the
process. The temperature response is a ramp due a voltage step therefore the
temperature is the integral of the voltage. In our experiment the process can be
modeled by the simple transfer function P(s).
Where
P(s)=(Kv)/s
And the parameter Kv is the slope of the
ramp.
2) Offset = 1.5 C
3) Offset =2 C
Result:- By increasing the offset in the signal generator the reference temperature increases.
If we keep all other settings unchanged and just increase offset, we can never get the actual
temperature equal to the reference temperature.
Vary the heater voltage relay amplitude Vh_amp and observe the heater voltage effect on
temperature variation1) V
h_amp = 2.5V
2) V
h_amp = 5V
Result:- By increasing heater voltage we get more damped response or we can say that we
get actual temperature approximately equal to the reference temperature within the same
time range.
2) Vh_off = 1V
Result:- By increasing the relay mean the overshoot and undershoot values increases (w.r.t.
reference temperature).
1) DTh = 0.5 C
2) DTh = 1 C
Result:- By increasing the relay width the overshoot and undershoot increases w.r.t. reference
temperature.
For the given signal generator set and control parameter set, find the parameter Kv for our
on- off control system which has transfer function P(s) = (Kv)/s-