What does a lighting design guarantee?

Modeling
Glare control
Task visibility
Contrast Colour

Safe

Ergonomic
Atmosphere
Ambience
Healthy

Energy Efficient

Integrated
Interesting

Stimulating

Managed
Colourful
Satisfaction

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Practical
Effective

Lighting Design - Why Maintenance Factors Matter

What does a lighting design guarantee?

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

What does a lighting design guarantee?

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

What does a lighting design guarantee?

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

What does a lighting design guarantee?

Lighting in the workplace: Good practice


39 Both interior and exterior lighting need to achieve a
reasonable uniform illuminance in all relevant working
areas, ie illuminance across any given task area
needs to be uniform. For more information see CIBSE
Code for lighting.

Minimum lighting recommendations


93 The illuminance needed depends on how much
detail needs to be seen. It also depends on the age of
the worker, and the speed and accuracy by which the
task needs to be performed. These performancerelated requirements and light levels are detailed in
the CIBSE Code for lighting.

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

What does a lighting design guarantee?

30%-90% w/p

0.6 minimum
Ceiling
= 0.7 - 0.9

0.3-0.7

Em = 30 lux, Uo = 0.1
Walls
= 0.5 - 0.8

50%-60% w/p

Em = 50 lux, Uo = 0.1

Floor
= 0.2 - 0.4
(Purple text values as in SLL Lighting Guide 7)

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

What does a lighting design guarantee?

Task area
Immediate surround width
at least 0.5m around the task
area
Background area width at
least 3m (within the limits of
the space)

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

What does a lighting design guarantee?

Modeling
Glare control
Task visibility
Contrast Colour

Safe

Ergonomic
Atmosphere
Ambience
Healthy

Energy Efficient

Integrated
Interesting

Stimulating

Managed
Colourful
Satisfaction

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Practical
Effective

Lighting Design - Why Maintenance Factors Matter

What does a lighting design guarantee?

maintained illuminance
minimum average illuminance
NOTE 1 Value below which average
illuminance should not fall.
NOTE 2 It is the average illuminance at
the time maintenance should be carried
out.
From EN 12665:2011

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

What does a lighting design guarantee?

The lighting scheme should be designed with an overall maintenance factor


(MF) calculated for the selected lighting equipment, environment and
specified maintenance schedule.
The MF has a great impact on energy efficiency. The assumptions made in
the derivation of the MF shall be optimized in a way that leads to a high
value. Guidance on the derivation of MF for artificial lighting systems can
be found in CIE 97-2005.

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

What is managed?

Modeling
Glare control
Task visibility
Contrast Colour

Safe

Ergonomic
Atmosphere
Ambience
Healthy

Energy Efficient

Integrated
Interesting

Stimulating

Managed
Colourful
Satisfaction

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Practical
Effective

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle

The light levels in an installation


depreciate over time
This is dependant upon ?

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle

The light levels in an installation


depreciate over time
This is dependant upon
-Ageing of the lamp
-Lamp failures
-Dirt on the luminaire
-Dirt on light reflecting surfaces

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle

The light levels in an installation depreciate


over time
This is dependant upon
- Ageing of the lamp
- Lamp failures
- Dirt on the luminaire
- Dirt on light reflecting surfaces
These combine to make up the scheme
maintenance factor
ratio of the average illuminance on the
working plane after a certain period of use of a
lighting installation to the average illuminance
obtained under the same condition for the
installation considered conventionally as new
(CIE 17.4:1987)

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle

The light levels in an installation


depreciate over time
This is dependant upon
-Ageing of the lamp
-Lamp failures
-Dirt on the luminaire
-Dirt on light reflecting surfaces

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle

The light levels in an installation


depreciate over time
This is dependant upon
-Ageing of the lamp
-Lamp failures
-Dirt on the luminaire
-Dirt on light reflecting surfaces

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle

The light levels in an installation depreciate


over time
This is dependant upon
-Ageing of the lamp
-Lamp failures
-Dirt on the luminaire
-Dirt on light reflecting surfaces
The maintenance cycle specifies
-When the luminaire is cleaned
-When the lamp is replaced
-When reflecting surfaces are cleaned
The scheme maintenance factor is the worst
case relative illuminance over this
maintenance cycle

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle lamp lumen maintenance factor (LLMF)

Ageing of the lamp


Let us assume for an office area
annual operating hours are 2500
hours (BS EN 15193:2007)
If we decide to change the lamps
every 4 years that is the equivalent
of every 10,000 hours

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle lamp lumen maintenance factor (LLMF)

91%

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle lamp lumen maintenance factor (LLMF)

Ageing of the lamp


Let us assume for an office area
annual operating hours are 2500
hours (BS EN 15193:2007)
If we decide to change the lamps
every 4 years that is the equivalent
of every 10,000 hours
So the lamp lumen maintenance
factor is 0.91

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle lamp survival factor (LSF)

Lamp failures
Let us assume in our office area
we do not do spot lamp
replacement, but bulk replace the
lamps
We decided to change the lamps
every 4 years

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle lamp survival factor (LSF)

95%

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle lamp survival factor (LSF)

Lamp failures
Let us assume in our office area
we do not do spot lamp
replacement, but bulk replace the
lamps
We decided to change the lamps
every 4 years
So the lamp survival factor is 0.95

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle luminaire maintenance factor (LMF)

Dirt on the luminaire


Luminaire types are classified
according to the table shown
(extracted from CIE 97:2005)

Type

Luminaire
type

Luminaire description

Bare batten

Bare lamp luminaires

Open top
housing
(natural
ventilated
and self
cleaning
types)

Direct-indirect luminaries without cover,


direct-indirect luminaries with indirect
reflector and closed optical device,
wallwashing luminaries (vertical
opening), wall mounted luminaries open
top and base, downlights with open top

Closed top Recessed and surface mounted


housing
luminaries (e.g. with louvers),
(unventilated) downlights, spotlights

Enclosed
IP2X

General purpose luminaries with closed


covers and optics

Dust proof
IP5X

Dust proof IP5X (protected, clean room


luminaries)

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Indirect
lighting and
uplight
Air handling
and forced
ventilated

Free standing, pendent, wall mounted


uplighters with closed base, cove lights
Air handling body and optic used with
air-conditioning or ventilation systems

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle luminaire maintenance factor (LMF)

Dirt on the luminaire

Type

Luminaire
type

Bare batten Bare lamp luminaires

Luminaire types are classified


according to the table shown
(extracted from CIE 97:2005)

These are used to reference a table


of luminaire maintenance factors

D
E
F

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Luminaire description

Open top
Direct-indirect luminaries without
housing
cover, direct-indirect luminaries with
(natural
indirect reflector and closed optical
ventilated
device, wallwashing luminaries
and self
(vertical opening), wall mounted
cleaning
luminaries open top and base,
types)
downlights with open top
Closed top
Recessed and surface mounted
housing
luminaries (e.g. with louvers),
(unventilated
downlights, spotlights
)
Enclosed
General purpose luminaries with
IP2X
closed covers and optics
Dust proof Dust proof IP5X (protected, clean room
IP5X
luminaries)
Indirect
Free standing, pendent, wall mounted
lighting and uplighters with closed base, cove
uplight
lights
Air handling
Air handling body and optic used with
and forced
air-conditioning or ventilation systems
ventilated

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle luminaire maintenance factor (LMF)

Environments are split into very clean (VC), clean (C), normal (N) and dirty
(D)
A maintenance value is read by determining the luminaire type and
environment, and then deciding the cleaning interval

Elapsed time between cleanings in years


0

0.5

1.0

1.5

2.0

2.5

3.0

Environment
Luminaire type Any VC

VC

VC

VC

VC

VC

0,98 0.95 0.92 0.88 0.96 0.93 0.89 0.83 0,95 0.91 0.87 0.80 0.94 0.89 0.84 0.78 0,93 0.87 0.82 0.75 0.92 0.85 0.79 0.73

0,96 0.95 0.91 0.88 0.95 0.90 0.86 0.83 0,94 0.87 0.83 0.79 0.92 0.84 0.80 0.75 0,91 0.82 0.76 0.71 0.89 0.79 0.74 0.68

0,95 0.93 0.89 0.85 0,94 0.89 0.81 0.75 0,93 0.84 0.74 0.66 0,91 0.80 0.69 0.59 0,89 0.77 0.64 0.54 0,87 0.74 0.61 0.52

0,94 0.92 0.87 0.83 0.94 0.88 0.82 0.77 0,93 0.85 0.79 0.73 0.91 0.83 0.77 0.71 0,90 0.81 0.75 0.68 0.89 0.79 0.73 0.65

0,94 0.96 0.93 0.91 0,96 0.94 0.90 0.86 0,92 0.92 0.88 0.83 0,93 0.91 0.86 0.81 0,92 0.90 0.85 0.80 0,92 0.90 0.84 0.79

0,94 0.92 0.89 0.85 0.93 0.86 0.81 0.74 0,91 0.81 0.73 0.65 0.88 0.77 0.66 0.57 0,86 0.73 0.60 0.51 0.85 0.70 0.55 0.45

1,00 1.00 0.99 0.98 1,00 0.99 0.96 0.93 0,99 0.97 0.94 0.89 0,99 0.96 0.92 0.87 0,98 0.95 0.91 0.86 0,98 0.95 0.90 0.85

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle luminaire maintenance factor (LMF)

Dirt on the luminaire

Environment Activity or Task area

The environment type for the


application can be determined
using the table shown. However
these should be adjusted if the
conditions are different from the
norm

Very Clean
Clean

Normal

Dirty

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Clean rooms, semi conductor


plants, hospital clinical areas,
computer centres
Offices, schools, hospital wards
Shops, laboratories,
restaurants, warehouses,
assembly areas, workshops
Steelworks, chemical works,
foundries, welding, polishing,
woodwork

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle luminaire maintenance factor (LMF)

For our example we will decide to clean the luminaires every 2 years
An office is normally considered a clean environment
Assume we are using a recessed luminaire, which is luminaire type C
Therefore our luminaire maintenance factor is 0.80
Elapsed time between cleanings in years
0

0.5

1.0

1.5

2.0

2.5

3.0

Environment
Luminaire type Any VC

VC

VC

VC

VC

VC

0,98 0.95 0.92 0.88 0.96 0.93 0.89 0.83 0,95 0.91 0.87 0.80 0.94 0.89 0.84 0.78 0,93 0.87 0.82 0.75 0.92 0.85 0.79 0.73

0,96 0.95 0.91 0.88 0.95 0.90 0.86 0.83 0,94 0.87 0.83 0.79 0.92 0.84 0.80 0.75 0,91 0.82 0.76 0.71 0.89 0.79 0.74 0.68

0,95 0.93 0.89 0.85 0,94 0.89 0.81 0.75 0,93 0.84 0.74 0.66 0,91 0.80 0.69 0.59 0,89 0.77 0.64 0.54 0,87 0.74 0.61 0.52

0,94 0.92 0.87 0.83 0.94 0.88 0.82 0.77 0,93 0.85 0.79 0.73 0.91 0.83 0.77 0.71 0,90 0.81 0.75 0.68 0.89 0.79 0.73 0.65

0,94 0.96 0.93 0.91 0,96 0.94 0.90 0.86 0,92 0.92 0.88 0.83 0,93 0.91 0.86 0.81 0,92 0.90 0.85 0.80 0,92 0.90 0.84 0.79

0,94 0.92 0.89 0.85 0.93 0.86 0.81 0.74 0,91 0.81 0.73 0.65 0.88 0.77 0.66 0.57 0,86 0.73 0.60 0.51 0.85 0.70 0.55 0.45

1,00 1.00 0.99 0.98 1,00 0.99 0.96 0.93 0,99 0.97 0.94 0.89 0,99 0.96 0.92 0.87 0,98 0.95 0.91 0.86 0,98 0.95 0.90 0.85

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle room surface maintenance factor


(RSMF)
Dirt on light reflecting surfaces
For the effect of dirt on the room
surfaces three pieces of
information are required
-Surface reflectances
-Environment cleanliness (as for
the luminaire maintenance
factor)
-Room surface cleaning interval
A table of room surface
maintenance factors is then
consulted

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle room surface maintenance factor


(RSMF)
reflectances

environment

0.00

0.50

1.00

1.50

2.00

2.50

3.00

3.50

4.00

4.50

5.00

5.50

1.00

0.97

0.96

0.95

0.95

0.95

0.95

0.95

0.95

0.95

0.95

0.95

0.95

clean

1.00

0.93

0.92

0.91

0.91

0.91

0.91

0.91

0.91

0.91

0.91

0.91

0.91

normal

1.00

0.88

0.86

0.86

0.85

0.85

0.85

0.85

0.85

0.85

0.85

0.85

0.85

dirty

1.00

0.81

0.80

0.80

0.80

0.80

0.80

0.80

0.80

0.80

0.80

0.80

0.80

1.00

0.98

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.80/0.70/0.20 very clean

0.80/0.50/0.20 very clean

6.00

clean

1.00

0.95

0.94

0.94

0.94

0.94

0.94

0.94

0.94

0.94

0.94

0.94

0.94

normal

1.00

0.91

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

dirty
0.80/0.30/0.20 very clean

1.00

0.86

0.85

0.85

0.85

0.85

0.85

0.85

0.85

0.85

0.85

0.85

0.85

1.00

0.99

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

clean

1.00

0.97

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

normal

1.00

0.94

0.93

0.93

0.93

0.93

0.93

0.93

0.93

0.93

0.93

0.93

0.93

dirty
0.70/0.70/0.20 very clean

1.00

0.91

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

1.00

0.97

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

clean

1.00

0.94

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

normal

1.00

0.89

0.87

0.87

0.87

0.87

0.87

0.87

0.87

0.87

0.87

0.87

0.87

dirty
0.70/0.50/0.20 very clean

1.00

0.83

0.81

0.81

0.81

0.81

0.81

0.81

0.81

0.81

0.81

0.81

0.81

1.00

0.98

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

clean

1.00

0.96

0.95

0.94

0.94

0.94

0.94

0.94

0.94

0.94

0.94

0.94

0.94

normal

1.00

0.92

0.91

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

dirty
0.70/0.30/0.20 very clean

1.00

0.87

0.86

0.86

0.86

0.86

0.86

0.86

0.86

0.86

0.86

0.86

0.86

1.00

0.99

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

clean

1.00

0.97

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

normal

1.00

0.95

0.94

0.94

0.94

0.93

0.93

0.93

0.93

0.93

0.93

0.93

0.93

dirty
0.50/0.70/0.20 very clean

1.00

0.92

0.91

0.91

0.91

0.91

0.91

0.91

0.91

0.91

0.91

0.91

0.91

1.00

0.98

0.97

0.97

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

clean

1.00

0.95

0.94

0.93

0.93

0.93

0.93

0.93

0.93

0.93

0.93

0.93

0.93

normal

1.00

0.91

0.89

0.89

0.89

0.89

0.89

0.89

0.89

0.89

0.89

0.89

0.89

dirty
0.50/0.50/0.20 very clean

1.00

0.85

0.84

0.84

0.84

0.84

0.84

0.84

0.84

0.84

0.84

0.84

0.84

1.00

0.98

0.98

0.98

0.98

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

clean

1.00

0.97

0.96

0.95

0.95

0.95

0.95

0.95

0.95

0.95

0.95

0.95

0.95

normal

1.00

0.94

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

dirty
0.50/0.30/0.20 very clean

1.00

0.89

0.89

0.88

0.88

0.88

0.88

0.88

0.88

0.88

0.88

0.88

0.88

1.00

0.99

0.99

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

clean

1.00

0.98

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

normal

1.00

0.96

0.95

0.95

0.95

0.95

0.95

0.95

0.95

0.95

0.95

0.95

0.95

dirty

1.00

0.93

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle room surface maintenance factor


(RSMF)
Dirt on light reflecting surfaces
For the effect of dirt on the room
surfaces three pieces of information
are required
-Surface reflectances
-Environment cleanliness (as for the
luminaire maintenance factor)
-Room surface cleaning interval
A table of room surface maintenance
factors is then consulted
So if we assume
-Reflectances 70/50/20
-Office environment, therefore clean
-A cleaning interval of 5 years
Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle room surface maintenance factor


(RSMF)
reflectances

environment

0.00

0.50

1.00

1.50

2.00

2.50

3.00

3.50

4.00

4.50

5.00

5.50

1.00

0.97

0.96

0.95

0.95

0.95

0.95

0.95

0.95

0.95

0.95

0.95

0.95

clean

1.00

0.93

0.92

0.91

0.91

0.91

0.91

0.91

0.91

0.91

0.91

0.91

0.91

normal

1.00

0.88

0.86

0.86

0.85

0.85

0.85

0.85

0.85

0.85

0.85

0.85

0.85

dirty

1.00

0.81

0.80

0.80

0.80

0.80

0.80

0.80

0.80

0.80

0.80

0.80

0.80

1.00

0.98

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.80/0.70/0.20 very clean

0.80/0.50/0.20 very clean

6.00

clean

1.00

0.95

0.94

0.94

0.94

0.94

0.94

0.94

0.94

0.94

0.94

0.94

0.94

normal

1.00

0.91

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

dirty
0.80/0.30/0.20 very clean

1.00

0.86

0.85

0.85

0.85

0.85

0.85

0.85

0.85

0.85

0.85

0.85

0.85

1.00

0.99

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

clean

1.00

0.97

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

normal

1.00

0.94

0.93

0.93

0.93

0.93

0.93

0.93

0.93

0.93

0.93

0.93

0.93

dirty
0.70/0.70/0.20 very clean

1.00

0.91

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

1.00

0.97

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

clean

1.00

0.94

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

normal

1.00

0.89

0.87

0.87

0.87

0.87

0.87

0.87

0.87

0.87

0.87

0.87

0.87

dirty
0.70/0.50/0.20 very clean

1.00

0.83

0.81

0.81

0.81

0.81

0.81

0.81

0.81

0.81

0.81

0.81

0.81

1.00

0.98

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

clean

1.00

0.96

0.95

0.94

0.94

0.94

0.94

0.94

0.94

0.94

0.94

0.94

0.94

normal

1.00

0.92

0.91

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

0.90

dirty
0.70/0.30/0.20 very clean

1.00

0.87

0.86

0.86

0.86

0.86

0.86

0.86

0.86

0.86

0.86

0.86

0.86

1.00

0.99

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

clean

1.00

0.97

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

normal

1.00

0.95

0.94

0.94

0.94

0.93

0.93

0.93

0.93

0.93

0.93

0.93

0.93

dirty
0.50/0.70/0.20 very clean

1.00

0.92

0.91

0.91

0.91

0.91

0.91

0.91

0.91

0.91

0.91

0.91

0.91

1.00

0.98

0.97

0.97

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

0.96

clean

1.00

0.95

0.94

0.93

0.93

0.93

0.93

0.93

0.93

0.93

0.93

0.93

0.93

normal

1.00

0.91

0.89

0.89

0.89

0.89

0.89

0.89

0.89

0.89

0.89

0.89

0.89

dirty
0.50/0.50/0.20 very clean

1.00

0.85

0.84

0.84

0.84

0.84

0.84

0.84

0.84

0.84

0.84

0.84

0.84

1.00

0.98

0.98

0.98

0.98

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

clean

1.00

0.97

0.96

0.95

0.95

0.95

0.95

0.95

0.95

0.95

0.95

0.95

0.95

normal

1.00

0.94

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

dirty
0.50/0.30/0.20 very clean

1.00

0.89

0.89

0.88

0.88

0.88

0.88

0.88

0.88

0.88

0.88

0.88

0.88

1.00

0.99

0.99

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

clean

1.00

0.98

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

0.97

normal

1.00

0.96

0.95

0.95

0.95

0.95

0.95

0.95

0.95

0.95

0.95

0.95

0.95

dirty

1.00

0.93

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

0.92

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle room surface maintenance factor


(RSMF)
Dirt on light reflecting surfaces
For the effect of dirt on the room surfaces
three pieces of information are required
-Surface reflectances
-Environment cleanliness (as for the
luminaire maintenance factor)
-Room surface cleaning interval
A table of room surface maintenance factors
is then consulted
So if we assume
-Reflectances 70/50/20
-Office environment, therefore clean
-A cleaning interval of 5 years
Therefore the room surface maintenance
factor is 0.94
Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle

So for this example the scheme maintenance factor would be


MF = LLMF * LSF * LMF * RSMF
MF = 0.91 * 0.95 * 0.80 * 0.94
MF = 0.65

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle

So for this example the scheme maintenance factor would be


MF = LLMF * LSF * LMF * RSMF
MF = 0.91 * 0.95 * 0.80 * 0.94
MF = 0.65
This means to ensure that the installation never falls below the maintained
light level (assuming the maintenance schedule is adhered to) we must
OVERLIGHT the area to 154% of the design level. So for example
Maintained light level = 500lx
Initial light level = 769lx
Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Scheme maintenance cycle

Exposure time (years)


Note that the example given was for
interior lighting.
For exterior lighting no room surface
maintenance factor is used.
The luminaire maintenance factor is
calculated differently, according to
the table shown.

Optical
IP
Pollution 1.0
rating category

1.5

2.0

2.5

3.0

High

0.53

0.48

0.45

0.43

0.42

Medium 0.62

0.58

0.56

0.54

0.53

Low

0.82

0.80

0.79

0.78

0.78

High

0.89

0.87

0.84

0.80

0.76

Medium 0.90

0.88

0.86

0.84

0.82

Low

0.92

0.91

0.90

0.89

0.88

High

0.91

0.90

0.88

0.85

0.83

Medium 0.92

0.91

0.89

0.88

0.87

Low

0.92

0.91

0.90

0.90

IP2X

IP5X

IP6X

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

0.93

Lighting Design - Why Maintenance Factors Matter

How do we calculate the effect of our maintenance schedule?

It also means we need to define a maintenance schedule


Change lamps

4 years

Clean luminaires

2 years

Clean room surfaces

5 years

If we do not convey this to the customer we cannot guarantee the light levels
(If the customer requires a set maintenance factor, for example 0.8, we should
then take no responsibility for the maintenance regime and can only
guarantee light levels at start of life)

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Using control to offset maintenance factors

Constant Illuminance

To improve the efficiency of an


installation the lighting can be
controlled to only produce the
correct amount of light at any time.
At start of life the lights are
dimmed, as the installation ages
the dimming is gradually reduced

24

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

1 MF
% savings 1

Lighting Design - Why Maintenance Factors Matter

Using control to offset maintenance factors

Maintenance factor : 0.65

1 MF
% savings 1

%savings= 1-[(1+MF)/2]
%savings= 1-[(1+0.65)/2] = 0.175
Saving : 17.5%

21

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors main influences

Change the lamp

Clean the luminaire

Clean the room

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors tracking them through time

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors tracking them through time

Lamps and Gear

Clean room surfaces :


Clean luminaires :
Group relamp :
MF :

L80 @ 40,000 hours


Clean room surfaces :
Clean luminaires :
Spot replacement
MF :

29

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

6 year
2 year
2 year
0.79

6 year
2 year
0.72

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors

Lamps and Gear


Clean room surfaces :
Clean luminaires :
Group relamp :
MF :

L80 @ 40,000 hours


Clean room surfaces :
Clean luminaires :
Spot replacement
MF :

L70 @ 50,000 hours


Clean room surfaces :
Clean luminaires :
Spot replacement
MF :

30

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

6 year
2 year
2 year
0.79

6 year
2 year
0.72

6 year
2 year
0.69

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors

Lamps and Gear

Building
Type
Clean room surfaces :
Clean luminaires :
Group relamp :
MF :

L80 @ 40,000 hours


Clean room surfaces :
Clean luminaires :
Spot replacement
MF :

L70 @ 50,000 hours


Clean room surfaces :
Clean luminaires :
Spot replacement
MF :

31

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

6 year
2 year
2 year
0.79

6 year
2 year

Installation life
to 100,000 hours
(years)
100,000 / to

Offices

40

Education

50

Hospitals

20

Hotels

20

Restaurants

40

Sports

25

Retail

20

Manufacturing

25

0.72

6 year
2 year
0.69

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors initial lighting levels

Lamps and Gear


Clean room surfaces :
Clean luminaires :
Group relamp :
MF :

L80 @ 40,000 hours


Clean room surfaces :
Clean luminaires :
Spot replacement
MF :

L70 @ 50,000 hours


Clean room surfaces :
Clean luminaires :
Spot replacement
MF :

32

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

6 year
2 year
2 year
0.79

6 year
2 year

Em
Einitial

500 lx
633 lx

Em
Einitial

500 lx
694 lx

Em
Einitial

500 lx
725 lx

0.72

6 year
2 year
0.69

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors effect of room surfaces


Clean room surfaces every 4 years instead of 6 years

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors effect of room surfaces


Clean room surfaces every 4 years instead of 6 years
Lamps and Gear
Clean room surfaces :
Clean luminaires :
Group relamp :
MF :

L80 @ 40,000 hours


Clean room surfaces :
Clean luminaires :
Spot replacement
MF :

L70 @ 50,000 hours


Clean room surfaces :
Clean luminaires :
Spot replacement
MF :

32

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

4 year
2 year
2 year
0.79

4 year
2 year

Em
Einitial

500 lx
633 lx

Em
Einitial

500 lx
694 lx

Em
Einitial

500 lx
725 lx

0.72

4 year
2 year
0.69

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors effect of room surfaces


Clean room surfaces every 4 years instead of 6 years

0.79

0.69

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors effect of room surfaces


Clean room surfaces every 4 years instead of 6 years

0.79

0.79

0.69

0.69

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors effect of room surfaces


Change luminaire type to an indirect solution

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors effect of room surfaces


Clean room surfaces every 6 years (indirect)

0.79 direct

0.74 indirect

0.69 direct

0.65 indirect

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors effect of room surfaces


Clean room surfaces every 4 years instead of 6 years (indirect)

0.74 @6

0.74 @4

0.65 @6

0.65 @4

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors effect of room surfaces


Clean room surfaces every 4 years instead of 6 years

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors


What influence does relamping period have?
Lamps and Gear
Clean room surfaces :
Clean luminaires :

4 year
2 year

Group relamp :

2 year

MF :

0.79

L80 @ 40,000 hours


Clean room surfaces :
Clean luminaires :
Spot replacement
MF :

L70 @ 50,000 hours


Clean room surfaces :
Clean luminaires :
Spot replacement
MF :

32

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

4 year
2 year

Em
Einitial

500 lx
633 lx

Em
Einitial

500 lx
694 lx

Em
Einitial

500 lx
725 lx

0.72

4 year
2 year
0.69

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors


What influence does relamping period have 2 years to 4 years?

0.79 T26@2

0.70 T26@4

0.69

0.69

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors


What influence does relamping period have?
Lamps and Gear
Clean room surfaces :
Clean luminaires :

4 year
2 year

Group relamp :

4 year

MF :

0.70

L80 @ 40,000 hours


Clean room surfaces :
Clean luminaires :
Spot replacement
MF :

L70 @ 50,000 hours


Clean room surfaces :
Clean luminaires :
Spot replacement
MF :

32

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

4 year
2 year

Em
Einitial

500 lx
714 lx

Em
Einitial

500 lx
694 lx

Em
Einitial

500 lx
725 lx

0.72

4 year
2 year
0.69

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors


What influence does lamp technology have T26 to T16?

0.79 T26@2

0.70 T26@4

0.70 T26@4

0.76 T16@4

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors


What influence does luminaire cleaning interval have?

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors


What influence does luminaire cleaning interval have?

0.76 T16@2

0.73 T16@4

0.69 LED@2

0.64 LED@4

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors


COST

Clean room surfaces :


Clean luminaires :
Group relamp :

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

6 year
2 year
4 year

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors


COST

Clean room surfaces :


Clean luminaires :
Group relamp :

~170

~80

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

6 year
4 year
4 year

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors


Reducing installation life from 15 years
4x18W T8
Clean room surfaces :
Clean luminaires :
Group relamp :
Maintenance factor

6 year
4 year
4 year
0.67

Em
Einitial

500 lx
746 lx

4x14W T16
Clean room surfaces :
Clean luminaires :
Group relamp :
Maintenance factor

6 year
4 year
4 year
0.73

Em
Einitial

500 lx
685 lx

6 year
4 year

Em
Einitial

500 lx
781 lx

Em
Einitial

500 lx
746 lx

LED L70@50,000 hrs


Clean room surfaces :
Clean luminaires :
Spot replacement
Maintenance factor

LED L80@40,000 hrs


Clean room surfaces :
Clean luminaires :
Spot replacement
Maintenance factor

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

0.64

6 year
4 year
0.67

Lighting Design - Why Maintenance Factors Matter

Looking at maintenance factors


Reducing installation life from 15 years to 10 years
4x18W T8
Clean room surfaces :
Clean luminaires :
Group relamp :
Maintenance factor

6 year
4 year
4 year
0.67

Em
Einitial

500 lx
746 lx

4x14W T16
Clean room surfaces :
Clean luminaires :
Group relamp :
Maintenance factor

6 year
4 year
4 year
0.73

Em
Einitial

500 lx
685 lx

6 year
4 year

Em
Einitial

500 lx
694 lx

Em
Einitial

500 lx
676 lx

LED L70@50,000 hrs


Clean room surfaces :
Clean luminaires :
Spot replacement
Maintenance factor

LED L80@40,000 hrs


Clean room surfaces :
Clean luminaires :
Spot replacement
Maintenance factor

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

0.72 (0.64@15)

6 year
4 year
0.74 (0.67@15)

Lighting Design - Why Maintenance Factors Matter


Looking at maintenance factors

Cleaning room surfaces more


frequently makes little difference
However changing luminaire
distribution does
Changing the luminaire cleaning
interval has an impact
For conventional sources
changing the lamp life has a large
impact
The lifetime of LED cannot be overextended

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter


Looking at maintenance factors

So for sensible use of modern technology it really comes down to cost


through life

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter


Looking at maintenance factors

If I can reduce maintenance times I can save money luminaire design!

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter


Looking at maintenance factors

Accessibility will have a big


influence on maintenance
costs

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Lighting Design - Why Maintenance Factors Matter

What does a lighting design guarantee?

Modeling
Glare control
Task visibility
Contrast Colour

Safe

Ergonomic
Atmosphere
Ambience
Healthy

Energy Efficient

Integrated
Interesting

Stimulating

Managed
Colourful
Satisfaction

Lighting Design - Why Maintenance Factors Matter Peter Thorns

ZLD

Practical
Effective

Lighting Design - Why Maintenance Factors Matter


What does a lighting design guarantee?

A design without....
-A maintenance factor
-Calculated according to a documented maintenance
schedule
-Presented to the customer as part of the solution
....is a guess!

Lighting Design - Why Maintenance Factors Matter Peter Thorns