Photo 1- HP stage turbine blades showing deposition of Photo 2: This photo shows the deposits in the outlet
solids. This is due to carry over of solids along with end of HP stage. The deposits can be seen over the
blades.
boiler water. This photo is at inlet end.
As we cann see theree is quite a lot of deeposits in the turbinee. Interestinngly there is a cationn
conductivitty meter whhich did noot detect thhe carry ov
ver incidencce. Continuuous carry over
o
can bee
easily deteccted by sodiium test. A deposit anaalysis was reecommendeed by us.
Observation
ns in steam
m drum
Photo 7: Chevron
P
C
sepparator plaaced above turbo Pho
oto 8: Thiss photo is from a diff
fferent plannt
separator allso showed foaming
fo
signss.
showing the maagnetite layerr formed by proper
p
waterr
chemistry mainttenance.
Figure 1: The above is the guideline for tube sample removal for deposit estimation. High heat flux
area, steaming point, change of direction, tubes with more bends are the criteria for selection.
Photo 13- furnace sloped tube sample inside is seen. Photo 14: furnace sloped tubes at another location
also confirmed that there is no on going corrosion.
There was no ongoing corrosion.
Photo 15: Tube at burner level - ribbed tube was found Photo 16: Another tube at burner level - ribbed
to be free from corrosion. The pH of boiler water must tube was found to be free from corrosion. The pH of
boiler water must have been OK during the past few
have been OK during the past few days.
days.
Photo 17: Observation inside by borescope inspection Photo 18: Another tube sample inside view by
borescope inspection revealed that there is no
revealed that there is no ongoing corrosion
ongoing corrosion
The inside tube inspection did not show any pH deviation prior to shutting the unit. However the ring
header inspection door was opened. Some floor tubes were cut and borescope inspection was done to
ensure that there is no choking of orifices at the inlet stubs.
Photo 19- Small amount of dirt is seen at the orifice Photo 20: The ring header was seen with mild
area in one of the sample. However choking is not reddish tint. However this cannot be considered as
seen around the orifice.
pH corrosion.
The SWAS panel parameters were reviewed by us. However detailed data in shorter intervals were
not available for review. It was seen that there was large scale variation in feed water flow. The unit
had a tube failure in LTSH area prior to shut down. High make up water requirement was there.
When there is large variance in feed water flow, there can be disturbance in pH in feed water and
boiler water. The ammonia requirement would have increased. If the dosing rate is not adjusted with
due care, there can be shift in pH in feedwater chemistry.
UNDER DEPOSIT CORROSION FAILURES IN ANOTHER UNIT AT THE SAME PLANT
There had been an incident of condenser tube leakage in another unit in the same plant about 12
months back. There had been under deposit corrosion in the next 2 months leading to hydrogen
cracks in sloped tubes at furnace bottom. Many tubes were changed and boiler was pressure flushed
to get rid of loose deposits which were generated due to low pH situation during the condenser tube
failure.
Nearly 12 months later there had been tube failures at burner level. There were two failures within a
time gap of 15 days. Plant engineers were of the opinion that it is the after effect of the condenser
tube failure which occurred 12 months back. This cannot be true as under deposit corrosion would
occur in few days time.
One of the failed tube was sent to lab. Another failed tube sample was available at the plant. The
photo of the tube inside can be seen below.
Photo 25- Tube showing under deposit corrosion Photo 26: Tube showing the deposits inside.
crack.
Under deposit corrosion occurs quite fast. The lowering of boiler water pH to 7.5 leads to dissolving
of the magnetite layer immediately. The boiler fire should be put off immediately and the unit should
have been flushed out, as the boiler water is contaminated. Failure to do show will lead to
development of sites wherein the under deposit corrosion begins. depending on the boiler water
treatment regime, the tube failure can be due to hydrogen crack or due to caustic corrosion.
A deposit site created 12 months back, would not be failing now. We explained there is fresh deposit
occurring. This can be due to pH deviation. If the deposits contain Iron and phosphate, it can be due
to boiler water pH deviation. If it contains chlorides, it would be due to condenser tube leak. There
were evidences that the boiler water pH may not be properly being maintained. There are two
conductivity meters available at condenser. We recommended that it shall be provided with cation
conductivity columns so that sea water ingress can be identified easily. Transport of corrosion
product from pre boiler system can be identified by SDI test. We had used SDI test elsewhere to
check ACC tube corrosion during start up.
CONCLUSION
Contamination of condensate can occur due to condenser tube leak. Boiler water contamination can
occur due to pH deviation. Condensate contamination can be identified by cation conductivity
monitors. As it is an important parameter, even 2 of 3 logic can be used. Cation conductivity of
saturated steam would reveal foaming situations, caused by low boiler water pH. Low boiler water
pH can occur not only due to condenser tube failure. It can be due improper HP / LP chemical dosing
practice. Deviations in water chemistry can result in SH tube failures / Deposition of solids at the
turbine blades / furnace tube failures. Trending of SWAS parameters need to have proper back up for
analysis. It cannot be stored as averaged parameters.
Fundamental of cation conductivity column
Engineers from our company, Venus energy audit system, conduct annual
inspection of power boilers and process boilers. Boiler problems related to
tube failures, efficiency issues, under capacity problems, vibration problems,
perennial nagging design issues have been resolved by us. We attend to PF
boilers, CFBC and AFBC boilers and grate fired boilers. Our sister concern
Sri Devi Boiler Equipment and Spares meet the customer needs for spare
pressure parts.