Test Package
SKY ORYX JOINT VENTURE
SIGNATURE
DATE
DOCUMENT REVIEW STATUS
Date Description
Prepared
Engr.
Checked
Comm.
Mgr.
QA/Q
C
Approved
Fet.
Eng
Project
Mgr
Mgr.
K.
J.
Rosenbaum Gillen
Second
K.
J.
28-Feb-12
M.Hammodeh
Issue
Rosenbaum Gillen
K.
13-Jun-11 Third Issue M.Hammodeh
B.Titus
Rosenbaum
Fourth
K.
14-Oct-12
Chitti.Babu
B.Titus
Issue
Rosenbaum
000
001
002
003
System:
r.
H.
Atsuta
H.
Atsuta
H.
Atsuta
H.
Atsuta
M.
Horikawa
M.
Horikawa
M.
Horikawa
M.
Horikawa
AHU A1121-003
Building:
OBI:
EKIN:
SOJV
Accepted By:
Siemens
EKIN
OBI
Name:
Name:
Name:
Signed:
Signed:
Signed:
Date:
Date:
Date:
SOJV
Name:
Signed:
Date:
Engineer:
On behalf of:
Signed:
Date:
Engineer:
On behalf of:
Signed:
Date:
Date of Test:
General Description
This is a variable volume cooling air handling unit with Supply fan, Relief fan and
Heat Recovery Wheel. This test document is applicable for the below listed Air
handling units.
No
1.
2.
3.
4.
5.
6.
7.
8.
AHU Reference
AHU-A1121-003
AHU-A1121-004
AHU-A1121-007
AHU-A1121-010
AHU-A1122-003
AHU-A1122-004
AHU-A1122-007
AHU-A1122-010
IFC Reference
A1121-18-M6-M003
A1121-18-M6-M004
A1121-18-M6-M007
A1121-18-M6-M010
A1122-18-M6-M003
A1122-18-M6-M004
A1122-18-M6-M007
A1122-18-M6-M010
DDC Reference
DDC-A1121-003
DDC-A1121-004
DDC-A1121-007+CHP
DDC-A1121-010
DDC-A1122-002
DDC-A1122-004
DDC-A1122-007+CHP
DDC-A1122-010
_____Yes ______No
_____Yes ______No
_____Yes ______No
_____Yes ______No
_____Yes ______No
_____Yes ______No
_____Yes ______No
_____Yes ______No
_____Yes ______No
Witnessed By:
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
11. Outside air damper positioned to minimum outside air _____Yes ______No
12. Cooling coil face damper (D4) is open
_____Yes ______No
_____Yes ______No
_____Yes ______No
______ Hz
_____Yes ______No
______ Hz
_____Yes ______No
_____Pass ______Fail
______ Hrs
______ Hrs
______ Hrs
______KPa
______ KPa
______ %
______ Hz
______LPS
______ %
______ Hz
______LPS
Function Description: Supply fan VFD speed is increased if the supply duct
pressure value is less than setpoint.
Increase the supply duct static pressure setpoint using PXM-20 (HMI)
30. New supply duct static pressure setpoint
______KPa
______ KPa
______LPS
______ %
______ Hz
Witnessed By:
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
______ %
______ %
______ %
______ Hz
______LPS
Supply duct static pressure functional test result according to the function description
_____Pass ______Fail
Function Description: Supply fan VFD speed is decreased if the supply duct
pressure value becomes higher than the setpoint.
Decrease the supply duct static pressure setpoint using PXM-20 (HMI)
40. New supply duct static pressure setpoint
______KPa
______ KPa
______LPS
______ %
______ Hz
______ %
______ %
______ %
______ Hz
______LPS
Supply duct static pressure functional test result according to the function description
_____Pass ______Fail
Supply fan flow control with VAV position
Function Description: Supply fan is modulated to maintain nominal flow at normal
load condition.
Set all the VAV temperature setpoint through PXM-20 to attain the nominal supply fan
flow
50. Current VAV temperature setpoint
______ C
______LPS
______KPa
______KPa
______%
______Hz
Witnessed By:
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
______%
______Hz
______LPS
______LPS
______LPS
Supply fan flow control with VAV position functional test result according to function
description
_____Pass ______Fail
______ C
______LPS
______KPa
______KPa
______%
______Hz
______%
______Hz
______LPS
______LPS
______LPS
Supply fan flow control with VAV position functional test result according to function
description
_____Pass ______Fail
______ PPM
______ PPM
Witnessed By:
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
______LPS
______ %
______ %
______LPS
______ %
______ %
______LPS
Override/ simulate the CO2 sensor feedback above setpoint by PXM-20 (HMI)
81. New CO sensor feedback
______ PPM
______LPS
______ %
______LPS
______ %
______LPS
______ PPM
______LPS
______ %
______LPS
______ %
______LPS
Outside air flow functional test result as per the function description
_____Pass ______Fail
Optimization
Function Description: Duct static pressure setpoint is reset upward or downward in
response to the system VAV terminal damper positions to maintain the most
demanding VAV damper position 90%
93. Current static pressure setpoint
______ KPa
______ KPa
______ LPS
______ %
Witnessed By:
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
Function Description: In partial load condition the static pressure setpoint is reset
(decreases) to modulate the most demanding VAV damper position to 90%
Simulate a condition to maintain all VAV damper position near to minimum value by
increasing the temperature setpoint of each unit to ________ C
97. New static pressure setpoint
______ KPa
______ KPa
______ %
100.
______ LPS
Static pressure optimization functional test result as per the function description
_____Pass ______Fail
Function Description: In full load condition the static pressure setpoint is reset
(increases) to modulate the most demanding VAV damper position to 90%
Simulate a condition to maintain all VAV damper position above 90% by decreasing
the temperature setpoint to ________ C
101.
______ KPa
102.
______ KPa
103.
______ %
104.
______ LPS
Static pressure optimization functional test result as per the function description
_____Pass ______Fail
Relief fan control
Function Description: Relief fan modulates in response to relief air flow sensor to
maintain a constant differential flow between outside air flow and relief air flow.
105.
______ LPS
106.
______ LPS
107.
______ LPS
108.
______ LPS
109.
______ Hz
Relief fan control functional test result as per the function description
_____Pass ______Fail
Witnessed By:
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
Function Description: Relief fan modulates (increased) in response to relief air flow
sensor to maintain a constant differential flow between outside air flow and relief air
flow.
Increase the outside air flow setpoint by PXM-20 (HMI)
110.
______ LPS
111.
______ LPS
112.
______ LPS
113.
______ LPS
114.
______ Hz
Relief fan control functional test result as per the function description
_____Pass ______Fail
Function Description: Relief fan modulates (decreased) in response to relief air
flow sensor to maintain a constant differential flow between outside air flow and relief
air flow.
Decrease the outside air flow setpoint by PXM-20 (HMI)
115.
______ LPS
116.
______ LPS
117.
______ LPS
118.
______ LPS
119.
______ Hz
Relief fan control functional test result as per the function description
_____Pass ______Fail
Cooling Coil Discharge air Temperature Control
Function Description: The two way chilled water valve is modulated in accordance
with the cooling coil discharge air temperature and cooling coil discharge air
temperature set point. The cooling coil discharge temperature is maintained at set
point of ______C (Nominal).
120.
______ C
121.
______ C
122.
______%
123.
______%
Witnessed By:
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
124.
______%
125.
______%
_____Pass ______Fail
Function Description: The two way chilled water valve is modulated to close in
accordance with the cooling coil discharge air temperature and increased cooling coil
discharge air temperature set point. The cooling coil discharge temperature is
maintained at the new setpoint.
Increase cooling coil discharge temperature setpoint to ______ C
126.
______ C
127.
______%
128.
______%
129.
______%
130.
______%
_____Pass ______Fail
Function Description: The two way chilled water valve is modulated to open in
accordance with the cooling coil discharge air temperature and increased cooling coil
discharge air temperature set point. The cooling coil discharge temperature is
maintained at the new setpoint.
Decrease cooling coil discharge temperature setpoint to ______ C
131.
______ C
132.
______%
133.
______%
134.
______%
135.
______%
_____Pass ______Fail
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
Function Description: When the space relative humidity is between 45% and 55%
the CC discharge air temperature set point will be the nominal value.
136.
______ %Rh
137.
______ C
138.
______ C
Function Description: If the space relative humidity exceeds 55%, the cooling coil
discharge air temperature setpoint will automatically adjusted to downward at 0.1
deg C per minute
Relative humidity increased to (Override Rh by PXM-20 (HMI))
139.
______ %
140.
______ C
141.
______ C
______ C
______ %
143.
______ C
144.
______ C
______ C
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
Face and bypass damper is modulated in response with the supply air temperature
and setpoint.
145.
______ C
146.
______ C
147.
______ C
148.
______ C
149.
______ %
150.
______ %
______ C
152.
______ C
153.
154.
______ C
155.
______ %
156.
______ %
Face & bypass damper control functional test result as per the function description.
_____Pass ______Fail
Function Description: If the supply air temperature is below setpoint, bypass
damper modulated to open position and face damper modulates to close position.
Simulate the Space air temperature setpoint below the minimum value through PXM20
157.
______ C
158.
______ C
159.
160.
______ C
161.
______ %
162.
______ %
Witnessed By:
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
Face & bypass damper control functional test result as per the function description.
_____Pass ______Fail
Interlock functions
Supply Fan
Function DescriptionThe Supply fan starts when all the dampers are proven open.
Fail alarm of any damper will shutdown the Supply fan
163.
______%
164.
______ %
165.
______ %
166.
______ %
167.
168.
_______%
____OFF _____ON
______%
170.
______ %
171.
______ %
172.
______ %
173.
174.
______ %
____OFF _____ON
Supply fan interlock functional test result according to the function description
_____Pass ______Fail
Relief fan
Function Description: The Relief fan is interlocked to supply fan status. The Relief
fan will shutdown if supply fan fail is detected.
175.
____OFF _____ON
176.
____OFF _____ON
____OFF _____ON
178.
____OFF _____ON
Relief fan interlock functional test result according to the function description
_____Pass ______Fail
Heat recovery wheel
Witnessed By:
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
Function Description: Heat recovery wheel is interlocked with Supply and Relief fan
Status. If any of them fails Heat recovery wheel disabled.
179.
____OFF _____ON
180.
____OFF _____ON
181.
____OFF _____ON
183.
____OFF _____ON
184.
Heat recovery wheel interlock functional test result according to the function
description
_____Pass ______Fail
186.
_____ON _____OFF
______ %
______ %
Cooling coil valve interlock functional test result according to the function description
_____Pass ______Fail
Function Description: The control valve is interlocked with the face damper open
status. Incase face damper fails the cooling coil temperature control loops will be
disabled and control valve will modulate to close.
188.
189.
_____ON _____OFF
______ %
______ %
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
Cooling coil valve interlock functional test result according to the function description
_____Pass ______Fail
Unoccupied Mode:
Function Description: In unoccupied mode the supply fan willstart after 15 minutes
when any VAV box calls for heating or cooling.
Simulate unoccupied mode by changing the time schedule with PXM20 (HMI)
Simulate heating demand (Override any space temperature value below heating
setback temperature setpoint by PXM-20)
191.
_____Yes ______No
192.
_____Yes ______No
193.
_____Yes ______No
194.
_____Yes ______No
195.
_____Yes ______No
196.
_____Yes ______No
197.
_____Yes ______No
198.
_____Yes ______No
200.
_____Yes ______No
201.
_____Yes ______No
202.
_____Yes ______No
203.
_____Yes ______No
204.
_____Yes ______No
205.
Witnessed By:
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
206.
______ Hrs
208.
______ Hrs
209.
______ Hrs
210.
______Hrs
211.
______Hrs
212.
______Hrs
_____Yes ______No
214.
_____Yes ______No
215.
_____Yes ______No
Maintenance schedule run hours functional test result according to the function
description
_____Pass ______Fail
_____Yes ______No
_____Yes ______No
218.
_____Off ______On
219.
_____Yes ______No
220.
_____Off ______On
Witnessed By:
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
221.
_____Yes ______No
222.
_____Off ______On
223.
_____Yes ______No
224.
_____Yes ______No
225.
_____Yes ______No
226.
_____Yes ______No
227.
_____Yes ______No
228.
_____Yes ______No
ALARMS
FILTERS
The following filter alarm points are checked and verified.
Note: Filters to be blocked to simulate clogged condition or Remove the tube from
the ve side of DPS and suck to create ve pressure
229.
______KPa
230.
_____Normal ______Alarm
231.
_____Normal ______Alarm
_____Pass ______Fail
232.
233.
_____Normal ______Alarm
234.
_____Normal ______Alarm
______KPa
_____Pass ______Fail
235.
236.
_____Normal ______Alarm
237.
_____Normal ______Alarm
______KPa
_____Pass ______Fail
Return Damper
Witnessed By:
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
Function Description: If the damper status is not available according to the damper
command an alarm will generated
238.
_____%
239.
_____%
240.
_____Normal ______Alarm
Remove the feedback cable from the damper actuator or override the feedback
signal through PXM-20 (HMI) below commanded value (Command% 5)
241.
_____%
242.
_____%
243.
_____Normal ______Alarm
Return damper alarm functional test result according to the function description
_____Pass ______Fail
Relief Damper
244.
_____%
245.
_____%
246.
_____Normal ______Alarm
Remove the feedback cable from the damper actuator or override the feedback
signal through PXM-20 (HMI) below commanded value (Command% 5)
247.
_____%
248.
_____%
249.
_____Normal ______Alarm
Relief damper alarm functional test result according to the function description
_____Pass ______Fail
Outside Damper
250.
_____%
251.
_____%
252.
_____Normal ______Alarm
Remove the feedback cable from the damper actuator or override the feedback
signal through PXM-20 (HMI) below commanded value (Command% 5)
253.
_____%
254.
_____%
255.
_____Normal ______Alarm
Witnessed By:
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
Outside damper alarm functional test result according to the function description
_____Pass ______Fail
Cooling coil face damper
256.
_____%
257.
258.
_____%
____Normal ____Alarm
Remove the feedback cable from the damper actuator or override the feedback
signal through PXM-20 (HMI) below commanded value (Command% 5)
259.
_____%
260.
_____%
261.
CC face damper alarm functional test result according to the function description
_____Pass ______Fail
Cooling Coil bypass damper
262.
_____%
263.
_____%
264.
____Normal____Alarm
Remove the feedback cable from the damper actuator or override the feedback
signal through PXM-20 (HMI) below commanded value (Command% 5)
265.
_____%
266.
_____%
267.
_____Pass ______Fail
Supply fan
Witnessed By:
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
Function Description: If the fan status is not available according to the command,
after 60 Sec a fan fail alarm will generated.
Simulate fan fail by removing power to fan
268.
_____Yes ______No
_____Yes ______No
Duct Static Pressure alarm activated when the supply duct pressure
exceeds the high limit (Override static pressure greater than high limit or
reduce the alarm setpoint less than current pressure value)
_____Yes ______No
Duct static pressure alarm functional test result
271.
_____Pass ______Fail
greater than setpoint and relief fan is running in maximum speed (Override
differential flow greater than setpoint and fan command to 100%)
_____Yes ______No
High differential flow alarm functional test result
272.
_____Pass ______Fail
If the outside air flow measured is low when the outside damper is
fully open an alarm is generated (Override flow to minimum value and damper
command to 100%)
_____Yes ______No
_____Pass ______Fail
Witnessed By:
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
273.
If the CO2 level is high even when the outside air flow is maximum; an
alarm is generated (Override CO2 level higher than setpoint and outside air
flow to maximum value)
_____Yes ______No
_____Pass ______Fail
____Normal ___Alarm
275.
____Normal ___Alarm
276.
CC discharge temperature
______ C
____Normal ___Alarm
High temperature alarm functional test result as per the function description
_____Pass ______Fail
Override the temperature below low limit setpoint
278.
____Normal ___Alarm
Low temperature alarm functional test result as per the function description
_____Pass ______Fail
____Normal ___Alarm
280.
____Normal ___Alarm
281.
______ C
____Normal ___Alarm
Witnessed By:
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
High temperature alarm functional test result as per the function description
_____Pass ______Fail
Override the temperature below low limit setpoint
283.
____Normal ___Alarm
Low temperature alarm functional test result as per the function description
_____Pass ______Fail
High space humidity Alarm
Function Description: If the relative humidity exceeds the maximum setpoint, a high
humidity alarm will be generated.
284.
285.
Space Humidity
____Normal ___Alarm
______% Rh
____Normal ___Alarm
High humidity alarm functional test result as per the function description
_____Pass ______Fail
____Normal ___Alarm
288.
____Normal ___Alarm
289.
_____LPS
____Normal ___Alarm
High flow alarm functional test result as per the function description
_____Pass ______Fail
Override the flow below low limit setpoint
291.
____Normal ___Alarm
Witnessed By:
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
Low flow alarm functional test result as per the function description
_____Pass ______Fail
Relief air flow Alarms
Function Description: If the Relief flow exceeds the maximum setpoint, a high flow
alarm will be generated and when relief flow reaches below the minimum setpoint a
low flow alarm will be generated.
292.
____Normal ___Alarm
293.
____Normal ___Alarm
294.
_____LPS
____Normal ___Alarm
High flow alarm functional test result as per the function description
_____Pass ______Fail
____Normal ___Alarm
Low flow alarm functional test result as per the function description
_____Pass ______Fail
Alarms and its effects on operation.
297.
When the damper fail alarm generated during the normal operation
_____Pass ______Fail
When the fan fail alarm generated during the normal operation the
_____Pass ______Fail
When the High duct pressure alarm is activated the supply fan of the
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
_____Pass ______Fail
_____Yes ______No
301.
_____Yes ______No
302.
303.
_____Yes ______No
304.
_____Yes ______No
305.
_____Yes ______No
306.
_____Yes ______No
307.
_____Yes ______No
308.
_____Yes ______No
_____Yes ______No
_____Pass ______Fail
VFD high Current Alarm simulate VFD current high using PXM(HMI)
Normal/Alarm
310.
VFD high power Alarm: simulate VFD low power using PXM(HMI)
Normal/Alarm
311.
_______V
VFD high Voltage alarm simulate VFD high voltage using PXM(HMI)
Normal/Alarm
312.
_______Hz
Witnessed By:
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
VFD low Frequency Alarm: simulate VFD low frequency using PXM(HMI)
Normal/Alarm
VFD high frequency alarm simulate VFD high frequency using PXM(HMI)
Normal/Alarm
313.
Normal/Alarm
_____Hrs (SFRT)
VFD Run hours exceed Alarm simulate VFD run Hours equal to the set value using
PXM(HMI)
Normal/Alarm
315.
Remove VFD communication cable all VFD values are with alarm
Normal/Alarm
316. General Alarm
Remove load from VFD by putting the MCC in bypass mode and enable the VFD
_______Alarm
RF VFD Interface points and Alarms
317.
VFD current
_____Amp (RFAMP)
VFD high Current Alarm simulate VFD current high using PXM(HMI)
Normal/Alarm
318.
_______Kw
VFD low power Alarm: simulate VFD low power using PXM(HMI)
Normal/Alarm
319.
_______V
VFD low Voltage Alarm: simulate VFD low voltage using PXM(HMI)
Normal/Alarm
Witnessed By:
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
320.
_______Hz
VFD low Frequency Alarm: simulate VFD low frequency using PXM(HMI)
Normal/Alarm
321.
_____Hrs (RFRT)
VFD Run hours exceed Alarm simulate VFD run Hours equal to the set value using
PXM(HMI)
Normal/Alarm
323.
Remove VFD communication cable all VFD values are with alarm
Normal/Alarm
324.
Remove load from VFD by putting the MCC in bypass mode and enable the VFD
_______Alarm
Heat Wheel Alarms
325.
REMARKS
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
Witnessed By:
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_____________________________________________________________
Witnessed By:
For:
Name:
Signed:
Date:
Remarks:
Siemens
Ekin
SOJV
OBI