Residential Customers
Business Customers
Investors
Suppliers
About TNB
Business
Home > Business > For Housing Developers & Electrical Contractors > TNB Electricity
For Commercial
For Industrial
Voltages
The transmission voltage networks are 500kV, 275kV and 132kV, whilst the distributi
11kV and 400/230 volts. However, in the case of certain parts of Johor & Perak the dis
also include 22kV and 6.6kV.
Supply Frequency
The supply frequency is 50Hz 1%.
Earthing System
High Voltage and Extra High Voltage
3 phase configuration
Solidly earthed or impedance earthed
Overhead lines and underground cable are used extensively for high and extra
Low Voltage 400/230V
As a guide, the maximum fault levels for the various voltage systems are as follows. A
be installed and connected to TNB supply must comply with the stated short circuit ra
System
500 kV
50 kA
275 kV
40 kA
132 kV
31.5 kA
66 kV
20 kA
33 kV
25 kA
22 kV
20 kA
11 kV
20 kA
6.6 kV
20 kA
400/230 V
31.5 kA
Generally, supplies to domestic premises are given at single phase 2-wire or three ph
actual supply voltage provided depends on the magnitude of the individual applicants
Low Voltage
It should be noted that voltages other than the above classifcations couldnt be provid
consumers can make their own transformation arrangements where necessary.