Sie sind auf Seite 1von 4

LEDway Series

LED Street Light


Includes: STR-LWY-HT, HT-IP

INSTALLATION INSTRUCTIONS

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always be followed including the following:

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

1. To avoid the possibility of electrical shock, turn off power supply before installation or servicing. Installation and servicing
should be performed by qualified personnel.
2. When closing cover of fixture, be sure all wires are inside housing to avoid pinching wires.
3. If NEMA photo control is installed refer to NEMA Receptacle section for instructions.
4. Product must be installed in accordance with NEC or your local electrical code. If you are not familiar with these codes and
requirements, consult a qualified electrician.
5. If mounting bolts are completely removed in the field they should be hand threaded (prior to use of power tools) to ensure
proper engagement of the thread when re-installing. Failure to pre-start threads may result in cross-threading or stripping of
the bolts during reinstallation.

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE


TO INSTALL:

Pole

Heatsink

STANDARD MOUNTING

STEP 1:
DO NOT remove splashguard from fixture. If
mounting fixture to 1.25 IP pipe (1.66 O.D.),
there is no need to modify the splashguard. If
mounting fixture onto 2.0 IP pipe (2.38 O.D.),
remove the knockout of the splashguard
thru the rear opening of the fixture while the
fixture is closed. See Figure 2.

Pipe Perimeter (IP66 Only)


Sealing Gasket/Plate

Mounting Clamp
Bracket
Mounting Clamp (2)
See Table 1
Cover in Open
Position

OR

STEP 2:

Driver
Splashguard

Cover in Open
Position
Fitter Pipe end

To open cover, hold fixture by heat sink


with the light bars facing down and hinges
facing away. Simultaneously pull latches
and the cover to swing open. Splashguard
may dislodge from fixture, but should be
repositioned once ready to mount. See Figure
1.

STEP 3:
3rd Stop Boss
2nd Stop Boss
Final Stop Boss
Terminal Block

TABLE 1
TORQUE VALUES
Pipe
Size

1.66 in O.D.

2.38 in O.D.

1 of 4

STEP 4:
To level fixture, use bubble level located
inside housing. Adjust leveling of fixture from
side to side. To level from front to back, slide
pole to different step in upper housing. Each
step changes the angle in 2.5 increments.
See Figure 3.

STEP 5:

Bolt Torque
Required (in-lbs)

Bolt Torque
Required (N-m)

+5.0 degrees tilt

200

22

+2.5 degrees tilt

200

22

0 degrees (no tilt)

200

22

-2.5 degrees tilt

200

22

-5.0 degrees tilt

200

22

+5.0 degrees tilt

200

22

+2.5 degrees tilt

200

22

0 degrees (no tilt)

200

22

-2.5 degrees tilt

200

22

-5.0 degrees tilt

200

22

Pipe Position

Slide fixture on to pole through opening on


the rear of housing and through splashguard.

Once desired position is achieved, tighten


(2) mounting bolts to the appropriate torque
values specified in TABLE 1. See Figure 1 (use
9/16" wrench socket).
IMPORTANT - DO NOT exceed these
torque levels on the mount bolts. Exceeding
recommended torque value resulting in
excessive deformation of mounting bracket
will cause stripping of mount hardware which
could lead to an unsafe mounting condition.

STEP 6:
Reference Electrical Connections section
for completing electrical connections.
LPN00216X0001A0

STANDARD MOUNTING - IP66 WEATHER SEALED

NOTE: Follow step instructions described in the Standard


Mounting section, disregarding the splashguard, and
following these additional steps:

STEP 1:
Before sliding fixture on pipe, pull supply wires and ground
wire (if necessary) from pipe thru small sealed holes in
sealing grommet. See Figure 4.

STEP 2:
Slide sealing grommet onto end of pipe. See Figure 4.

STEP 3:
NEMA RECEPTACLE (OPTIONAL)

Fully seat the sealing grommet by forcing the compression


cap over the sealing grommet, until fully engaged. (This
may require slight lubrication) See Figure 4.

STEP 1:

STEP 4:

DO NOT loosen/tighten flat head screws for the NEMA


receptacle.

STEP 2:
Rotational adjustment of the photo control is tool-less.

STEP 3:
Engage/install photo control into NEMA receptacle on top of
the fixture.

STEP 4:

Carefully, slide fixture onto pipe thru the opening on the


rear of the housing and thru pipe perimeter sealing gasket/
plate.

STEP 5:
This fixture is designed for mounting to 2.38" O.D. pipe.
If your application requires 1.66" O.D. pipe, the Sealing
Grommet and Compression Cap provided in the fixture will
need to be replaced with the 1.66" O.D. parts (parts sold
separately, Cat. No. XAXIL125IP). See Figure 4.

Firmly rotate photo-control with its photo-eye approximately


in the N north direction. Some photo-controls operate best
somewhere between NW and NE.

ELECTRICAL CONNECTIONS
PHASE TO NEUTRAL WIRING

ELECTRICAL CONNECTIONS
PHASE TO NEUTRAL WIRING

STEP 1:

STEP 1:

Make the following Electrical Connections:

Make the following Electrical Connections:


a. Connect supply ground conductor to green wire
position of the terminal block within the LED Driver
Enclosure.
b. Connect supply voltage conductor to black wire
position of the terminal block within the LED Driver
Enclosure.
c. Connect supply neutral conductor to the white wire
position of the terminal block within the LED Driver
Enclosure.

a. Connect supply ground conductor to green wire


position of the terminal block within the LED Driver
Enclosure.
b. Connect supply L1 (Hot) conductor to black wire
position of the terminal block within the LED Driver
Enclosure.
c. Connect supply L2 (Hot) conductor to the white wire
position of the terminal block within the LED Driver
Enclosure.

STEP 2:

STEP 2:

Push excess supply wires into pole.

Push excess supply wires into pole.

STEP 3:

STEP 3:

Close cover by firmly pushing cover towards fixture, making


sure that no wires are pinched and latches are fully engaged.

Close cover by firmly pushing cover towards fixture, making


sure that no wires are pinched and latches are fully engaged.

STEP 4:

STEP 4:

Insulate all electrical connections with wire nuts suitable for at


least 90C

LINE
OR LINE 1

GROUND-GREEN

LINE-BLACK
LINE-BLACK

LINE (L2)

208, 240, 480V

NEUTRAL-WHITE
COMMON-WHITE

SUPPLY WIRING

GREEN

TERMINAL BLOCK

GROUND

LINE (L1)

FIXTURE WIRING

COMMON-WHITE

GROUND-GREEN

LINE-BLACK

LED DRIVER(S)

2 of 4

NEUTRAL
OR LINE 2

FIXTURE WIRING

LED DRIVER(S)

SUPPLY WIRING

TERMINAL BLOCK

Insulate all electrical connections with wire nuts suitable for at


least 90C

LPN00216X0001A0

ADJUSTING LIGHT OUTPUT

DRIVER WIRED FOR 525mA (STANDARD)

DRIVER 1
GRAY

VIOLET

WHITE

BLUE

BLACK

RED

RED

ORANGE 350mA
YELLOW 525mA
GRAY

DRIVER 2

WHITE

BLUE

BLACK

RED

RED

LED DRIVER INPUT

For more or less light output, follow the


instructions below.

LED LIGHT BAR(S)

BLUE 700mA

VIOLET

GRAY

BLACK

TRI-TAP
MODULE

LED LIGHT BAR(S)

BLACK

NOTE: It is possible to switch the fixture in the


field to obtain less or more light output. The
fixture leaves the factory with the LED driver(s)
wired at one of the following:
350mA = -UH (Figure 6)
525mA = -U, -UC (Figure 5)
700mA = -UD (Figure 7)

TO SWITCH FROM 525mA TO 350mA


STEP 1:
Locate the lever nut containing the violet lead(s)
from the Driver(s) and the yellow lead from the
Tri-Tap Module.

LED DRIVER OUTPUT

STEP 2:
Remove the yellow wire by lifting the orange
lever.

STEP 3:
Locate the lever nut containing the orange wire
from the Tri-Tap Module and remove the wire by
lifting the orange lever.

DRIVER WIRED FOR 350mA (LESS LIGHT OUTPUT)

VIOLET

DRIVER 1

WHITE

BLUE

BLACK

RED

RED

GRAY

ORANGE 350mA
YELLOW 525mA
GRAY

DRIVER 2

WHITE

BLUE 700mA

BLUE

BLACK

RED

RED

LED DRIVER INPUT

LED LIGHT BAR(S)

VIOLET

GRAY

BLACK

TRI-TAP
MODULE

LED LIGHT BAR(S)

BLACK

LED DRIVER OUTPUT

STEP 4:
Place the orange wire into the lever nut
containing the violet lead(s) from the Driver(s)
and snap down the orange lever to secure.

STEP 5:
Place the yellow lead from the Tri-Tap Module
in to the empty lever nut and snap down the
orange lever to secure.

TO SWITCH FROM 525mA TO 700mA


STEP 1:
Locate the lever nut containing the violet lead(s)
from the Driver(s) and the yellow lead from the
Tri-Tap Module.

STEP 2:
Remove the yellow wire by lifting the orange
lever.

STEP 3:

DRIVER WIRED FOR 700mA (MORE LIGHT OUTPUT)

DRIVER 1
GRAY

VIOLET

WHITE

BLUE

BLACK

RED

RED

ORANGE 350mA
YELLOW 525mA
GRAY

WHITE

LED DRIVER INPUT

3 of 4

BLUE

BLACK

RED

RED

LED LIGHT BAR(S)

DRIVER 2

BLUE 700mA

VIOLET

GRAY

BLACK

TRI-TAP
MODULE

LED LIGHT BAR(S)

BLACK

LED DRIVER OUTPUT

Locate the lever nut containing the blue wire


from the Tri-Tap Module and remove the wire by
lifting the orange lever.

STEP 4:
Place the blue wire into the lever nut containing
the violet lead(s) from the Driver(s) and snap
down the orange lever to secure.

STEP 5:
Place the yellow lead from the Tri-Tap Module
in to the empty lever nut and snap down the
orange lever to secure.
CAUTION - By switching the LED fixture to have
more light output, the fixture will have also have
a greater amp draw. Refer to fixture label for the
amp draw at 700 mA.

LPN00216X0001A0

TWO LEVEL REMOTE SENSOR OPTION (G OPTION)


STEP 1:

LOW MODE:

Never open or disconnect the neutral when voltage is applied to


L1 or L2 conductors.

STEP 2:
If wiring fixture to a phase to phase (typically 208/240/480V)
circuit, make sure that the neutral jumper is removed. See Figure
9 or 11.

STEP 3:
Fixture may be operated at low mode (175 mA), standard mode
(350 mA) or high mode (525 mA). NOTE: High mode is not
applicable for 140-240 LED Luminaires.

STEP 4:
How Multi-Level LED products work: Drive currents determine
the light output of the LEDs. By applying voltage to the
luminaires supply conductors, different light levels can be
achieved. Line 1 and Line 2 can be switched on and off separately
using a manual switch or other automated device supplied by
the customer.

HG or CG Option LEDs run at 175 mA


DG Option LEDs run at 350mA
Low mode is achieved when voltage is applied to Line 1
(L1) and Line 2 (L2) is de-energized.

NORMAL MODE:
CG Option LEDs run at 350mA
Normal mode is achieved when voltage is applied to Line 2
(L2) and Line 1 (L1) is de-energized.

HIGH MODE:



HG Option LEDs run at 350mA


CG Option LEDs run at 525 mA
DG Option LEDs run at 700mA
High mode is achieved when voltage is applied to both
Line 1 (L1) and Line 2 (L2).
Driver Current
Output

Option

Mode

Line 1

Line 2

HG or CG

Low

ON

OFF

175mA

DG

Low

ON

OFF

350mA

NOTE: See the luminaires label to verify the following Remote


Sensor Options:
HG Option = 175/350mA
CG Option = 175/350/525mA
DG Option = 350/700mA

CG

Normal

OFF

ON

350mA

HG

High

ON

ON

350mA

CG

High

ON

ON

525mA

DG

High

ON

ON

700mA

REMOTE SENSOR OPTION WIRING


Wire fixture based on the available electrical circuit. See diagrams below: Figure 8 or 9 for fixtures with terminal block and
Figure 10 or 11 for fixtures without a terminal block.
L1 or L2 leads from fixture can be connected to the same phase or different phases.
L1 or L2 leads can be switched together or independently depending on the applications requirements.
IMPORTANT - On phase to phase circuits remove neutral jumper. See Figure 9 or 11.

10

PHASE TO NEUTRAL

* Switch or
Sensor

* Neutral

NEUTRAL

TERMINAL BLOCK

120V,277V
or 347V

LINE (175 mA)


COMMON (WHITE)

LINE (350 mA) +


COMMON (WHITE)

175mA
LED
DRIVER
OUTPUT

LINE (175 mA)

350mA +
LED
DRIVER
OUTPUT

Sensor

LINE

LED FIXTURE

Sensor

Ground

LED FIXTURE

* Switch or

* Switch or
LINE

PHASE TO NEUTRAL

COMMON
R

R O
VE T
LE NEC
N

CO

120V,277V
or 347V

(White or Orange)

LINE (350 mA) +

* Switch or
Sensor

COMMON
(White or Orange)
R

R O
VE T
LE NEC
N

NEUTRAL

175mA
LED
DRIVER
OUTPUT

350mA +
LED
DRIVER
OUTPUT

CO

Jumper

GROUND

+ 140-240 LED LUMINAIRES LINE 2 (175MA)


* SWITCH OR SENSOR SUPPLIED BY CUSTOMER

Lead Located in Housing

+ 140-240 LED LUMINAIRES LINE 2 (175MA)

* SWITCH OR SENSOR SUPPLIED BY CUSTOMER

PHASE TO PHASE
* Switch or

11

208/240/480V

* Switch or

LINE
NEUTRAL
Ground

Sensor

LINE
NEUTRAL

TERMINAL BLOCK

LINE (175 mA)


COMMON (WHITE)

LINE (350 mA) +


COMMON (WHITE)

175mA
LED
DRIVER
OUTPUT

350mA +
LED
DRIVER
OUTPUT

Sensor

LED FIXTURE

Sensor

* Switch or

PHASE TO PHASE

COMMON
R

R O
VE T
LE NEC
N
CO

NEUTRAL

* Switch or

(White or Orange)

LINE (350 mA) +

Sensor

LINE

COMMON
(White or Orange)

NEUTRAL

R O
VE T
LE NEC
N

350mA +
LED
DRIVER
OUTPUT

CO

Neutral Jumper

+ 140-240 LED LUMINAIRES LINE 2 (175MA)


* SWITCH OR SENSOR SUPPLIED BY CUSTOMER
** IMPORTANT - REMOVE NEUTRAL JUMPER WHEN CIRCUIT IS PHASE TO PHASE

175mA
LED
DRIVER
OUTPUT

LINE (175 mA)

LINE

** Remove
208/240/480V

LED FIXTURE

208/240/480V

GROUND

** Remove

Neutral Jumper

Lead Located in Housing

+ 140-240 LED LUMINAIRES LINE 2 (175MA)


* SWITCH OR SENSOR SUPPLIED BY CUSTOMER
** IMPORTANT - REMOVE NEUTRAL JUMPER WHEN CIRCUIT IS PHASE TO PHASE

2013 Cree, Inc. All rights reserved. For informational purposes only. Content is subject to change. See
www.cree.com/lighting/products/warranty for warranty and specifications. Cree, the Cree logo, and
LEDway are registered trademarks.

www.cree.com/lighting
4 of 4