Sie sind auf Seite 1von 2

FEATURES OF CCI THYRISTORS

1
2

Operating Temperature (needed for


derating calculation)
Incoming & Outgiong connections

Rated Voltage

Rated Current

Inbuilt Fan

Accuracy

Display

upto 50C
Top - Bottom
24-600V (with Auto Detecting Facility which
provides a protection in case of manual error
in connections)
up to 1200A
upto 50A - Natural Convection,
Cooling Fan per Zone
0.1%

>80A One

b) Type

Can be fixed along with the unit or same


display can be mounted in the front panel
LCD-Two Row Display

c) Protection

IP-65, also rated uL Type-I

Communication

Certification

RS-485 MODBUS, Profibus & Profinet for linking


with SIEMENS PLC, Ethernet IP for linking with
AB PLC, Devicenet, MODBUS TCP/IP
uL, CE, RoHS, Pb

10

Fuses

11

Analog Outputs

12

Isolation

13

Peak Voltage Ratings

14

Transguard

a) Position

ZCT (Zero-Cross Transformer) Mode


15

16

SYNC-GUARD

Fast Acting Semiconductor Fuses with Holder


to be fixed externally which allows easy
replacement in future.
2nos for each channel may be assigned either
the RMS or AVG value of the load voltage,
load current, or true instantaneous load power
Signal to Line/Load 3750 Vac minimum,
Line/Load to Ground 2500 Vac minimum,
Signal to Ground 1500 Vac minimum, USB
2500 Vac minimum, Remote Display 2500 Vac
are provided as minimum
1600 V for Peak Forward & Reverse
A special feature eliminates a DC component
that can exist with zero-cross operation.
Elimination of this DC component prevents
saturation and overheating of the upstream
supply transformers. TRANS-GUARD is a
standard feature on all zero-cross controllers.
There is no setup required
A proprietary algorithm that uses hybrid
control to avoid the excessive inrush currents
that can occur when firing into inductive or
variable resistive loads.
The SYNC-GUARD feature reduces the
possibility of synchronous operation of two or
more zero cross controllers. This feature,
available on some zero-cross controllers
produced by Control Concepts, reduces the
possibility of synchronous operation of two or
more controllers. It reduces the variations in
power demand resulting in a more stable
supply voltage and improved power factor. .
The SYNC-GUARD feature can significantly
reduce the peak current required from a
source that is connected to multiple power
controllers while all are zero cross firing.

17

DC Power Controllers

Power Controllers of rating 40-1500A DC is


available
This method provides superior transient
immunity and electrical isolation better than
pulse transformers which are generally used
in thyristors.
Provided to trigger the Thyristors accurately

18

Optically Coupled SCR Gate Drives

19

Phase Lock Loop

20

USB Connectivity

Easy Setup is possible via USB port,Using


this configuration files can be copied easily.

21

Short Circuit Current Rating

22

MTBF(Mean Time Between Failure)

Type Tested and Certified for 100kA short


circuit rating. This also meets theUL508A and
NFPA requirements.
Designed for 50,000 hrs

23

Relay Outputs for better alarm conditions.

Yes- Over Temperature, SCR Failure, Over


current tripping, etc through 250 V AC 5A relay
contacts etc

Das könnte Ihnen auch gefallen