87B1-A

Low Impedance
differential relay
Contractor N

P741

F/O

Salwa L11

Reactor XL1

Salwa L12

Reactor XL2

BUS 4A2

GCCIA-3-A/SIL-34-D-200

33kV

P742

P742

33kV

P742

00
GCCIA N GCCIA-C8-2010-48-0200-0034

P742

00

87B2-A
Low Impedance
differential relay

P742

F/O

Shuweihat L13

Shuweihat L14

Page 2-2

87B1-A
Low Impedance
differential relay

P741

BUS 4B2

P742

Salwa L11
Contractor N

87B1-B
P142
High
Impedance
differential relay

Reactor XL1

Salwa L12

Reactor XL2

BUS 4A2

GCCIA-3-A/SIL-34-D-200

33kV

33kV

00
GCCIA N GCCIA-C8-2010-48-0200-0034

87B2-B
High
Impedance
differential relay

P142
Shuweihat L13

Shuweihat L14

Page 2-3

87B1-B
High Impedance
differential relay

00

BUS 4B2

Salwa L11

Reactor XL1

Salwa L12

Reactor XL2

Contractor N

BUS 4A2

GCCIA-3-A/SIL-34-D-200

TEE
High Impedance
differential relay

P142
33kV

33kV

00
GCCIA N GCCIA-C8-2010-48-0200-0034

To Remote end
trip via DTT

00

BUS 4B2
Shuweihat L14

Page 2-4

TEE1
High Impedance
differential relay

Shuweihat L13

Salwa L11

Reactor XL1

Salwa L12

Reactor XL2

Contractor N

GCCIA-3-A/SIL-34-D-200

POR communication
scheme (1)

BUS 4A2

33kV

33kV

P443
21A/67NA
Distance Relay
DEF
Stub bus

00
GCCIA N GCCIA-C8-2010-48-0200-0034

In case line
isolator opened,
MiCOM P443 is
converted to
overcurrent relay.
(stub bus
protection)

00

BUS 4B2

Page 2-5

(1)
POR : Permissive Over reach
(Tlaction sent for Z2 fault)

Shuweihat L14

21A/67NA
Distance Relay
DEF
Stub bus

Shuweihat L13

Communication
(single channel)

Contractor N

GCCIA-3-A/SIL-34-D-200

(1)
Back up distance function
automatically set in operation
in case of line differential
communication failure
Only Zone 1 is used :
Z1 : 70% of the line
No teleaction
No reverse zone
Internal VT supervision block
Power swing block

(3)

Salwa L11

Reactor XL1

Salwa L12

Reactor XL2

BUS 4A2

P544
87LB/
21 BU
67 BU
Line diff. relay
Back up distance (1)
Back up overcurrent (2)

33kV

33kV

00
GCCIA N GCCIA-C8-2010-48-0200-0034

(2)
Back up directional
overcurrent function
automatically set in
operation in case of line
differential
communication failure
Inverse time overcurrent
See appendix 7-3
(3)
Intertrip signal via
communication channel of
MiCOM P544

00

BUS 4B2
Shuweihat L14

Page 2-6

87LB/
21BU/
50BU
Line diff. relay

Shuweihat L13

Salwa L11
Contractor N

27/59
Over and
under
voltage

Reactor XL1

Salwa L12

Reactor XL2

BUS 4A2
P141

GCCIA-3-A/SIL-34-D-200

33kV

33kV

GCCIA N GCCIA-C8-2010-48-0200-0034

Intertripping
remote end
(1)

00
00

BUS 4B2

Page 2-7

(1)
Tripping from function 59(over voltage) only
No tripping from function 27 (under voltage)

27/59
Over and under
voltage

Shuweihat L14

Shuweihat L13

Salwa L11

Reactor XL1

Salwa L12

Reactor XL2

Contractor N

BUS 4A2
87RA
High Impedance
differential relay

GCCIA-3-A/SIL-34-D-200

Protected
zone

P142
33kV

00

33kV SST.
breaker Trip

33kV

Trip

GCCIA N GCCIA-C8-2010-48-0200-0034

00

BUS 4B2
Shuweihat L14

Page 2-8

87RA
High Impedance
differential relay

Shuweihat L13

Salwa L11

Salwa L12

Reactor XL1

Reactor XL2

Contractor N

BUS 4A2
87RB
High Impedance
differential relay

GCCIA-3-A/SIL-34-D-200

P132
33kV

Trip

33kV

Protected
zone

00

33kV SST
breaker Trip

GCCIA N GCCIA-C8-2010-48-0200-0034

00

BUS 4B2
Shuweihat L14

Page 2-9

87RB
High Impedance
differential relay

Shuweihat L13

Salwa L11

Reactor XL1

Salwa L12

Reactor XL2

Contractor N

BUS 4A2

GCCIA-3-A/SIL-34-D-200

50/51R
Non directional
Phase O/C
50/51NR
Non Directional
Earth Fault

33kV

33kV

P141
Trip

00

33kV SST
breaker Trip

GCCIA N GCCIA-C8-2010-48-0200-0034

00

BUS 4B2

Page 2-10

50/51R
Non directional
Phase O/C

Shuweihat L14

50/51NR
Non Directional
Earth Fault

Shuweihat L13

Salwa L11
Contractor N

BUS 4A2

Reactor XL1

Salwa L12

Reactor XL2

50RN
Earth Fault

P141

GCCIA-3-A/SIL-34-D-200

Trip

33kV

33kV

Alarm to
DCS
33kV SST
breaker Trip

00
GCCIA N GCCIA-C8-2010-48-0200-0034

00

BUS 4B2
Shuweihat L14

Page 2-11

50AL
Earth Fault

Shuweihat L13

BUS 4A2
Contractor N

GCCIA-3-A/SIL-34-D-200

00

P142

BUS 4B2
00

Intertripping
remote end

GCCIA N GCCIA-C8-2010-48-0200-0034

TEE1
High
Impedance
differential
relay

Page 2-12

TEE1
High Impedance
differential relay

Shuweihat L14
Shuweihat L13

33kV
33kV

Reactor XL2
Salwa L12
Reactor XL1
Salwa L11

BUS 4A2
Contractor N

GCCIA-3-A/SIL-34-D-200

00

P633

BUS 4B2
00

Intertripping
remote end

GCCIA N GCCIA-C8-2010-48-0200-0034

TEE2
Low
Impedance
differential
relay

Page 2-13

TEE1
High Impedance
differential relay

Shuweihat L14
Shuweihat L13

33kV
33kV

Reactor XL2
Salwa L12
Reactor XL1
Salwa L11

Salwa L11

Reactor XL1

Salwa L12

Reactor XL2

Contractor N

BUS 4A2

GCCIA-3-A/SIL-34-D-200

33kV

33kV

00

7SD522

Communication

7SA522
Communication

GCCIA N GCCIA-C8-2010-48-0200-0034

Line diff.
relay

Line Dist
relay

00

BUS 4B2
Shuweihat L14

Page 2-14

HVDC Line
diff. relay

Shuweihat L13

Salwa L11

Reactor XL1

Salwa L12

Reactor XL2

Contractor N

BUS 4A2

GCCIA-3-A/SIL-34-D-200

33kV

33kV

00

P132
Alarm

32F (2)
Active
power
relay
Forward

P132

00

BUS 4B2

Page 2-15

Applicable for any feeder interfaced with utility

Shuweihat L14
(1) 32R Export Power (from utility toward GCCIA)
(2) 32F Import Power (from GCCIA toward utility)
(3) At Al Fadhili : 32F alarm only

32R
Active power relay
Reverse

Shuweihat L13

32F
Active power relay
Forward

Intertripping
remote end

GCCIA N GCCIA-C8-2010-48-0200-0034

32R (1)
Active
power
relay
Reverse

Salwa L11

Salwa L12

Reactor XL1

Reactor XL2

Contractor N

BUS 4A2
bus VT

bus VT

GCCIA-3-A/SIL-34-D-200

P841
Close

P841
33kV

Close

line VT

line VT

line VT

00
GCCIA N GCCIA-C8-2010-48-0200-0034

Important note : the


Voltage control function is
used to check In case of 3p
autoreclose sequence only

P841
Close

line VT

line VT

line VT

79/25
Autorecloser
Voltage control

line VT

P841

P841

Close

Close

line VT

line VT

line VT

P841

P841

Close

Close

bus VT

33kV

bus VT

00

BUS 4B2
Shuweihat L14

Page 2-16

79/25
Autorecloser
Voltage control

Shuweihat L13

Salwa L11
Contractor N

BUS 4A2

Bus VT
25A/25SC
Synchronizer

GCCIA-3-A/SIL-34-D-200

Close

33kV
line VT

line VT

Reactor XL2
line VT
25A/25SC
Synchronizer

7VE61

7VE61

Close

Close

33kV

line VT

line VT

line VT

line VT

00
GCCIA N GCCIA-C8-2010-48-0200-0034

25A/25SC
Synchronizer

25A/25SC
Synchronizer

7VE61

7VE61

7VE61

Close

Close

Close

25A/25SC
Synchronizer

line VT

line VT

line VT

line VT

25A/25SC
Synchronizer

-Voltage rise or decrease


signal sent to BCU
-Frequency rise or
decrease signal sent to
BCU
-Signal Synchro in
progress sent to ICC

Bus VT
25SC
Synchro check

7VE61

Important note :
used to check Live Bus
Live line conditions. In case
of manual close from BCU
only when BCU not able to
give directly the
authorization for closing
- initiation of MX3EG is
received from BCU
-if conditions are OK :
Breaker closing given by
7VE61
-if conditions are not OK :

Salwa L12

Reactor XL1

Bus VT

Bus VT

25A/25SC
Synchronizer

7VE61

7VE61

Close

Close

Bus VT

25SC
Synchro check

7VE61
Close

Bus VT
line VT

00

BUS 4B2

Page 2-17

(1)
Relays installed in the panels with
inputs connected but close command
not connected

25A
Synchronizer

Shuweihat L14

Shuweihat L13

Salwa L11

Salwa L12

Reactor XL1

Reactor XL2

Contractor N

BUS 4A2
1st stage
(Retrip)

GCCIA-3-A/SIL-34-D-200

50/62
Breaker
Failure
Note : retrip is sent
to the two trip coils

P841

2nd
stage
trip

00

Tripping of adjacent
breakers through P740
bus bar protection
tripping circuit and P142
protection tripping
circuit

33kV

2nd
stage
trip

2nd
stage
trip

33kV

Intertripping to
remote end

GCCIA N GCCIA-C8-2010-48-0200-0034

2nd stage
trip

2nd
stage
trip

00

BUS 4B2
Shuweihat L14

Page 2-18

50/62
Breaker
Failure

Shuweihat L13

Salwa L11

Reactor XL1

Salwa L12

Reactor XL2

Contractor N

BUS 4A2

GCCIA-3-A/SIL-34-D-200

2nd stage
trip

Note : retrip is sent


to the two trip coils

00

50/62
Breaker
Failure

33kV

33kV

P841

GCCIA N GCCIA-C8-2010-48-0200-0034

1st stage
(Retrip)

Intertripping
remote end
2nd
stage
trip

00

BUS 4B2
Shuweihat L14

Page 2-19

50/62
Breaker
Failure

Shuweihat L13

Salwa L11

Salwa L12

Reactor XL1

Reactor XL2

Contractor N

BUS 4A2

GCCIA-3-A/SIL-34-D-200

33kV

33kV

Note : retrip is
sent to the two
trip coils

00

2nd
stage
trip

GCCIA N GCCIA-C8-2010-48-0200-0034

50/62
Breaker
Failure

P841

Tripping of adjacent
breakers through P740
bus bar protection
tripping circuit and P122
protection tripping
circuit

2nd
stage
trip

1st stage
(Retrip)

2nd
stage
trip

2nd
stage
trip

00

BUS 4B2
Shuweihat L14

Page 2-20

50/62
Breaker
Failure

Shuweihat L13