Beruflich Dokumente
Kultur Dokumente
Low Impedance
differential relay
Contractor N
P741
F/O
Salwa L11
Reactor XL1
Salwa L12
Reactor XL2
BUS 4A2
GCCIA-3-A/SIL-34-D-200
33kV
P742
P742
33kV
P742
00
GCCIA N GCCIA-C8-2010-48-0200-0034
P742
00
87B2-A
Low Impedance
differential relay
P742
F/O
Shuweihat L13
Shuweihat L14
Page 2-2
87B1-A
Low Impedance
differential relay
P741
BUS 4B2
P742
Salwa L11
Contractor N
87B1-B
P142
High
Impedance
differential relay
Reactor XL1
Salwa L12
Reactor XL2
BUS 4A2
GCCIA-3-A/SIL-34-D-200
33kV
33kV
00
GCCIA N GCCIA-C8-2010-48-0200-0034
87B2-B
High
Impedance
differential relay
P142
Shuweihat L13
Shuweihat L14
Page 2-3
87B1-B
High Impedance
differential relay
00
BUS 4B2
Salwa L11
Reactor XL1
Salwa L12
Reactor XL2
Contractor N
BUS 4A2
GCCIA-3-A/SIL-34-D-200
TEE
High Impedance
differential relay
P142
33kV
33kV
00
GCCIA N GCCIA-C8-2010-48-0200-0034
To Remote end
trip via DTT
00
BUS 4B2
Shuweihat L14
Page 2-4
TEE1
High Impedance
differential relay
Shuweihat L13
Salwa L11
Reactor XL1
Salwa L12
Reactor XL2
Contractor N
GCCIA-3-A/SIL-34-D-200
POR communication
scheme (1)
BUS 4A2
33kV
33kV
P443
21A/67NA
Distance Relay
DEF
Stub bus
00
GCCIA N GCCIA-C8-2010-48-0200-0034
In case line
isolator opened,
MiCOM P443 is
converted to
overcurrent relay.
(stub bus
protection)
00
BUS 4B2
Page 2-5
(1)
POR : Permissive Over reach
(Tlaction sent for Z2 fault)
Shuweihat L14
21A/67NA
Distance Relay
DEF
Stub bus
Shuweihat L13
Communication
(single channel)
Contractor N
GCCIA-3-A/SIL-34-D-200
(1)
Back up distance function
automatically set in operation
in case of line differential
communication failure
Only Zone 1 is used :
Z1 : 70% of the line
No teleaction
No reverse zone
Internal VT supervision block
Power swing block
(3)
Salwa L11
Reactor XL1
Salwa L12
Reactor XL2
BUS 4A2
P544
87LB/
21 BU
67 BU
Line diff. relay
Back up distance (1)
Back up overcurrent (2)
33kV
33kV
00
GCCIA N GCCIA-C8-2010-48-0200-0034
(2)
Back up directional
overcurrent function
automatically set in
operation in case of line
differential
communication failure
Inverse time overcurrent
See appendix 7-3
(3)
Intertrip signal via
communication channel of
MiCOM P544
00
BUS 4B2
Shuweihat L14
Page 2-6
87LB/
21BU/
50BU
Line diff. relay
Shuweihat L13
Salwa L11
Contractor N
27/59
Over and
under
voltage
Reactor XL1
Salwa L12
Reactor XL2
BUS 4A2
P141
GCCIA-3-A/SIL-34-D-200
33kV
33kV
GCCIA N GCCIA-C8-2010-48-0200-0034
Intertripping
remote end
(1)
00
00
BUS 4B2
Page 2-7
(1)
Tripping from function 59(over voltage) only
No tripping from function 27 (under voltage)
27/59
Over and under
voltage
Shuweihat L14
Shuweihat L13
Salwa L11
Reactor XL1
Salwa L12
Reactor XL2
Contractor N
BUS 4A2
87RA
High Impedance
differential relay
GCCIA-3-A/SIL-34-D-200
Protected
zone
P142
33kV
00
33kV SST.
breaker Trip
33kV
Trip
GCCIA N GCCIA-C8-2010-48-0200-0034
00
BUS 4B2
Shuweihat L14
Page 2-8
87RA
High Impedance
differential relay
Shuweihat L13
Salwa L11
Salwa L12
Reactor XL1
Reactor XL2
Contractor N
BUS 4A2
87RB
High Impedance
differential relay
GCCIA-3-A/SIL-34-D-200
P132
33kV
Trip
33kV
Protected
zone
00
33kV SST
breaker Trip
GCCIA N GCCIA-C8-2010-48-0200-0034
00
BUS 4B2
Shuweihat L14
Page 2-9
87RB
High Impedance
differential relay
Shuweihat L13
Salwa L11
Reactor XL1
Salwa L12
Reactor XL2
Contractor N
BUS 4A2
GCCIA-3-A/SIL-34-D-200
50/51R
Non directional
Phase O/C
50/51NR
Non Directional
Earth Fault
33kV
33kV
P141
Trip
00
33kV SST
breaker Trip
GCCIA N GCCIA-C8-2010-48-0200-0034
00
BUS 4B2
Page 2-10
50/51R
Non directional
Phase O/C
Shuweihat L14
50/51NR
Non Directional
Earth Fault
Shuweihat L13
Salwa L11
Contractor N
BUS 4A2
Reactor XL1
Salwa L12
Reactor XL2
50RN
Earth Fault
P141
GCCIA-3-A/SIL-34-D-200
Trip
33kV
33kV
Alarm to
DCS
33kV SST
breaker Trip
00
GCCIA N GCCIA-C8-2010-48-0200-0034
00
BUS 4B2
Shuweihat L14
Page 2-11
50AL
Earth Fault
Shuweihat L13
BUS 4A2
Contractor N
GCCIA-3-A/SIL-34-D-200
00
P142
BUS 4B2
00
Intertripping
remote end
GCCIA N GCCIA-C8-2010-48-0200-0034
TEE1
High
Impedance
differential
relay
Page 2-12
TEE1
High Impedance
differential relay
Shuweihat L14
Shuweihat L13
33kV
33kV
Reactor XL2
Salwa L12
Reactor XL1
Salwa L11
BUS 4A2
Contractor N
GCCIA-3-A/SIL-34-D-200
00
P633
BUS 4B2
00
Intertripping
remote end
GCCIA N GCCIA-C8-2010-48-0200-0034
TEE2
Low
Impedance
differential
relay
Page 2-13
TEE1
High Impedance
differential relay
Shuweihat L14
Shuweihat L13
33kV
33kV
Reactor XL2
Salwa L12
Reactor XL1
Salwa L11
Salwa L11
Reactor XL1
Salwa L12
Reactor XL2
Contractor N
BUS 4A2
GCCIA-3-A/SIL-34-D-200
33kV
33kV
00
7SD522
Communication
7SA522
Communication
GCCIA N GCCIA-C8-2010-48-0200-0034
Line diff.
relay
Line Dist
relay
00
BUS 4B2
Shuweihat L14
Page 2-14
HVDC Line
diff. relay
Shuweihat L13
Salwa L11
Reactor XL1
Salwa L12
Reactor XL2
Contractor N
BUS 4A2
GCCIA-3-A/SIL-34-D-200
33kV
33kV
00
P132
Alarm
32F (2)
Active
power
relay
Forward
P132
00
BUS 4B2
Page 2-15
Shuweihat L14
(1) 32R Export Power (from utility toward GCCIA)
(2) 32F Import Power (from GCCIA toward utility)
(3) At Al Fadhili : 32F alarm only
32R
Active power relay
Reverse
Shuweihat L13
32F
Active power relay
Forward
Intertripping
remote end
GCCIA N GCCIA-C8-2010-48-0200-0034
32R (1)
Active
power
relay
Reverse
Salwa L11
Salwa L12
Reactor XL1
Reactor XL2
Contractor N
BUS 4A2
bus VT
bus VT
GCCIA-3-A/SIL-34-D-200
P841
Close
P841
33kV
Close
line VT
line VT
line VT
00
GCCIA N GCCIA-C8-2010-48-0200-0034
P841
Close
line VT
line VT
line VT
79/25
Autorecloser
Voltage control
line VT
P841
P841
Close
Close
line VT
line VT
line VT
P841
P841
Close
Close
bus VT
33kV
bus VT
00
BUS 4B2
Shuweihat L14
Page 2-16
79/25
Autorecloser
Voltage control
Shuweihat L13
Salwa L11
Contractor N
BUS 4A2
Bus VT
25A/25SC
Synchronizer
GCCIA-3-A/SIL-34-D-200
Close
33kV
line VT
line VT
Reactor XL2
line VT
25A/25SC
Synchronizer
7VE61
7VE61
Close
Close
33kV
line VT
line VT
line VT
line VT
00
GCCIA N GCCIA-C8-2010-48-0200-0034
25A/25SC
Synchronizer
25A/25SC
Synchronizer
7VE61
7VE61
7VE61
Close
Close
Close
25A/25SC
Synchronizer
line VT
line VT
line VT
line VT
25A/25SC
Synchronizer
Bus VT
25SC
Synchro check
7VE61
Important note :
used to check Live Bus
Live line conditions. In case
of manual close from BCU
only when BCU not able to
give directly the
authorization for closing
- initiation of MX3EG is
received from BCU
-if conditions are OK :
Breaker closing given by
7VE61
-if conditions are not OK :
Salwa L12
Reactor XL1
Bus VT
Bus VT
25A/25SC
Synchronizer
7VE61
7VE61
Close
Close
Bus VT
25SC
Synchro check
7VE61
Close
Bus VT
line VT
00
BUS 4B2
Page 2-17
(1)
Relays installed in the panels with
inputs connected but close command
not connected
25A
Synchronizer
Shuweihat L14
Shuweihat L13
Salwa L11
Salwa L12
Reactor XL1
Reactor XL2
Contractor N
BUS 4A2
1st stage
(Retrip)
GCCIA-3-A/SIL-34-D-200
50/62
Breaker
Failure
Note : retrip is sent
to the two trip coils
P841
2nd
stage
trip
00
Tripping of adjacent
breakers through P740
bus bar protection
tripping circuit and P142
protection tripping
circuit
33kV
2nd
stage
trip
2nd
stage
trip
33kV
Intertripping to
remote end
GCCIA N GCCIA-C8-2010-48-0200-0034
2nd stage
trip
2nd
stage
trip
00
BUS 4B2
Shuweihat L14
Page 2-18
50/62
Breaker
Failure
Shuweihat L13
Salwa L11
Reactor XL1
Salwa L12
Reactor XL2
Contractor N
BUS 4A2
GCCIA-3-A/SIL-34-D-200
2nd stage
trip
00
50/62
Breaker
Failure
33kV
33kV
P841
GCCIA N GCCIA-C8-2010-48-0200-0034
1st stage
(Retrip)
Intertripping
remote end
2nd
stage
trip
00
BUS 4B2
Shuweihat L14
Page 2-19
50/62
Breaker
Failure
Shuweihat L13
Salwa L11
Salwa L12
Reactor XL1
Reactor XL2
Contractor N
BUS 4A2
GCCIA-3-A/SIL-34-D-200
33kV
33kV
Note : retrip is
sent to the two
trip coils
00
2nd
stage
trip
GCCIA N GCCIA-C8-2010-48-0200-0034
50/62
Breaker
Failure
P841
Tripping of adjacent
breakers through P740
bus bar protection
tripping circuit and P122
protection tripping
circuit
2nd
stage
trip
1st stage
(Retrip)
2nd
stage
trip
2nd
stage
trip
00
BUS 4B2
Shuweihat L14
Page 2-20
50/62
Breaker
Failure
Shuweihat L13