Beruflich Dokumente
Kultur Dokumente
ii
Section 4:
1.1
Introduction
The 7200 series UPS employs a fully controlled, 3-phase SCR bridge rectifier to
provide a regulated DC busbar suitable for charging the UPS batteries and present
the inverter with a stable input voltage. This chapter describes the principles of
operation of an SCR device and its use in a phase-controlled rectifier circuit.
1.2
SCR principles
The Thyristor, or Silicon Controlled Rectifier (SCR), is a three-terminal device
which was first introduced to the power electronics industry in 1957. It is essentially a solid-state switch which is normally triggered from its non-conducting
state (OFF condition) to its conducting state (ON condition) by a pulse applied between its gate and cathode terminals. In general, in its ON-state the SCR acts as a
unidirectional conducting device and blocks current flow in the reverse direction
(cathode-to-anode). In its OFF-state, it blocks current flow in both directions.
Figure 4-1: SCR principles (summary)
SCR Three Terminal Device
ANODE
CATHODE
GATE
ANODE
CATHODE
SCR OFF
no current flow
ANODE
CATHODE
4-1
1.2.1
Gate
Gate
P2
N2
Anode
Gate
IA
Anode
P1
N1
P2
N2
N1
P2
T1
T2 (NPN)
T1 (PNP)
Anode
I2
I1
Gate
T2
Ig
Cathode
Cathode
Cathode
Cathode
With reference to the transistor model above, the two transistors are connected in
a regenerative manner i.e. ignoring the gate current (Ig), T2s collector current
(I2) is drawn through T1 emitter-base junction (turning T1 on) and T1s collector
current (I1) flows through T2 base-emitter junction (turning T2 on). This can be
expressed mathematically as I2 = 2 x I1 (where 2 is the current gain of T2)
and I1 = 1 x I2 (where 1 is the current gain of T1).
Regeneration occurs when the sum of the current gain of both transistors (T1 and
T2), also described as the loop gain of the two transistors, is greater than unity;
at which point the transistors try to turn ON each other harder and harder until
both devices rapidly reach full saturation. This equates to the SCR being in its
conduction state, whereby the voltage drop across the device is approximately
1.0V and its anode current is determined only by the external voltage and load impedance.
As with a normal transistor, the current gain T1 and T2 varies proportionally
with emitter current, and in the absence of any gate signal the only current initially
flowing through the transistors is a leakage current comparable to with the reverse
current of a diode. Under these conditions the value of the current gain associated
with each emitter falls to a very low figure, and the device is designed such that
the loop gain is made less than unity, and the transistors remain non-conducting
i.e. this is equivalent to the SCRs non-conducting forward blocking state. Indeed, the fact that the two emitter-base pairs need be designed only for an average
value of of 0.5, to produce the effective unity loop gain necessary to make conduction self-sustaining, makes it possible to use relatively thick base layers, and
hence obtain a much greater voltage blocking capability than in a practicable transistor.
In summary, the SCR can be triggered from its non-conducting to conducting
state by increasing the circulating current through T1 and T2 to the point where
the loop gain rise above unity. This may be accomplished by several means, some
of which are undesirable, as described below.
4-2
1.2.2
Conducting
Holding
Current
Reverse
VAK
Avalanche
Breakdown
Forward
Blocking
Breakover
Voltage
Reverse
Figure 4-3 illustrates the static characteristics for the SCR anode current (IA) and
anode-cathode voltage (VAK) with zero gate current. This shows that in the reverse
direction the SCR characteristic is similar to that of a normal diode, in that very
little current flows as the reverse voltage increases until the reverse avalanche
breakdown point is reached, where-upon the current rapidly increase.
In the forward blocking region, increasing the forward voltage does not tend to
increase the leakage current until the point is reached where avalanche multiplication begins to take place. Past this breakover voltage point, the leakage current
increases quite rapidly until the total current through the device is sufficient to
raise the internal loop gain 1 whereupon the SCR switches to its conduction
state provided the anode current remains in excess of a minimum current known
as the holding current. When the anode current falls below the holding current
the loop gain falls below unity and the device will revert to its forward blocking
(non-conducting) state.
Albeit not necessarily destructive, this means of triggering the SCR is undesirable
(especially in phase-control applications) and usually avoided by employing a
device whose forward breakover voltage and peak inverse voltage ratings are well
outside the available circuit voltage. Additionally, external components may be
used to prevent spurious voltage spikes inadvertently triggering the device by this
means.
4-3
Gate triggering
Conducting
Ig2 > Ig1 > Ig0
Holding
Current
Ig2
Ig1 Ig0
Reverse
Avalanche
Breakdown
Blocking
VAK
Forward
Reverse
The usual method employed to trigger the SCR from the blocking to the conducting state, is to inject sufficient current into the gate terminal (T2 base) to increase the current in the main circuit by the modest amount required to raise the
loop gain to greater than unity. That is, the injected gate current (Ig) leads to an
increase in I2 which in turn leads to an increase in I1, which further increases I2....
and so on, until both transistors are saturated.
Figure 4-4 shows that for increasing magnitudes of gate current, the region of
characteristics between breakover current and holding current is narrowed and the
effective forward breakover voltage is reduced. For sufficiently high gate currents
the entire forward blocking region is removed and the V-I characteristics are essentially identical to those of a P-N rectifier.
This is a very advantageous mode of operation, since it is possible to use a device
with a forward breakover voltage much higher than any voltage likely to be encountered in the circuit, and use only a moderate amount of trigger power to start
the high-conduction state.
Once the gate has been used to trigger the device into conduction it loses control
and can be removed without affecting the external circuits operation i.e. once
the SCR is conducting, the anode current is determined solely by the external circuits voltage and impedance, and the only method of turning the device off is to
reduce this to below the SCRs holding-current level. To minimise internal losses
and heating effects, it is usual therefore not to apply the gate current for much
longer than is necessary to assure the device turns on; for this reason the gate
signal normally takes the form of a current pulse of sufficient amplitude and duration to ensure this condition is satisfied.
4-4
Maximum
gate current
allowed
12
Maximum
gate voltage
allowed
SAFE
OPERATING
AREA
Maximum
gate power
dissipation
(V x I)
Minimum
gate voltage
allowed
Minimum
gate current
allowed
0.5
1.0
1.5
Gate Current (A)
2.0
As can be seen from Figure 4-5, the spread of gate voltage versus gate current can
be quite wide for different load variations. The gate circuitry must therefore be
able to accommodate this variation and also allow for different sizes of SCR. Typical design values are for 6V and 1A pulses for 10sec.
dV/dt triggering
As with all semiconductor devices, there are internal capacitive effects between
the various P and N layers, and between the electrodes. In the case of the SCR
these effects can turn-on the device inadvertently if the rate of change of voltage
applied to it are sufficient to raise the current flow to a level which raises the internal loop gain above unity:
i.e.the current flowing through the capacitor = CdV/dt and has the same effect
as injecting a gate current if allowed to increase to the appropriate level.
As with the breakover-voltage triggering mechanism described above, this
method of turning on the device is not generally used as it is uncontrollable and
is normally prevented by connecting additional components (known as snubbers)
across the device to limit the rate of such voltage changes (see paragraph 4.1 on
page 4-41).
4-5
1.2.3
VAK x IA
Power
Dissipation
t
VAK
90%
Voltage across
SCRs
10%
t
IA
90%
Anode
Current
10%
0
td
t
tr
ton
Gate
Current
0
10%
4-6
Conventionally, as shown in Figure 4-6, the total switching time is divided into
the delay time (td) and the rise time (tr); these periods are arbitrarily delimited, for
the purpose of measurement, at the instants when the voltage across the SCR falls
to 90% and 10% of the initial blocking voltage. The rise-time (tr) is defined as the
time required for the anode voltage to drop from 90% to 10% of its forward blocking value. The rise of current as voltage across the SCR falls is determined largely
by the external circuit. In a purely resistive circuit the current will rise in the same
manner as the voltage falls; hence the term rise time. It is important that the instantaneous current-voltage product during the turn on interval does not exceed
the device dissipation capability. For this reason, the rate of rise of anode current
(di/dt) must be limited. The delay time (td) is reduced as the gate current is increased; however there are other considerations that affect the chosen gate signal,
as described later (see paragraph 3.2 on page 4-39).
1.2.4
Anode
IA
Anode
P1 +
N1
Gate
Gate
P2 +
N2
J1
J2
J3
Cathode
Cathode
Referring to Figure 4-7, when an SCR is conducting, each its three semiconductor
junctions (J1-J3) are forward-biased and the two base regions (N1 & P2) are
heavily saturated with holes and electrons (stored charge).
When the SCR is commutated by the application of a reverse anode-cathode voltage, the holes and electrons in the vicinity of the two end junctions (J1 & J3) will
diffuse to the junctions and result in a reverse current in the external circuit. The
voltage across the SCR will remain at about 0.7V as long as an appreciable reverse current flows. After the holes and electrons in the vicinity of J1 and J3 have
been removed, the reverse current will cease; the junctions J1 and J3 will assume
a blocking state and the voltage across the SCR will then increase to a value determined by the external circuit. However, recovery of the device is not complete,
since a high concentration of holes and electrons still exists in the vicinity of the
centre junction (J2). This concentration decreases by the process of recombination in a manner which is largely independent of the external bias conditions.
After the hole and electron concentration at J2 has decreased to a low value, J2
4-7
will regain its blocking state and a forward voltage may then be reapplied to the
SCR without turning it back on. The time that elapses after the cessation of forward current flow and before forward voltage may safely be applied is called the
SCR turn-off time (toff), and can typically range from 3sec to 50sec depending on the design and construction of the particular device.
1.2.5
trr
0
tfb
toff
Voltage across 0
SCRs
t1
t2
t3
t5
t4
t6
t9
t7
t10
t8
Figure 4-8 illustrates graphically the (some-what idealised) effects on the SCR
voltage and current of the turn-off mechanism described above. The total turn-off
time (toff) is the total time between the anode current falling to zero (t3) and the
device being capable of supporting a forward voltage (t8). This is shown to comprise two components. First the reverse recovery time (trr) (t3 to t6) followed by
the forward blocking time (tfb) (t6 to t8). These intervals are not constant, but are
a affected by several, mainly external, parameters.
For example the turn-off time will increase with:
As its title suggests, natural commutation takes place automatically when the
voltage across the SCR reverses as part of the external circuit function this is the
case in the phase-controller application, as the device is fed with the input a.c.
4-8
1.3
SCR Ratings
Junction temperatures
Power losses in an SCR produces thermal energy (heat) which must be conducted
away from the junction region. Heat dissipation is achieved by mounting the SCR
on a suitable heatsink the heat developed within the device then flows via the
device case and heatsink to the ambient air, and can be dispersed by fan extraction
if necessary.
The maximum operating junction temperatures are typically 125C - 150C.
Heat losses are a function of:
ON-state conduction losses
A product of the voltage drop across the device (about 1.5V) and the
amount of current flowing through it. This can be as high as 500W.
OFF-state losses
These losses are due to leakage current and are therefore very small.
Switching losses
The heat generated during turn-on and turn-off is a function of the voltage
across the device and the current flowing through the device at the time of
switching. These losses can be very large but exist for a very short duration only, as illustrated in the characteristic curves shown previously.
An upper temperature limit must be imposed to restrict mechanical failure and
prevent excessive temperatures to internal joints and leads (which may interfere
within the device package). When such a temperature limit is imposed (e.g.
125C) it will have a direct affect on the device rated current capability.
Current ratings
Several rated current conditions can be stipulated in the device specification; and
thermal breakdown is likely if any one of these values are exceeded.
Average current rating (IAV)
This is the maximum average ON-state current the device may conduct
continuously.
RMS Current rating (IRMS)
This is the maximum RMS ON-state current the device may conduct continuously i.e. this is the steady-state operating current.
4-9
Voltage ratings
4-10
1.4
1.4.1
Input
AC
RL
Max Output
SCR gate permanently
turned ON
Mean
DC
Input
AC
RL
0V
Min. Output
SCR gate permanently
turned OFF
The top diagram shows the situation where the SCR receives a permanent gate
drive signal i.e. the gate is permanently positive with respect to the cathode. In
this condition the SCR passes current during the whole of the input AC waveform
positive half-cycles but blocks the negative half-cycles, as the anode-cathode are
reverse biased during the reverse periods i.e. the SCR is said to be naturally
commutated at the end of each positive half-cycle. This results in a half-wave
rectified voltage being developed across the load resistor, and the SCR can be
seen to be acting in the same manner as a normal rectifier diode. Note that in this
example the mean (d.c.) load voltage is approximately 0.45 times the input peak
voltage, and is shown as a dotted line superimposed on the output waveform.
In the lower diagram the SCR gate drive voltage is removed altogether and under
these circumstances the SCR is permanently turned off during both the positive
4-11
and negative half-cycles of the input voltage waveform. In this case the mean
(d.c.) load voltage will of course be zero.
The two conditions described above illustrate how the maximum and minimum load voltages are obtained. The description on the following page shows
how phase control techniques may be used to vary the mean load voltage to any
point between these two extremes.
Figure 4-10: Simple controlled rectifier; showing 45 and 90 output waveforms
SCR conducts only during the shaded
period of the input positive half-cycle
Vdc(max)
Vdc(mean)
Input
AC
RL
0
90
180
270
360
0V
Output waveform at 45 delay
Vdc(mean) is slightly less than the maximum
available dc voltage Vdc(max)
Gate ON
SCR turned ON by gate pulse
Vdc(max)
Vdc(mean)
Input
AC
0
90
180
Gate ON
270
360
RL
0V
Output waveform at 90 delay
Vmean is even less than that achieved
at 45 delay
The examples on the previous page showed that the mean voltage, Vdc(mean),
produced by the simple half-wave rectifier circuit is at a maximum when the SCR
is turned on throughout the whole of its positive (forward biased) half cycle, and
at a minimum when the SCR gate is totally devoid of a drive signal.
When used in a phase-controlled circuit, the mean voltage, Vdc(mean), is varied
between these two extremes by applying the gate drive signal at a variable point
in its forward biased half-cycle as illustrated in Figure 4-10. In the top diagram
the SCR gate is triggered when the input waveform is 45 into its positive half
cycle. The SCR therefore conducts during the period between 45 and 180 only
i.e. it is not turned on between 0 and 45, and is turned off by natural commutation at 180. As shown in the top waveform diagram, under these circumstances
the mean dc voltage Vdc(mean) is slightly less than maximum Vdc(max).
In the lower diagram the SCR gate trigger is delayed by a further 45, to a total of
90, which leads to a corresponding fall in mean output voltage, as shown.
This is the basic principle of a phase-controlled rectifier i.e. controlling the
mean DC voltage between its maximum and minimum limits by controlling the
variable phase delay between the point at which the SCR becomes forward biased
and the application of its gate drive signal.
4-12
The terms phase forward and phase back are used in power engineering
fields to describe the action of advancing or retarding the gate drive signal respectively e.g. phasing forward the rectifier implies that the SCR is turned on earlier in its forward conduction cycle and more energy is therefore allowed through
the rectifier, leading to an increased mean DC voltage.
1.4.2
S+
T+
90
30
R+
S+
T+
R (load)
R+
150
S current
T current
Each SCR controls the rectifier conduction during one half cycle period of an
input cycle. Taking the R phase as an example, the top SCR (R+) controls the R
phase positive half cycle, and the lower SCR (R) controls the negative half cycle.
Looking at the R phase positive half cycle (R+) in detail, the three-phase waveform diagram shows that this device is forward-biased only for a 120 period between 30 and 150 of the incoming R phase waveform. This is true of all six
SCRs and means that the bridge output voltage can be controlled over its full
range by controlling the individual SCR conduction angles between 30 and 150.
In practice all six SCRs are controlled such that their conduction phase angles are
identical, therefore the rectifier load current is shared equally between all three
phases.
Note: in the practical 7200 circuit, the load comprises the DC Busbar filter
(smoothing) capacitors, the batteries (when the battery circuit breaker is closed)
and the power inverter section. The rectifier SCRs are thus controlled at the phase
angle necessary to maintain the DC Bus voltage at the required battery charge
voltage while at the same time passing the power demanded by the inverter to
enable it to produce its correct output voltage over a wide load range.
4-13
1.5
Rectifier construction
The rectifier power components and the static switch power components are assembled on the same heatsink , as illustrated below.
Figure 4-12: Power rectifier construction
RECTIFIER 3-Ph
MAINS FEED
STATIC BYPASS
MAINS FEED
Bypass SCRs
4-14
Snubber board
Yellow
Red
Yellow
Red
X4
2 1
Yellow
Red
X3
2 1
Yellow
Red
X2
2 1
Yellow
Red
X1
2 1
1 4
2 1
X8
Black
T8
X5
2 1
Black
V6
K2
3
X3
White
Yellow
Red
X6
2 1
G2
Black
G1
K1
X7
G2
4542040W
G1
K1
Black
K2
Black
3
X2
4540043B
V5
White
G2
T7
V4
G1
K1
57
58
59
+
s4-c1.fm5 - Issue 2 Dated 21/08/97
1 4
Black
K2
3
X1
White
4-15
Depending on the module rating, the rectifier SCRs can take the form of Twinpak or individual devices. As their name suggests, Twinpak devices contain
two SCRs in a single moulded package (See Figure 4-14). As shown, the anode
of one device is internally connected to the cathode of the other, and brought out
to a power connection along with the remaining free anode and cathode. This then
forms a convenient package for the phase controlled rectifier application, with the
a.c. input connected to the common power connection and the DC Bus positive
and negative connections made to the appropriate anode and cathode, as shown.
Separate gate connections are provided, with connection G1 being internally connected to the (+) SCR and G2 to the () SCR.
Where single devices are used, their anode, cathode and gate connections are individually identified.
The gate drive signals take the form of a high frequency modulated waveform 2
which is produced by the Rectifier Logic Board and present whenever the particular SCR is due to be turned on. The gate signal is not required once the device is
turned on, in practice it is applied only for a short burst which avoids excessive
wear on the SCR gate material (see paragraph 3.2 on page 4-39).
The Rectifier Logic Board gate drive signals are connected via ribbon cables to
the Driver Interface Board which contains snubber components designed to
ensure clean rectifier SCR switching, and is mounted on the rectifier assembly
itself. This board applies the drive signals to the SCR gate/cathode via twisted pair
cables note that an auxiliary cathode connection is often provided on the SCR
device for connecting to the negative end of the gate drive cables.
Figure 4-14: Twinpak SCR internal details
AC Input
+VE DC BUS
VE DC BUS
+VE SCR Gate (G1)
4-16
1.6
Rectifier Assembly
Phase
Controlled
Rectifier
DC Bus Neg
+
-
Battery
Breaker
Battery
Drive
Interface Bd.
DC Bus Pos
TO INVERTER
SECTION
Input
Choke
DC Busbar
filter capacitors
Input mains
Input
Isolator
Remote Alarms
Operator Control
Panel
High Voltage
Interface Board
ON GENERATOR
1.6.1
4-17
The 3-phase input mains voltage is attenuated on the High Voltage Interface
Board and three line-line proportional sense signals are passed to the Rectifier
Logic Board where they provide zero-crossing reference signals for the phasecontrol timing circuits and are also monitored by input undervoltage and input
phase sequence fault detection circuits.
Input current sense
The rectifier input current is detected by CTs fitted to the power rectifier assembly. The signals produced by these CTs are rectified on the High Voltage Interface
Board and a single input current sense signal, proportional to the total input current, is connected to the input current limit circuit on the Rectifier Logic Board
via the UPS Logic Board.
Note: the sensitivity of this signal is selected by jumpers on the High Voltage Interface Board.
DC Bus (battery) voltage sense
The DC busbar voltage is a function of the rectifier output when the rectifier is
operative, and a function of the battery voltage when the rectifier is inoperative
and the batteries are discharging. This voltage is attenuated on the High Voltage
Interface Board and a proportional DC voltage sense signal is passed to the Rectifier Logic Board where it provides a feedback input to the rectifier voltage regulation control loop.
Battery current sense
Battery current is sensed by a Hall-effect DCCT connected in the battery positive line. The signal produced by the CT is rectified on the High Voltage Interface
Board and a current-proportional signal is connected to the battery current limit
circuit on the Rectifier Logic Board via the UPS Logic Board. The sense signal is
polarity-sensitive i.e. a positive signal indicates a charging current, and vice
versa.
Note: the sensitivity of this signal is selected by jumpers on the High Voltage Interface Board.
1.6.1.2
Various digital signals are passed between the UPS Logic Board and all the other
boards connect to it. These can broadly be categorised as:
alarm data generated on the Rectifier Logic Board and UPS Logic Board
which are passed to the Operator Control Panel via the Operator Logic
Board also to the Alarms Interface Board (for remote indication) where
fitted.
rectifier metering data generated on the UPS Logic Board and passed to
the Operator Control Panel e.g. input voltage, battery volts current
metering.
control data entered at the Operator Control Panel which is stored by the
UPS Logic Board e.g. boost charge parameters, DC voltage monitor
threshold parameters; manual selection of Rectifier ON/OFF status and
immediate Boost Charge mode.
external control options e.g. remote stop, emergency shutdown, on-generator input current limit.
4-18
1.6.2
1.6.3
1.6.4
1.6.5
1.6.6
4-19
Board which is then passed to the Rectifier Logic Board via the UPS Logic Board
(See paragraph 1.6.6).
1.6.7
Controlled start/stop
The Rectifier Logic Board contains a start/stop control circuit which effectively
turns ON/OFF the rectifier SCR drive signals. This circuit is affected by several
circuits on the Rectifier Logic Board itself (e.g. input undervoltage or phase rotation error) and also by a start/stop signal produced on the UPS Logic Board in response to various monitored system-wide control signals (See paragraph 2.3.6).
1.6.8
1.6.9
4-20
Section 4:
2.1
Chapter overview
This chapter contains a circuit description of the Rectifier Logic Board used
across the whole 7200 Series UPS model range, and should be read in conjunction
with circuit diagram SE-4520074-A (4 pages). Signal annotations shown on the
circuit diagrams are shown in italics in the following text e.g. [IREC>.
2.2
2.2.1
General description
Circuit board functions
The board is responsible for providing the drive signals for the rectifier SCRs at
the appropriate phase angle necessary to produce the required DC Bus (battery
charging) voltage. In so doing, the board monitors the following UPS parameters
via the High Voltage Interface Board and UPS Logic Board (See Figure 4-15):
As part of its control function, the Rectifier Logic Board detects several abnormal
operating conditions and provides the UPS Logic Board control system with the
following error status signals:
2.2.2
Rectifier overload.
Input supply phase rotation error.
Input supply undervoltage.
Rectifier On/Off.
Control power supply failure.
Input/Output connections
The Rectifier Logic Board has four connectors, described below:
X1 Output SCR gate drive signals to Rectifier Driver Interface Board
4542040-W
X2 System control signals to/from the UPS Logic Board 4550007-H
(See Table 4-1).
X3 Control power supplies input from AC-DC Power Supply Board
4503030-M.
X4 Interface to second rectifier control circuit in a 12-pulse rectifier system (optional facility not used in standard module).
4-21
I/O
1-4
I/O
5-8
9-12
13-14
I/O
15
VREC_AC Input mains voltage sense signal phases U-W (approx. 15Vp-p)
16
VREC_BA Input mains voltage sense signal phases V-U (approx. 15Vp-p)
17
VREC_CB Input mains voltage sense signal phases W-V (approx. 15Vp-p)
18
19
20
Function
Not in use
I
21-23
24
25
26
27
IDC_1 Not used in standard model (12 pulse rectifier option only)
28
IDC_2 Not used in standard model (12 pulse rectifier option only)
29
DB Used in parallel systems only (used for input current sharing control)
30
DB_0 Used in parallel systems only (used for input current sharing control)
31
Not in use
32
33
34
SEQ Signals input mains phase sequence error status to UPSLB (Error = 1)
35
IN_LOW Signals low input volts error status to UPSLB (Low Volts = 1)
36
ON-REC Rectifier Run/Stop selection from UPSLB micro (RUN = 1 and STOP = 0)
37
38
39
40
4-22
Not in use
2.2.3
Batt I sense
Bus Volts F/B
Volts
Error
Amplifier
DC Control
voltage
DC Reference
voltage
Batt temp sense
Charge Mode
Selection
(UPSLB)
Reference
Voltage
Generator
Bi-directional
Control
(UPSLB)
AC-DC Supply
Start/
Stop
Logic
Rectifier
SCR
Drive
Pulses
Start/Stop
control line
Input I sense
Drive
Pulse
Generator
Fault
Detection
Logic
Power
Supply
The board regulates the DC busbar (battery charging) voltage using standard
phase controlled techniques i.e. by controlling the point at which each rectifier
SCR is turned on during its forward biased period. This is achieved by detecting
the point at which each SCR becomes forward biased and then applying a variable
time delay between this point and the production of its gate drive pulses. Maximum DC busbar voltage is obtained when the delay is very short, whereupon the
SCRs are allowed to conduct for the whole of their forward biased period. Consequently, as the time delay is increased the SCRs conduct for a shorter period
leading to a reduced DC busbar voltage (See paragraph 1.4).
Drive pulse generator
This block has two major responsibilities. First, it contains a timing circuit which,
in conjunction with the DC control voltage signal, controls the timing of the
SCR drive pulses relative to the mains voltage sense signals (i.e. it uses the mains
sense signals to synchronise each SCRs timing to the relevant forward biased
period of the incoming supply); second, it contains a signal conditioning circuit
which processes the resulting drive pulses to provide a modulated drive waveform.
The DC control voltage directly controls the adopted SCR drive signals time
delay and therefore also the DC busbar voltage i.e. increasing the DC control
voltage reduces the time delay and results in a greater DC busbar voltage.
4-23
The reference voltage generator provides the volts error amplifier with its DC
reference voltage input. This is seen as a voltage demand signal by the voltage
error amplifier in that it represents the DC busbar target voltage.
The reference voltage generator can produce one of four DC reference voltage
levels equating to float charge, boost charge, manual charge, or test; as requested
by the processor on the UPS Logic Board. Note that although the charge mode is
selected by the UPS Logic Board, the respective DC reference voltage for each
mode is individually adjustable by potentiometers on the Rectifier Logic Board
itself.
An analogue signal proportional to the battery temperature is also applied to the
reference voltage generator and can be used to reduce the DC reference voltage by 1.5Vdc/C as the battery temperature rises between 25C and 35C.
The test mode is used for fault-finding only and allows the DC busbar voltage to
be manually adjusted within the range 0V to 650Vdc.
Volts error amplifier
In the block diagram the primary output of the voltage error amplifier is annotated DC control voltage. This is the signal which directly controls the DC
busbar voltage via the time delay circuit in the drive pulse generator see above.
The magnitude of the DC control voltage is determined by a comparator within
the volts error amplifier which compares the DC busbar voltage feedback signal
with the DC reference voltage produced by the reference voltage generator
block. This basically forms a closed-loop control system, in that the error amplifier constantly modifies the DC control voltage in such a way as to make the rectifier phase-forward or phase-back (as required) to maintain equilibrium between
the DC reference and DC bus feedback signal voltages.
The volts error amplifier also monitors the input current and battery current
sense signals and reduces the DC control voltage if either of these signals reaches a preset current limit threshold. Such an event reduces the DC busbar voltage
to maintain the particular current at its limiting value.
Start/Stop Logic
4-24
The fault detection block output is also connected to the start/stop control line
and has the same effects as the start/stop control signal applied from the UPS
Logic Board. It also applies an input to the start/stop logic block which passes a
fault status signal back to the UPS Logic Board in response to certain detected
fault events hence the start/stop line between the UPS Logic Board and Rectifier
Logic board is shown as bi-directional in the block diagram.
Fault detection logic
This block detects several abnormal/fault conditions on the Rectifier Logic Board
and, depending on the condition will:
provide on-board led indication.
send a fault signal to UPS Logic Board (via the Start/Stop Logic block).
apply a stop condition to the start/stop control line.
Following is a list of the monitored conditions see paragraph 2.3.4.3 for a full
circuit description.
Signals to
UPSLB
Indication
No
CHG
H5
No
OVL
H6
Yes
IN_LOW
BLK_REC
H9
Yes
SEQ
BLK_REC
H8
Yes
BLK_REC
H7
Condition
The Rectifier Logic Board requires regulated 12Vdc supplies for its operation.
These are obtained from the AC-DC Power Supply Board and will be present
whenever the UPS input mains supply (or static bypass supply in a split-bypass
system) is live. An on-board, three-terminal +5V regulator (N14) is driven from
the +12V supply to provide a regulated +5V supply voltage rail.
In the event of a mains failure the AC-DC Power Supply Board will become inactive and the 12V rails are provided by the DC-DC Power Supply Board via the
UPS Logic Board provided the batteries remain connected to the DC busbar (see
section 3 of this manual for details of the control power supplies).
4-25
2.3
2.3.1
Introduction
The Rectifier Logic Board circuit diagram (SE-4520074-A) comprises 4 sheets.
With reference to the block diagram description in Figure 4-16, the drawings can
broadly be described as follows:
Sheet 1 contains a signal map showing the interconnection of the signals
passing between the other three sheets.
Sheet 2 contains the:
reference voltage generator circuit
battery temperature compensation circuit
volts error amp circuit
battery current limit circuit
input current limit circuit
soft-start control amplifier
Sheet 3 contains the timing portion of the drive pulse generator circuit
together with the mains undervoltage (-15%) detection circuit
Sheet 4 contains the:
signal conditioning portion of the drive pulse generator circuit
start/stop logic and fault detection circuits
control power supplies and its power failure detection circuit
2.3.2
REC_A
REC_B
Output X =
Output Y =
Manual
X1
Y1 (H4 Yellow)
Float
X2
Y2 (H3 Green)
Boost
X3
Y3 (H2 Green)
Test
X4
Y4 (H1 Yellow)
Notice that the multiplexers Y channel provides on-board led indication of the
selected charger mode by switching the return path for leds H1-H4.
4-26
As shown on sheet 4, the [REC_A/B> signals are obtained directly from the UPS
Logic Board via connector X2-38 and X2-39: however, these can be overridden
by links connected to X9 positions 1 & 2. This is a test facility, and enables the
bench/commissioning engineer to select any one of the four charger modes while
undertaking the board set-up procedures. X9 links 1 and 2 must be open during
normal UPS operation.
The selected reference voltage from Q1 (X) (pin13), which can be monitored at
test-point X8-6, is inverted by N4a and applied to the volts error amplifier (N4b)
via R43 (22k) this is the point annotated DC reference voltage in Figure 4-16,
and is approximately 3.0Vdc when the dc bus is at 432Vdc. As the signal is inverted by N4a, the DC reference voltage is always of a negative polarity i.e.
the demanded DC bus voltage increases as the signal goes more negative. As a
guide, this (linear) signal has a sensitivity of around -7.24mV/V(bus demand).
2.3.3
2.3.4
4-27
Fixed bias
If the DC busbar falls below its required voltage the DC busbar feedback signal
will be lower in amplitude than the DC reference voltage and the voltage error
amplifier output will ramp in a positive direction, lifting the clamp (by V5) on
N3a non-inverting input. This allows the DC control voltage ([MOD>) to increase so raising the DC Busbar voltage. This action will take place until the
DC busbar feedback signal increases to a level equal to the DC reference voltage at which point the output from N4b output will remain constant and cease
demanding an increase in DC busbar voltage.
If the DC busbar rises above the required voltage the circuit will respond with the
opposite polarity i.e. if the DC busbar feedback signal is higher than the DC
reference voltage then N4b output will decrease and further clamp the input to
N31 with a resulting reduction in the DC control voltage ([MOD>).
Due to the presence of C28 in its feedback path, the volts error amplifier (N4b)
integrates any amplitude difference between its DC busbar feedback (+) and
DC reference voltage (-) input signals, and so affects the rectifiers regulation
speed of response. The circuit response can be selected by jumper X6 which
should be positioned (1-2) in modules rated at 60kVA and below (faster response), and (2-3) in modules rated at 80kVA and above.
4-28
2.3.4.1
From test point X8-2 the battery current sense signal is connected to a level detector circuit (N1a) whose output pin 1 changes from logic high to low if the battery current exceeds the level set by R18. When this occurs it clamps the input to
the volts error summing amplifier (N3a), via V4, reducing the DC control voltage ([MOD>) which in turn reduces the DC busbar voltage thereby reducing the
battery charge current. The reference voltage set by R18 can be monitored at test
point X8-8 and can be in the range 0V to -5V. This range is determined by a 5V
regulator circuit, based on N5, connected between the 0V and -12V power rails.
If the regulator circuit is operating correctly the junction of R12 and R13 will be
held at -2.5V. R18 is normally adjusted to obtain 0.1Vdc per amp of required current limit at X8-8 for the 30kVA, 40kVA and 60kVA models respectively.
This circuit is dynamic in its operation i.e. as the DC busbar voltage reduces so
too does the battery charge current. Ultimately, the circuit operation reduces the
DC busbar voltage to a level which sustains the battery charge current at the level
set by R18.
In practice the battery current limit circuit is only likely to become active when
the UPS input mains supply returns from a prolonged outage: whereupon the
heavily discharged batteries are certain to demand a high initial recharge current.
Under these circumstances the DC busbar voltage is initially restricted but will
gradually increase to its nominal value while maintaining the battery current at its
set limit level as the batteries regain their charge.
Battery current limit indication
Led H5 illuminates when the battery current limit circuit is active. The indication
circuit operates by detecting whether or not V4 is turned on. When V4 is conducting, the input to N3 pin 6 via R56 is approximately -0.6V with respect to the signal
applied via R57 to pin 5. These conditions force N3 pin 7 to switch high which
illuminates H5 and produce a logic high [CHG> signal, which is connected to the
UPS Logic Board, via X2-23, to inform it of the battery current limit status.
2.3.4.2
The UPS input current is sensed by current transformers (CTs) fitted to the rectifier assembly input R and T lines. The CTs outputs are rectified and normalised
on the High Voltage Interface Board (see paragraph 2.3.18 on page 7-10) and the
resulting dc voltage, which is proportional to the input current, is connected via
the UPS Logic Board to the Rectifier Logic Board X2-20. From here the sense
signal is buffered by N1b and can be measured as a positive voltage at test point
X8-3.
4-29
From test point X8-3 the input current sense signal is connected to a level detector
circuit (N1d) whose output pin 14 changes from logic high to low if the input current exceeds the level set by R17. When this occurs it clamps the input to the
volts error summing amplifier (N3a), via V3, reducing the DC control voltage
([MOD>) which in turn reduces the DC busbar voltage thereby reducing the input
current. The reference voltage set by R17 can be monitored at test point X8-7 and
can be in the range -0.5V to -5V. This range is determined by a 5V regulator circuit, based on N5, as described above for the battery current limit circuit. In practice R17 is adjusted to obtain 0.8Vdc at test point X8-7 in a 30kVA model; this is
increased to 1.2Vdc for 40kVA and 1.6Vdc for 60kVA models.
This circuit is dynamic in its operation i.e. as the DC busbar voltage reduces so
too does the input current. Ultimately, the circuit operation reduces the DC busbar
voltage to a level which sustains the input current at the level set by R17.
When electronic switch D2 closes it increases the sensitivity of the input current
sense signal to N1d by connecting R35 in parallel with R49. This results in the
current sense signal reaching the set limit threshold at a reduced input current
level and effectively reduces the circuits operation by approximately 25%. This
reduced threshold is controlled by the [STAT> signal generated on the UPS Logic
Board and applied via X3-37 (see paragraph 3.3.12.2 on page 7-46). This is used
to reduce the rectifier input current when the UPS is supplied from a stand-by generator.
Note: this signal is applied via the optional Remote Alarms Board which provides an interface between the external on generator signal and the UPS Logic
Board control logic.
Input current limit indication
Led H6 illuminates when the input current limit circuit is active. The indication
circuit operates by detecting whether or not V3 is turned on. When V3 is conducting, the input to N3c pin 9 via R58 is approximately -0.6V with respect to the
signal applied via R59 to pin 10. These conditions force N3 pin 8 to switch high
which illuminates H6 and produce a logic high [OVL> signal, which is connected
to the UPS Logic Board, via X2-32, to inform it of the input current limit status.
Parallel module operation
When two or more 7200 UPS modules are connected to a common battery a
system of input current sharing is employed to ensure that both modules share the
battery charging burden. Such a system monitors the input current from both
modules and employs a correction signal to either phase-forward or phase-back
the rectifiers as necessary.
In practice the monitored current is obtained from X2-24, which is connected to
the output of the input current sensing buffer amplifier (N1b); and the correction
signal is applied to X2-29, from where it applies an offset signal to the volts error
amplifier (N4b) via buffer N2b. The correction signal can be monitored at test
point X8-4.
2.3.4.3
Start/Stop control
A start/stop control input is applied to the volts error amplifier via diode V6.
This signal, annotated [STOP> (on sheet 1), goes high when the start/stop circuit
requires a rectifier shut-down, and vice-versa. In its stop mode, this signal is inverted to a logic low at N4 pin 8 which is then buffered by N4d and applied as a
clamp to the volts error amplifier. This effectively phases-back the rectifier and
4-30
2.3.5.1
The drive signal timing is controlled by three comparator circuits (one per phase)
which compare sense signals proportional to the three phase input mains supply
with the variable DC control voltage ([MOD>). In reality each comparator contains two similar circuits: one to handle the timing for the positive SCR and the
other for the negative SCR in each phase i.e. one deals with the positive half
cycle and the other with the negative half cycle of the incoming a.c. mains waveform. A full description of the comparators operation is given below.
Note: as all three phases are identical only the R phase is described in detail.
Input supply sensing (for synchronising SCR timing to the Input Supply)
The three phase input mains supply is sensed via an attenuator circuit on the High
Voltage Interface Board (see paragraph 2.3.3 on page 7-7) whose outputs pass
through the UPS Logic Board and are then connected to the Rectifier Logic Board
connector X2 pins 15, 16, 17 (sheet 3). On the High Voltage Interface Board the
mains sense signals are monitored by differential amplifiers on a line-to-line
basis; the input to the R phase control circuit at X2-15 ([VREC_AC>) is in fact derived from the R-T phase and will in fact lag the R phase voltage by 90. A further
lag of 180 is imposed by N12a, therefore the resulting output at N12 pin 1 is a
sine-wave which lags the true mains R phase by 270.
4-31
Mains R-Ph
[VREC_AC>
Mains delayed
by 270
(N12 pin 1)
270 lag
dead band
Figure 4-17 shows that due to the applied 270 phase shift the maximum and minimum levels of the sense signal at N12 pin 1 coincide with the changeover between positive and negative half cycles of the true incoming R-phase voltage
i.e. the sense signal falls from max to min during the true R-phase positive half
cycle and from min to max during the negative half cycle.
N8a buffers the R-phase sense voltage and passes it to N8b and N8c where it is
compared with the DC control voltage. N8b controls the positive R-phase SCR
(i.e. the SCR connected between the rectifier R phase input and the positive DC
busbar) while N8c controls the R-phase negative SCR.
DC Control voltage
The DC control voltage ([MOD>), which is produced by the voltage error amplifier and fully described in paragraph 2.3.4, was previously described as being a
DC busbar volts demand signal, in that the bus voltage is ultimately proportional
to the [MOD> signal level.
Sheet 3 of the circuit diagram shows that [MOD> is inverted by N11a and connected to the non-inverting input of N8c (pin 10), then re-inverted back to its original
polarity by N11b and connected to N8b non-inverting input (pin 5). These two
sections of N11 are configured as comparators and compare the R-phase sense
voltage with the [MOD> signal, as described below.
Comparators operation
The R-phase drive gate drive generation circuit uses three comparators: N8b controls the timing for the drive to the positive SCR, N8c controls the timing for the
drive to the negative SCR, and N8d provides dead-band timing control to both
devices.
The outputs from the above comparators are annotated [A>, [B>, [C> on the diagram and the their effects on the following digital drive circuit can be summarised
as follows:
The R-phase positive SCR is turned on when [A> and [C> are both high
(logic 1).
The R-phase negative SCR is turned on when [B> and [C> are both low
(logic 0).
4-32
The digital signal processing aspect of the drive pulse generator circuit is controlled by D6 and its associated components shown on the diagram sheet 4. This
ASIC applies modulation and start/stop control to the comparators outputs (signals [A> to [I>), and provides further timing checks to ensure that the resulting
drive signals are suitable for driving the rectifier SCRs.
Signal summary
The following signal summary describes the relationship between the [A> [I>
inputs and the drive output signals.
Note 1: the output drive waveforms will be modulated by a 19kHz oscillator connected to D6 pin 7.
Note 2: the outputs all assume that the start/stop line (described in detail later) is
in its start mode i.e. outputs enabled.
4-33
ON (U6-18 = 1)
ON (U6-20 = 1)
Outputs
ON (U6-19 = 1)
ON (U6-24 = 1)
1
0
ON (U6-21 = 1)
ON (U6-25 = 1)
Modulating oscillator
The drive pulse generator circuit is controlled by the same start/stop control line
used to control the volts error amplifier (See paragraph 2.3.4.3) to ensure that
the rectifier stops and starts in a controlled manner. The stop/start logic is contained within U6 and is described in detail below.
4-34
2.3.6
Start/Stop logic
The start/stop logic circuit is contained within D6 and has several inputs derived
from fault detection circuits on this board and on the UPS Logic Board. It produces summary stop/start line which:
inhibits/enables the production of the rectifier drive pulses within D6
via the [STOP> output on D6 pin 34, reduces to zero the DC control voltage produced by the volts error amplifier when in the stop mode (See
paragraph 2.3.4.3)
produces a start/stop status signal at D6 pin 36 which is connected to the
UPS Logic Board via X2-33 (See paragraph 3.3.11.1). This signal is
annotated [BLK_REC> (Blocked Rectifier) and is logic high when the start/
stop line in the stop mode. This informs the UPS Logic board that the
Rectifier Logic Board has detected a fault which results in the UPS Logic
Board turning OFF the rectifier run command signal.
The start/stop line is affected by the following fault detection and control signals.
2.3.6.1
A phase sequence comparator within D6 monitors the R-phase and S-phase zero
crossover signals at D6 pins 4 and 44 (signals [C> and [F>) and produces and error
signal if these are not of the correct phase relationship.
If an error is detected:
the start/stop line is driven to its stop mode
led H8 illuminates to provide on-board indication of phase rotation error
a logic high error signal is produced at U6 pin 33 and passed to the UPS
Logic Board via X2-34 where it is processed by the system control logic
2.3.6.2
4-35
One function of the UPS Logic Boards system control logic is to provide the
Rectifier Logic Board with a general ON/OFF control signal (see paragraph 3.3.7
on page 7-29).
This signal, which is annotated [ON_REC>, is connected to the Rectifier Logic
Board X2-36 and goes low when in the OFF state. In this state:
the start/stop line is driven to its stop mode
led H10 illuminates to provide on-board indication
2.3.6.4
A purpose designed supply voltage supervisor i.c. (N13) monitors the +12V
power rail and flags an error if this falls below approximately 4.55Vdc. If the
+12V supply falls below this level N13 output pin 6 goes high which:
drives the start/stop line to its stop mode
illuminates H10 to provide on-board indication
2.3.7
4-36
2.4
Summary Information
Table 4-5: Rectifier Logic Board configuration jumpers
Jumper
Link
Position
X5
1-2
2-3
1-2
2-3
1-2
2-3
0-1
open
0-2
open
0-1
closed
0-2
open
0-1
open
0-2
closed
0-1
closed
0-2
closed
0-3
closed
open
(Standard)
closed
open
open
Disable driver IC - D6
closed
X6
X7
X9
0-4
0-5
X10
Function
1-2
2-3
Function
Rectifier input current limit adjust (100 - 130%)
R18
R19
R20
R21
R22
4-37
Colour
Function
H1
Amber
H2
Green
H3
Green
H4
Amber
H5
Green
H6
Red
X8 - 2
X8 - 3
X8 - 4
X8 - 5
X8 - 6
DC voltage reference
X8 - 7
X8 - 8
Test Point X5
X5 - 1
4-38
Section 4:
3.1
Introduction
A single Gate Drive Interface Board is used to interface the gate drive signals to
all six rectifier SCRs.
The boards primary function is to provide the SCR gate drive signals with galvanic isolation between their source (i.e. the low voltage control electronic environment of the Rectifier Logic Board) and the noisy, high voltage environment of
the power rectifier SCR devices to which they are applied. This is achieved
through the means of suitable pulse transformers.
3.2
4-39
3.3
X1
1
2
Rectifier
Logic
Board
1
2
Gate drive
ribbon cables
(maximum 3m)
X1
1
Yellow
100n
1k
22R
3
4
V37
X7
R+
V1
3
4
Red
R-ph
mains
0V
min (30)
max (150)
SCR Conduction
period
Trigger pulses
R-
DC Bus
Figure 4-18 illustrates the complete gate drive signal path for the R-phase positive
SCR (R+) all other SCRs are similarly gated.
As has previously been explained, the Gate Drive interface Board contains a pulse
transformer to provide necessary signal isolation. To minimise the size of this
component the Rectifier Logic Board produces a modulated drive waveform
based on a 40kHz square-wave carrier i.e. when the Rectifier Logic Board wants
to trigger the SCR it sends a 40kHz burst firing signal and the pulse transformer
sees the 40kHz signal as opposed to 50Hz. The chosen 40kHz modulation frequency is sufficiently low so as not to be greatly affected by transmission losses
over the gate drive ribbon cables (to 3m) therefore the signal reaching the pulse
transformer maintains its fast rising edge.
When the Rectifier Logic Board requires to trigger the R+ SCR, the 40KHz
square-wave signal is applied to V37. When V37 turns on it connects the lower
end of the pulse transformer to 0V via a current limiting 22R resistor. A current
is induced in the pulse transformer secondary which makes the SCR gate potential
higher than the cathode and triggers the SCR into conduction. Note that diode
V1 blocks reverse gate current in the event of ringing or voltage reversal of the
pulse transformer secondary and also reduces the SCR holding current.
Figure 4-18 shows that the trigger pulse is not applied for the complete possible
conduction period. In fact the turn-on envelope contains only 9 or 10 of the
40kHz trigger pulses. This prolongs the SCR life by avoiding excessive wear on
the gate which would otherwise occur due to the additional heat generated by the
continued gate current after the SCR has turned on.
4-40
Section 4:
4.1
External transients are generated by the external supply and may be super-imposed on the normal AC supply source due to an input circuit breaker switching
operation or occasional lightening strikes.
Transients are also generated when energising and de-energising supply transformers, which may exhibit ringing oscillations on their secondary windings
caused by the sudden application of voltage to secondary leakage reactance and
winding capacitance. Peak voltage of twice the normal value may be observed
when the transformer is energised; whilst de-energising may cause peak values as
high as ten times to be generated as the transformer flux is forced to decay rapidly
to zero.
Also, starting and stopping air conditioning units and motors might momentarily
alter the supply line impedance quite suddenly, and introduce voltage notching
sufficient to cause dv/dt SCR switching within the rectifier.
Internal sources
4-41
tion voltage during the turn-off period causes a reverse current to flow until the
SCR blocks, at which time the reverse current stops suddenly. This rapid change
in current (which can be as high as 106 or 107 amps/second) can result in high reverse voltage spikes which can destroy the SCR device.
These rapid current changes also generate considerable radio frequency interference (RFI); both radiated and conducted.
4.2
Snubber board
A simple R-C snubber circuit is usually employed to provide clamping of such
transient over-voltages. The snubber is connected across the device and if correctly designed will limit both the amplitude and rate-of-rise of the voltage transient.
The R-C circuit is effectively a single-pole high-pass filter, tuned to a high frequency relative to the transient dv/dt. That is, the capacitor blocks the 50Hz
supply voltage but will allow the higher-speed transient voltages through to the
resistor. The R-C time constant at fast dv/dt limits the rate of rise of the over-voltage and therefore also the magnitude. The resistor provides a discharge path for
any transient energy stored within the capacitor, thus the snubber is effective
against both external dv/dt and internal di/dt transient voltage spikes.
Figure 4-19: R-C Snubber filters transients
DC Bus +
Transient only
is allowed through
R-C filter
R+
R-ph
mains
100R
100W
0.1f
1kV
R-
DC Bus
4-42