Beruflich Dokumente
Kultur Dokumente
Fig.1.
The meaning of each function is shown as follows,
GPRS communication Enable GPRS module or not;
Working mode Short message means short message function only;
Short message +GPRS means short message and GPRS
functions are both available.
1
Fig.2
5.1. Run Server.exe, and set parameters correctly, then run meters.
The information of the meter is shown as follows:
Fig.3
The upper box shows the dynamic IP and address of the meter
which is in communicating. In Fig.16, the IP of the meter is
117.136.19.199, and the address is 5. 00 00 00 00 00 06 05 30 FF 1B
FF FF is the registration information which compliances with
MODBUS TCP/IP frame format. 0x30 is command type; 0x05 is
the address of the meter; 00 00 F6 00 00 06 05 31 FF 1B FF DD is
heatbeat data; 0x05 is the address of the meter; 0x31 is command
type.
5.2. Run Modbus Poll
Run Modbus Poll and click Connection to bring out dialogue
box as shown in Fig.17. Select TCP/IP. Input the IP of the computer
which is running Server in IP Address. It is usually set as 502 in
Port, which is the same as the port of users parameter in Server.
Click OK to link Server.
4
Fig. 4
After being connected to Server, click Read/Write Definition in
Setup to bring out the dialogue box as shown in Fig.18.
Fig. 5
Slave ID is the address of slave computer. Function command
type is 0x03/0x04. Address is the initial address (decimal system)
of Modbus TCP/IP protocol. As for Sfere 300 meters, the address range
which can be read is 0x0000-0x0035 and 0x0100- 0x01C3. Quantity
is the data length (byte). Data length and initial address should be
within 0x0000-0x0035 and 0x0100- 0x01C3. After completing the
settings, click OK. Fig.19 shows the Modbus Poll is linking with
Server and the data exchanging between them. On-line User shows
the IP of user; 51723 is the automatically distributed communication
2 means the administrator, User 1 and User 2 can receive the alarming
message; 3 means the administrator, User 1, User 2 and User 3 can
receive the alarming message.
6.2.3. CFGPDI:PORT/DNS/IP* means to change the listening port
number, dynamic domain name and IP address;
For example: CFGPDI:6000/123/* means to change the listening port
to be 6000, change dynamic domain name to be 123, and not to
change the IP address (notice: if the IP address is not changed, please
do not input IP address.)
6.2.4. CFGNCP:corpname/code/password* means to change the
company name, users code and password of the meter.
For example, CFGNCP:SFERE//6666* means to change the
company name to be SFERE, not to change users code, and change
password to be 6666.
6.2.5. CFGANPH:APN/NAME/PASSWORD/HEARTIME* means
to change APN access point, the name of that point, password of that
point and heartbeat time.
For example, CFGANPH:cmnet///60* means to change the APN
access point to be cmnet, set the name and password of that point as
null, and change the heartbeat time to be 60.
6.2.6. CFGID:ID* means to change the ID of the meter, which is the
slave address in GPRS communication.
6.2.7. CFGHT:TIME* means to change heartbeat time.
Remark: when you adopt short message mode to read or change the
data of the meter, please make sure that the number of the phone
which sends that message has been saved in the meter. If there is no
such number in the meter, please add the password to the short
message, then send that message to meter to read or change its data.
For example, if the password is 6666, you can send READ01*6666
to read the data or send CFGPCL:1100*6666 to change the data.
10