Beruflich Dokumente
Kultur Dokumente
GSec
Gas-insulated
Switch-disconnector / Isolator
GSec
Main feature
Safety
ABB Group
Month DD, Year
| Slide 2
Door lock
Rated current:
800 A @ 12 17,5 kV
630 A @ 24 kV
GSec
Main data and ratings
Electricalcharacteristics
Standards:
IEC 60694,
IEC 62271-102,
IEC 62271-200,
IEC 60265-1.
Operating
temperature:
-25C +40C (5)
Max installation
altitude:
3000 m (6)
Phase distance:
230mm
SF6 pressure:
1,48 bar
(absolute)
ABB Group
Month DD, Year
| Slide 3
Ratedvoltage
kV
12
17,5
24
Withstandvoltage(5060Hz1min)
kV
28
38
50
Impulsewithstandvoltage
kV
75
95
125
Ratedfrequency
Hz
5060
5060
5060
Ratedcurrent(40C)
800(***)
800(***)
630
Ratedshorttimewithstandcurrent
kA
Ratedshorttimemakingcapacity(peakcurrent)
kA
62,5
52,5
52,5
Activeload
800(***)
800(***)
630
Noloadtransformers
16
16
16
Noloadcables/lines
50
50
50
Ringcircuit
For21kA(3s)pleasecontactABB
(**) ForGSec/T216kA(3s)
(***) ForGSec/T2630A
800(***)
800(***)
630
Lineelectricalendurance(1)
class
E3
E3
E3
Earthelectricalendurance(1)
class
E2
E2
E2
Linemechanicalendurance(2)
class
M2(4)
M2(4)
M2(4)
Earthmechanicalendurance(3)
class
M0
M0
M0
Breakingcapacity
(*)
Electricalandmechanicalperformance
(1)
(2)
upto5makings
(3)
upto1000operations (4)M1forType2actuator(upto1000operations)
upto5000operations
GSec
Main components and dimensions
ABB Group
Month DD, Year
| Slide 4
Components
Power part Enclosure
ABB Group
Month DD, Year
| Slide 5
No leackage currents
Components
Actuators
Type1 SingleSpring
Closing/Opening
Operatingenergyisprovidedby
chargingaspring(leverormotor),
which,whenreleased,causesthe
contactstoopenorclose
Type2 DoubleSpring
Springscharging(withleverormotor)
Usingthestoredenergyforclosing
andopeningoperations
(withpushbuttonsorshunts)
Speedofthe
Independent
Independent
operation
Manualoperation Lever
Leverandpushbutton
Automatic/Remote
Motor
Motorandcoils
operation
Operatingenergyisprovidedbychargingaspring(withalever),
Earthingswitch
which,whenreleased,causesthecontactstoopenorclose
function
Independentspeed
Forautomaticoperations,incaseofemergency,itisalwayspossibleto
operatemanuallytheactuators
Safety
Separateseatsforlineandearthoperation
Operatingleverwithantireflexfunction
Incombinationwithfuses,opening
canbeperformedbythetrip
Note
mechanism
Possibilitytodischargespringsonce
loaded
ABB Group
Month DD, Year
| Slide 6
Components
Front cover
1.
2.
3.
4.
5.
6.
7.
6
4
3
5
ABB Group
Month DD, Year
| Slide 7
1
7
Typical units
GSec/T1 and GSec/T2
GSec/T1
GSec/T2
Incoming/outgoing panels
Incoming/outgoing panels
ABB Group
Month DD, Year
| Slide 8
Typical units
GSec/T2F and GSec/IB
GSec/T2F
GSec/IB
Earthing switch
ES transmission
Fuse base
ABB Group
Month DD, Year
| Slide 9
Accessories
Overview
Auxiliary contacts
(4 line + 4 earth)
Change-over
contacts for
normally open and
normally closed
250 V AC, 16 A
250V DC, 0.3 A
ABB Group
3th May Slide 10
Shunt opening
release
(type 2 actuator)
Shunt closing
release
(type 2 actuator)
Low Voltage:
High Voltage:
Undervoltage
release
(type 2 actuator)
24 V DC
48-60 V AC/DC
110-220 V AC/DC
Spring
charging
motor
Accessories
Overview
Voltage
indicators
Capacitive
dividers integrated
in the apparatus
bottom isolators
Fuse blown
signalling contact
Contact to
remote the signal
when a fuse
blows
Temperaturecompensated
pressure switch
Temperaturecompensated
device
Three levels:
ok, low, very low
Manometer
Temperaturecompensated
scale
Indication from
remote
(on request)
Key locks
and padloks
Key locks
Lock in open or
closed position
Up to 2 for line
Up to 2 for earth
Standard, Ronis
and Profalux
Possibility to have
up to 3 padlocks
ABB Group
3th May Slide 11