Beruflich Dokumente
Kultur Dokumente
AIR-CONDITIONING SYSTEM
ChBE 343
Department of Chemical and Biomolecular Engineering
Rice University
Revised 11 March 2013
A. PURPOSE OF EXPERIMENT
To carry out heat and material balances on a refrigerant evaporator, determine the coefficient of perfomance of an
air-conditioning system and how it is influenced by various parameters, and to study the characteristics of a typical
expansion valve.
C. REFRIGERANT CIRCUIT
The refrigerant is chiorodifluoromethane (CHCIF2) also known as R-22, and by trade names such as Freon-22. A
diagram showing the ideal thermodynamic cyclic path taken by the refrigerant is shown in Figure 1. Thermodynamic
data for this refrigerant are widely available and may be obtained from any reliable source, including the NIST Chemistry Webbook1 may be used.
Z = 0.03204 Z US GPH
10 11235.8
All essential temperatures are measured by copper-constantan thermocouples. The temperature probe locations are indicated in the diagrams in the appendix. A rotary switch is provided to switch among the temperature probes. Proper
Refrigerant Flow Rate =
wet-bulb temperature readings require that the water reservoirs (inverted funnels on the back of the unit) are filled to
the line with de-ionized water.
Several measuring devices are associated with the inside are circuit. Inside air is drawn in through a filter, passes
through a reducer and a honeycomb straightener, and flows through an 11 x 11 (inside dimensions) wooden duct to
a test section where the velocity profile can be measured with an anemometer whose range is (0-25 ft/sec) and wet and
dry thermocouples provide temperature and humidity information. The air then flows across the refrigerant evaporator
where some water drops out. Next comes another measuring zone where wet and dry thermocouples are located.
Finally, the air is moved through a blower and exhausted into the room. The air flow rate is changed by adjusting the
damper at the exit of the blower.
Upstream of the anemometer in the test section is another anemometer (with range 0-50 ft/sec). This anemometer enables the center line velocity to be maintained constant (by adjusting the damper if necessary) while velocity profiles
are being measured with the other.
The anemometers are EXPENSIVE and DELICATE. Adequate velocity profile information is already available. Please
do not adjust the position of these devices. To obtain the average air velocity from the measured centerline velocity,
use
v = Cvo
with C = 0.8 unless instructed otherwise by the teaching staff.
There are wet and dry thermocouples (all referenced to 32 F) which register air properties before and after passage
through the refrigerant evaporator.
The condensate water which leaves the evaporator should be measured, recorded and discarded about every 15 minutes, simultaneously with other measurements.
There are two meters that measure power. Each has a digital gauge, but generally you should rely on the reading from
the rotating disk power meters. The smaller meter on the left reads the power from the compressor motor and the condensing unit fan. For your calculations you should neglect the fan and assume that the compressor power dominates.
The meter on the right measures the power to the inside blower motor.
The dials (designed to be read periodically by meter-readers) rotate much too slowly to be useful in this application.
The main disk is used. Every revolution of the disk corresponds to 3.6 watt-hours for the compressor meter and 14.4
watt-hours for the blower power meter. The power consumed over a small time period may be determined by timing
a few revolutions, or, in the case of the small Kw-H meter by reading the associated pulse counter. Each revolution of
the main disk gives rise to 8 pulses being sent to a pulse counter. This counter counts for one minute and then displays.
The power consumption corresponding to a reading on the pulse counter is therefore,
Power =
(60)(3.6)
= 27 watts
8
measurements from all of the temperature ports and all of the flows mentioned in the previous section. This includes
the power measurements for the compressor and the air blower. You also need to record the pressure of the condenser
and evaporator. As mentioned above, you should check and measure the condensate accumulation at about fifteen
minute intervals. Each run should be about 90 minutes long to allow for accurate condensation rate measurements. It
will take the unit a while to reach steady-state operation.
G. HELPFUL HINTS
VERY IMPORTANT: You must not open or close any valves on the air conditioner unit, with the exception of
the drain on the condesate collector.
Keep in mind that it is an honor code violaton to refer to or use any materials from previous years courses. For
the case of this lab, it will result in some very serious (and obvious) mistakes.
Each team of three is responsible for completing both the Expansion Valve Experiment and the Air Conditioning
Experiment and include both in your report.
You should complete sample calculations of your expectations for a typical humidity level before you come to
the lab.
Additional hints can be found in the Appendix.
Bibliography
[1] P. J. Linstrom and W. G. Mallard, editors. NIST Chemistry WebBook, NIST Standard Reference Database Number
69. National Institute of Standards and Technology, Gaithersburg MD, 20899, June 2005.
[2] J.M. Smith, H.C. Van Ness, and M.M. Abbott. Introduction to chemical engineering thermodynamics. McGrawHill chemical engineering series. McGraw-Hill, 2005.
[3] R.H. Perry and D.W. Greeen. Perrys Chemical Engineers Handbook, Eighth Edition. McGraw-Hill Education,
2007.
[4] W.L. McCabe, J.C. Smith, and P. Harriott. Unit Operations of Chemical Engineering. McGraw-Hill Chemical
Engineering Series. McGraw-Hill, 2005.