This manual describes the details of Diagnostic Information messages displayed in the Diagnostic Information Window of SCS Maintenance Support Tool or System Alarm View of HIS.
The table of the contents of this manual can be used as message number index.
This manual consists of the following chapters:
Chapter 1 : This chapter explains how to refer to the Diagnosis Information in SENG.
Chapter 2 : This chapter explains the details about SCS Messages.
Chapter 3 : This chapter explains the details about common messages of CENTUM VP or
CS 3000 and SENG.
Appendix : A list of the alarm class for the corresponding message number is provided.

Media No. IM 32Q02B10-31E (CD)


4th Edition : Jan. 2015 (YK)
All Rights Reserved Copyright 2011, Yokogawa Electric Corporation

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

ii

Safety Precautions for Use


n Safety, Protection, and Modification of the Product

To protect the system controlled by the Product and the Product itself and to ensure safe
operation, please observe the safety precautions described in this Manual. Yokogawa
Electric Corporation ("YOKOGAWA") assumes no liability for safety if users fail to observe
the safety precautions and instructions when operating the Product.

If the Product is used in a manner not specified in the User's Manuals, the protection provided by the Product may be impaired.

If any protection or safety circuit is required for the system controlled by the Product or for
the Product itself, please install it externally.

Use only spare parts that are approved by YOKOGAWA when replacing parts or consumables of the Product.

Do not use the Product and its accessories such as power cords on devices that are not
approved by YOKOGAWA. Do not use the Product and its accessories for any purpose
other than those intended by YOKOGAWA.

Modification of the Product is strictly prohibited.

The following symbols are used in the Product and User's Manuals to indicate the accompanying safety precautions:
Indicates that caution is required for operation. This symbol is labeled on the Product to refer the user to the User's Manuals for necessary actions or behaviors in
order to protect the operator and the equipment against dangers such as electric
shock. In the User's Manuals, you will find the precautions necessary to prevent
physical injury or death, which may be caused by accidents, such as electric
shock resulting from operational mistakes.
Identifies a protective conductor terminal. Before using the Product, you must
ground the protective conductor terminal to avoid electric shock.
Identifies a functional grounding terminal. A terminal marked "FG" also has the
same function. This terminal is used for grounding other than protective grounding.
Before using the Product, you must ground this terminal.
Indicates an AC supply.
Indicates a DC supply.
Indicates the ON position of a power on/off switch.
Indicates the OFF position of a power on/off switch.

n Notes on Handling User's Manuals

Hand over the User's Manuals to your end users so that they can keep the User's Manuals on hand for convenient reference.

Thoroughly read and understand the information in the User's Manuals before using the
Product.

For the avoidance of doubt, the purpose of the User's Manuals is not to warrant that the
Product is suitable for any particular purpose but to describe the functional details of the
Product.

Contents of the User's Manuals are subject to change without notice.

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

iii

Every effort has been made to ensure the accuracy of contents in the User's Manuals.
However, should you have any questions or find any errors, contact us or your local distributor. The User's Manuals with unordered or missing pages will be replaced.

n Warning and Disclaimer

Except as specified in the warranty terms, YOKOGAWA shall not provide any warranty for
the Product.

YOKOGAWA shall not be liable for any indirect or consequential loss incurred by either
using or not being able to use the Product.

n Notes on Software

YOKOGAWA makes no warranties, either expressed or implied, with respect to the Software Product's merchantability or suitability for any particular purpose, except as specified in the warranty terms.

Purchase the appropriate number of licenses of the Software Product according to the
number of computers to be used.

No copy of the Software Product may be made for any purpose other than backup; otherwise, it is deemed as an infringement of YOKOGAWA's Intellectual Property rights.

Keep the software medium of the Software Product in a safe place.

No reverse engineering, reverse compiling, reverse assembling, or converting the Software Product to human-readable format may be performed for the Software Product.

No part of the Software Product may be transferred, converted, or sublet for use by any
third-party, without prior written consent from YOKOGAWA.

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

iv

Documentation Conventions
n Symbols
The following symbols are used in the User's Manuals.
Identifies instructions that must be observed to avoid physical
injury, electric shock, or death.
Identifies instructions that must be observed to prevent damage
to the software or hardware, or system failures of the Product.
Identifies important information required to understand operations or functions.
Identifies additional information.

Identifies referenced content.


In online manuals, you can view the referenced content by clicking the links that are in green text. However, this action does not
apply to the links that are in black text.

n Typographical Conventions
The following typographical conventions are used throughout the User's Manuals.

Commonly Used Conventions throughout the User's Manuals

Mark
Indicates that a space must be entered between character strings.
Example:
.ALPIC010-SC

Character string enclosed by braces { }


Indicates character strings that may be omitted.
Example:
.PRTAG{.sheet name}

Conventions Used to Show Key or Button Operations

Characters enclosed by brackets [ ]


When characters are enclosed by brackets in the description of a key or button operation,
it indicates a key on the keyboard, a button name in a window, or an item in a list box
displayed in a window.
Example:
To alter the function, press the [ESC] key.

Conventions of a User-defined Folder

User-defined folder name enclosed by parenthesis ( )


User definable path is written in a pair of parentheses.
Example:

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

v
(RS Project Folder)\SCS0101
If the RS Project Folder is C:\MYRSPJT, the above path becomes C:
\MYRSPJTSCS0101.

n Drawing Conventions
Drawings used in the User's Manuals may be partially emphasized, simplified, or omitted for
the convenience of description.
Drawings of windows may be slightly different from the actual screenshots with different settings or fonts. The difference does not hamper the understanding of basic functionalities and
operation and monitoring tasks.

n Integration with CENTUM


The Product can be integrated with CENTUM VP or CENTUM CS 3000. In the User's Manuals, the integration with CENTUM VP or CENTUM CS 3000 is referred to as "Integration with
CENTUM."
In the User's Manuals, the explanations for integrating the Product with CENTUM VP or
CENTUM CS 3000, the glossary for various features of CENTUM VP is used instead of the
glossary for CENTUM CS 3000. For example, the term "CENTUM VP System Alarm View" is
used instead of "CENTUM CS 3000 System Alarm window." Nevertheless, if the features for
integrating the Product with CENTUM VP and CENTUM CS 3000 are different, both features
will be explained separately.

SEE
ALSO

For more information about the functions and usage of CENTUM VP components for integrating the Product
with CENTUM VP, refer to:
User's Manuals (IM), Technical Information (TI), and General Specifications (GS) of CENTUM VP
For more information about the features and usage of CENTUM CS 3000 components for integrating the
Product with CENTUM CS 3000, refer to:
User's Manuals (IM), Technical Information (TI), and General Specifications (GS) of CENTUM CS 3000

n Explanation of Hardware and Software Behaviors in the User's


Manuals
In the User's Manuals, system behaviors are explained assuming that the latest versions of
YOKOGAWA software and hardware at the time of publication of the User's Manuals are installed.
If additional precise information about the safety of legacy versions of software or hardware is
required, a link to the corresponding explanation is provided. Please refer to the information
according to your system.

n Station Types
A safety control station (hereafter referred to as SCS) is named according to the type of the
safety control unit used in it.
Table Info-1 Names of SCS and Safety Control Unit Used
Name of SCS

Model of the safety control unit

SCSV1-S

SSC10S/SSC10D

SCSP1-S

SSC50S/SSC50D

SCSP2-S

SSC60S/SSC60D

SCSU1-S

SSC57S/SSC57D

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

vi
In the User's Manuals, the following abbreviations may be used to describe functions of these
SCS as a whole.

SCSV1: Abbreviation of SCSV1-S

SCSP1: Abbreviation of SCSP1-S

SCSP2: Abbreviation of SCSP2-S

SCSU1: Abbreviation of SCSU1-S

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

vii

Copyright and Trademark Notices


n All Rights Reserved
The copyright of the programs and online manuals contained in the software medium of the
Software Product shall remain with YOKOGAWA.
You are allowed to print the required pages of the online manuals for the purposes of using or
operating the Product; however, reprinting or reproducing the entire document is strictly prohibited by the Copyright Law.
Except as stated above, no part of the online manuals may be reproduced, transferred, sold,
or distributed to a third party in any manner (either in electronic or written form including, without limitation, in the forms of paper documents, electronic media, and transmission via the
network). Nor it may be registered or recorded in the media such as films without permission.

n Trademark Acknowledgments

CENTUM, ProSafe, Vnet/IP, and STARDOM are registered trademarks of YOKOGAWA.

Microsoft, Windows, Windows Vista, Windows Server, Visual Basic, Visual C++, and Visual Studio are either registered trademarks or trademarks of Microsoft Corporation in the
United States and other countries.

Adobe, Acrobat, and Adobe Reader are registered trademarks of Adobe Systems Incorporated.

Ethernet is a registered trademark of Xerox Corporation.

HART is a registered trademark of the HART Communication Foundation.

Modicon and Modbus are registered trademarks of Schneider Electric SA.

All other company and product names mentioned in the User's Manuals are trademarks
or registered trademarks of their respective companies.

TM or mark are not used to indicate trademarks or registered trademarks in the User's
Manuals.

Logos and logo marks are not used in the User's Manuals.

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

Toc-1

Messages
IM 32Q02B10-31E 4th Edition

CONTENTS
1.

2.

Referencing Diagnostic Information Messages on the SENG......... 1-1


1.1

How to Display the Diagnostic Information Window.................................1-2

1.2

Diagnostic Information Window..................................................................1-3

1.3

Printout of Diagnostic Information Message............................................. 1-4

Details of Output Messages Specific to the SCS.............................. 2-1


2.1

System Alarms (Message Numbers 4101 through 4199).......................... 2-2


No. 4101 Inter-SCS safety communication error information ....................... 2-2
No. 4102 Inter-SCS safety communication error recovery information .........2-3
No. 4103 Variable lock .................................................................................. 2-3
No. 4104 Cancellation of variable lock ..........................................................2-4
No. 4105 I/O module lock ............................................................................. 2-4
No. 4106 Cancellation of I/O module lock .....................................................2-5
No. 4107 All input module locks ....................................................................2-5
No. 4108 Cancellation of all input module locks ........................................... 2-5
No. 4109 All output module locks ................................................................. 2-5
No. 4110 Cancellation of all output module locks ......................................... 2-5
No. 4111 All module locks ............................................................................ 2-5
No. 4112 Cancellation of all module locks .................................................... 2-6
No. 4113 Number of locks exceeded ............................................................2-6
No. 4114 Recovery from exceeded number of locks .................................... 2-6
No. 4115 Override setting ............................................................................. 2-6
No. 4116 Cancellation of override .................................................................2-6
No. 4117 Information of change to override enabled state ........................... 2-7
No. 4118 Information of change to override disabled state .......................... 2-7
No. 4119 Number of overrides exceeded ..................................................... 2-7
No. 4120 Recovery from exceeded number of overrides ............................. 2-7
No. 4121 Number of enabled overrides exceeded ....................................... 2-8
No. 4122 Recovery from exceeded number of enabled overrides ................2-8
No. 4123 Number of active PASSWD FBs exceeded ................................... 2-8
No. 4124 Recovery from exceeded number of active PASSWD FBs ........... 2-8
No. 4125 I/O module channel error occurred ................................................2-9
No. 4126 Recovery from I/O module channel error ...................................... 2-9
No. 4127 Setting PASSWD FB to ON ........................................................... 2-9
IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

Toc-2
No. 4128 Setting PASSWD FB to OFF ......................................................... 2-9
No. 4129 GPS interface unit error ...............................................................2-10
No. 4130 Recovery of GPS interface unit ................................................... 2-10
No. 4131 Communication module lock ....................................................... 2-10
No. 4132 Cancellation of Communication module lock .............................. 2-10
No. 4133 Information of a diagnosis error in the received data of SCS Link
Transmission. .............................................................................. 2-11
No. 4134 Information of a diagnosis error recovery in the received data of
SCS Link Transmission. .............................................................. 2-12
No. 4135 SCS Link Transmission data lock ................................................2-12
No. 4136 Cancellation of SCS Link Transmission data lock ....................... 2-13
No. 4137 Number of Locked Stations in SCS Link Transmission Exceeded .....
..................................................................................................... 2-13
No. 4138 Recovery from exceeded number of locked stations in SCS Link
Transmission ............................................................................... 2-13
No. 4139 Inter-SCS Safety Communication data lock ................................ 2-13
No. 4140 Cancellation of Inter-SCS Safety Communication data lock ....... 2-14
No. 4141 Number of locked stations in Inter-SCS Safety Communication
exceeded .....................................................................................2-14
No. 4142 Recovery from exceeded number of locked stations in Inter-SCS
Safety Communication ................................................................ 2-14
No. 4143 Start of automatic scan period extension .................................... 2-14
No. 4144 Cancellation of automatic scan period extension ........................ 2-15
No. 4145 Abnormal calculation occurred .................................................... 2-15
No. 4146 Recovery from abnormal calculation ........................................... 2-15
No. 4151 Information of retainable data initialization .................................. 2-16
No. 4152 Online change of scan period ......................................................2-16
No. 4153 Information of Inter-SCS Safety Communication data lock time-up ...
..................................................................................................... 2-16
No. 4154 Information of forced cancellation of Inter-SCS Safety
Communication data locks .......................................................... 2-16
No. 4155 Information of SCS Link Transmission status change. ................2-17
No. 4156 Information of SCS Link Transmission definition change ............ 2-17
No. 4157 Information of SCS Link Transmission wiring change ................. 2-17
No. 4158 Information of SCS Link Transmission lock time-up ....................2-17
No. 4159 Information of forced cancellation of SCS Link Transmission locks ...
..................................................................................................... 2-17
No. 4160 Invalid password for Manual Operation FB ................................. 2-18
No. 4161 Information of Output IOM Shutdown ..........................................2-18
No. 4162 Information of communication I/O definition change ................... 2-18
No. 4163 Information of communication I/O wiring change ........................ 2-18
No. 4164 Information of disabling security level change .............................2-18
No. 4165 Information of enabling security level change ............................. 2-19
No. 4166 Information of communication module lock time-up .................... 2-19

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

Toc-3
No. 4167 Information of forced cancellation of communication module locks ...
..................................................................................................... 2-19
No. 4168 Information of tag name change by online change download ............
..................................................................................................... 2-19
No. 4169 NVRAM diagnosis error ...............................................................2-19
No. 4170 Flash memory diagnosis error .....................................................2-20
No. 4172 Information of resource change by online change download ...... 2-20
No. 4173 Completion of writing to flash memory ........................................ 2-20
No. 4174 Failed to write to flash memory ................................................... 2-21
No. 4175 Failed to update external communication data ............................2-21
No. 4177 Information of SCS security level change ................................... 2-21
No. 4178 Information of security level time-up ............................................2-22
No. 4179 Information of communication I/O module output enabled operation .
..................................................................................................... 2-22
No. 4180 Information of password change ................................................. 2-22
No. 4181 Information of output enabled operation ......................................2-22
No. 4182 Information of output module start operation ...............................2-23
No. 4183 Request to upload SOE to SENG ............................................... 2-23
No. 4184 Notification on saving SOE trip signal file in SCS ....................... 2-23
No. 4185 Information of variable value change .......................................... 2-23
No. 4186 Information of lock time-up .......................................................... 2-24
No. 4187 Information of forced cancellation of locks .................................. 2-24
No. 4188 Start of online change download ................................................. 2-24
No. 4189 Completion of online change download ...................................... 2-24
No. 4190 Online change download error .................................................... 2-24
No. 4191 Completion of I/O definition rewriting .......................................... 2-25
No. 4192 Information of override state time-up ...........................................2-25
No. 4193 Information of forced release of all overrides .............................. 2-25
No. 4194 Information of override enabled state time-up .............................2-25
No. 4195 Information of communication I/O data status change ................ 2-26
No. 4196 Invalid password for PASSWD FB ...............................................2-26
No. 4197 Information on active PASSWD FB time-up ................................ 2-26
No. 4198 Information on forced reset of PASSWD FB ................................2-26
No. 4199 Override communication error .....................................................2-27

3.

Details of Output Messages in Common with CENTUM................... 3-1


3.1

Safety Control Station Error Occurrence and Recovery Messages


(Message Numbers 0001 through 0094)..................................................... 3-2
No. 0001 Reset start of safety control station ............................................... 3-2
No. 0003 Safety control station automatic reset start ................................... 3-2
No. 0005 Power ON initial cold start of safety control station ....................... 3-2
No. 0009 Transfer of control right of safety control station ........................... 3-2
No. 0011 Fail information of safety control station ........................................3-3
No. 0013 AC power supply failure of safety control station .......................... 3-4

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

Toc-4
No. 0015 Self-diagnosis error of clock inside CPU module .......................... 3-4
No. 0017 ROM checksum error of CPU module ...........................................3-4
No. 0021 Internal task error of safety control station .................................... 3-5
No. 0023 Mapping block fatal error ...............................................................3-5
No. 0025 Function control word error ........................................................... 3-5
No. 0027 Mapping block record information error .........................................3-5
No. 0033 Online downloading abnormal end ................................................3-5
No. 0041 Safety control station fan alarm .....................................................3-6
No. 0042 Recovery from safety control station fan alarm ............................. 3-6
No. 0043 Safety control station temperature alarm ...................................... 3-6
No. 0044 Recovery from safety control station temperature alarm ...............3-7
No. 0045 Power supply module alarm of safety control station .................... 3-7
No. 0046 Recovery from power supply module alarm of safety control station .
....................................................................................................... 3-7
No. 0047 Battery alarm of CPU module ........................................................3-7
No. 0048 Recovery from battery alarm of CPU module ................................3-8
No. 0055 Information of same frame reception in online change download
communication .............................................................................. 3-8
No. 0057 Information of online change download error ................................ 3-8
No. 0059 Information of recovery from node power failure ...........................3-8
No. 0063 ESB bus error ................................................................................3-8
No. 0064 Normal recovery of ESB bus ......................................................... 3-9
No. 0065 Failure of ESB Bus Interface module (SSB401) of node ...............3-9
No. 0066 Normal recovery of ESB Bus Interface module (SSB401) of node ....
..................................................................................................... 3-10
No. 0067 Failure of power supply module of node ..................................... 3-10
No. 0068 Normal recovery of power supply module of a node ................... 3-10
No. 0069 Error before database download to I/O module .......................... 3-10
No. 0081 Failure of I/O module ................................................................... 3-11
No. 0082 Normal recovery of I/O module ................................................... 3-13
No. 0083 I/O module database error occurred ........................................... 3-13
No. 0085 I/O module communication error occurred .................................. 3-13
No. 0086 Recovery from I/O module communication error .........................3-13
No. 0087 Node error occurred .................................................................... 3-13
No. 0088 Normal recovery of node ............................................................. 3-14
No. 0089 Subsystem communication error .................................................3-14
No. 0090 Subsystem communication recovered ........................................ 3-15
No. 0093 CPU nodes housekeeping unit error ...........................................3-15
No. 0094 Normal recovery of CPU nodes housekeeping unit ....................3-15
3.2

Safety Control Station Status Change Related Messages (Message


Numbers 0450 through 0480).................................................................... 3-16
No. 0450 Copy program and database on control side of safety control station
to standby side ............................................................................ 3-16

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

Toc-5
No. 0451 Information of switching of control side of safety control station ........
..................................................................................................... 3-16
No. 0452 Information of switching of standby side of safety control station .......
..................................................................................................... 3-16
No. 0459 Information on I/O module service side .......................................3-16
No. 0460 Information of I/O module out service ......................................... 3-16
No. 0471 Normal completion of online change download ...........................3-17
No. 0474 Information of tag list duplicate error ........................................... 3-17
No. 0475 Start of database download to I/O module .................................. 3-17
No. 0476 Normal completion of database download to I/O module ............3-17
No. 0477 Database download error to I/O module ..................................... 3-17
No. 0480 Heavy load on periodical processing ...........................................3-18
3.3

Safety Control Station Related Messages (Message Numbers 0727


through 0787).............................................................................................. 3-19
No. 0727 Block mode recovery error information ....................................... 3-19
No. 0743 Self-diagnostic SEN-BUS Failure ................................................3-19
No. 0744 Self-diagnostic SEN-BUS Recovery ............................................3-19
No. 0749 Self-diagnosis detected an I/O Error ........................................... 3-19
No. 0750 I/O Recovery from the error detected by self-diagnosis .............. 3-20
No. 0751 Time self-diagnostic testing error ................................................ 3-20
No. 0753 Communication Overload ............................................................3-20
No. 0767 Faulty one ESB bus in CPU module ........................................... 3-20
No. 0768 Single ESB bus in CPU module Recovery .................................. 3-20
No. 0787 Self-diagnosis detected I/O error in CPU module ....................... 3-21

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

TocApp.-1

Messages
IM 32Q02B10-31E 4th Edition

CONTENTS
Appendix
Appendix 1. Alarm Class..................................................................... App.1-1

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<1. Referencing Diagnostic Information Messages on the SENG>

1.

1-1

Referencing Diagnostic Information


Messages on the SENG
You can view diagnostic information messages on the Diagnostic Information window, which
is called up from SCS Status Overview window.

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

1-2

<1.1 How to Display the Diagnostic Information Window>

1.1

How to Display the Diagnostic Information


Window
You can display the Diagnostic Information window from the SCS Status Overview window.
1.

In the SCS Status Overview window, select an SCS.


The following figure shows an example of the SCS Status Overview window.
RS project name
Diagnostic information button
Domain number

Status of control bus with SENG

SCS Status Overview


File View Window Tool

MYRSPJT
Station

Domain:01

V net 1

V net 2

SCS Status

CPU Status

Ready
R-Fail

Ready

Station name SCS status


Diagnostic information mark

CPU status

Comment

Station Comment

Figure 1.1-1 SCS Status Overview Window and Diagnostic Information button

2.

Click the [Diagnostic Information] button on the tool bar.


The Diagnostic Information window is displayed, showing the diagnostic information messages of the station you have selected.

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

1-3

<1.2 Diagnostic Information Window>

1.2

Diagnostic Information Window


The Diagnostic Information window is shown in the figure below.
Information

Help button

Toolbar

Alarm class

Diagnostic Information
Message

Diagnostic Information-[SCS0101 1.3]


File View Operation Help

Number

Date

Class

Message

4125

5/30/2008 10:26:19.720 AM

SCS0101 IOM Channel Error NO.

4125

5/30/2008 10:26:19.720 AM

SCS0101 IOM Channel Error NO.

0082

5/30/2008 10:26:17.620 AM

SCS0101 IOM Recover F10 NODE

0476

5/30/2008 10:26:09.131 AM

SCS0101 IOM Download Complete.

0475

5/30/2008 10:26:04.235 AM

SCS0101 IOM Download Start F10.

0082

5/30/2008 10:25:55.320 AM

SCS0101 IOM Recover F10 NODE

0459

5/30/2008 10:25:55.320 AM

SCS0101 IOM In Service F10 NO.

0476

5/30/2008 10:25:51.931 AM

SCS0101 IOM Download Complete.

0475

5/30/2008 10:25:48.388 AM

SCS0101 IOM Download Start F10.

0047

5/30/2008 10:25:36.851 AM

SCS0101 LEFT Battery Alarm

4129

5/30/2008 10:25:33.328 AM

SCS0101 GPS Interface Unit Error

0081

5/30/2008 10:25:33.320 AM

SCS0101 IOM Fail FIO NODE 0.

Number

Date

Class

Message

30/95

Alarm marks
Warning

Status bar

Number of currently
generated messages

Figure 1.2-1 Diagnostic Information Window

SEE
ALSO

For more information about the diagnostic information window, refer to:
3.2, Displaying SCS Diagnostic Information in Utilities and Maintenance Reference (IM
32Q04B20-31E)

n How to Display the Help Dialog Box


The details of Diagnostic Information window is displayed in the Help dialog box.

SEE
ALSO

1.

In the Diagnostic Information window, select a diagnostic information message.

2.

Click the [Help] button on the tool bar.


The Help dialog box is displayed.

For more information about the Help dialog box, refer to:
3.2.3, Diagnostic Information Message Help Function in Utilities and Maintenance Reference (IM
32Q04B20-31E)

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

1-4

<1.3 Printout of Diagnostic Information Message>

1.3

Printout of Diagnostic Information


Message
The printout of diagnostic information messages is shown in the figure below.
5/30/2008 2:02:44 PM
Search condition

SCS0101 1.3

Format

Alarm mark, Message number, Date, Class, Message

Selection mark

New Alarm:No mark, Acknowledged:A, Deleted:D

page 1/1

0081 5/30/2008 9:00:15.980 AM 1 SCS0101 IOM Fail


FIO NODE 01 SLOT 05 Code = 5103
0083 5/30/2008 9:00:15.980 AM 2 SCS0101 IOM Configuration Error FIO NODE 01 SLOT 05
0081 5/30/2008 9:00:15.980 AM 1 SCS0101 IOM Fail
FIO NODE 01 SLOT 03 Code = 5103
0083 5/30/2008 9:00:15.980 AM 2 SCS0101 IOM Configuration Error FIO NODE 01 SLOT 03
0081 5/30/2008 9:00:15.980 AM 1 SCS0101 IOM Fail
FIO NODE 01 SLOT 01 Code = 5103
0083 5/30/2008 9:00:15.980 AM 2 SCS0101 IOM Configuration Error FIO NODE 01 SLOT 01
0451 5/30/2008 9:00:00.465 AM 2 SCS0101 LEFT
Control
0005 5/30/2008 9:00:00.465 AM 2 SCS0101 Power ON (Cold Start)
0013 5/30/2008 9:00:00.465 AM 2 SCS0101 AC Fail (Time 1/1/1970 9:00:00 AM)

Figure 1.3-1 Printout of Diagnostic Information Message

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-1

<2. Details of Output Messages Specific to the SCS>

2.

Details of Output Messages Specific


to the SCS
This section describes the details of output messages specific to the SCS. The format for
each message follows the example shown below, Cause, Action, Remark, Note and Error
code may be omitted, depending on the message.

No.xxxx
Message name

Name of the message.


Example: Information of security level time-up

Printing example

Indicates an example of print or display.


Example: SCS0101 Security Level = 1 Elapsed the Specified Period = 08 :
00 : 00
In this document, space in messages and the leading 00 of various numbers
may be different from actual printing examples to the extent they do not impair
the understanding of messages.

Meaning

Meaning of a message.
Example: The security level is set to 1 for the duration exceeding the time
limit (8 hours in the above example) specified in SYS_SECURE Function
Block (hereinafter referred to as FB).

Cause

Describes the cause of occurrence. The description may be omitted depending on the message.
Example: The security level has not been reverted.

Action

Describes the action to take. The description may be omitted depending on


the message.
Example: Revert the security level to 2.

Remark

Describes an item(s) related to the message. The description may be omitted


depending on the message.

Note

Describes cautions. The description may be omitted depending on the message.

Error code

Describes details of the error code included in the message, if any. The description may be omitted depending on the message.

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-2

<2.1 System Alarms (Message Numbers 4101 through 4199)>

2.1

System Alarms (Message Numbers 4101


through 4199)
This section describes system alarm messages issued from the SCS.

No.4101
Message name

Inter-SCS safety communication error information

Printing example

SCS0101 Inter-SCS Safety Communication Receive Error Variable =


C0102001 Code = 5041-8000

Meaning

An error is detected during inter-SCS safety communication. The erroneous


binding variable (C0102001 in the above example) is included in the message.

Cause

The following causes may be considered. Check the error codes for more detail.
Stop/restart on the producing side SCS
Problem in the communication path
Change in the application of inter-SCS safety communication

Remark

Inter-SCS safety communication

Error code

The first four digits are an error code, and the next four digits are a cause
code. The error detail can be found from the descriptions of the both codes.
The error codes and cause codes are listed below.
The error code represents the type of error. The following table explains each
error code and the action you can take to fix the error.

Table 2.1-1 Message No. 4101 - Error Code List


Code (hexadecimal)

Description

Action

5040

An error that occurs


when an application is
created incorrectly.

5041

No data received within the reception interval timeout value.

5042

Time diagnosis found


an error.

5043

Communication protocol error (internal error)

Check the application logic.

Check the producing side SCS and the communication


path.

Record the message content and report to Yokogawas


service department.

The cause code represents the event that caused the problem and is logical
OR of the following codes.
Table 2.1-2 Message No. 4101 - Cause Code List
Code (hexadecimal)

Errors

Description

Presumed cause

8000

No response

Communication stopped and


data no longer arrived.

Communication was cut off,


or the producing side stopped.

4000

Reset detection

The restart on the producing


side was detected.

Restart on the producing side


Continues on the next page

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-3

<2.1 System Alarms (Message Numbers 4101 through 4199)>


Table 2.1-2 Message No. 4101 - Cause Code List (Table continued)
Code (hexadecimal)

Errors

Description

Presumed cause

2000

The CRC code of delay-relaCRC error in delay-related dited diagnosis information is


agnosis information
not correct.

1000

CRC mismatch

0400

Communication for acquiring


Equalization error of delay-redelay-related diagnosis inforlated diagnosis information
mation stopped.

0200

Variable name error

The variable name is not


Cddssxxx.

0100

Address error

The domain and station numAn application was created


bers are different from the
incorrectly.
binding variable.

0040

Transmission delay occurred

Communication was updated


later than the transmission
Communication delay
delay timeout time.

0020

Date/time error on the producing side

An error occurred in time


management on the producing side, so the date/time is
not reliable.

0010

Date/time error on the consuming side

An error occurred in time


management on the consum- Date/time management error
ing side, so the date/time is
on the producing side
not reliable.

0004

Different FB ID information

The FB ID information is different from the initial value.

Internal error

0001

Data type error

The data type does not


match.

Internal error

The communication content


and CRC do not match.

Temporary communication
error
Temporary communication
error
Communication was interrupted or the producer SCS is
stopped.
An application was created
incorrectly.

Date/time management error


on the producing side

No.4102
Message name
Printing example
Meaning
Cause

Inter-SCS safety communication error recovery information


SCS0101 Inter-SCS Safety Communication Receive Recover Variable =
C0102001
An inter-SCS safety communication error for the variable (C0102001 in the
above example) recovered. (This is a recovery message of No. 4101.)
The following causes may be considered.
Recovery of the producing side SCS
Recovery of the communication path
Recovery of the application of inter-SCS safety communication

Remark

Inter-SCS safety communication

No.4103
Message name
Printing example

Variable lock
In the case of I/O variables:
SCS0101 Variable Locked Variable=VAR001 NODE 01 SLOT 02 CH 03
In the case of internal variables:
IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-4

<2.1 System Alarms (Message Numbers 4101 through 4199)>

SCS0101 Variable Locked Variable=VAR001


Meaning

Remark
Note

The variable (VAR001 in the above example) was locked by operation from
the SENG. In the case of I/O variables, the channel position (node 1, slot 2
and channel 3 in the above example) corresponding to the variable is also included in the message.
Forcing function
Be sure to unlock the variables that were locked.
If an IO_BOOL type or IO_REAL type variable is locked, the member variable
v or status will be indicated in the format of [Variable=VAR001.v] at the position of the variable name in the system alarms. If the variable is not wired to
the channel, the member variable v will be always displayed. Nevertheless, in
any of the above cases, the whole IO_BOOL type or IO_REAL type variable
will be locked.
When locking an array element, the whole array will be locked. Under this circumstance, the variable name displayed in the system alarm will be attached
with the array element subscript as [Variable=VAR001[1]].

No.4104
Message name

Cancellation of variable lock

Printing example

In the case of I/O variables:


SCS0101 Variable Unlocked Variable=VAR001 NODE 01 SLOT 02 CH 03
In the case of internal variables:
SCS0101 Variable Unlocked Variable=VAR001

Meaning

Remark
Note

The lock of the variable (VAR001 in the above example) was cancelled by operation from the SENG. In the case of I/O variables, the channel position
(node 1, slot 2 and channel 3 in the above example) corresponding to the variable is also included in the message.
Forcing function
If an IO_BOOL type or IO_REAL type variable is unlocked, the member variable v or status will be indicated in the format of [Variable=VAR001.v] at the position of the variable name in the system alarms. If the variable is not wired to
the channel, the member variable v will be always displayed. Nevertheless, in
any of the above cases, the whole IO_BOOL type or IO_REAL type variable
will be unlocked.
Moreover, when unlocking an array element, the whole array will be unlocked.
Under this circumstance, the variable name displayed in the system alarm will
be attached with the array element subscript as [Variable=VAR001[1]].

No.4105
Message name
Printing example
Meaning
Remark
Note

I/O module lock


SCS0101 IOM Locked NODE 01 SLOT 02
An I/O module was locked by operation from the SENG. The I/O module position (node 1 and slot 2 in the above example) is included in the message.
Forcing function
Be sure to cancel the lock of the I/O module that was locked.

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-5

<2.1 System Alarms (Message Numbers 4101 through 4199)>

No.4106
Message name
Printing example
Meaning

Remark

Cancellation of I/O module lock


SCS0101 IOM Unlocked NODE 01 SLOT 02
The lock of an I/O module was cancelled by operation from the SENG. The I/O
module position (node 1 and slot 2 in the above example) is included in the
message.
Forcing function

No.4107
Message name
Printing example
Meaning
Remark
Note

All input module locks


SCS0101 All Input IOM Locked
All input modules were locked by operation from the SENG.
Forcing function
Be sure to cancel the locks of the input modules that were locked.

No.4108
Message name
Printing example
Meaning
Remark

Cancellation of all input module locks


SCS0101 All Input IOM Unlocked
The locks of all input modules were cancelled by operation from the SENG.
Forcing function

No.4109
Message name
Printing example
Meaning
Remark
Note

All output module locks


SCS0101 All Output IOM Locked
All output modules were locked by operation from the SENG.
Forcing function
Be sure to cancel the locks of the output modules that were locked.

No.4110
Message name
Printing example
Meaning
Remark

Cancellation of all output module locks


SCS0101 All Output IOM Unlocked
The locks of all output modules were cancelled by operation from the SENG.
Forcing function

No.4111
Message name
Printing example
Meaning

All module locks


SCS0101 All IOM Locked
All I/O modules were locked by operation from the SENG.
IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-6

<2.1 System Alarms (Message Numbers 4101 through 4199)>

Remark
Note

Forcing function
Be sure to cancel the locks of the I/O modules that were locked.

No.4112
Message name
Printing example
Meaning
Remark

Cancellation of all module locks


SCS0101 All IOM Unlocked
The locks of all I/O modules were cancelled by operation from the SENG.
Forcing function

No.4113
Message name
Printing example
Meaning

Number of locks exceeded


SCS0101 Number of Locks Exceeds the Limit = 3
The total number of locked variables exceeded the limit count (3 in the above
example) specified in SYS_FORCE FB.

Cause

This is an operation from the SENG. The number of locks is too many.

Action

Cancel the variable locks.

Remark
Note

SYS_FORCE FB
Lock variables within the limit count.

No.4114
Message name
Printing example
Meaning

Cause
Remark

Recovery from exceeded number of locks


SCS0101 Number of Locks Within the Limit = 3
The total number of locked variables is reduced to within the limit count (3 in
the above example) specified in SYS_FORCE FB. (This is a recovery message of No. 4113.)
This is an operation from the SENG.
SYS_FORCE FB

No.4115
Message name
Printing example
Meaning

Remark

Override setting
SCS0101 TAG001 Overridden (Instance = OVR0001)
Override operation was performed for the override FB (OVR0001 in the above
example) that corresponds to the tag name (TAG001 in the above example)
from the HIS.
OVR_B, OVR_I, OVR_R, OVR_IB, OVR_IR, GOV_B, GOV_IB FB

No.4116
Message name
Printing example

Cancellation of override
SCS0101 TAG001 Override Released (Instance = OVR0001)
IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-7

<2.1 System Alarms (Message Numbers 4101 through 4199)>

Meaning

Remark

An override was cancelled for the override FB (OVR0001 in the above example) that corresponds to the tag name (TAG001 in the above example) from
the HIS.
OVR_B, OVR_I, OVR_R, OVR_IB, OVR_IR, GOV_B, GOV_IB FB

No.4117
Message name
Printing example
Meaning
Cause
Remark
Note

Information of change to override enabled state


SCS0101 Override Enabled
An override was enabled.
The SW input parameter of the override FB was set to TRUE.
OVR_B, OVR_I, OVR_R, OVR_IB, OVR_IR, GOV_B, GOV_IB FB
If the SW input parameter of any override FB is set to TRUE, this message is
generated.

No.4118
Message name
Printing example
Meaning
Cause
Remark
Note

Information of change to override disabled state


SCS0101 Override Disabled
An override was disabled.
The SW input parameter of all override FBs were set to FALSE.
OVR_B, OVR_I, OVR_R, OVR_IB, OVR_IR, GOV_B, GOV_IB FB
If the SW input parameters of all override FBs are set to FALSE, this message is generated.

No.4119
Message name
Printing example
Meaning

Number of overrides exceeded


SCS0101 Number of Overrides Exceeds the Limit = 3
The total number of overridden override FBs exceeded the limit count (3 in the
above example) specified in SYS_OVR FB.

Cause

This is an operation from the HIS. There are too many overrides.

Action

Cancel overrides.

Remark
Note

SYS_OVR FB
Override within the limit count.

No.4120
Message name
Printing example
Meaning

Cause

Recovery from exceeded number of overrides


SCS0101 Number of Overrides Within the Limit = 3
The total number of overridden override FBs is within the limit count (3 in the
above example) specified in SYS_OVR FB. (This is a recovery message of
No. 4119.)
This is an operation from the HIS.
IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-8

<2.1 System Alarms (Message Numbers 4101 through 4199)>

Remark

SYS_OVR FB

No.4121
Message name
Printing example
Meaning
Action
Remark
Note

Number of enabled overrides exceeded


SCS0101 Number of Enabled OVR FBs Exceeds the Limit = 3
The total number of override FBs in the override enabled state exceeded the
limit count (3 in the above example) specified in SYS_OVR FB.
Disable override FBs.
SYS_OVR FB
Enable overrides within the limit count.

No.4122
Message name
Printing example
Meaning

Remark

Recovery from exceeded number of enabled overrides


SCS0101 Number of Enabled OVR FBs Within the Limit = 3
The total number of override FBs in the override enabled state is within the
limit count (3 in the above example) specified in SYS_OVR FB. (This is a recovery message of No. 4121.)
SYS_OVR FB

No.4123
Message name
Printing example
Meaning

Number of active PASSWD FBs exceeded


SCS0101 Number of Activated PASSWD FBs Exceeds the Limit = 3
The total number of active PASSWD FBs exceeded the limit count (3 in the
above example) specified in SYS_PSWD FB.

Cause

This is an operation from the HIS. There are too many active PASSWD FBs.

Action

Inactivate (reset to OFF) the PASSWD FBs that have exceeded the limit
count.

Remark
Note

SYS_PSWD FB
Make PASSWD FBs active within the limit count.

No.4124
Message name
Printing example
Meaning

Cause
Remark

Recovery from exceeded number of active PASSWD FBs


SCS0101 Number of Activated PASSWD FBs Within the Limit = 3
The total number of active PASSWD FBs is within the limit count (3 in the
above example) specified in SYS_PSWD FB. (This is a recovery message of
No. 4123.)
Active PASSWD FBs were inactivated (reset to OFF) by operation from the
HIS.
SYS_PSWD FB

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-9

<2.1 System Alarms (Message Numbers 4101 through 4199)>

No.4125
Message name
Printing example
Meaning

Cause

I/O module channel error occurred


SCS0101 IOM Channel Error NODE 01 SLOT 02 CH 03 XXXXXXXX (YYYY)
An error occurred in an I/O module channel (node 1, slot 2 and channel 3 in
the above example). XXXXXXXX indicates an error cause, and YYYY indicates an error code.
Error codes and causes of errors are shown on the following list.

Table 2.1-3 Message No. 4125 - Error Causes


Error cause

Code

Description

TRNS+

5121

Upper limit error of the transmitter occurred.

TRNS-

5122

Lower limit error of the transmitter occurred.

IOP+

5123

Upper limit error of the IOP occurred.

IOP-

5124

Lower limit error of the IOP occurred.

Ovr Range

5125
5126

Input value is outside of the range of


input values (-25 % to 125 %). This indicates a failure of the I/O module.

Ch Fail

5127

A channel error was detected.

Action

Remark

Open circuit of DI/DO is included


in this error code.

Check to see if the connected devices and connecting cables are normal.

No.4126
Message name
Printing example
Meaning

Recovery from I/O module channel error


SCS0101 IOM Channel Recover NODE 01 SLOT 02 CH 03
An error occurred in an I/O module channel (node 1, slot 2 and channel 3 in
the above example) recovered. (This is a recovery message of No. 4125.)

No.4127
Message name
Printing example
Meaning

Setting PASSWD FB to ON
SCS0101 TAG001 PASSWD FB Set to ON (Instance = PASSWD001)
PASSWD FB (PASSWD001 in the above example) that corresponds to the tag
name (TAG001 in the above example) was set to ON (active) by operation
from the HIS.

No.4128
Message name
Printing example
Meaning

Setting PASSWD FB to OFF


SCS0101 TAG001 PASSWD FB Set to OFF (Instance = PASSWD001)
PASSWD FB (PASSWD001 in the above example) that corresponds to the tag
name (TAG001 in the above example) was inactivated (reset to OFF) by operation from the HIS.

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-10

<2.1 System Alarms (Message Numbers 4101 through 4199)>

No.4129
Message name
Printing example
Meaning
Cause

Action

Note

GPS interface unit error


SCS0101 GPS Interface Unit Error (RIGHT CPU)
A CPU module (right side in the above example) detected a GPS unit error or
time synchronization error.
The following causes may be considered.

Problem in the cable connecting the GPS unit and the GPS interface unit.

Failure of the GPS interface unit

Check to see if a cable connecting the GPS unit and the GPS interface unit is
disconnected or cut. Also, check to see if a terminator is connected to the
ends of the cable. If everything is in place, replace the GPS interface unit.
If this message is displayed while the time synchronization method is V net
time synchronization, the CPU module may be faulty.

No.4130
Message name
Printing example
Meaning

Recovery of GPS interface unit


SCS0101 GPS Interface Unit Recover (RIGHT CPU)
Time synchronization of the GPS unit detected by CPU module (right side in
the above example) is recovered. (This is a recovery message of No. 4129.)

No.4131
Message name

Communication module lock

Printing example 1

SCS0101 Communication Module All Inputs/Outputs Locked NODE 01 SLOT


02

Printing example 2

SCS0101 Communication Module All Inputs Locked NODE 01 SLOT 02

Printing example 3

SCS0101 Communication Module All Outputs Locked NODE 01 SLOT 02

Meaning

Remark
Note

The communication module was locked by operation from the SENG. The
message varies depending on the locked range (inputs and outputs, inputs only or outputs only). The location of the communication module is also included
in the messages (such as node 1, slot 2).
Forcing function, subsystem communication
Be sure to cancel the lock of the communication module that was locked.

No.4132
Message name

Cancellation of Communication module lock

Printing example 1

SCS0101 Communication Module All Inputs/Outputs Unlocked NODE 01


SLOT 02

Printing example 2

SCS0101 Communication Module All Inputs Unlocked NODE 01 SLOT 02

Printing example 3

SCS0101 Communication Module All Outputs Unlocked NODE 01 SLOT 02

Meaning

The lock of the communication module was cancelled by operation from the
SENG. The message varies depending on the locked range (inputs and out-

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-11

<2.1 System Alarms (Message Numbers 4101 through 4199)>

puts, inputs only or outputs only). The location of the communication module is
also included in the messages (such as node 1, slot 2).
Remark

Forcing function, subsystem communication

No.4133
Message name

Information of a diagnosis error in the received data of SCS Link Transmission.

Printing example

SCS0101 SCS Link Transmission Receive Error Stn(SCS)=05 Code =


5041-8000

Meaning

A diagnosis error has been found in the received data of SCS Link Transmission. The source station number (such as 05) and the station type (SCS in the
above example) that sent the Link Transmission are indicated in the message
text. The station type indicated in the message is the station type defined on
the SCS Link Transmission builder.

Cause

The following causes may be considered. Check the error codes for more detail.
Stop or restart the sender station
Problem in the communication path
The definition of the SCS Link Transmission builder may contain errors.

Remark

SCS Link Transmission

Error code

The first four digits are an error code, and the next four digits are a cause
code. The error detail can be found from the descriptions of the both codes.
The error codes and cause codes are listed below.
The error code represents the type of error. The following table explains each
error code and the action you can take to fix the error.

Table 2.1-4 Message No. 4133 - Error Code List


Code (hexadecimal)

Description

Action

5041

No data received within the reception interval timeout value.

5042

Time diagnosis found


an error.

5043

Communication protocol error (internal error)

Check the sender SCS and its communication path.

Record the message content and report to Yokogawas


service department.

The cause code represents the event that caused the problem and is logical
OR of the following codes.
Table 2.1-5 Message No. 4133 - Cause Code List
Code (hexadecimal)

Errors

Description

Presumed Cause

Communication stopped and


data no longer arrived.

Communication error, or the


sender station stopped or unable to send outputs.

8000

No response

2000

The CRC code of delay-relaCRC error in delay-related dited diagnosis information is


agnosis information
not correct.

Temporary communication
error
Continues on the next page

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-12

<2.1 System Alarms (Message Numbers 4101 through 4199)>


Table 2.1-5 Message No. 4133 - Cause Code List (Table continued)
Code (hexadecimal)

Errors

Description

Presumed Cause

1000

CRC error in communication


data

The CRC code of SCS Link


Transmission data is not correct.

Temporary communication
error, or SCS Link Transmission builder definition may
contain [Type] error.

0400

Communication for acquiring


Equalization error of delay-redelay-related diagnosis inforlated diagnosis information
mation stopped.

Communication was interrupted or the sender station is


stopped.

0100

Address error

Illegal station number

The application may contain


errors, or the setting in the
database is inconsistent with
the setting of dipswitches.

0040

Transmission delay occurred

Communication was updated


later than the transmission
Communication delay
delay timeout time.

0020

Time diagnosis error of the


sender

Time diagnosis error occurTime diagnosis error of the


red in the sender, so that this
sender
date/time may not be correct.

0010

Time diagnosis error of the


receiver

Time diagnosis error occurred in the receiver, so that


Time diagnosis error of the
this date/time may not be cor- receiver
rect.

0008

Illegal scan cycle

The detected scan cycle is


an illegal value 0.

Internal error

No.4134
Message name
Printing example
Meaning

Information of a diagnosis error recovery in the received data of SCS Link


Transmission.
SCS0101 SCS Link Transmission Receive Recover Stn(SCS)=05
The diagnosed reception error of SCS link transmission has been recovered.
The source station number (such as 05) and the station type (SCS in the
above example) are indicated in the message text. The station type indicated
in the message is the same station type defined on the SCS Link Transmission
builder.
(This is a recovery message of No. 4133.)

Cause

The following causes may be considered.


Recovery of the sender station
Recovery of the communication path
The errors in the SCS Link Transmission definition have been removed.

Remark

SCS Link Transmission

No.4135
Message name
Printing example
Meaning

SCS Link Transmission data lock


SCS0101 SCS Link Transmission Data Locked Stn(SCS)=02
The reception/transmission data for SCS Link Transmission (in the above example, data received from station 2) were locked. The (SCS) in the message
text indicates the station type defined on the SCS Link Transmission builder.

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-13

<2.1 System Alarms (Message Numbers 4101 through 4199)>

Remark
Note

Forcing function, SCS Link Transmission


Be sure to cancel the lock of the station that was locked.

No.4136
Message name
Printing example
Meaning

Remark

Cancellation of SCS Link Transmission data lock


SCS0101 SCS Link Transmission Data Unlocked Stn(SCS)=02
The lock of reception/transmission data for SCS Link Transmission (in the
above example, data received from station 2) was cancelled. The (SCS) in the
message text indicates the station type defined on the SCS Link Transmission
builder.
Forcing function, SCS Link Transmission

No.4137
Message name

Number of Locked Stations in SCS Link Transmission Exceeded

Printing example

SCS0101 Number of Locks about SCS Link Transmission Exceeds the Limit =
3

Meaning

The number of locked stations exceeded the limit (3 in the above example),
which is defined in SYS_FORCE_ LT FB as the number of stations allowed for
forcing.

Cause

Operation from the SENG to lock too many stations.

Action

Cancel SCS Link Transmission locks for some SCS.

Remark
Note

Forcing function, SCS Link Transmission, SYS_FORCE_LT FB


You should not lock stations beyond the limit.

No.4138
Message name

Recovery from exceeded number of locked stations in SCS Link Transmission

Printing example

SCS0101 Number of Locks about SCS Link Transmission Within the Limit = 3

Meaning

The number of locked stations fell within the limit (3 in the above example),
which is defined in SYS_FORCE_ LT FB as the number of stations allowed for
forcing. (This is the recovery message of No.4137.)

Cause
Remark

Operation from the SENG.


Forcing function, SCS Link Transmission, SYS_FORCE_LT FB

No.4139
Message name
Printing example
Meaning

Inter-SCS Safety Communication data lock


SCS0101 Inter-SCS Safety Communication Data Locked Dom=01 Stn=02
The Inter-SCS Safety Communication data received from a producer SCS (in
the above example, station 2 in domain 1) were locked.
The message for a lock of the local station (data produced by the station are
locked) is also output in the same format, showing its own domain number and
station number.

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<2.1 System Alarms (Message Numbers 4101 through 4199)>

Remark
Note

2-14

Forcing function, Inter-SCS Safety Communication


Be sure to cancel the lock of the station that was locked.

No.4140
Message name

Cancellation of Inter-SCS Safety Communication data lock

Printing example

SCS0101 Inter-SCS Safety Communication Data Unlocked Dom=01 Stn=02

Meaning

The lock of Inter-SCS Safety Communication data received from a producer


SCS (in the above example, station 2 in domain 1) was cancelled.
The message of cancellation for the lock of local station (data produced by the
station are locked) is also output in the same format, showing its own domain
number and station number.

Remark

Forcing function, Inter-SCS Safety Communication

No.4141
Message name
Printing example
Meaning

Number of locked stations in Inter-SCS Safety Communication exceeded


SCS0101 Number of Locks about Inter-SCS Safety Communication Exceeds
the Limit = 3
The number of locked stations exceeded the limit (3 in the above example),
which is defined in SYS_FORCE_ BD FB as the number of stations allowed
for forcing.

Cause

Operation from the SENG to lock too many stations

Action

Cancel Inter-SCS Safety Communication locks for some SCS.

Remark
Note

Forcing function, Inter-SCS Safety Communication


You should not lock stations beyond the limit.

No.4142
Message name

Recovery from exceeded number of locked stations in Inter-SCS Safety Communication

Printing example

SCS0101 Number of Locks about Inter-SCS Safety Communication Within the


Limit = 3

Meaning

Cause
Remark

The number of locked stations fell within the limit (3 in the above example),
which is defined in SYS_FORCE_ BD FB as the number of stations allowed
for forcing. (This is the recovery message of No.4141.)
Operation from the SENG
SYS_FORCE_BD FB

No.4143
Message name
Printing example

Start of automatic scan period extension


SCS0101 Scan Period Extended from the Original Scan Period 100ms to
200ms

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-15

<2.1 System Alarms (Message Numbers 4101 through 4199)>

Meaning

Cause
Remark

Automatic extension of the scan period of the application logic execution started. (In the above example, the original scan period of 100 ms was extended
to 200 ms.)
The application caused heavy load on the SCS.
SYS_SCANEXT FB, automatic scan period extension

No.4144
Message name
Printing example
Meaning

Cause
Remark

Cancellation of automatic scan period extension


SCS0101 Scan Period Recovered to the Original Scan Period 100ms
Automatic extension of the scan period of the application logic execution is
cancelled. (In the above example, the scan period recovered to its original period of 100 ms.)
The load on the SCS caused by the application was reduced.
SYS_SCANEXT FB, automatic scan period extension

No.4145
Message name

Abnormal calculation occurred

Printing example 1

SCS0101 Calculation Error (XXXXXX) Program=PG01

Printing example 2

SCS0101 Calculation Error (XXXXXX) Program=PG01 FU/FB=UFB01

Meaning

Abnormal calculation occurred in the application logic.


XXXXXX indicates the type of abnormal calculation. The types are as follows:
Div by Zero :
Division by zero
Access to the Outside of Array : Access to the outside of an array
FPU Overflow :

Overflow in the floating-point calculation

Cast Overflow :

Overflow in casting

At Program=, the name of the program (POU name) where the abnormal calculation occurred is indicated. If the abnormal calculation occurred in a userdefined FU/FB, the POU name of that FU/FB is indicated at FU/FB=.
Cause
Remark

Error in the application


SYS_CERR FB

No.4146
Message name

Recovery from abnormal calculation

Printing example 1

SCS0101 Calculation Recover (XXXXXX) Program=PG01

Printing example 2

SCS0101 Calculation Recover (XXXXXX) Program=PG01 FU/FB=UFB01

Meaning

Indicates a recovery from the abnormal calculation occurred in the application


logic.
XXXXXX indicates the type of abnormal calculation. The types are as follows:
Div by Zero :
Division by zero
Access to the Outside of Array : Access to the outside of an array
FPU Overflow :

Overflow in the floating-point calculation


IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-16

<2.1 System Alarms (Message Numbers 4101 through 4199)>

Cast Overflow :

Overflow in casting

At Program=, the name of the program (POU name) where the abnormal calculation occurred is indicated. If the abnormal calculation occurred in a userdefined FU/FB, the POU name of that FU/FB is indicated at FU/FB=.
Cause
Remark

The error in the application was corrected.


SYS_CERR FB

No.4151
Message name
Printing example
Meaning
Cause

Information of retainable data initialization


SCS0101 Retain Data Initialized
Retainable data have been initialized.
Database with different CRC codes or generation time was offline-downloaded to the SCS.
Data saved in the memory with backup battery volatilized.

Action

Set the setting values of the external communication function blocks with data
retaining function again.

Remark

Data retaining function, external communication function blocks with data retaining function (ECWR_B, ECWR_I, ECWR_R), ACCUM FB, AGA_R FB

No.4152
Message name
Printing example
Meaning
Cause
Remark

Online change of scan period


SCS0101 Scan Period Changed to 200ms
The scan period of the application logic was changed by online change download.
Operation from the SENG
Online change download

No.4153
Message name

Information of Inter-SCS Safety Communication data lock time-up

Printing example

SCS0101 Inter-SCS Safety Communication Data Lock Elapsed the Specified


Period = 08:00:00

Meaning

Inter-SCS Safety Communication lock exceeded the time limit (8 hours in the
above example) specified in SYS_FORCE_BD FB.

Action

Check whether all Inter-SCS Safety Communication locks have been cancelled and cancel unnecessary locks.

Remark

Forcing function, Inter-SCS Safety Communication, SYS_FORCE_BD FB

No.4154
Message name
Printing example

Information of forced cancellation of Inter-SCS Safety Communication data


locks
SCS0101 All Inter-SCS Safety Communication Data Unlocked.
IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-17

<2.1 System Alarms (Message Numbers 4101 through 4199)>

Meaning
Cause
Remark

Locks of all the Inter-SCS Safety Communication data (reception/transmission) in the station were forcibly cancelled.
Locks of all the Inter-SCS Safety Communication data were cancelled by using the SYS_FORCE_BD FB.
Forcing function, Inter-SCS Safety Communication, SYS_FORCE_BD FB

No.4155
Message name
Printing example
Meaning

Remark

Information of SCS Link Transmission status change.


SCS0101 SCS Link Transmission Data Status Set to TRUE Old=FALSE
Stn(SCS)=03
The data status of SCS Link Transmission (such as from station 03) has been
changed (For an example, changed from FALSE to TRUE). The (SCS) in the
message text indicates the station type defined on the SCS Link Transmission
builder.
Forcing function

No.4156
Message name
Printing example
Meaning
Cause

Information of SCS Link Transmission definition change


SCS0101 SCS Link Transmission Definition Changed
SCS Link Transmission definitions were changed by online change download.
Online change download was executed from the SENG.

No.4157
Message name
Printing example
Meaning
Cause

Information of SCS Link Transmission wiring change


SCS0101 SCS Link Transmission Wiring Changed
SCS Link Transmission wirings were changed by online change download.
Online change download was executed from the SENG.

No.4158
Message name
Printing example
Meaning
Action
Remark

Information of SCS Link Transmission lock time-up


SCS0101 SCS Link Transmission Data Lock Elapsed the Specified Period =
08:00:00
SCS Link Transmission lock continued exceeding the time limit (8 hours in the
above example) specified in SYS_FORCE_LT FB.
Check whether all SCS Link Transmission locks have been cancelled, and
cancel unnecessary locks.
Forcing function, SCS Link Transmission, SYS_FORCE_LT FB

No.4159
Message name
Printing example

Information of forced cancellation of SCS Link Transmission locks


SCS0101 All SCS Link Transmission Data Unlocked
IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-18

<2.1 System Alarms (Message Numbers 4101 through 4199)>

Meaning

Locks of all the locked SCS Link Transmission were forcibly cancelled.

Cause

Locks of all SCS Link Transmission were cancelled by operation using


SYS_FORCE_LT FB.

Remark

Forcing function, SCS Link Transmission, SYS_FORCE_LT FB

No.4160
Message name
Printing example

Invalid password for Manual Operation FB


SCS0101 TAG001 Specified Invalid Password

Meaning

The password string specified for Manual Operation FB (MOB_21, MOB_11,


MOA) from the HIS is invalid.

Cause

The password entered from the HIS and the password set in Manual Operation FB did not match.

Action

Enter the correct password for Manual Operation FB again.

Remark

Manual Operation FB (MOB_21, MOB_11, MOA)

No.4161
Message name

Information of Output IOM Shutdown

Printing example 1

SCS0101 All Output IOM Shutdown

Printing example 2

SCS0101 Output IOM Shutdown NODE 01 SLOT 02

Meaning

Remark

An output IOM shutdown task is performed by a Shutdown FB (SYS_ALLSD


or SYS_IOSD). If the shutdown task is performed by SYS_IOSD, the output
module location for shutting down (node 1 and slot 2 in the above example) is
also included in the message.
SYS_ALLSD, SYS_IOSD

No.4162
Message name
Printing example
Meaning
Cause

Information of communication I/O definition change


SCS0101 Communication Definition Changed
The communication I/O definitions of the communication module were
changed by online change download.
Online change download was executed from the SENG.

No.4163
Message name
Printing example
Meaning
Cause

Information of communication I/O wiring change


SCS0101 Communication I/O Wiring Changed
The communication I/O wirings were changed by online change download.
Online change download was executed from the SENG.

No.4164
Message name

Information of disabling security level change


IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-19

<2.1 System Alarms (Message Numbers 4101 through 4199)>

Printing example
Meaning
Remark

SCS0101 Security Levels Change Disabled


The security level change of the SCS by a password-authenticated operation
performed from SENG is disabled.
SYS_SEC_CTL FB

No.4165
Message name
Printing example
Meaning
Remark

Information of enabling security level change


SCS0101 Security Levels Change Enabled
The security level change of the SCS by a password-authenticated operation
performed from SENG is enabled.
SYS_SEC_CTL FB

No.4166
Message name
Printing example
Meaning
Action
Remark

Information of communication module lock time-up


SCS0101 Communication Module Lock Elapsed the Specified Period =
08:00:00
The communication module lock continued exceeding the time limit (8 hours in
the above example) specified in SYS_FORCE_SC FB.
Check whether all communication module locks have been cancelled, and
cancel unnecessary locks.
Forcing function, subsystem communication, SYS_FORCE_SC FB

No.4167
Message name
Printing example
Meaning
Cause
Remark

Information of forced cancellation of communication module locks


SCS0101 All Communication Modules Unlocked
Locks of all communication modules were forcibly cancelled.
Locks of all communication modules were cancelled by operation using
SYS_FORCE_SC FB.
Forcing function, subsystem communication, SYS_FORCE_SC FB

No.4168
Message name
Printing example
Meaning
Cause

Information of tag name change by online change download


SCS0101 Online Change Download Tag Name = TAG001 Changed
The tag name (TAG001 in the above example) of PASSWD FB or override FB
was changed by online change download.
Online change download was executed from the SENG.

No.4169
Message name
Printing example

NVRAM diagnosis error


SCS0101 RIGHT NVRAM Diagnosis Error
IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-20

<2.1 System Alarms (Message Numbers 4101 through 4199)>

Meaning

An error was detected during diagnosis of NVRAM (nonvolatile memory) in a


CPU module (right side in the above example).

Cause

NVRAM may be faulty.

Action

Replace the applicable CPU module.

No.4170
Message name
Printing example
Meaning

Flash memory diagnosis error


SCS0101 RIGHT Flash Memory Diagnosis Error
An error was detected during self-diagnosis of flash memory in a CPU module
(right side in the above example).

Cause

Part of data stored in flash memory was destroyed, or flash memory may be
faulty.

Action

If the SCS is in a single CPU module configuration, the SCS will not be able to
start when this CPU restarts next time. It is necessary to change the CPU
module right away.
If the SCS is configured with redundant CPU modules, the control will switch
to the other module after detecting this error, and the module where the error
occurs is restarted as a standby module.
If the error is caused by damage to the data in the flash memory, data in the
control side will be copied to the standby module where the error occurs, and
that module will then recover from abnormal to normal status.
If the error is caused by the physical damage of the flash memory, this system
alarm will occur even after the damaged CPU is switched to standby. Under
this circumstance, it is necessary to change the damaged CPU module.

No.4172
Message name
Printing example
Meaning

Information of resource change by online change download


SCS0101 Online Change Download Resource Changed (Total POU=10)
The resource was changed by online change download. The resource defines
total number of POU (10 in the above example).

Cause

Online change download was executed from the SENG.

Action

Check and confirm that the total number of POU indicated in this message is
equal to the total number of POU indicated by Database Validity Check Tool.

No.4173
Message name
Printing example
Meaning

Completion of writing to flash memory


SCS0101 Writing XXXXXX to Flash Memory Succeeded
Writing to flash memory in a CPU module was normally completed.
XXXXXX: Indicates the data written. The items of the data are as follows.
Security Password :
Security password
System Database :

System database

Integration Database : Integration database


Variable Database :

Variable database
IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<2.1 System Alarms (Message Numbers 4101 through 4199)>

Difference Data :
Cause

2-21

Difference data

When online change download from SENG to SCS was executed or the password was changed, data was normally written to flash memory.

No.4174
Message name
Printing example
Meaning

Failed to write to flash memory


SCS0101 Writing XXXXX to Flash Memory Error
Write data error was detected during check at flash memory write in a CPU
module.
XXXXXX: Indicates the data attempted to be written. The items of the data are
as follows.
Security Password :
Security password
System Database :

System database

Integration Database : Integration database


Variable Database :

Variable database

Difference Data :

Difference data

Cause

Flash memory may be faulty.

Action

If the SCS is in a single CPU module configuration, the CPU module continues
the operation even if this error occurs. However, the SCS will not start properly
when this CPU module restarts next time. It is necessary to change the CPU
module as soon as possible.
On a dual-redundant CPU module configuration SCS, if this writing error to
flush memory occurs on one of the CPU modules, the CPU module will be
failed and operation is continued with the other CPU module. It is necessary to
change the failed CPU module right away. If writing to the flash memories in
both CPU modules fails, the SCS will not be able to start when the CPU restarts. Under this circumstance, it is necessary to change both CPU modules
right away.

Remark

Flash memory diagnosis

No.4175
Message name
Printing example
Meaning

Failed to update external communication data


SCS0101 External Data Refresh Failed
The SCS has failed to update external communication data. This data is referenced in communications with CENTUM stations and Modbus, so when this
error occurs, data will not be updated in those stations.

Cause

The CPU processing time allocated for the external communication function
processing was not sufficient. As a result, processing to update the external
communication data is not performed.

Action

Reduce the communication load on the SCS. If this error occurs regularly, review the balance between the application logic amount and the scan period.

No.4177
Message name

Information of SCS security level change


IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-22

<2.1 System Alarms (Message Numbers 4101 through 4199)>

Printing example
Meaning
Cause
Note

SCS0101 Security Level Changed to 1


The security level of the SCS was changed (1 in the above example).
The security level of the SCS was changed. The security level can be changed
from the SENG or SYS_SECURE FB.
Be sure to revert the security level to 2.

No.4178
Message name
Printing example
Meaning

Information of security level time-up


SCS0101 Security Level = 1 Elapsed the Specified Period = 08:00:00
The security level is set to 1 for the duration exceeding the time limit (8 hours
in the above example) specified in SYS_SECURE FB.

Cause

The security level has not been reverted.

Action

Revert the security level to 2.

Remark
Note

SYS_SECURE FB
When the security level is 0, the message is not generated.

No.4179
Message name
Printing example
Meaning
Remark
Note

Information of communication I/O module output enabled operation


SCS0101 Communication Modules Output Enabled
The communication modules are enabled for output.
I/O Channel Status dialog box, SYS_STAT_SC FB
This is irrelevant for enabling the output of the safety I/O modules. If you have
done the Output enabled operation for the safety output modules, confirm the
message 4181.

No.4180
Message name
Printing example
Meaning
Cause
Note

Information of password change


SCS0101 Security Level = 1 Password was Changed
The password for the SCS security level (1 in the above example) was
changed.
The password was changed from the SENG.
The message of No. 4173 is also generated after this alarm.

No.4181
Message name
Printing example
Meaning

Information of output enabled operation


SCS0101 Output Enabled
The output enabled operation for the SCS was performed from the SENG.
When all the safety modules output channels go into output-enabled state,
the SCSs operating mode changes to Running.

Remark

I/O Channels Status dialog box, SYS_STAT_FB


IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<2.1 System Alarms (Message Numbers 4101 through 4199)>

2-23

No.4182
Message name
Printing example
Meaning
Remark

Information of output module start operation


SCS0101 IOM Started NODE 01 SLOT 02
An output module (node 1 and slot 2 in the above example) was started from
the SENG.
SCS State Management window

No.4183
Message name
Printing example
Meaning

Request to upload SOE to SENG


SCS0101 SOE Save Request
This notification prompts to upload the event information collected on the SCS
to SENG.

Cause

This message is generated every time 12,000 events have occurred on the
SCS.

Action

Start SOE Viewer on SENG and upload events from SCS.

Remark
Note

SOER function
This system alarm is generated even if SOE Viewer is started periodically.
Events can be uploaded from the SCS by starting SOE Viewer and displaying
the latest event.

No.4184
Message name
Printing example
Meaning
Action
Remark
Note

Notification on saving SOE trip signal file in SCS


SCS0101 SOE Trip Signal File No.= 01 Saved
The SOE trip signal file (No. 01 in the above example) was saved in SCS.
Start SOE Viewer on SENG and upload the events in the file.
SOER function
When uploading the events is complete, the trip signal files need to be reset.
Up to two trip signal files can be held in the SCS. The trip signal files can be
reset by starting the Message Cache Tool and initializing the trip information.

No.4185
Message name

Information of variable value change

Printing example 1

SCS0101 Variable Set to 10.0 Old = 5.0 Variable = VAR001

Printing example 2

SCS0101 Variable Set to TRUE Old = FALSE Variable = VAR001 NODE 01


SLOT 02

Printing example 3

SCS0101 Variable Set to TRUE Old = FALSE Variable = VAR001 NODE 01


SLOT 02 CH 03

Printing example 4

SCS0101 Variable Set to TRUE Old = FALSE Variable = VAR001 Stn=02


No=025

Meaning

The value of the variable (VAR001 in the above example) was changed from
the SENG. For a communication I/O, a variable corresponds to the communication module location (as shown in example 2, node 1, slot 2) is also included
IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-24

<2.1 System Alarms (Message Numbers 4101 through 4199)>

in the message. For an I/O variable, a variable corresponds to the variable location (as shown in example 3, node 1, slot 2, channel 3) is also included in
the message.
The VAR001 in the above printing example 4 is the instance name of the function block that accesses the data of SCS Link Transmission. The related station number and bit number are also printed.
Remark

Forcing function

No.4186
Message name
Printing example
Meaning
Action
Remark

Information of lock time-up


SCS0101 Lock Elapsed the Specified Period = 08:00:00
Lock continued exceeding the time limit (8 hours in the above example) specified in SYS_FORCE FB.
Check whether all locks have been cancelled, and cancel unnecessary locks.
Forcing function, SYS_FORCE FB

No.4187
Message name
Printing example
Meaning
Cause
Remark

Information of forced cancellation of locks


SCS0101 All Variables Unlocked
Locks of all variables were forcibly cancelled.
Locks of all variables were cancelled by operation using SYS_FORCE FB.
Forcing function, SYS_FORCE FB

No.4188
Message name

Start of online change download

Printing example

SCS0101 Online Change Download (System Database) Start

Meaning

Online change download to the system database was started.

Remark

Download function

No.4189
Message name
Printing example
Meaning
Remark

Completion of online change download


SCS0101 Online Change Download (System Database) Complete
Online change download to the system database was normally completed.
Download function

No.4190
Message name
Printing example
Meaning

Online change download error


SCS0101 Online Change Download (System Database) Error = 5340-0001
Online change download to the system database ended with an error.

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-25

<2.1 System Alarms (Message Numbers 4101 through 4199)>

Cause/Action

Causes and actions vary depending on the error code.

Table 2.1-6 Message No. 4190 - Error Causes and Actions


Error code

Cause

Action

5340-****

The security level stays 2.

Set the security level to 1 and then execute online


change download again.

Others

Internal error

Record the message content and report to Yokogawas service department.

No.4191
Message name
Printing example
Meaning

Completion of I/O definition rewriting


SCS0101 IOM Definition Changed NODE 01 SLOT 02
I/O definition was changed by online change download to the system database. The I/O module position is included in the message (node 1, slot 2 in the
above example).
If the number following SLOT is 00, it means that the node definition information has been changed. The node definition information is changed when you
do the following:
Change comments of the node
Add or delete I/O modules of the node
Change slots of the I/O modules of the node
Change the model of the I/O modules of the node

No.4192
Message name
Printing example
Meaning
Action
Remark

Information of override state time-up


SCS0101 Override Elapsed the Specified Period = 08:00:00
Override continued exceeding the time limit (8 hours in the above example)
specified in SYS_OVR FB.
Check whether overrides were released, and release unnecessary overrides.
SYS_OVR FB

No.4193
Message name
Printing example
Meaning
Cause
Remark

Information of forced release of all overrides


SCS0101 All Overrides Released
The overrides for all variables were forcibly released.
The overrides for all variables were forcibly released by operation using
SYS_OVR FB.
SYS_OVR FB

No.4194
Message name
Printing example

Information of override enabled state time-up


SCS0101 Enabled OVR FB Elapsed the Specified Period = 08:00:00
IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-26

<2.1 System Alarms (Message Numbers 4101 through 4199)>

Meaning
Cause
Remark

The override enabled state continued exceeding the time limit (8 hours in the
above example) specified in SYS_OVR FB.
Check override FB in the override enabled state, and release unnecessary
override enabled state.
SYS_OVR FB

No.4195
Message name
Printing example
Meaning

Remark

Information of communication I/O data status change


SCS0101 Communication Data Status Set to TRUE Old = FALSE NODE 01
SLOT 02 Definition 001
The data status of the communication I/O (such as node 1, slot 2, definition 1
in the above example) was changed (such as from FALSE to TRUE) from the
SENG.
Forcing function

No.4196
Message name
Printing example
Meaning

Invalid password for PASSWD FB


SCS0101 TAG001 PASSWD FB Specified Invalid Password
The password string specified for PASSWD FB from the HIS is invalid.

Cause

The password entered from the HIS and the password set in PASSWD FB did
not match.

Action

Specify the correct password for PASSWD FB and enter it again.

Remark

PASSWD FB

No.4197
Message name
Printing example
Meaning
Action
Remark

Information on active PASSWD FB time-up


SCS0101 Activated PASSWD FB Elapsed the Specified Period = 10:00:00
PASSWD FB has been active exceeding the time limit (10 hours in the above
example) specified in SYS_PSWD.
Deactivate PASSWD FB that is not required to be active.
SYS_PSWD FB

No.4198
Message name
Printing example
Meaning
Cause
Remark

Information on forced reset of PASSWD FB


SCS0101 All PASSWD FB Reset to OFF
The outputs of all active PASSWD FBs were forcibly set to OFF.
The outputs of all active PASSWD FBs were forcibly inactivated (reset to OFF)
by operation using SYS_PSWD FB.
SYS_PSWD FB

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

2-27

<2.1 System Alarms (Message Numbers 4101 through 4199)>

No.4199
Message name
Printing example
Meaning

Override communication error


SCS0101 TAG001 Override Communication Error (Instance = OVR001)
Despite an attempt to operate override on the FB OVR001 (in the above example) with the tag name TAG001 (in the above example) from HIS, communication error has occurred.

Cause

A temporary communication error occurred, and the SCS detected the problem of the communication data.

Action

Execute override operation again.

Remark

SYS_OVR FB

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

3-1

<3. Details of Output Messages in Common with CENTUM>

3.

Details of Output Messages in


Common with CENTUM
This section describes the details of output messages used in common with CENTUM.

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through

3-2

0094)>

3.1

Safety Control Station Error Occurrence


and Recovery Messages (Message
Numbers 0001 through 0094)
This section describes messages having the same message numbers as those of the
CENTUM control station.

No.0001
Message name
Printing example
Meaning
Cause

Reset start of safety control station


SCS0101 RIGHT Manual Reset Start
A CPU module (right side in the above example) of the safety control station
(station name = SCS0101) was reset and started.
Start operation from the SENG or from the front switch of the CPU module

No.0003
Message name
Printing example
Meaning

Cause

Safety control station automatic reset start


SCS0101 RIGHT Automatic Reset Start
An error occurred in the displayed CPU module (right side in the above example) of the safety control station (station name=SCS0101), which caused the
safety control station to be automatically reset started.
CPU module is faulty.

No.0005
Message name
Printing example
Meaning
Cause
Note

Power ON initial cold start of safety control station


SCS0101 Power ON (Cold Start)
The safety control station (station name = SCS0101) performed the initial cold
start processing after it was powered ON.
Recovery from power failure
The safety control station always performs the initial cold start processing after
recovery from power failure.

No.0009
Message name
Printing example
Meaning
Cause

Transfer of control right of safety control station


SCS0101 Control Transfer
A transfer of control right occurred in the redundant safety control station (station name = SCS0101).
The CPU module on one side was stopped.
An error occurred in the CPU module on one side.

Action

The CPU module on the standby side takes over control. Replace the CPU
module that was stopped.

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through

3-3

0094)>

No.0011
Message name
Printing example
Meaning
Cause

Fail information of safety control station


SCS0101 RIGHT Fail (xxxxxxxx Code= yyyy yyyy yyyy yyyy)
A CPU module (right side in the above example) of the safety control station
(station name = SCS0101) failed.
The causes are indicated by causes (xxxxxxxx) and a code. For more information, see the following table.

Table 3.1-1 Message No. 0011 - Cause List


Item

Causes
xxxxxxxx

Code (hex 16 digits)


yyyy yyyy yyyy yyyy

SW STOP
-

V STOP
DC STOP
NSR3(*1)
CPU
module
stop

CPU
DOWN

INTSTS(*1)
ERRSTS1(*1)
ERRSTS2(*1)

SELFSTOP
UNKNOWN

(*2)

RESTART
*1:
*2:

Auto restart

Description
Stop by operation of the front switch of
the CPU module

No

Stop instruction via control bus

No

Stop due to power failure

No

An error occurred during CPU module error check.


NSR3, INTSTS, ERRSTS1 and
ERRSTS2 are detailed error codes.

Yes

Stop after software detected an error

No

Stop due to unknown cause

No

Restart after software detected an error

Yes

If this error message is displayed, report the display contents of causes (xxxxxxxx) and code to Yokogawas service department.
Refer to the following Table 2.1-4 Error Codes and Solutions.

Table 3.1-2 Error Codes and Solutions


Code (hex; 16 digits)

Error

Solution

0000 5090 yyyy yyyy

Zero division occurred when running


the application logic.

Check to see if the application logic contains zero division or not, and correct the
application logic if it contains.

0000 5091 yyyy yyyy

The application logic is trying to access an array datum beyond the


scope of the array.

Check the application and find out which


logic program is accessing the out-of-range
array data and correct the error.

0000 50a9 yyyy yyyy

The database inconsistence is detected. It may be caused by restarting the SCS without releasing the
brake point.

Run offline downloading.

4000 3BF1 0255 8082


(*1)

The firmware (Revision F4) in the


CPU module is too old to support the
system with Optical ESB Bus Repeater modules.

For a system that contains Optical ESB


Bus Repeater modules, the firmware of
CPU with the proper revision number
should be used.

4000 3BF1 xxxx xxxx

An error has been detected in the


I/O unit of the CPU module.
SCSV1-S : There may be a failure in
the I/O unit of the CPU module.
SCSP2-S: There may be a failure in
the I/O unit of the CPU module or
the I/O communication is posing
heavy load on the CPU.

If one of the redundant CPU modules has


stopped, message No. 0787 is generated
at the same time.
Refer to the explanation of message No.
0787.
Continues on the next page

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through

3-4

0094)>
Table 3.1-2 Error Codes and Solutions (Table continued)
Code (hex; 16 digits)

Error

Solution

0000 5010 yyyy yyyy

The CPU model and station model


are inconsistent.

Match the CPU model and station model


with each other.

FFFF 000B 0000 000F

The calculation in a running application overflowed.

Check the application and find out what


caused the calculation overflow and then
modify it.

Other

Other

If this error message is displayed, report


the display contents of causes (xxxxxxxx)
and the code to Yokogawas service department.

*1:

This code is not generated in SCSP2-S

Action

If the safety control station operates normally after restarting automatically,


continue operation. If the safety control station stops after restarting automatically, replace the CPU module.

No.0013
Message name
Printing example
Meaning

Cause
Note

AC power supply failure of safety control station


SCS0101 AC Fail (Time 05.02.01 18:45)
AC power of the safety control station (station name = SCS0101) failed and
was then recovered. The date and time indicated are when the power failed.
This message is output after the power is recovered.
The voltage of AC power supply dropped, or a power failure occurred.
The SCS has been initialized and then started.

No.0015
Message name
Printing example
Meaning

Self-diagnosis error of clock inside CPU module


SCS0101 RTC Diagnose Error Code=0001
An error was detected during self-diagnosis of the clock inside the safety control station (station name = SCS0101).
Code=0001: Check pattern mismatch
Code=0002: Inappropriate date/time value
Code=0003: Date/time not updated

Action

Replace the CPU module.

No.0017
Message name
Printing example
Meaning
Action

ROM checksum error of CPU module


SCS0101 RIGHT ROM Sum Check Error
A ROM checksum error was detected in the indicated CPU module (right side
in the above example) of the safety control station (station name = SCS0101).
Replace the CPU module.

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through

3-5

0094)>

No.0021
Message name
Printing example
Meaning

Internal task error of safety control station


SCS0101 Internal Error TASK=TSK1 Code=100 Error=1000 - E0F0
An error state was detected during the execution of a task (TSK1 in the above
example) in the safety control station (station name = SCS0101). TASK,
Code and Error indicate detailed error information.

Cause

This is a software problem.

Action

Report the message content to Yokogawas service department.

No.0023
Message name
Printing example
Meaning

Mapping block fatal error


SCS0101 Block TAG001 Return Error 8E04 and stop
An execution disabled error was detected during the execution of a mapping
block (TAG001 in the above example) in the safety control station (station
name = SCS0101).

Cause

There is a problem in the integration DB. Error indicates detailed error information.

Action

Report the message content to Yokogawas service department.

No.0025
Message name
Printing example
Meaning

Function control word error


SCS0101 No Block Control Word for Block Type=1804
The internal program that corresponds to the block type code of the safety
control station (station name = SCS0101) does not exist. Type indicates detailed internal information.

Cause

This is an internal error at task initialization.

Action

Report the message content to Yokogawas service department.

No.0027
Message name
Printing example
Meaning

Mapping block record information error


SCS0101 TAG001 Block Bad Record No = 3
There is a bad record in the mapping block (TAG001 in the above example) of
the safety control station. No indicates the bad record number in the database.

Cause

The mapping block and the record block number do not match.

Action

Report the block type and record number where an error occurred to Yokogawas service department.

Note

Do not perform online change download after this alarm occurred.

No.0033
Message name

Online downloading abnormal end


IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through

3-6

0094)>

Printing example
Meaning

Cause/Action

SCS0101 Online Download Error Code=9402 - 0000


Online change download of the safety control station (station name =
SCS0101) ended with an error. Error Code indicates detailed internal information.
See the following table.

Table 3.1-3 Message No. 0033 - Error Code List


Code

Error Contents

Cause

Action

9402
9403
9404
9405

Online change
downloading abnormal end

The SCS was reset and started


during online change download.

Execute offline download.

Others

Internal error

Internal error

Report the display content of the code


to Yokogawas service department.

No.0041
Message name

Safety control station fan alarm

Printing example

SCS0101 Fan (SCU N1) Alarm

Meaning

A cooling fan of the safety control station (station name = SCS0101) is abnormal. One of the following items is displayed in the parentheses in the above
example.
SCU N1: Left side fan
SCU N2: Right side fan

Cause

The cooling fan stopped or its revolution is abnormal.

Action

Replace the failed fan unit.

Remark

HKU function

No.0042
Message name
Printing example
Meaning

Remark

Recovery from safety control station fan alarm


SCS0101 Fan(SCU N1) Recover
The cooling fan of the safety control station (station name = SCS0101) recovered. The content in the parentheses in the above example is the same as
message No. 0041. (This is a recovery message of No. 0041.)
HKU function

No.0043
Message name
Printing example
Meaning

Safety control station temperature alarm


SCS0101 Temperature(RIGHT BATTERY) Alarm
This is a temperature rise alarm of the safety control station (station name =
SCS0101). One of the following items is displayed in the parentheses in the
above example.
RIGHT BATTERY: Battery of the right side CPU module
LEFT BATTERY:

Battery of the left side CPU module


IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through

3-7

0094)>

AIR IN:

Air inlet

AIR OUT:

Air outlet

Cause

The CPU module temperature exceeded the specified value.

Action

After checking the operation of the cooling fans, report to Yokogawas service
department as necessary.

Remark

HKU function

No.0044
Message name
Printing example
Meaning

Remark

Recovery from safety control station temperature alarm


SCS0101 Temperature(RIGHT BATTERY) Recover
The temperature of the safety control station (station name = SCS0101) recovered normally. The content in the parentheses in the above example is the
same as message No. 0043. (This is a recovery message of No. 0043.)
HKU function

No.0045
Message name
Printing example
Meaning

Power supply module alarm of safety control station


SCS0101 RIGHT PSU Alarm
The power supply module of a CPU node (right side in the above example) of
the safety control station (station name = SCS0101) is abnormal.

Cause

Power supply module failure

Action

Replace the applicable power supply module.

No.0046
Message name
Printing example
Meaning

Recovery from power supply module alarm of safety control station


SCS0101 RIGHT PSU Recover
The power supply module of a CPU node (right side in the above example) of
the safety control station (station name = SCS0101) recovered normally. (This
is a recovery message of No. 0045.)

No.0047
Message name
Printing example
Meaning

Battery alarm of CPU module


SCS0101 RIGHT Battery Alarm
A battery of the CPU module (right side in the above example) of the safety
control station (station name = SCS0101) is abnormal.

Cause

The battery switch is OFF, or the battery is faulty.

Action

Make sure that the switch of the applicable battery is ON. If the above message occurs even if the battery switch is ON, replace the battery.

Remark

HKU function

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through

3-8

0094)>

No.0048
Message name
Printing example
Meaning

Remark

Recovery from battery alarm of CPU module


SCS0101 RIGHT Battery Recover
A battery of the CPU module (right side in the above example) of the safety
control station (station name = SCS0101) recovered normally. (This is a recovery message of No. 0047.)
HKU function

No.0055
Message name
Printing example
Meaning

Action

Information of same frame reception in online change download communication


SCS0101 Received Same Online Download Frame Code=1 Frame=3
The same communication frame was received twice during the execution of
online change download. Code and Frame indicate detailed internal information.
Execute online change download again.

No.0057
Message name
Printing example
Meaning

Information of online change download error


SCS0101 Online Download Error Call Code=9601 - 0000 Data=91,0,0,0
An error occurred during the execution of online change download of the safety control station (station name = SCS0101). Code and Data indicate detailed internal information.

Cause

This error occurs if error data cannot be saved on the safety control station
side.

Action

It is necessary to determine an action to take based on the Code and Data


information. Report the display contents of Code and Data to Yokogawas
service department.

Note

Do not execute online change download after this alarm occurred.

No.0059
Message name
Printing example
Meaning

Information of recovery from node power failure


SCS0101 FIO NODE Power On FIO NODE 02
An I/O node (2 in the above example) of the safety control station (station
name = SCS0101) recovered from power failure.

No.0063
Message name
Printing example
Meaning
Cause

ESB bus error


SCS0101 FIO-BUS Fail FIO BUS No.1
An error occurred on one side (No. 1 in the above example) of the ESB buses
of the safety control station (station name = SCS0101).
This is an ESB bus error on one side.
IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through
0094)>

Action

3-9

SSB401, SEC402/SEC401 or ESB bus failure may be considered as an error


cause. Take appropriate action in the following:
Check to see if the ESB bus cables are connected correctly. Check for incorrect connection or bad connection of the cables, or check the terminators of the bus.
Check to see if one SSB401 is causing a bus error of the entire buses according to the following procedure.
Pull out the ESB bus connector of each SSB401 that connects to the corresponding bus, one by one, from the node.
Wait for two to three seconds, and if Recover is not printed, insert the
ESB bus connector again, and pull the bus connector of the next node.
If Recover is printed, the bus connector of the SSB401 that was pull out
at that time is faulty, so replace the SSB401.
If no recovery was made even after the bus connectors of all nodes were
pulled out, the SEC402/SEC401 may be faulty. In such a case, replace
the SEC402/SEC401.
If no recovery was still made, press the [START/STOP] button on the
CPU modules front panel on the control side twice, and switch the control
right of the CPU module. Replace the CPU module after restarting.
If the bus does not recover even after these operations, the error may be related to the ESB bus cable (T-shape connector and so on). Replace the ESB
bus cable.

Note

This message is generated if all the I/O nodes, excluding the CPU node, become abnormal.
However, if a system contains Optical ESB Bus Repeater module, when all the
I/O nodes directly connected to/from SEC402/SEC401 (i.e., the I/O nodes not
connected via Optical ESB Bus Repeater module), become abnormal, but the
I/O nodes connected via the Optical ESB Bus Repeater module are normal,
this message is not generated.

No.0064
Message name
Printing example
Meaning

Normal recovery of ESB bus


SCS0101 FIO-BUS Recover FIO BUS No.1
The ESB bus indicated in the message recovered normally. (This is a recovery
message of No. 0063.)

No.0065
Message name
Printing example
Meaning

Cause

Failure of ESB Bus Interface module (SSB401) of node


SCS0101 SBS Fail FIO NODE 02 SBS RIGHT
An error occurred in an ESB Bus Interface module (right side in the above example) of an I/O node (2 in the above example) of the safety control station
(station name = SCS0101).
One of the following causes may be considered.
ESB Bus Interface module becomes abnormal.
Connection route to the ESB Bus Interface module becomes abnormal.

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through

3-10

0094)>

For the I/O nodes that are connected via Optical ESB Bus Repeater module, the Optical ESB Bus Repeater module related hardware such as
module or Fiber-optic cable may have problem.
Action

If an I/O node routed through the Optical ESB Bus Repeater related devices
becomes abnormal, the erroneous device can be identified according to the
content of the messages or the LED status so as to replace the damaged device. If all the I/O nodes routed through the Optical ESB Bus Repeater related
devices become abnormal, the error may have occurred in the Optical ESB
Bus Repeater module related hardware such as module or Fiber-optic cable.
Moreover, if the Optical ESB Bus Repeater modules are mounted in the
SNT10D, the error may be caused by the failure of a power supply module of
SNT10D unit.

No.0066
Message name
Printing example
Meaning

Normal recovery of ESB Bus Interface module (SSB401) of node


SCS0101 SBS Recover FIO NODE 02 SBS RIGHT
An ESB Bus Interface module (right side in the above example) of an I/O node
(2 in the above example) of the safety control station (station name =
SCS0101) recovered normally. (This is a recovery message of No. 0065.)

No.0067
Message name
Printing example
Meaning

Failure of power supply module of node


SCS0101 PSU Fail FIO NODE 02 PSU RIGHT
An error occurred in a power supply module (right side in the above example)
of an I/O node (2 in the above example) of the safety control station (station
name = SCS0101).

Cause

Failure of a power supply module of an I/O node

Action

Replace the power supply module of the applicable node.

Note

When the message shows node 1, it indicates that an error occurred in a PSU
for the CPU node.

No.0068
Message name

Normal recovery of power supply module of a node

Printing example

SCS0101 PSU Recover FIO NODE 02 PSU RIGHT

Meaning

The power supply module of the I/O node indicated in the message (2 in the
above example) recovered normally. (This is a recovery message of No.
0067.)

No.0069
Message name
Printing example
Meaning
Cause/Action

Error before database download to I/O module


SCS0101 IOM Download Error=A701
Database download to the I/O module (IOM) can not be started.
The cause and action vary depending on the content of the error.
A701
IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through

3-11

0094)>

This message occurs when attempting to download to an IOM while another IOM download is still running. Only one IOM download can be performed at one time, so please wait for the other IOM download to complete before running an IOM download operation again.
A72C
Automatic IOM download to a standby side I/O module is running. This
error occurs if IOM download to the same I/O module is manually executed from the SENG or online change download is executed to make
changes in I/O parameter settings while automatic IOM download is running.
5135
This message occurs when attempting to download to an IOM even
though it is running normally.
Others
Report the error display content to Yokogawas service department.

No.0081
Message name
Printing example
Meaning

Failure of I/O module


SCS0101 IOM Fail FIO NODE 01 SLOT 01 Code=5101
An error occurred in the I/O module mounted in slot 1 of node 1 (CPU node) of
the safety control station (station name = SCS0101).

Cause

For more information about error codes, see the following table.

Action

Replace the applicable I/O module.

Table 3.1-4 Error Details of Message No. 0081 - Errors of Analog Input Modules and Contact I/O Modules
Error code

Description of error

5101

The communication between CPU and I/O modules encounters a no-response error.
This error is caused either by the I/O module abnormality or by the communication
route abnormality.

5102

The type of the I/O module defined on the SENG and the type of the I/O module
mounted does not match. Check type of the I/O module.

5103

The setting information defined on the SENG and the I/O module setting information
do not match. Execute IOM download.

5104

A hardware error of the I/O module was detected. Check detailed error causes in the
IOM report.

5105

A setting error of the I/O module. Check detailed error causes in the IOM report (field
side connector disconnection, field power supply/wiring problem, etc.)

5106

The I/O module recovered from an error state. Check detailed error causes in the IOM
report.

5107

The error that actuated the output shutoff switch occurred. Check detailed error causes in the IOM report. When this error occurred, start the I/O module after recovering
from the error.

5111, 5112, 5113

A communication data check error was detected between the CPU and the I/O module. A failure of the I/O module or a problem of the communication path up to the I/O
module may be the cause.
Continues on the next page

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through

3-12

0094)>

Table 3.1-4 Error Details of Message No. 0081 - Errors of Analog Input Modules and Contact I/O Modules (Table continued)
Error code

Description of error

5114, 5115

An error was detected in the redundant control part of the I/O module. Replace the I/O
module.
However, when two I/O modules in single configuration are changed to dual-redundant configuration and online change download is performed, this error may be detected if a connector cable is plugged to only one of the two modules. In this case, plug
the connector cables to both modules. Recovery from this error is notified with system
alarm message No.0082 Normal recovery of I/O module, and there is no need to replace the I/O modules.

5116, 5117

An I/O module error was detected. Replace the I/O module.

5118

An SCS internal error (SCS database error) was detected.

Table 3.1-5 Error Details of Message No.0081 Errors on ALR111/ALR121/ALE111 Modbus Slave and
ALE111 DNP3 Slave
Error Code

Cause/Action

C580

The communication between CPU and I/O modules encounters a no-response error.
This error may be caused by the I/O module abnormality, communication route abnormality or an abnormality other than C581 to C583 depicted.

C581

The communication program is not downloaded to the communication module. Run


IOM download.

C582

The communication program in the communication module is not the program for
Modbus slave communication/DNP3 slave function. Run IOM download.

C583

The physically installed communication module shows a different model name from
the communication module defined in SENG. Check the model of the communication
module.

Table 3.1-6 Error Details of Message No.0081 - ALR111/ALR121 Subsystem Communication


Error Code

Cause/Action

A33D

No response from the communication module due to communication module abnormality. Change the communication module.

A33E

Error occurred in the communication route between CPU and node.

C581

The communication program is not downloaded to the communication module. Run


IOM download.

C582

The communication program in the communication module is not the program for the
communication defined in SENG. Run IOM download.

C583

The physically installed communication module shows a different model name from
the communication module defined in SENG. Check the model of the communication
module.

C585

Error is found by self-diagnosis. Change the communication module.

C598

The communication module is reset due to online change download or the IOM downloading.

C599

Downloading to database.

C59A

Downloading communication program.

C5C1

Error found after resetting the communication module. Change the communication
module.

C5C6

Failed to download the communication program. Waiting time for shifting to the downloading mode of the communication program exceeded the time limit. Start IOM
download again.

C5C7

Failed to download the communication program. Processing time for downloading the
communication program exceeded the time limit. Start IOM download again.

C5E2

Communication module encountered an error and stopped. Change the communication module.

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through

3-13

0094)>

No.0082
Message name
Printing example
Meaning

Normal recovery of I/O module


SCS0101 IOM Recover FIO NODE 01 SLOT 01
The I/O module mounted in slot 1 of node 1 in the safety control station (station name = SCS0101) recovered normally. (This is a recovery message of
No. 0081.)

No.0083
Message name
Printing example
Meaning
Cause

I/O module database error occurred


SCS0101 IOM Configuration Error FIO NODE 01 SLOT 01
An error occurred in the database on the I/O module mounted in slot 1 of node
1 in the safety control station (station name = SCS0101).
The database on the I/O module and the database on the SCS do not match.
The following causes may be considered.
IOM download has not been executed.
IOM failure.

Action

If this error occurred after replacing a module or at startup, the database might
not have been downloaded to the I/O module. Execute IOM download.
If this error occurred during I/O module operation, the I/O module may be faulty. Replace the I/O module.

No.0085
Message name
Printing example

I/O module communication error occurred


SCS0101 IOM Communication Error FIO NODE 01 SLOT 01 RIGHT

Meaning

An error occurred in one of the SB buses (right side in the above example). An
error occurred when accessing the I/O module mounted in slot 1 of node 1 in
the safety control station (station name = SCS0101).

Cause

If this error occurred on all input modules within the same node, an I/O module
may be faulty, or the backboard bus of the node may be faulty. Or, an ESB bus
(right side in the above example) or an SSB401 (right side in the above example) may be faulty, or they may not be connected properly.

Action

Report to Yokogawas service department.

No.0086
Message name
Printing example
Meaning

Recovery from I/O module communication error


SCS0101 IOM Communication Recover FIO NODE 01 SLOT 01 RIGHT
A communication error with the I/O module mounted in slot 1 of node 1 in the
safety control station (station name = SCS0101) recovered. (This is a recovery
message of No. 0085.)

No.0087
Message name

Node error occurred

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through

3-14

0094)>

Printing example
Meaning
Cause

SCS0101 NODE Fail FIO NODE 02


An error occurred in node 2 of the safety control station (station name =
SCS0101).
One of the following causes may be considered.
A power failure occurred in the node, or both of the two ESB buses are
abnormal.
Both SSB401 are abnormal.
For the I/O nodes that connected via Optical ESB Bus Repeater module,
the Optical ESB Bus Repeater module related hardware such as module
or Fiber-optic cable may have problem.

Action

Report to Yokogawas service department.

No.0088
Message name
Printing example
Meaning

Normal recovery of node


SCS0101 NODE Recover FIO NODE 02
The node indicated in the message recovered normally. (This is a recovery
message of No. 0087.)

No.0089
Message name
Printing example
Meaning
Cause/Action

Subsystem communication error


SCS0101 SS-COM Error FIO NODE 01 SLOT 01 PORT 01 STN001 Code=
A3B0
A communication error occurred between the indicated communication module
and the subsystem.
The error details can be found in the instruction manuals of the connected
subsystem. See the manuals for error details.
The error codes that irrelevant to the connected subsystems are shown.

Table 3.1-7 Error Details of Message No.0089 - Errors that irrelevant to subsystems
Code

Error

Cause/Action

A391

Driver Busy

Occurs when sending or receiving.

A392

Communication Line Busy

This message occurs when carrier detection fails due to the


CD line is energized within the transmission enable monitoring time.(*1)

A393

Communication Line Not Ready

This message occurs when clear to send fails due to the CS


line is not energized within the transmission enable monitoring time, or when data ready fails due to the DR line is not
energized within the transmission enable monitoring time.
(*1)

A394

Data size is too large for sending.

A395

The port for sending is not declared.

A397

Underrun

A398

Interval of characters became


timeout

This message occurs when the interval of characters exceeds the specified time.
Continues on the next page
IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through

3-15

0094)>

Table 3.1-7 Error Details of Message No.0089 - Errors that irrelevant to subsystems (Table continued)
Code

Error

A399

Reception buffer overflow

A39A

Reception parity error

A39B

Reception overrun

A39C

Reception frame error

A39D

Number of characters beyond


range

A39F

Other errors

A3B0 to
A3FF

Reserved for subsystems

*1:

Cause/Action

For more information, see the instruction manuals of subsystems.

The transmission-watching timer monitors the waiting time of the transmission line become ready for transmission. When RS
is sent, and the waiting time for transmission exceeds the specified time period, the transmission becomes error. The transmission waiting time is normally set to 1000 ms.
The conditions for transmission are as follows:
CD line off (When CD check is enabled)
CS (CTS) line on
DR line on (When DR check is enabled)

Remark

Subsystem communication

No.0090
Message name
Printing example
Meaning
Remark

Subsystem communication recovered


SCS0101 SS-COM Recover FIO NODE 01 SLOT 01 PORT 01 STN001
The communication between the indicated communication module and the
subsystem recovered from the error.
Subsystem communication

No.0093
Message name
Printing example
Meaning
Action
Remark

CPU nodes housekeeping unit error


SCS0101 RIGHT HKU Error Code=0001
The CPU nodes housekeeping unit of the safety control station (station name
= SCS0101) is faulty. Code indicates detailed internal information.
Report to Yokogawas service department.
HKU function

No.0094
Message name
Printing example
Meaning
Remark

Normal recovery of CPU nodes housekeeping unit


SCS0101 RIGHT HKU Recover Code=0001
The CPU nodes housekeeping unit of the safety control station (station name
= SCS0101) recovered normally. (This is a recovery message of No. 0093.)
HKU function

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<3.2 Safety Control Station Status Change Related Messages (Message Numbers 0450 through 0480)>

3-16

3.2

Safety Control Station Status Change


Related Messages (Message Numbers
0450 through 0480)
This section describes status change-related messages from the safety control station.

No.0450
Message name
Printing example
Meaning
Cause

Copy program and database on control side of safety control station to standby side
SCS0101 Copy
The copying of the program and database on the control side of the safety
control station to the standby side has been started.
This message is displayed when the CPU module on the standby side of the
safety control station (station name = SCS0101) was started.

No.0451
Message name
Printing example
Meaning

Information of switching of control side of safety control station


SCS0101 RIGHT Control
The CPU module on the right or left side (right side in the above example) of
the safety control station (station name = SCS0101) has been set to the control side.

No.0452
Message name
Printing example
Meaning

Information of switching of standby side of safety control station


SCS0101 LEFT Stand-By
The CPU module on the right or left side (left side in the above example) of the
safety control station (station name = SCS0101) has been set to the standby
side.

No.0459
Message name
Printing example
Meaning

Information on I/O module service side


SCS0101 IOM In Service FIO NODE 01 SLOT 01
One side (slot 1 of node 1 in the above example) of a redundant I/O module
has gained control right.

No.0460
Message name
Printing example
Meaning

Information of I/O module out service


SCS0101 IOM Out Service FIO NODE 01 SLOT 01
An I/O module (slot 1 of node 1 in the above example) has been set to standby or stopped.

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<3.2 Safety Control Station Status Change Related Messages (Message Numbers 0450 through 0480)>

3-17
No.0471
Message name
Printing example
Meaning

Normal completion of online change download


SCS0101 Online Download (Integration Database) Complete
Online change download to the safety control station has normally been completed.

No.0474
Message name
Printing example
Meaning
Action

Information of tag list duplicate error


SCS0101 Tag Duplication Error Tag = TAG001
A duplicate tag list name exists in the same safety control station.
Report to Yokogawas service department.

No.0475
Message name
Printing example

Start of database download to I/O module


SCS0101 IOM Download Start FIO NODE 01 SLOT 01
In the case of automatic IOM download:
SCS0101 Automatic IOM Download Start FIO NODE 01 SLOT 02

Meaning

Database download to the I/O module indicated in the message has been started.

No.0476
Message name
Printing example

Normal completion of database download to I/O module


SCS0101 IOM Download Complete FIO NODE 01 SLOT 01
In the case of automatic IOM download:
SCS0101 Automatic IOM Download Complete FIO NODE 01 SLOT 02

Meaning

Database download to the I/O module indicated in the message has normally
been completed.

No.0477
Message name
Printing example

Database download error to I/O module


SCS0101 IOM Download Error FIO NODE 01 SLOT 01 Error= xxxx
In the case of automatic IOM download:
SCS0101 Automatic IOM Download Error FIO NODE 01 SLOT 02 Error= xxxx

Meaning
Cause/Action

An error occurred during database download to the I/O module indicated in the
message. xxxx indicates an error code.
The following lists error codes. If an error occurs, remove the cause, and execute IOM download again.
If an error other than the following occurred, replace the I/O module and execute IOM download again. If other error occurred again, report details to Yokogawas service department.

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<3.2 Safety Control Station Status Change Related Messages (Message Numbers 0450 through 0480)>

3-18
IOM error codes other than ALR111, ALR121, and ALE111.
A701: This I/O module is currently executing download.
3B1B: The I/O module is faulty.
CFxx: An error was replied from the I/O module.
CF10: The type of the I/O module is not correct.
Error codes of ALR111, ALR121, and ALE111
A33D: Communication cannot be performed with the ALR1x1 and
ALE111.
A33E: The communication path between the CPU module and the
ALR1x1 is abnormal. (Node failure, etc.)
A731: Simultaneous download attempts were made for communication
programs. In one attempt of the online change download,
ALR1x1 for subsystems, ALR1x1 for Modbus Slave, ALE111 for
Modbus/TCP Slave and ALE111 for DNP3 Slave are not allowed
to add simultaneously. If you try to add them simultaneously,
A731 error occurs when downloading is attempted for the second and subsequent modules. When an error occurs, perform
IOM download to the failed communication module on SCS State
Management Window after the online change download completes.

No.0480
Message name
Printing example
Meaning

Heavy load on periodical processing


SCS0101 Too Heavy Load
The processing time of External Communication Function of the safety control
station has exceeded the four times the scan period that is specified for External Communication Function.

Cause

The load on the safety control station is too heavy.

Action

Correct the application and reduce the load on the safety control station.

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

3-19

<3.3 Safety Control Station Related Messages (Message Numbers 0727 through 0787)>

3.3

Safety Control Station Related Messages


(Message Numbers 0727 through 0787)
This section describes messages that have common message numbers with the messages of
the CENTUM control station.

No.0727
Message name
Printing example

Block mode recovery error information


SCS0101 Block Mode Change Error Block=TAG001 Code=9601-0000
TAG001:

Tag name

9601-0000: Error code


Meaning
Action

Block mode recovery failed at the end of downloading.


Report the error code to Yokogawas Service department.

No.0743
Message name
Printing example
Meaning

Self-diagnostic SEN-BUS Failure


SCS0101 SEN-BUS Alarm SEN-BUS No.1
The SEN-BUS in question has failed.

Cause

There is a failure in the SEN-BUS in the CPU node or the CPU module mounted.

Action

Replace the CPU node or the CPU module mounted.

No.0744
Message name
Printing example
Meaning

Self-diagnostic SEN-BUS Recovery


SCS0101 SEN-BUS Recover SEN-BUS No.1
The SEN-BUS in question has returned to normal. (This is a recovery message of No. 0743.)

No.0749
Message name
Printing example
Meaning
Cause/Action

Self-diagnosis detected an I/O Error


SCS0101 FIO Self Diag Error FIO CODE = 00005119 DET = 00000000
I/O error was detected during self-diagnosis.
The action varies depending on the Code and DET. Contact Yokogawa service
department with the contents of CODE and DET.
The following describes the contents of CODE and DET.
CODE = 00005119 :

An error was detected in the redundant control


unit. Switching is not performed even if an error occurred on the control side. Replace the I/O module.

CODE = 0000511B :

An error was detected in the I/O unit of the CPU


module.

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

3-20

<3.3 Safety Control Station Related Messages (Message Numbers 0727 through 0787)>

DET = 0000 Y48x :

A detail code of CODE = 0000511B. Y = 0 indicates an error in the right CPU module, and Y = 8
indicates an error in the left CPU module.

No.0750
Message name
Printing example
Meaning

I/O Recovery from the error detected by self-diagnosis


SCS0101 FIO Self Diag Recover FIO CODE = 00000000 DET = 00000000
Recovery from I/O error detected by self-diagnosis. (This is a recovery message of No. 0749.)

No.0751
Message name
Printing example
Meaning

Time self-diagnostic testing error


SCS0101 RIGHT Time Self Diag Error Code=00030021
A clock error is detected by self-diagnosis while the CPU of either redundant
or non-redundant is running.

Cause

VEHICLE clock, RTC or GPS clock trouble

Action

Replace the CPU module.

No.0753
Message name
Printing example
Meaning

Communication Overload
SCS0101 Communication Overload
Communication load to safety control station exceeded the limit.

Cause

There were many communication demands from the operation and monitoring
function window or application programs to the safety control station.

Action

If the windows for the indicated safety control station are displayed on the
CENTUM HIS, the windows need to be closed. Modifying the application programs may also reduce the communication load to the safety control station.

No.0767
Message name
Printing example
Meaning

Faulty one ESB bus in CPU module


SCS0101 FIO-BUS Fail FIO RIGHT BUS No.1
A communication error (bus1 in the above example) occurred in standby side
CPU module (right side in the above example) of the safety control station
(station name = SCS0101). (Communication with all nodes on the bus1 side
became abnormal.)

Cause

The CPU module or the backboard of the CPU node may be faulty.

Action

Replace the CPU module or the CPU node.

No.0768
Message name
Printing example

Single ESB bus in CPU module Recovery


SCS0101 FIO-BUS Recover FIO RIGHT BUS No.1
IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

3-21

<3.3 Safety Control Station Related Messages (Message Numbers 0727 through 0787)>

Meaning

A communication error (bus1 in the above example) in standby side CPU


module (right side in the above example) of the safety control station (station
name = SCS0101) recovered. (This is a recovery message of No. 0767.)

No.0787
Message name
Printing example
Meaning

Self-diagnosis detected I/O error in CPU module


SCS0101 I/O Diagnosis Error IO RIGHT CODE=02518000 00000000
A self-diagnosis error occurred in a CPU module (right side in the above example) of the safety control station (station name = SCS0101).

Table 3.3-1 Message No. 0787 - Error Code Detail


CODE(hexadecimal, 16
digits)
Error code Error detail
(Upper 8
(Lower 8
digits)
digits)

Factor

0251 8000

0000 0000 A CPU module error was detected.

Replace the CPU module.

0255 8082

This code indicates that the revision of


0000 0270 the firmware (F4) in the CPU module is
(*1)
obsolete for the system configured with
Optical ESB Bus Repeater modules.

If a system contains Optical ESB Bus


Repeater module, the proper revision
of CPU should be used.

xxxx0471

xxxx xxxx

SCSP2-S: An error was detected during


the diagnosis of I/O operation.
The CPU module have failed or the load
in the I/O communication band is too
heavy.

xxxx0313

xxxx xxxx

SCSP2-S: There may be a failure in the


I/O unit of the CPU module.

*1:

If many I/O modules are installed on


the ESB bus extended with optical cables, estimate the I/O communication
band and check the validity.
Replace the SCP461 card.

This code is not generated in SCSP2-S.

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

App.1-1

<Appendix 1. Alarm Class>

Appendix 1. Alarm Class


The following table shows the alarm class that is added to each Diagnostic Information Message.
Table Appendix 1-1 Alarm Class
Message number

Message name

Alarm class

0001

Reset start of safety control station

0003

Safety control station automatic reset start

0005

Power ON initial cold start of safety control station

0009

Transfer of control right of safety control station

0011

Fail information of safety control station

0013

AC power supply failure of safety control station

0015

Self-diagnosis error of clock inside CPU module

0017

ROM checksum error of CPU module

0021

Internal task error of safety control station

0023

Mapping block fatal error

0025

Function control word error

0027

Mapping block record information error

0033

Online downloading abnormal end

0041

Safety control station fan alarm

0042

Recovery from safety control station fan alarm

0043

Safety control station temperature alarm

0044

Recovery from safety control station temperature alarm

0045

Power supply module alarm of safety control station

0046

Recovery from power supply module alarm of safety control


station

0047

Battery alarm of CPU module

0048

Recovery from battery alarm of CPU module

0055

Information of same frame reception in online change download communication

0057

Information of online change download error

0059

Information of recovery from node power failure

0063

ESB bus error

1, or 2

0064

Normal recovery of ESB bus

0065

Failure of ESB Bus Interface module (SSB401) of node

1, or 2

0066

Normal recovery of ESB Bus Interface module (SSB401) of


node

0067

Failure of power supply module of node

1, or 2

0068

Normal recovery of power supply module of a node

0069

Error before database download to I/O module

1, or 2

0081

Failure of I/O module

1, or 2

0082

Normal recovery of I/O module

0083

I/O module database error occurred

1, or 2
Continues on the next page
IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

App.1-2

<Appendix 1. Alarm Class>


Table Appendix 1-1 Alarm Class (Table continued)
Message number

Message name

Alarm class

0085

I/O module communication error occurred

1, or 2

0086

Recovery from I/O module communication error

0087

Node error occurred

0088

Normal recovery of node

0089

Subsystem communication error

0090

Subsystem communication recovered

0093

CPU nodes housekeeping unit error

0094

Normal recovery of CPU nodes housekeeping unit

0450

Copy program and database on control side of safety control


station to standby side

0451

Information of switching of control side of safety control station

0452

Information of switching of standby side of safety control station

0459

Information on I/O module service side

0460

Information of I/O module out service

0471

Normal completion of online change download

0474

Information of tag list duplicate error

0475

Start of database download to I/O module

0476

Normal completion of database download to I/O module

0477

Database download error to I/O module

0480

Heavy load on periodical processing

0727

Block mode recovery error information

0743

Self-diagnostic SEN-BUS Failure

0744

Self-diagnostic SEN-BUS Recovery

0749

Self-diagnosis detected an I/O Error

1, or 2

0750

I/O Recovery from the error detected by self-diagnosis

0751

Time self-diagnostic testing error

0753

Communication Overload

0767

Faulty one ESB bus in CPU module

0768

Single ESB bus in CPU module Recovery

0787

Self-diagnosis detected I/O error in CPU module

1, or 2

4101

Inter-SCS safety communication error information

4102

Inter-SCS safety communication error recovery information

4103

Variable lock

4104

Cancellation of variable lock

4105

I/O module lock

4106

Cancellation of I/O module lock

4107

All input module locks

4108

Cancellation of all input module locks

4109

All output module locks

4110

Cancellation of all output module locks

4
Continues on the next page
IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

App.1-3

<Appendix 1. Alarm Class>


Table Appendix 1-1 Alarm Class (Table continued)
Message number

Message name

Alarm class

4111

All module locks

4112

Cancellation of all module locks

4113

Number of locks exceeded

4114

Recovery from exceeded number of locks

4115

Override setting

4116

Cancellation of override

4117

Information of change to override enabled state

4118

Information of change to override disabled state

4119

Number of overrides exceeded

4120

Recovery from exceeded number of overrides

4121

Number of enabled overrides exceeded

4122

Recovery from exceeded number of enabled overrides

4123

Number of active PASSWD FBs exceeded

4124

Recovery from exceeded number of active PASSWD FBs

4125

I/O module channel error occurred

4126

Recovery from I/O module channel error

4127

Setting PASSWD FB to ON

4128

Setting PASSWD FB to OFF

4129

GPS interface unit error

4130

Recovery of GPS interface unit

4131

Communication module lock

4132

Cancellation of Communication module lock

4133

Information of a diagnosis error in the received data of SCS


Link Transmission.

1, or 2

4134

Information of a diagnosis error recovery in the received data


of SCS Link Transmission.

4135

SCS Link Transmission data lock

4136

Cancellation of SCS Link Transmission data lock

4137

Number of Locked Stations in SCS Link Transmission Exceeded

4138

Recovery from exceeded number of locked stations in SCS


Link Transmission

4139

Inter-SCS Safety Communication data lock

4140

Cancellation of Inter-SCS Safety Communication data lock

4141

Number of locked stations in Inter-SCS Safety Communication exceeded

4142

Recovery from exceeded number of locked stations in InterSCS Safety Communication

4143

Start of automatic scan period extension

4144

Cancellation of automatic scan period extension

4145

Abnormal calculation occurred

4146

Recovery from abnormal calculation

4151

Information of retainable data initialization

4
Continues on the next page
IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<Appendix 1. Alarm Class>

App.1-4

Table Appendix 1-1 Alarm Class (Table continued)


Message number

Message name

Alarm class

4152

Online change of scan period

4153

Information of Inter-SCS Safety Communication data lock


time-up

4154

Information of forced cancellation of Inter-SCS Safety Communication data locks

4155

Information of SCS Link Transmission status change.

4156

Information of SCS Link Transmission definition change

4157

Information of SCS Link Transmission wiring change

4158

Information of SCS Link Transmission lock time-up

4159

Information of forced cancellation of SCS Link Transmission


locks

4160

Invalid password for Manual Operation FB

4161

Information of Output IOM Shutdown

4162

Information of communication I/O definition change

4163

Information of communication I/O wiring change

4164

Information of disabling security level change

4165

Information of enabling security level change

4166

Information of communication module lock time-up

4167

Information of forced cancellation of communication module


locks

4168

Information of tag name change by online change download

4169

NVRAM diagnosis error

4170

Flash memory diagnosis error

4172

Information of resource change by online change download

4173

Completion of writing to flash memory

4174

Failed to write to flash memory

4175

Failed to update external communication data

4177

Information of SCS security level change

4178

Information of security level time-up

4179

Information of communication I/O module output enabled operation

4180

Information of password change

4181

Information of output enabled operation

4182

Information of output module start operation

4183

Request to upload SOE to SENG

4184

Notification on saving SOE trip signal file in SCS

4185

Information of variable value change

4186

Information of lock time-up

4187

Information of forced cancellation of locks

4188

Start of online change download

4189

Completion of online change download

4190

Online change download error

2
Continues on the next page

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

<Appendix 1. Alarm Class>

App.1-5

Table Appendix 1-1 Alarm Class (Table continued)


Message number

Message name

Alarm class

4191

Completion of I/O definition rewriting

4192

Information of override state time-up

4193

Information of forced release of all overrides

4194

Information of override enabled state time-up

4195

Information of communication I/O data status change

4196

Invalid password for PASSWD FB

4197

Information on active PASSWD FB time-up

4198

Information on forced reset of PASSWD FB

4199

Override communication error

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

Rev-1

Revision Information
Title

: Messages

Manual No. : IM 32Q02B10-31E


Jan. 2015/4th Edition/R3.02.20 or later*
*: Denotes the release number of the Software Product corresponding to the contents of this Manual. The revised contents are valid until the next edition is issued.
Introduction

ProSafe-RS document map has been removed,


descriptions of Safety, Protection, and Modification of the Product have been modified.

No.0081, No.0477

Descriptions of messages changed.

Oct. 2013/3rd Edition/R3.02.10 or later


Introduction

Description of station types has been changed.

No.4151

New message added.

Appendix 1

No.4151 added.

Dec. 2012/2nd Edition/R3.02 or later


1.1, 1.2

Descriptions changed.

No.4145, No.4146, No.0081, No.0477, No.0749

Descriptions of messages changed.

Appendix 1

Newly added.

Aug. 2011/1st Edition/R3.01 or later


Newly published.

n For Questions and More Information


Online Query: A query form is available on the following URL for online query.
http://www.yokogawa.com/iss
Yokogawa Electric Corporation
n Written by
n Published by Yokogawa Electric Corporation
2-9-32 Nakacho, Musashino-shi, Tokyo 180-8750, JAPAN

IM 32Q02B10-31E

4th Edition : Jan.30,2015-00

Das könnte Ihnen auch gefallen