Sie sind auf Seite 1von 4

Product Specification

03301A

EGCP-3 MC
Multi-unit Mains Controller
Generator System Control Package
DESCRIPTION
The EGCP-3 MC is a powerful
microprocessor-based system control
and management package designed
for the most demanding power
generation applications.

Complete system
control package
Automatic loaddemand
sequencing of
multiple units

The EGCP-3 MC combines power


system, switchgear, bus and utility
monitoring, protection, and control
functions in a single, compact, and
cost-effective package.

Synchronization of
two breakers/
contactors

Perfect for medium and large-sized


generating systems, the EGCP-3 MC
is designed for use in ATS, peaking, or
utility paralleled systems.
The MC is a supervisory control system that works with EGCP-3 LS units to provide
total system control, including multiple utility tie applications.

APPLICATIONS
Real kW Load Control

True RMS power calculations


Configurable load/unload ramp rates
Load control of up to 15 EGCP-3 LS
units using percentage based load
sharing
Utility Import/Export KW control
Process control
Externally adjustable load or process
references (using Analog Inputs or
Modbus)

Reactive kVAR Control

Configurable load/unload ramp rates


PF or VAR control using percentage
based load sharing
Utility Import/Export VAR or PF
control
Externally adjustable VAR or PF
references (using Analog Inputs or
Modbus)
Manual voltage control capability

Automatic Transfer Switch (ATS)

Open or Closed transition


Configurable fast transfer time, LOM
action delay, utility and bus stable
delay

Zero power transfer across breaker


during closed transition
Emergency Power Supply (EPS)
supplying load alarm and discrete
output
LOM alarms and discrete output
Load shed on overload

Peaking Control

Automatic start/stop based on time of


day or demand level
Four time-of-day programs with two
starts and durations per program
Parallel to utility or perform
open/closed transition for time-of-day
starts
Configurable time delayed start/stop
and immediate start for demand
levels
Configurable time delay
Automatic demand monitoring of
multiple mains inputs

Comprehensive
system
protectionbus
and utility
Revenue-grade
power and energy
metering
Digital display of
bus, utility, and
system data
Real kW and
reactive kVAR
control
Advanced network
communications
with Echelon and
Modbus networks
Built-in system

diagnostics

Synchronizing

Bus Protective Features

Communications

Utility Protective Features

Diagnostic Features

*Inverse Time Protections implemented are according to


IEEE C37.112 Very Inverse curves

*Modbus is a trademark of Modicon, Inc.

**Echelon is a trademark of Echelon Corporation

G1_52

4 Analog Inputs
4 Analog Outputs
All Configurable (*)

LOAD 1

LOAD 2

12 Relays Total
9 Configurable (**)

LOAD 3

16 Digital Inputs Total


12 Configurable (^^)

G2_52

Group52

U52

G3_52

Analog Output 4

EGCP-3 MC Interactions

Horn

Mains CTs

Mains PTs

Stop All Engines


**

EPS Supplying
Load **
DI Wetting Voltage

Meter Phase B ^^

Loss of Mains **

3-Phase or
1-Phase Sensing

Meter Phase A ^^

Audible Alarm
Enable Process ^^

Light
Visual Alarm **
Load Ramp Pause ^^

Load 3
Trip Coil
Load Shed 3 **
Load Lower ^^

Load 1
Trip Coil
Load Shed 1 **

Utility
Trip Coil
Voltage Raise ^^

Remote Alarm 2 ^^

Mains Breaker
Trip

Utility
Close Coil
Remote Alarm 1 ^^

Mains Breaker
Close

Group
Trip Coil
Mains Breaker
Aux (52)

Battery +

Battery -

Group Breaker
Close **

Group Breaker
Aux (52) ^^

Analog Output 1
Analog Output 2
Analog Output 3

Run w/ Load

Analog Alarm *
Synchroscope *
Utility KW *
System Load *
Bus Frequency *

Analog Input 1
Analog Input 2
Analog Input 3
Analog Input 4

Test

Process Input *
Process Reference *
PF Reference *

Echelon Network
(LON) Communications

Auto

To Other
EGCP-3's

Bus PTs

3-Phase or
1-Phase Sensing

Group Breaker
Trip **

Group
Close Coil

-+

Reset Alarm ^^

Breaker/Contactor synchronization timeout and


re-close alarms
Breaker/Contactor feedback and shunt trip alarms
Phase Rotation Mismatch
Network communication error alarms
Analog input out-of-range alarms
Configuration check

Bus CTs

Over/Under Voltage (59, 27)


Over/Under Frequency (81O, 81U)
Directional (Import/Export) Power (32) *
Negative Sequence Phase Overcurrent (46)
Negative Sequence Phase Overvoltage (47)
Phase Overcurrent (51) *
Voltage Restrained Phase Overcurrent (51V) *
Directional VAR
Phase Current Imbalance (46) *
Loss of Mains/Loss of Mains with Alarm
Load Surge (islanding protection)

Load 2
Trip Coil

Modbus * RTU via RS-232/-422/-485 serial ports


ServLink, Watch Window via RS-232/-422/-485
serial ports
Echelon ** TP/XF-1250 network (LON)

Load Raise ^^

Load Shed 2 **

Over/Under Voltage (59, 27)


Over/Under Frequency (81O, 81U)
Directional (Forward/Reverse) Power (32) *
Negative Sequence Phase Overcurrent (46)
Negative Sequence Phase Overvoltage (47)
Phase Overcurrent (51) *
Voltage Restrained Phase Overcurrent (51V)*
Directional VAR
Phase Current Imbalance (46) *

Voltage Lower ^^

Phase match or slip frequency synchronization


with voltage matching
Full three-phase sensing on both buses
Adjustable phase window, voltage window,
re-close attempts, re-close timing
Dead bus closing logic internal to the control
Synch check (25)
Breakers or contactors

COM Port 1

Servlink or Modbus
(RS-232,485,422)

COM Port 2

Modbus
(RS-232,485,422)

COM Port 3

Servlink
(RS-232)

HARDWARE SPECIFICATIONS
Size:
Operator Interface Panel:
Power Supply Voltage:
Control Part Numbers:

282 mm (11.1) high x 358 mm (14.1) wide x 134 mm (5.275) deep


8 (20 character) lines plus membrane keypad
24 Vdc system (1832 Vdc nominal; 940 Vdc maximum)
MC: 8406-114
Installation Manual: 26122
Operation Manual: 26195
Terminal blocks are screwless CageClamp-style blocks. PT and CT
inputs are fixed screw terminals.
70300 Vac
5 Aac RMS nominal, 7 Aac RMS maximum
20 to +70 C (4 to +158 F) operating
30 to +80 C (22 to +176 F) storage
95% at 60 C non-condensing
Type 4 (NEMA) requirements from the front panel and properly installed
in an equivalent enclosure
Suitable for engine skid or control cabinet
Random Test: 102000 Hz at 0.04 G/Hz and 8.2 Grms PSD
30 G peak, 11 ms duration, non-operating
Class I, Division 2, Groups A, B, C, D for North America
Zone 2, Group IIC for Europe
Declared to the EMC; Low-Voltage, and ATEX Directives
Type Approval by ABS, DNV, and LR for marine applications

Connectors:
Voltage Measuring Input Range:
Current Measuring Inputs:
Temperature Range:
Humidity:
Enclosure Rating:
Vibration:
Mechanical Shock:
Regulatory Compliance:

CAUTION

WARNING
FIELD CONFIGURABLE GOVERNOR

WOODWARD
TM

TM

PART NO.
SERIAL NO.

REV.
CAGE 31661

MANUFACTURED IN FORT COLLINS CO U.S.A. 9606

281.94
(11.100)

EGCP-3 CONTROL

260.35
(10.250)

INSTALLATION CATEGORY III


MAXIMUM AMBIENT 70 C
10-29 VDC, 20W MAXIMUM

130.18
(5.125)
DANGER

10.8
(0.425)

10.8
(0.425)

168.28
(6.625)
336.55
(13.250)
358.14
(14.100)

15.88
(0.625)

118.14
(4.651)

336.55
(13.250)

25.65
(0.250)
TYP 8 PLACES

168.28
(6.625)

260.35
(10.250)

241.3
(9.500)

130.18
(5.125)

7.14
(0.280)

322.28
(12.688)

9.53
(0.375)

EGCP-3 Outline Drawing and Panel Layout Template


(Do not use for construction)

EGCP-3 MC Applications/Configurations
Multiple UnitUtility Parallel

Woodward
Industrial Controls
PO Box 1519
Fort Collins CO, USA
80522-1519
1000 East Drake Road
Fort Collins CO 80525
Ph: +1 (970) 482-5811
Fax: +1 (970) 498-3058

Unit 16
EGCP-3
MC

Load
Breakers

Bus A

Unit 2
EGCP-3
LS

Distributors & Service


Woodward has an
international network of
distributors and service
facilities. For your nearest
representative, call the
Fort Collins plant or see
the Worldwide Directory
on our website.

GS

Load

Unit 1
EGCP-3
LS

GS

Multiple UnitATS
Load
Breakers

Unit 16
EGCP-3
MC

Corporate Headquarters
Rockford IL, USA
Ph: +1 (815) 877-7441

Bus A
Group
Breaker

Load

www.woodward.com
Unit 2
EGCP-3
LS

Unit 1
EGCP-3
LS

GS

GS

Multiple UnitMultiple Unit Parallel


Synchronizer

Unit 16
EGCP-3
MC

Unit 15
EGCP-3
MC

SPM-D

Tie W

Load
Breakers

Load
Breakers

Bus A

Bus B
Load

Unit 2
EGCP-3
LS

Unit 1
EGCP-3
LS

GS

Load

Unit 3
EGCP-3
LS

GS

Unit 4
EGCP-3
LS

GS

GS

Other Configurations

Single UtilityMultiple Bus


Multiple UtilitySingle/Multiple Bus

For a complete set of EGCP-3 Installation/Operation manuals or Application Notes on the


above configurations, download from the Woodward Industrial Controls website at:
This document is distributed

www.woodward.com/ic

for informational purposes


only. It is not to be construed
as creating or becoming part
of any Woodward Governor
Company contractual or
warranty obligation unless
expressly stated in a written
sales contract.

For more information contact:

Woodward Governor
Company, 2002
All Rights Reserved