Beruflich Dokumente
Kultur Dokumente
M. A. Alaam
Ahmed M. Azmy
Abstract This paper presents a sequence componentsbased analytical technique for fault location in distribution
systems. The technique considers different distribution system
characteristics including non homogeneity in feeder sections, load
distribution along the feeder, laterals are tapped at various nodes
and load variation. The proposed technique depends on sequence
components and uses a power flow analysis based on ladder
technique for compensating the load variation. To evaluate this
technique, it is implemented on 11 kV feeder using ATP/EMTP
package. Single-line-to-ground and three phase faults with
various fault resistance values are simulated. To examine the
technique accuracy with load variation, four loading cases are
included. The results achieved ensure the validity and ability of
the proposed technique to reduce the error in determining fault
location.
Index Terms Fault location, Impedance-based techniques,
Load variation
I. INTRODUCTION
Electric power distribution systems face various
problems caused by lightning, storms, insulation breakdown,
and others [1]. This leads to power interruption and hence,
unacceptable power continuity indices [2]. Therefore, fault
location is essential to reduce the outage time. In contrast to
transmission system, distribution system usually consists of
non homogenous feeder sections, with loads distributed along
the feeder. In addition, laterals are tapped at various nodes,
where the loads are time variant in nature.. For conventional
distribution systems, the measurements are available at the
substation only.
Fault location suffers from many sources of error that
may be divided into two categories. The first is related to
abovementioned distribution system inherent characteristics,
while the second considers the fault itself, i.e. fault type, point
and resistance value. Several impedance-based fault location
techniques have been developed [3]-[10]. However, each
method individually does not totally cover these sources of
error. Time-varying loads are one of sophisticated problems
that decrease the fault location accuracy. Load variation is not
N-1
XZL1 F (1-X)ZL1
Zs12
Zs11
Is
Main
Substation
ZM2
Zsc1
Loads
Vs
Zk11
Zk12
ZM0
Zk1n
3Rf
Zs12 2
Zth
n+1
Zs1N N
Zsc1
L
E
Zk11
Zk12
Zk1N
(a)
Zs21 1
Zs22 2
Zk21
Zk22
Zk2N
ZP1
ZL1
(b)
Zs01
Zsc0
Zk01
Zs02
Zs0N
Zk02
Zk0N
(1)
u
L
Zs2N N
where
Zu1
:
Zsc2
(c)
where
s
s
L
s
s
s
s
:
:
:
:
A. SLG Fault
For a SLG fault with a fault resistance of Rf occurred at
point F, all positive, negative and zero sequence circuits are
included. The system beyond the fault section in the positive
sequence circuit is represented by Thevenin equivalent
impedance Zth. Also, negative and zero sequence circuits are
reduced to the equivalent impedances ZM2 and ZM0
respectively as illustrated in Fig. 3. ZM2 is calculated using (1)
(2)
(3)
(4)
where
Vk
Ik
:
:
ZM2
Iy
ZM0
Zth
3Rf
n
n+1
(5)
Start
fs = 1
(6)
where
L
fs = fs+1
L
No
(8)
Yes
m = fs
End
Fig. 5 Flowchart for proposed technique procedure
(9)
(10)
where, Ai, Bi and Ci are the imaginary parts of terms A, B and
C respectively.
The value of fault distance (X) measured from node (n)
is calculated by solving (10) as stated in (11).
(11)
st
(12)
where
Dj
: Length of jth feeder section
m
: Actual fault section number
The following flow chart illustrates the procedure for
fault distance calculation in case of SLG faults. In this chart
s r rs to t
ssu
uts to
st
tu
fault section.
(13)
(14)
where
ZPFM
ZPFE
100
kVA
300
63
kVA
160
kVA
400
kVA
620
160
kVA
510
1640
kVA
500 300
kVA kVA
740
Start
160
kVA
1100
63 160
kVA kVA
240
Fault
Locator
Read VPFM
and IPFM
Calculate ZPFM
| |
360
kVA
120
Main
Substation
980
500
200
kVA
kVA
1
2
3
4
5
6
7
8
9 10 11
12 13 14
2800
720 160 560 870 560 2150 500 520 530 300 340 420 530
2402
2402
mm
mm
(15)
300
kVA
100
kVA
1200
400
1200
35 mm2
No
where
Dest
Dact
Yes
:
:
st
ot
(16)
End
RLV10
RLV50
Rf=50
0.12
0.6
0.1
0.4
0.08
0.2
% Error
% Error
Rf=0
0.06
0.04
RLV30
URLV
0
-0.2
-0.4
0.02
-0.6
0
0
2000
4000
6000
-0.8
8000 10000
6000
8000 10000
RLV10
RLV50
Rf=50
0.01
0.005
% Error
% Error
Rf=10
4000
Rf=0
2000
-0.005
-0.01
RLV30
URLV
1
0
-1
-2
-0.015
0
2000
4000
6000
-3
8000 10000
2000
4000
6000
8000 10000
RLV10
RLV50
0.15
RLV30
URLV
VI. CONCLUSION
0.1
% Error
0.05
0
-0.05
-0.1
-0.15
-0.2
0
2000
4000
6000
8000 10000
r t
three-phase circuit analysis-based fault location for line-to-line
ut
r s t o o ow r
v ry vo .
pp. 5 -2547,
Oct. 2007.
[9]
. L o G eralized fault location methods for overhead electric
str but o syst s
r s t o o ow r
v ry vo . 6
pp. 53-64, Jan. 2011.
[10] R. H. Salim, M. Resener, A. D. Filomena, K. R. Caino de Oliveira,
. S. r t s xt
u t location formulation for power
str but o syst s
r s t o o ow r
v ry vo .
24,pp. 508-516, Apr. 2009.
[11] W. . K rst
str but o syst
o
ys s o
Ratn, London, 2nd edition, CRC press, 2007.
[12] Alternative Transient Program: ATP/EMTP, Bonneville Power
Administration, 2002. [Online]. Available: http://www.emtp.org/.
[1]