2014
225/33kV SIN - SUBSTATION
NO
EQUIPMENTS
1.1
HV EQUIPMENT
QUANTITY
UNIT
PACKAGE
Nos
REMARKS
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2.Surge arrester ratings,type,class are subject to
approval to insulation co-ordination study by the client
and the consultant.
Nos
No
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1. CT ratings,type and clause mentioned are tentaive
and shall be confirmed after the approval of calculation
by the client and the consultant.
225kV,1200-800/1-1-1-1A,core1:0.5Fs5,30VA.
Core2:5P20,30VA.Core3:5P20,30VA.Core4:5P20,30VA, Current transformers
(CT)(Free standing)(Outdoor)
225 kV,1250 A,31.5kA/1sec, Three phase circuit breaker - single pole operated,
equipped with a central control cubicle(Outdoor)
Page 1 of 35
Nos
No
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
No
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
EQUIPMENTS
QUANTITY
UNIT
REMARKS
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2.1
HV EQUIPMENT
set
PACKAGE
Nos
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2.Surge arrester ratings,type,class are subject to
approval to insulation co-ordination study by the client
and the consultant.
Nos
No
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1. CT ratings,type and clause mentioned are tentaive
and shall be confirmed after the approval of calculation
by the client and the consultant.
225kV,1200-800/1-1-1-1A,core1:0.5Fs5,30VA.
Core2:5P20,30VA.Core3:5P20,30VA.Core4:5P20,30VA, Current transformers
(CT)(Free standing)(Outdoor)
Page 2 of 35
Nos
EQUIPMENTS
QUANTITY
225 kV,1250 A,31.5kA/1sec, Three phase circuit breaker - single pole operated,
equipped with a central control cubicle(Outdoor)
UNIT
REMARKS
No
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
No
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
3.1
HV EQUIPMENT
set
PACKAGE
Nos
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2.Surge arrester ratings,type,class are subject to
approval to insulation co-ordination study by the client
and the consultant.
Page 3 of 35
Nos
EQUIPMENTS
QUANTITY
UNIT
No
REMARKS
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1. CT ratings,type and clause mentioned are tentaive
and shall be confirmed after the approval of calculation
by the client and the consultant.
225kV,1200-800/1-1-1-1A,core1:0.5Fs5,30VA.
Core2:5P20,30VA.Core3:5P20,30VA.Core4:5P20,30VA, Current transformers
(CT)(Free standing)(Outdoor)
225 kV,1250 A,31.5kA/1sec, Three phase circuit breaker - single pole operated,
equipped with a central control cubicle(Outdoor)
Nos
No
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
No
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
4.1
HV EQUIPMENT
Page 4 of 35
set
PACKAGE
EQUIPMENTS
QUANTITY
UNIT
Nos
REMARKS
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2.Surge arrester ratings,type,class are subject to
approval to insulation co-ordination study by the client
and the consultant.
Nos
No
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1. CT ratings,type and clause mentioned are tentaive
and shall be confirmed after the approval of calculation
by the client and the consultant.
225kV,1200-800/1-1-1-1A,core1:0.5Fs5,30VA.
Core2:5P20,30VA.Core3:5P20,30VA.Core4:5P20,30VA, Current transformers
(CT)(Free standing)(Outdoor)
225 kV,1250 A,31.5kA/1sec, Three phase circuit breaker - single pole operated,
equipped with a central control cubicle(Outdoor)
Page 5 of 35
Nos
No
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
No
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
EQUIPMENTS
QUANTITY
UNIT
REMARKS
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
5.1
HV EQUIPMENT
set
PACKAGE
Nos
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2.Surge arrester ratings,type,class are subject to
approval to insulation co-ordination study by the client
and the consultant.
Nos
No
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1. CT ratings,type and clause mentioned are tentaive
and shall be confirmed after the approval of calculation
by the client and the consultant.
225kV,1200-800/1-1-1-1A,core1:0.5Fs5,30VA.
Core2:5P20,30VA.Core3:5P20,30VA.Core4:5P20,30VA, Current transformers
(CT)(Free standing)(Outdoor)
Page 6 of 35
Nos
EQUIPMENTS
QUANTITY
225 kV,1250 A,31.5kA/1sec, Three phase circuit breaker - single pole operated,
equipped with a central control cubicle(Outdoor)
UNIT
REMARKS
No
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
No
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
6.1
HV EQUIPMENT
set
No
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
Page 7 of 35
set
EQUIPMENTS
QUANTITY
UNIT
Nos
REMARKS
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1. CT ratings,type and clause mentioned are tentaive
and shall be confirmed after the approval of calculation
by the client and the consultant.
225kV,2500-1250/1-1-1-1A,core1:0.5Fs5,30VA.
Core2:5P20,30VA.Core3:5P20,30VA.Core4:5P20,30VA, Current transformers
(CT).(free standing)
7.1
HV EQUIPMENT 225KV
Nos
No
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2. Surge arrester(245kV,33kV) to be mounted in the
transformer itself as per the particular technical
specifications (REF - NKT-NDB/4FG/0300293/001/00)
page no 17/44clause no 4.2.1.5
225 kV,1250 A,31.5kA/1sec, three phase circuit breaker - Three pole operated,
equipped with a central control cubicle (outdoor)
No
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
Page 8 of 35
set
No
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
EQUIPMENTS
QUANTITY
UNIT
REMARKS
1. CT ratings,type and clause mentioned are tentaive
and shall be confirmed after the approval of calculation
by the client and the consultant.
225kV,200-100/1-1-1-1A,core1:0.5Fs5,30VA.
Core2:5P20,30VA.Core3:5P20,30VA.Core4:5P20,30VA, Current transformers (CT)
(outdoor)(free standing)
Nos
No
Nos
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2. Surge arrester(220kV,33kV) to be mounted in the
transformer itself as per the particular technical
specifications (REF - NKT-NDB/4FG/0300293/001/00)
page no 17/44clause no 4.2.1.5
1. CT ratings,type and clause mentioned are tentaive
and shall be confirmed after the approval of calculation
by the client and the consultant.
No
HV EQUIPMENT 33KV
PACKAGE
No
Page 9 of 35
No
No
EQUIPMENTS
QUANTITY
UNIT
Nos
REMARKS
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2.Surge arrester ratings,type,class are subject to
approval to insulation co-ordination study by the client
and the consultant.
9.1
HV EQUIPMENT
PACKAGE
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
No
225 kV,1250 A,31.5kA/1sec, Three phase circuit breaker - single pole operated,
equipped with a central control cubicle (outdoor)
No
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
Page 10 of 35
set
No
EQUIPMENTS
QUANTITY
UNIT
REMARKS
Nos
No
Nos
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2.Surge arrester ratings,type,class are subject to
approval to insulation co-ordination study by the client
and the consultant.
10
10.1
HV EQUIPMENT
No
PACKAGE
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
225 kV - 50 Mvar compensation shunt reactor equipped with all its
accessories including in built neutral CT's (outdoor)
No
225 kV,1250 A,31.5kA/1sec, Three phase circuit breaker - single pole operated,
equipped with a central control cubicle (outdoor)
Page 11 of 35
No
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
EQUIPMENTS
QUANTITY
UNIT
REMARKS
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
set
No
Nos
No
Nos
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2.Surge arrester ratings,type,class are subject to
approval to insulation co-ordination study by the client
and the consultant.
Page 12 of 35
No
EQUIPMENTS
QUANTITY
UNIT
PACKAGE
11
Nos
REMARKS
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
12
12.1
Nos
600
Mtr
1850
Mtr
30
Mtr
Conductor (AAAC)
12.2
12.3
Post insulators
1. BOQ is tentative and may vary based on the actual
overall equipment layout,section drawings, erection key
drawing,cantilever strength claculation which is subject
to client and consultant approval.
145
Page 13 of 35
Nos
EQUIPMENTS
QUANTITY
UNIT
REMARKS
1. BOQ is tentative and may vary based on the actual
overall equipment layout,section drawings, erection key
drawing,cantilever strength claculation which is subject
to client and consultant approval.
Nos
Nos
Nos
Nos
Nos
Nos
Nos
72
Nos
90 connector (CVT,TRAFO)
Cable: 630Sq.mm, AAAC
18
Nos
30
Nos
12.4
12.5
12.5.1
POWER CONNECTORS
225kV Side
Straight connector(CT,CB)
Cable: 630Sq.mm, AAAC
Page 14 of 35
EQUIPMENTS
QUANTITY
UNIT
15
Nos
Tee Connector
Cable: 630Sq.mm, AAAC
Cable: 630Sq.mm, AAAC
30
Nos
18
Nos
12
Nos
33
Nos
Nos
54
Nos
24
Nos
85
Nos
63
Nos
30
Nos
10
Nos
90
Nos
Page 15 of 35
REMARKS
EQUIPMENTS
QUANTITY
UNIT
15
Nos
Nos
Nos
Nos
Tee connector with base (for Post insulator used for tube support in tertiary of
power transformer)
Tube: Cu, 40/50mm dia
Nos
Nos
Nos
12.5.2
REMARKS
33kV side
13
13.1
PACKAGE
No
33kV,800-400/1-1-1A,Core1:5P20,30VA, Core2:5P20,30VA,Core3:
0.5Fs5,30VA,Current transformers equipped with three secondary windings:
measurements and protections
Nos
Nos
Three pole operated earthing switch manual operated equipped with a locking coil
in combination with push button
No
Nos
lot
LV COMPARTMENT:
The LV compartment of switchgear shall comprise of protection/auxillary relays
,test blocks ,metering,wiring terminals all other associated LV equipments
complying to technical specification and scope of work ,technical data sheet ,SLD
and protection logic diagram.
Energy meter(0.5)class Located in the LV compartment
Page 16 of 35
EQUIPMENTS
QUANTITY
UNIT
REMARKS
PACKAGE
No
Nos
Three pole operated earthing switch manual operated equipped with a locking coil
in combination with push button
No
Nos
LOT
LOT
PACKAGE
No
Nos
Three pole operated earthing switch manual operated equipped with a locking coil
in combination with push button
No
Nos
lot
lot
PACKAGE
LV COMPARTMENT:
The LV compartment of switchgear shall comprise of protection/auxillary relays
,test blocks ,metering,wiring terminals all other associated LV equipments
complying to technical specification and scope of work ,technical data sheet ,SLD
and protection logic diagram.
LV COMPARTMENT:
The LV compartment of switchgear shall comprise of protection/auxillary relays
,test blocks ,metering,wiring terminals all other associated LV equipments
complying to technical specification and scope of work ,technical data sheet ,SLD
and protection logic diagram.
13.5
Nos
Three pole operated earthing switch manual operated equipped with a locking coil
in combination with push button
No
Page 17 of 35
EQUIPMENTS
QUANTITY
UNIT
REMARKS
One test connector for each type of protection relays located in 33kV switchgear
LT
14
14.01.01
Notes-All of the cable paths, trays and their supports shall be hot-dip
galvanised as per General Technical Specifications,clause 3 page no 9/11 Cable installation and cable connection works REF.: NKTNDB/4FG/0292672/001/00 .
Straight Section sheet steel Material hot dip galvanised , 600mm Wide 20mm
Outside Stiffened Upper Return Flange, Swaged Round Tubular Rungs, Material
Thickness-2mm, Side Rail Height - 175mm, Rung Spacing - 140mm, Length 3660mm Cable ladder having the following widths. (indoor)
600mm Wide Horizontal Tee cable ladder of hot dip galvanised , sheet steel
Material Thickness-2mm, Side rail height - 175mm, 20mm flange, 300mm radius,
Aluminum, Round tubular rung type with the following wide & side heights
(indoor)
Blind End with Screw of hot dip galvanised, nut & flat washer for 600mm Wide&
Side rail height-175mm
Blind End with Screw of hot dip galvanised, nut & flat washer for 450mm Wide&
Side rail height-175mm
31
31
6m long, Double unistruct channel of hot dip galvanised for cable ladder supports.
14.01.02
16
Nos
Nos
Nos
No
Nos
Nos
Nos
Nos
Nos
Double Channel high Post base of hot dip galvanised with two hole fixing plate
26
52
Page 18 of 35
EQUIPMENTS
QUANTITY
52
70
39
14.01.03
REMARKS
Nos
Nos
Nos
Notes-All of the cable paths, trays and their supports shall be hot-dip galvanised as
per General Technical Specifications,clause 3 page no 9/11 - Cable installation and
cable connection works REF.: NKT-NDB/4FG/0292672/001/00 .
Straight Section sheet steel Material hot dip galvanised , 600mm Wide 20mm
Outside Stiffened Upper Return Flange, Swaged Round Tubular Rungs, Material
Thickness-2mm, Side Rail Height - 175mm, Rung Spacing - 140mm, Length 3660mm Cable ladder having the following widths. (outdoor)
600mm Wide Horizontal Tee cable ladder of hot dip galvanised , sheet steel
Material Thickness-2mm, Side rail height - 175mm, 20mm flange, 300mm radius,
Aluminum, Round tubular rung type with the following wide & side heights
(outdoor)
600mm Wide Horizontal cross cable ladder of hot dip galvanised , sheet steel
Material Thickness-2mm, Side rail height - 175mm, 20mm flange, 300mm radius,
Aluminum, Round tubular rung type with the following wide & side heights
(outdoor)
600mm Wide Horizontal elbow cable ladder of hot dip galvanised, sheet steel
Material Thickness-2mm, Side rail height - 175mm, 20mm flange, 300mm radius,
Aluminum, Round tubular rung type with the following wide & side heights
(outdoor)
Blind End with Screw of hot dip galvanised, nut & flat washer for 600mm Wide&
Side rail height-175mm
361
50
20
55
722
722
6m long, Double unistruct channel of hot dip galvanised for cable tray supports.
14.01.04
UNIT
Page 19 of 35
241
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
EQUIPMENTS
QUANTITY
Double Channel high Post base of hot dip galvanised with two hole fixing plate
14.02.01
241
UNIT
Nos
REMARKS
QTY&TYPE arrived are tentative and subject to vary
based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.
241
963
481
60
450mm Wide, Inside returned flange, Straight section, sheet steel Material
thickness-2mm, Side rail height-100mm, length - 3660mm Cable Tray having the
following widths.(indoor)
450mm Wide Horizontal Tee, sheet steel Material Thickness-2mm, Inside returned
20mm flange, side rail height - 100mm, 300mm radius, Aluminum with the
following wide.(indoor)
Blind End with Screw, nut & flat washer with 900mm Wide, 100mm Height
16
10
23
Page 20 of 35
Nos
Nos
Nos
Nos
Nos
EQUIPMENTS
QUANTITY
14.02.02
14
REMARKS
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
450mm Wide, Inside returned flange of hot dip galvanised, Straight section, sheet
steel material, Material thickness-2mm, Side rail height-100mm, length - 3660mm
perforated Cable Tray with cover having the following widths(oudoor)
450mm Wide Horizontal Tee with cover of hot dip galvanised, sheet steel
material,Material Thickness-2mm, Inside returned 20mm flange, side rail height 100mm, 300mm radius, Aluminum with the following wide. (oudoor)
Blind End with Screw of hot dip galvanised, nut & flat washer with 900mm Wide,
100mm Height
120
25
28
241
241
30
14.03
UNIT
300 mm long, Double Channel Aluminium Vertical Arm of hot dip galvanised
Page 21 of 35
40
EQUIPMENTS
QUANTITY
3300 mm long, Double Channel Aluminium Vertical Arm (Swgr End) of hot dip
galvanised
1500 mm long, Double Channel Aluminium Horizontal Arm (Swgr End) of hot dip
galvanised
25
26
50
50
78
15
17
Page 22 of 35
UNIT
REMARKS
Nos
Nos
Nos
Nos
Nos
Nos
Nos
LT
LT
LT
EQUIPMENTS
QUANTITY
UNIT
REMARKS
Mtr
200
Mtr
Nos
Nos
33kV Indoor Termination Kit to suit 1C X 300Sq.mm Cable at 33kV Switchgear End
Nos
Nos
Nos
Nos
Nos
600
Nos
Nos
Nos
Nos
Nos
16
LV ELECTRICAL EQUIPMENT
16.01
PROTECTION SYSTEM
95
67
32
Nos
No
Nos
Page 23 of 35
EQUIPMENTS
QUANTITY
UNIT
No
No
LT
PACKAGE
No
No
No
PACKAGE
PACKAGE
REMARKS
TEST CONNECTORS
One test connector for each type of protection relays located in 225kV PANELS
16.02
16.03
16.03.01
16.03.01.01
DCS SYSTEM
No
No
No
16.03.01.03
Power distribution board-1 (control building), Indoor, WALL mounted400V, 3Ph, 4Wire, 125A,CU, 50Hz, 10kA .
1.Incomer- 400V , 125A TPN, MCCB -2 no
16.03.01.04
Page 24 of 35
EQUIPMENTS
QUANTITY
UNIT
REMARKS
No
No
No
No
PACKAGE
Nos
Nos
FUSE BOX
Nos
Control and relay panel distribution board , Indoor, Floor mounted400V, 3Ph, 4Wire, 63A,CU, 50Hz, 10kA .
1. Incomer- 400V ,63A ,TPN, MCCB -1 NOS
16.03.01.06
16.03.01.07
16.04
16.04.01
Page 25 of 35
EQUIPMENTS
QUANTITY
UNIT
REMARKS
No
Nos
Nos
FUSE BOX
Nos
No
PACKAGE
No
communication panel
Nos
No
625
Mtrs
LT
NOS
PACKAGE
16.04.02
16.04.03
48VDC - BATTERY
1.Incomer-DP,MCCB,63A - 2nos
16.04.04
17.01
17.02
Page 26 of 35
QUANTITY
UNIT
18
PACKAGE
19
Earthing system
PACKAGE
17.03
19.01
EQUIPMENTS
REMARKS
11950
Mtrs
275
Mtr
300
Mtr
160
Mtr
175
Mtr
16 Sq.mm Copper Yellow green PVC insulation ( for cable trays/ladder, wiring
boxes, protection
cabinets, protective circuits of the LV cables)
200
Mtr
63
Nos
13
Nos
32
Nos
21
Nos
2112
Nos
Page 27 of 35
19.02
EQUIPMENTS
QUANTITY
UNIT
194
Nos
15
Nos
20
Nos
20
Nos
13
Nos
725
Nos
PACKAGE
Early Streamer Emission Air Terminal (ESEAT). Equipped with a metal rods made
of stainless steel(minimum diameter of 4 cm) minimum of 4 metres in height
attached to the gantries and lightning poles.
NOS
135
NOS
27
NOS
NOS
NOS
PACKAGE
20
21
REMARKS
Page 28 of 35
EQUIPMENTS
QUANTITY
UNIT
REMARKS
21.01
No
No
No
No
60
Nos
30
Nos
25
Nos
Nos
Wall / Surface / Pendant / Recess mounted, Indoor, IP21, 1X60W, 110V DC lamp
lighting fixtures
(Note-Charging to be done by AC-230V)
35
Nos
Wall / Surface / Pendant / Recess mounted, Indoor, IP21, 1X60W, 110V DC lamp
lighting fixtures (explosion proof-indoor)
(Note-Charging to be done by AC-230V)
Nos
Indoor Lighting Panel-2 (accomodation building), Indoor, Floor mounted400V, 3Ph, 4W,CU, 16A, 50Hz, 10kA
21.03
21.06
Page 29 of 35
EQUIPMENTS
QUANTITY
UNIT
REMARKS
10
Nos
Outdoor, Flood light fixture 250W HPS, 230V, AC, 50HZ - Trunnion mounting
60
Nos
Outdoor, Flood light fixture 70W HPS, 230V, AC, 50HZ - Trunnion mounting
10
Nos
21
Nos
64
Nos
20
Nos
15
Nos
35
Nos
21.08
10
Nos
21.09
Receptacles
400V,160A, 3,TPN,5 PIN HEAVY DUTY SWITCH SOCKET OUTLET IP55
PROTECTION WITH BASS SCREW COVER AND PLUGS (WEATHER PROOF)
230V AC 16A flush mounted duplex indoor receptacle with parallel slot &
grounding u-slot
Page 30 of 35
Nos
28
Nos
Nos
EQUIPMENTS
QUANTITY
UNIT
REMARKS
16
Nos
PACKAGE
230V AC 25A flush mounted duplex indoor receptacle with parallel slot &
grounding u-slot
22
22.01
NOTES - As per General Technical Specifications Power, control and signalling cables (ref.: NKTNDB/4FG/0292669/001/00) clause 4.3 page 8 of 12,
The cables shall be of the type with PVC insulation, a
protective circuit with a
copper screen (stranded wire) and a PVC outer sleeve.
PVC Sheathed,cable
1510
Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
1.Size ,no of cores, Type of cables and BOQ and
descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.
8285
Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
1.Size ,no of cores, Type of cables and BOQ and
descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.
225
Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
1.Size ,no of cores, Type of cables and BOQ and
descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.
7855
Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
1.Size ,no of cores, Type of cables and BOQ and
descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.
675
Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
Page 31 of 35
EQUIPMENTS
QUANTITY
UNIT
REMARKS
1.Size ,no of cores, Type of cables and BOQ and
descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.
5865
Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
1.Size ,no of cores, Type of cables and BOQ and
descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.
3910
Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
1.Size ,no of cores, Type of cables and BOQ and
descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.
1310
Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
22.02
LT
NOTES - As per General Technical Specifications Power, control and signalling cables (REF.: NKTNDB/4FG/0292669/001/00) clause 4.2 page 8 of
12,The LV cables shall have either PVC or XLPE
insulation, with a PVC outer jacket; a
protective conductor shall be provided under the outer
jacket of the cable.
XLPE Sheathed,cable
335
Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
570
Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
Page 32 of 35
EQUIPMENTS
QUANTITY
UNIT
REMARKS
385
Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
3155
Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
650
Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
855
Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
115
Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
Page 33 of 35
EQUIPMENTS
QUANTITY
UNIT
REMARKS
1310
Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
210
Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
1575
Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
2555
Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
220
Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
3245
Mtr
1500
Mtr
Page 34 of 35
23
EQUIPMENTS
QUANTITY
450
UNIT
Mtr
REMARKS
24
No
25
No
NOTES
1. The boq/descriptions, types mentioned under sl.no (12.1 to 12.4,12.5.1 to 12.5.2, 13.1 to 13.5, 14.01.01 to 14.01.04 , 14.02.01 to 14.02.02, 14.03 , 15 , 16.03.01.01
to 16.03.01.08 , 16.04.01 to 16.04.04, 17.01 to 17.03 , 19.01 to 19.02 , 20 , 21.01 to 21.09 and 22.01 to 22.02) of this BOQ are tentative only and not for ordering
purpose. Actaul quantity shall be confirmed during detailed engineering which is subject to approval of client/consultant only.
*********************X************************