BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.

2014
225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

BAY 1 LINE NKT CENTRALE NORD

1.1

HV EQUIPMENT

245kV,10kA,CL:3, Surge arresters equipped with individual discharge


counters(Outdoor)

QUANTITY

UNIT

PACKAGE

Nos

REMARKS

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2.Surge arrester ratings,type,class are subject to
approval to insulation co-ordination study by the client
and the consultant.

1. VT ratings,type and clause mentioned are tentaive


and shall be confirmed after the approval of calculation
by the client and the consultant.
225/3 kV/ (100 )/3V/100/3V ,Core1:0.5/3P,50VA,Core2:0.5/3P,50VA
Capacitive voltage transformer (CVT) designed to be equipped with line traps and
two secondary windings(Outdoor)

225kV,1250A,31.5kA/1sec, line combined disconnector, motorized, three pole,


operated, and associated with two earthing disconnector switches manual
operated.(Outdoor)

Nos

No

2. As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1. CT ratings,type and clause mentioned are tentaive
and shall be confirmed after the approval of calculation
by the client and the consultant.

225kV,1200-800/1-1-1-1A,core1:0.5Fs5,30VA.
Core2:5P20,30VA.Core3:5P20,30VA.Core4:5P20,30VA, Current transformers
(CT)(Free standing)(Outdoor)

225kV,1250A,31.5kA/1sec,Earthing disconnector switch, manual operated


equipped with a temporized locking coil (Free standing)(3-Phase)(Outdoor)

225 kV,1250 A,31.5kA/1sec, Three phase circuit breaker - single pole operated,
equipped with a central control cubicle(Outdoor)

Page 1 of 35

Nos

2. As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

No

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

No

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

UNIT

REMARKS

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

225 kV,1250 A,31.5kA/1sec, Busbar vertical disconnector(Pantograph type),


motorized - single pole operated and equipped with a central control cubicle (3PHASE)(outdoor)

BAY 2 LINE NKT CENTRALE NORD

2.1

HV EQUIPMENT

245kV,10kA,CL:3, Surge arresters equipped with individual discharge


counters(Outdoor)

set

PACKAGE

Nos

2. As per particular technical specification (REF NKT-NDB/4FG/0300291/000/01) clause no


(4.2.1.2,4.2.1.4,4.2.1.5,4.2.1.6)busbar
disconnectors is mentioned as vertical
disconnector type ,motorised-single pole
operated, Whereas as per as per tender
layout(dwg no 1256618 ) and section
drawings(dwg no
1257016&1257018&1257124&1256789) high
post bus bar scheme is followed in which
pantograph disconnectors are used. In light of
above we are proposing Pantograph
disconnectors .This is for information and clarity.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2.Surge arrester ratings,type,class are subject to
approval to insulation co-ordination study by the client
and the consultant.

1. VT ratings,type and clause mentioned are tentaive


and shall be confirmed after the approval of calculation
by the client and the consultant.
225/3 kV/ (100 )/3V/100/3V ,Core1:0.5/3P,50VA,Core2:0.5/3P,50VA
Capacitive voltage transformer (CVT) designed to be equipped with line traps and
two secondary windings(Outdoor)

225kV,1250A,31.5kA/1sec, line combined disconnector, motorized, three pole,


operated, and associated with two earthing disconnector switches manual
operated.(Outdoor)

Nos

No

2. As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1. CT ratings,type and clause mentioned are tentaive
and shall be confirmed after the approval of calculation
by the client and the consultant.

225kV,1200-800/1-1-1-1A,core1:0.5Fs5,30VA.
Core2:5P20,30VA.Core3:5P20,30VA.Core4:5P20,30VA, Current transformers
(CT)(Free standing)(Outdoor)

Page 2 of 35

Nos

2. As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

225kV,1250A,31.5kA/1sec,Earthing disconnector switch, manual operated


equipped with a temporized locking coil (Free standing)(3-Phase)(Outdoor)

225 kV,1250 A,31.5kA/1sec, Three phase circuit breaker - single pole operated,
equipped with a central control cubicle(Outdoor)

UNIT

REMARKS

No

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

No

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

225 kV,1250 A,31.5kA/1sec, Busbar vertical disconnector(Pantograph type),


motorized - single pole operated and equipped with a central control cubicle (3PHASE)(outdoor)

BAY 1 LINE PK41

3.1

HV EQUIPMENT

245kV,10kA,CL:3, Surge arresters equipped with individual discharge


counters(Outdoor)

set

PACKAGE

Nos

2. As per particular technical specification (REF NKT-NDB/4FG/0300291/000/01) clause no


(4.2.1.2,4.2.1.4,4.2.1.5,4.2.1.6)busbar
disconnectors is mentioned as vertical
disconnector type ,motorised-single pole
operated, Whereas as per as per tender
layout(dwg no 1256618 ) and section
drawings(dwg no
1257016&1257018&1257124&1256789) high
post bus bar scheme is followed in which
pantograph disconnectors are used. In light of
above we are proposing Pantograph
disconnectors .This is for information and clarity.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2.Surge arrester ratings,type,class are subject to
approval to insulation co-ordination study by the client
and the consultant.

1. VT ratings,type and clause mentioned are tentaive


and shall be confirmed after the approval of calculation
by the client and the consultant.
225/3 kV/ (100 )/3V/100/3V ,Core1:0.5/3P,50VA,Core2:0.5/3P,50VA
Capacitive voltage transformer (CVT) designed to be equipped with line traps and
two secondary windings(Outdoor)

Page 3 of 35

Nos

2. As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

225kV,1250A,31.5kA/1sec, line combined disconnector, motorized, three pole,


operated, and associated with two earthing disconnector switches manual
operated.(Outdoor)

UNIT

No

REMARKS

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1. CT ratings,type and clause mentioned are tentaive
and shall be confirmed after the approval of calculation
by the client and the consultant.

225kV,1200-800/1-1-1-1A,core1:0.5Fs5,30VA.
Core2:5P20,30VA.Core3:5P20,30VA.Core4:5P20,30VA, Current transformers
(CT)(Free standing)(Outdoor)

225kV,1250A,31.5kA/1sec,Earthing disconnector switch, manual operated


equipped with a temporized locking coil (Free standing)(3-Phase)(Outdoor)

225 kV,1250 A,31.5kA/1sec, Three phase circuit breaker - single pole operated,
equipped with a central control cubicle(Outdoor)

Nos

2. As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

No

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

No

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

225 kV,1250 A,31.5kA/1sec, Busbar vertical disconnector(Pantograph type),


motorized - single pole operated and equipped with a central control cubicle (3PHASE)(outdoor)

BAY 2 LINE PK41

4.1

HV EQUIPMENT

Page 4 of 35

set

PACKAGE

2. As per particular technical specification (REF NKT-NDB/4FG/0300291/000/01) clause no


(4.2.1.2,4.2.1.4,4.2.1.5,4.2.1.6)busbar
disconnectors is mentioned as vertical
disconnector type ,motorised-single pole
operated, Whereas as per as per tender
layout(dwg no 1256618 ) and section
drawings(dwg no
1257016&1257018&1257124&1256789) high
post bus bar scheme is followed in which
pantograph disconnectors are used. In light of
above we are proposing Pantograph
disconnectors .This is for information and clarity.

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

245kV,10kA,CL:3, Surge arresters equipped with individual discharge


counters(Outdoor)

UNIT

Nos

REMARKS

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2.Surge arrester ratings,type,class are subject to
approval to insulation co-ordination study by the client
and the consultant.

1. VT ratings,type and clause mentioned are tentaive


and shall be confirmed after the approval of calculation
by the client and the consultant.
225/3 kV/ (100 )/3V/100/3V ,Core1:0.5/3P,50VA,Core2:0.5/3P,50VA
Capacitive voltage transformer (CVT) designed to be equipped with line traps and
two secondary windings(Outdoor)

225kV,1250A,31.5kA/1sec, line combined disconnector, motorized, three pole,


operated, and associated with two earthing disconnector switches manual
operated.(Outdoor)

Nos

No

2. As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1. CT ratings,type and clause mentioned are tentaive
and shall be confirmed after the approval of calculation
by the client and the consultant.

225kV,1200-800/1-1-1-1A,core1:0.5Fs5,30VA.
Core2:5P20,30VA.Core3:5P20,30VA.Core4:5P20,30VA, Current transformers
(CT)(Free standing)(Outdoor)

225kV,1250A,31.5kA/1sec,Earthing disconnector switch, manual operated


equipped with a temporized locking coil (Free standing)(3-Phase)(Outdoor)

225 kV,1250 A,31.5kA/1sec, Three phase circuit breaker - single pole operated,
equipped with a central control cubicle(Outdoor)

Page 5 of 35

Nos

2. As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

No

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

No

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

UNIT

REMARKS

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

225 kV,1250 A,31.5kA/1sec, Busbar vertical disconnector(Pantograph type),


motorized - single pole operated and equipped with a central control cubicle (3PHASE)(outdoor)

BAY LINE TASIAST

5.1

HV EQUIPMENT

245kV,10kA,CL:3, Surge arresters equipped with individual discharge


counters(Outdoor)

set

PACKAGE

Nos

2. As per particular technical specification (REF NKT-NDB/4FG/0300291/000/01) clause no


(4.2.1.2,4.2.1.4,4.2.1.5,4.2.1.6)busbar
disconnectors is mentioned as vertical
disconnector type ,motorised-single pole
operated, Whereas as per as per tender
layout(dwg no 1256618 ) and section
drawings(dwg no
1257016&1257018&1257124&1256789) high
post bus bar scheme is followed in which
pantograph disconnectors are used. In light of
above we are proposing Pantograph
disconnectors .This is for information and clarity.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2.Surge arrester ratings,type,class are subject to
approval to insulation co-ordination study by the client
and the consultant.

1. VT ratings,type and clause mentioned are tentaive


and shall be confirmed after the approval of calculation
by the client and the consultant.
225/3 kV/ (100 )/3V/100/3V ,Core1:0.5/3P,50VA,Core2:0.5/3P,50VA
Capacitive voltage transformer (CVT) designed to be equipped with line traps and
two secondary windings(Outdoor)

225kV,1250A,31.5kA/1sec, line combined disconnector, motorized, three pole,


operated, and associated with two earthing disconnector switches manual
operated.(Outdoor)

Nos

No

2. As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1. CT ratings,type and clause mentioned are tentaive
and shall be confirmed after the approval of calculation
by the client and the consultant.

225kV,1200-800/1-1-1-1A,core1:0.5Fs5,30VA.
Core2:5P20,30VA.Core3:5P20,30VA.Core4:5P20,30VA, Current transformers
(CT)(Free standing)(Outdoor)

Page 6 of 35

Nos

2. As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

225kV,1250A,31.5kA/1sec,Earthing disconnector switch, manual operated


equipped with a temporized locking coil (Free standing)(3-Phase)(Outdoor)

225 kV,1250 A,31.5kA/1sec, Three phase circuit breaker - single pole operated,
equipped with a central control cubicle(Outdoor)

UNIT

REMARKS

No

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

No

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

225 kV,1250 A,31.5kA/1sec, Busbar vertical disconnector(Pantograph type),


motorized - single pole operated and equipped with a central control cubicle (3PHASE)(outdoor)

BAY BUSBARS COUPLING 225KV

6.1

HV EQUIPMENT

225kV,2000A,31.5kA,1sec,Three-phase, circuit breakers - Three pole operated

set

No

2. As per particular technical specification (REF NKT-NDB/4FG/0300291/000/01) clause no


(4.2.1.2,4.2.1.4,4.2.1.5,4.2.1.6)busbar
disconnectors is mentioned as vertical
disconnector type ,motorised-single pole
operated, Whereas as per as per tender
layout(dwg no 1256618 ) and section
drawings(dwg no
1257016&1257018&1257124&1256789) high
post bus bar scheme is followed in which
pantograph disconnectors are used. In light of
above we are proposing Pantograph
disconnectors .This is for information and clarity.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

225 kV,1250A,31.5kA,1sec, busbar vertical disconnector(Pantograph type),


motorized - single pole operated and equipped with a central control cubicle (3
phase)

Page 7 of 35

set

2. As per particular technical specification (REF NKT-NDB/4FG/0300291/000/01) clause no


(4.2.1.2,4.2.1.4,4.2.1.5,4.2.1.6)busbar
disconnectors is mentioned as vertical
disconnector type ,motorised-single pole
operated, Whereas as per as per tender
layout(dwg no 1256618 ) and section
drawings(dwg no
1257016&1257018&1257124&1256789) high
post bus bar scheme is followed in which
pantograph disconnectors are used. In light of
above we are proposing Pantograph
disconnectors .This is for information and clarity.

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

225kV,Earthing disconnector switch, manual operated equipped with a temporized


locking coil (Free standing) (3 phase)

UNIT

Nos

REMARKS

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1. CT ratings,type and clause mentioned are tentaive
and shall be confirmed after the approval of calculation
by the client and the consultant.

225kV,2500-1250/1-1-1-1A,core1:0.5Fs5,30VA.
Core2:5P20,30VA.Core3:5P20,30VA.Core4:5P20,30VA, Current transformers
(CT).(free standing)

BAY TRANSFORMER 225/33KV

7.1

HV EQUIPMENT 225KV

225/33kV,1250A, 20 MVA - YNd11 power transformer equipped with all its


accessories and on load tap changer (outdoor)

Nos

No

2. As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2. Surge arrester(245kV,33kV) to be mounted in the
transformer itself as per the particular technical
specifications (REF - NKT-NDB/4FG/0300293/001/00)
page no 17/44clause no 4.2.1.5

225 kV,1250 A,31.5kA/1sec, three phase circuit breaker - Three pole operated,
equipped with a central control cubicle (outdoor)

No

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

225 kV,1250 A,31.5kA/1sec, Busbar vertical disconnector (Pantograph type),


motorized - single pole operated and equipped with a central control cubicle
(outdoor)(3 phase)

225kV,1250A,31.5kA/1sec,Earthing disconnector switch, manual operated


equipped with a temporized locking coil (Free standing),Busbar side(3-phase)
(outdoor)

Page 8 of 35

set

No

2. As per particular technical specification (REF NKT-NDB/4FG/0300291/000/01) clause no


(4.2.1.2,4.2.1.4,4.2.1.5,4.2.1.6)busbar
disconnectors is mentioned as vertical
disconnector type ,motorised-single pole
operated, Whereas as per as per tender
layout(dwg no 1256618 ) and section
drawings(dwg no
1257016&1257018&1257124&1256789) high
post bus bar scheme is followed in which
pantograph disconnectors are used. In light of
above we are proposing Pantograph
disconnectors .This is for information and clarity.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

UNIT

REMARKS
1. CT ratings,type and clause mentioned are tentaive
and shall be confirmed after the approval of calculation
by the client and the consultant.

225kV,200-100/1-1-1-1A,core1:0.5Fs5,30VA.
Core2:5P20,30VA.Core3:5P20,30VA.Core4:5P20,30VA, Current transformers (CT)
(outdoor)(free standing)

225kV,1250A,31.5kA/1sec,Earthing disconnector switch, manual operated


equipped with a temporized locking coil (Free standing),Transformer side
(outdoor) (3 phase)

245kV,10kA,CL:3, Surge arresters equipped with individual discharge counters


(outdoor)

Nos

No

Nos

2. As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2. Surge arrester(220kV,33kV) to be mounted in the
transformer itself as per the particular technical
specifications (REF - NKT-NDB/4FG/0300293/001/00)
page no 17/44clause no 4.2.1.5
1. CT ratings,type and clause mentioned are tentaive
and shall be confirmed after the approval of calculation
by the client and the consultant.

CT: 200-100/1A,Core1:5P20,30VA, 1250A ,31.5kA/1sec,torodal current


transformer (CT) equipped with one secondary winding, installed on the neutral
earthing connection of the transformer(outdoor type)

No

HV EQUIPMENT 33KV

PACKAGE

33/0.4 kV - 250 kVA - Dyn5 auxiliary transformer

No

2. As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

1. As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2.Ratings of Auxillary transformer is subject to
calculation approval by the client and the consultant

ZN - 1000 A / 5s earthing transformer

800-400/1-1A,core1:5P20,30VA,Core2:5P20,30VA,1kA, 5sec,Torodal current


transformer equipped with two secondary windings, installed on the 33 kV neutral
earthing connection of the ZN earthing transformer(outdoor type)

Page 9 of 35

No

No

1. As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

1. CT ratings,type and clause mentioned are tentaive


and shall be confirmed after the approval of calculation
by the client and the consultant.

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

33kV,10kA,CL:3,surge arresters equipped with individual discharge counters

UNIT

Nos

REMARKS

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2.Surge arrester ratings,type,class are subject to
approval to insulation co-ordination study by the client
and the consultant.

BAY 1 REACTANCE COMPENSATION 225KV

9.1

HV EQUIPMENT

PACKAGE
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

225 kV - 50 Mvar compensation shunt reactor equipped with all its


accessories including in built neutral CT's (outdoor)

No

2. Surge arrester to be mounted in the reactor itself as


per the particular technical specifications (REF - NKTNDB/4FG/0300291/001/00) page no 16/44 clause no
4.2.1.6
3.CT ratings,type and clause shall be confirmed during
detailed engineering.CT mounting on the reactors to be
discussed during detailed engineering.

225 kV,1250 A,31.5kA/1sec, Three phase circuit breaker - single pole operated,
equipped with a central control cubicle (outdoor)

No

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

225 kV,1250 A,31.5kA/1sec, Busbar vertical disconnector(Pantograph type),


motorized - single pole operated and equipped with a central control cubicle (3PHASE)(outdoor)

225kV,1250A,31.5kA/1sec,Earthing disconnector switch, manual operated


equipped with a temporized locking coil (Free standing),Busbar side (3PHASE)(outdoor)

Page 10 of 35

set

No

2. As per particular technical specification (REF NKT-NDB/4FG/0300291/000/01) clause no


(4.2.1.2,4.2.1.4,4.2.1.5,4.2.1.6)busbar
disconnectors is mentioned as vertical
disconnector type ,motorised-single pole
operated, Whereas as per as per tender
layout(dwg no 1256618 ) and section
drawings(dwg no
1257016&1257018&1257124&1256789) high
post bus bar scheme is followed in which
pantograph disconnectors are used. In light of
above we are proposing Pantograph
disconnectors .This is for information and clarity.
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

UNIT

REMARKS

1. CT ratings,type and clause mentioned are tentaive


and shall be confirmed after the approval of calculation
by the client and the consultant.
225kV,400-200/1-1-1-1A,core1:0.5Fs5,30VA.
Core2:5P20,30VA.Core3:5P20,30VA.Core4:5P20,30VA, Current transformers
(CT)(free standing) (outdoor)

225kV,1250A,31.5kA/1sec,Earthing disconnector switch, manual operated


equipped with a temporized locking coil (Free standing),Reactor side (3PHASE)(outdoor)

245kV,10kA,CL:3, Surge arresters equipped with individual discharge counters


(outdoor)

Nos

No

Nos

2. As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2.Surge arrester ratings,type,class are subject to
approval to insulation co-ordination study by the client
and the consultant.

1. CT ratings,type and clause mentioned are tentaive


and shall be confirmed after the approval of calculation
by the client and the consultant.
CT: Core 1: 75/1A,CL:5P20, Core 2: 75/1A,CL:5P20,torodal current transformer
(TC) equipped with two secondary windings, installed on the neutral earthing
connection reactor(outdoor type)

10

BAY 2 REACTANCE COMPENSATION 225KV

10.1

HV EQUIPMENT

No

PACKAGE

2. As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
225 kV - 50 Mvar compensation shunt reactor equipped with all its
accessories including in built neutral CT's (outdoor)

No

2. Surge arrester to be mounted in the reactor itself as


per the particular technical specifications (REF - NKTNDB/4FG/0300291/001/00) page no 16/44 clause no
4.2.1.6
3.CT ratings,type and clause shall be confirmed during
detailed engineering.CT mounting on the reactors to be
discussed during detailed engineering.

225 kV,1250 A,31.5kA/1sec, Three phase circuit breaker - single pole operated,
equipped with a central control cubicle (outdoor)

Page 11 of 35

No

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

UNIT

REMARKS

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

225 kV,1250 A,31.5kA/1sec, Busbar vertical disconnector(Pantograph type),


motorized - single pole operated and equipped with a central control cubicle (3PHASE)(outdoor)

225kV,1250A,31.5kA/1sec,Earthing disconnector switch, manual operated


equipped with a temporized locking coil (Free standing),Busbar side (3PHASE)(outdoor)

set

No

2. As per particular technical specification (REF NKT-NDB/4FG/0300291/000/01) clause no


(4.2.1.2,4.2.1.4,4.2.1.5,4.2.1.6)busbar
disconnectors is mentioned as vertical
disconnector type ,motorised-single pole
operated, Whereas as per as per tender
layout(dwg no 1256618 ) and section
drawings(dwg no
1257016&1257018&1257124&1256789) high
post bus bar scheme is followed in which
pantograph disconnectors are used. In light of
above we are proposing Pantograph
disconnectors .This is for information and clarity.
1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

1. CT ratings,type and clause mentioned are tentaive


and shall be confirmed after the approval of calculation
by the client and the consultant.
225kV,400-200/1-1-1-1A,core1:0.5Fs5,30VA.
Core2:5P20,30VA.Core3:5P20,30VA.Core4:5P20,30VA, Current transformers
(CT)(free standing)

225kV,1250A,31.5kA/1sec,Earthing disconnector switch, manual operated


equipped with a temporized locking coil (Free standing),Reactor side (3PHASE)(outdoor)

245kV,10kA,CL:3, Surge arresters equipped with individual discharge counters


(outdoor)

Nos

No

Nos

2. As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
2.Surge arrester ratings,type,class are subject to
approval to insulation co-ordination study by the client
and the consultant.

1. CT ratings,type and clause mentioned are tentaive


and shall be confirmed after the approval of calculation
by the client and the consultant.
CT: Core 1: 75/1A,CL:5P20, Core 2: 75/1A,CL:5P20,torodal current transformer
(TC) equipped with two secondary windings, installed on the neutral earthing
connection reactor(outdoor type)

Page 12 of 35

No

2. As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

UNIT

PACKAGE

HV EQUIPMENT (BUS BAR BAY)

11

Busbar earthing disconnector switches manual operated equipped with a


temporized locking coil in combination with push button(3 PHASE) (OUTDOOR)

Nos

REMARKS

1.As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no
4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

1. VT ratings,type and clause mentioned are tentaive


and shall be confirmed after the approval of calculation
by the client and the consultant.

12
12.1

Nos

Conductors,Aluminium& CU Tubes, Power connectors, Post Insulator,


CT/CVT/VT junction box & BMK

600

Mtr

BOQ is tentative and may vary based on the actual


overall equipment layout,section drawings, erection key
drawing, conductor sizing claculation which is subject
to client and consultant approval.

1850

Mtr

BOQ is tentative and may vary based on the actual


overall equipment layout,section drawings, erection key
drawing, conductor sizing claculation which is subject
to client and consultant approval.

30

Mtr

BOQ is tentative and may vary based on the actual


overall equipment layout,section drawings, erection key
drawing, conductor sizing claculation which is subject
to client and consultant approval.

Conductor (AAAC)

Total Length of the 630 mm2 Al Conductor

12.2

Tube (Al & Cu)

AGS 104/120 mm dia

Cu tube 40/50 mm dia (For neutral earthing of transformers)

12.3

2. As per particular technical specification (REF - NKTNDB/4FG/0300291/000/01) page no 14/42 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

225/3 kV/ (100 )/3 V/100/3V ,Core1:0.5/3P,50VA,Core2:0.5/3P,50VA ,


voltage transformer (VT) on busbar (OUTDOOR)

Post insulators
1. BOQ is tentative and may vary based on the actual
overall equipment layout,section drawings, erection key
drawing,cantilever strength claculation which is subject
to client and consultant approval.

145

225kV,8kN,post insulator(Horizontal mounting)

Page 13 of 35

Nos

2. As per general technical specification (REF - NKTNDB/4FG/0300292/000/01) page no 17/40 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

UNIT

REMARKS
1. BOQ is tentative and may vary based on the actual
overall equipment layout,section drawings, erection key
drawing,cantilever strength claculation which is subject
to client and consultant approval.

225kV,8kN,post insulator(Vertical mounting)

Nos

2. As per general technical specification (REF - NKTNDB/4FG/0300292/000/01) page no 17/40 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1. BOQ is tentative and may vary based on the actual
overall equipment layout,section drawings, erection key
drawing,cantilever strength claculation which is subject
to client and consultant approval.

33kV,8kN,post insulator(Horizontal mounting)

Nos

2. As per general technical specification (REF - NKTNDB/4FG/0300292/000/01) page no 17/40 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.
1. BOQ is tentative and may vary based on the actual
overall equipment layout,section drawings, erection key
drawing,cantilever strength claculation which is subject
to client and consultant approval.

Nos

220kV CT junction box (outdoor)(structure mounted)

Nos

220kV CVT junction box (outdoor)(structure mounted)

Nos

220kV VT junction box (outdoor)(structure mounted)

Nos

220kV BMK (outdoor)(structure mounted)

Nos

72

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

90 connector (CVT,TRAFO)
Cable: 630Sq.mm, AAAC

18

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

90 bimetallic connector (LINE LA,ISO)


Cable: 630Sq.mm, AAAC

30

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

33kV,8kN,post insulator(Vertical mounting)

12.4

12.5
12.5.1

2. As per general technical specification (REF - NKTNDB/4FG/0300292/000/01) page no 17/40 clause no


4.2.1.1 the Contractor must use aerodynamicallyprofiled cups (without ribs) for the insulator strings,
also guaranteeing a creepage distance of at least 40
mm/kV.

CT/VT/CVT JUNCTION BOX & BMK

POWER CONNECTORS
225kV Side

Straight connector(CT,CB)
Cable: 630Sq.mm, AAAC

Page 14 of 35

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

UNIT

Straight connector with Bi metallic(ISO)


Cable: 630Sq.mm, AAAC

15

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

Tee Connector
Cable: 630Sq.mm, AAAC
Cable: 630Sq.mm, AAAC

30

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

18

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

12

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

33

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

90 Connector (HV Neutral)


Tube: AL, 40/50mm dia

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

Straight connector with Bi metallic (BUS ISO)


Tube: AL, 104/120mm dia

54

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

Straight connector with flexible Bi metallic(BUS ISO)


Tube: AL, 104/120mm dia

24

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

Tee connector with base (For BPI)


Tube: AL, 104/120mm dia

85

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

Tee connector with flexible base (For BPI)


Tube: AL, 104/120mm dia

63

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

Tee Connector (ES)


Tube: AL, 104/120mm dia

30

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

Round tube end cap: AGS 104/120mm dia

10

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

Flat tube end cap: AGS 104/120mm dia

90

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

Tee Connector (VT,LA,ES)


Cable: 630Sq.mm, AAAC

Tee Connector (ES)


Tube: AL, 104/120mm dia
Cable: 630Sq.mm, AAAC

Straight connector(CB,CT,BUS VT)


Tube: AL, 104/120mm dia

Page 15 of 35

REMARKS

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

UNIT

15

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

90 DEG connector(TRAFO MV PHASE TERMINAL)


Tube: Cu, 40/50mm dia

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

90DEG connector(TRAFO Neutral EARTHING)


Tube: Cu, 40/50mm dia

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

Tee connector bimetallic(LA)


Tube: Cu, 40/50mm dia

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

Tee connector with base (for Post insulator used for tube support in tertiary of
power transformer)
Tube: Cu, 40/50mm dia

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

Cable connector(185mm) to tube cu 40/50mm

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

Cable connector(300mm) to tube cu 40/50mm

Nos

QTY & Type of connectors may vary based on the


vendor drawings and the erection key drawings,
conductor sizing caculations,section drawings which is
subject to approval pf client/consultant.

PG Clamp(for line 630sqmm conductor)

12.5.2

REMARKS

33kV side

13

BOARD 33KV - CEL INCOMER TRANSFORMER 225/33KV

13.1

33kV EQUIPMENT (INDOOR)

PACKAGE

33kV,800A,25kA/1sec,Withdrawable three pole operated circuit breaker

No

33kV,800-400/1-1-1A,Core1:5P20,30VA, Core2:5P20,30VA,Core3:
0.5Fs5,30VA,Current transformers equipped with three secondary windings:
measurements and protections

Nos

33/3 kV/ (100 )/3 V/100/3 V,Core1:0.5/3P,50VA,Core2:0.5/3P,50VA Voltage


transformers equipped with two secondary windings

Nos

Three pole operated earthing switch manual operated equipped with a locking coil
in combination with push button

No

Voltage detector system indicators (VDS)

Nos

lot

1. CT ratings,type and clause mentioned are tentaive


and shall be confirmed after the approval of calculation
by the client and the consultant.
1. CT ratings,type and clause mentioned are tentaive
and shall be confirmed after the approval of calculation
by the client and the consultant.

LV COMPARTMENT:
The LV compartment of switchgear shall comprise of protection/auxillary relays
,test blocks ,metering,wiring terminals all other associated LV equipments
complying to technical specification and scope of work ,technical data sheet ,SLD
and protection logic diagram.
Energy meter(0.5)class Located in the LV compartment

Page 16 of 35

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO
13.2

EQUIPMENTS

QUANTITY

UNIT

REMARKS

33kV EQUIPMENT (INDOOR)

PACKAGE

33kV,800A,25kA/1sec,Withdrawable three pole operated circuit breaker

No

33kV, 400-200/1-1A,Core1:5P20,30VA, Core2:5P20,30VA, Current transformers


equipped with three secondary windings: measurements and protections

Nos

Three pole operated earthing switch manual operated equipped with a locking coil
in combination with push button

No

Voltage detector system indicators (VDS)

Nos

LOT

LOT

33kV EQUIPMENT (INDOOR)

PACKAGE

33kV,800A,25kA/1sec,Withdrawable three pole operated circuit breaker

No

33kV, 400-200/1-1A,Core1:5P20,30VA, Core2:5P20,30VA, Current transformers


equipped with three secondary windings: measurements and protections

Nos

Three pole operated earthing switch manual operated equipped with a locking coil
in combination with push button

No

Voltage detector system indicators (VDS)

Nos

lot

lot

PACKAGE

BOARD 33KV - CEL FEEDER CABLE 1

1. CT ratings,type and clause mentioned are tentaive


and shall be confirmed after the approval of calculation
by the client and the consultant.
1. CT ratings,type and clause mentioned are tentaive
and shall be confirmed after the approval of calculation
by the client and the consultant.

LV COMPARTMENT:
The LV compartment of switchgear shall comprise of protection/auxillary relays
,test blocks ,metering,wiring terminals all other associated LV equipments
complying to technical specification and scope of work ,technical data sheet ,SLD
and protection logic diagram.

1.The supply of a cable differential protection relay-87L (identical to the


SIN-33kV Cable feeder at SIN end) as a loose item and associated
auxillary relays and accessories for the remote end is included in the
scope of supply .
13.3

BOARD 33KV - CEL FEEDER CABLE 2

1. CT ratings,type and clause mentioned are tentaive


and shall be confirmed after the approval of calculation
by the client and the consultant.

LV COMPARTMENT:
The LV compartment of switchgear shall comprise of protection/auxillary relays
,test blocks ,metering,wiring terminals all other associated LV equipments
complying to technical specification and scope of work ,technical data sheet ,SLD
and protection logic diagram.

1.The supply of a cable differential protection relay-87L (identical to the


SIN-33kV Cable feeder at SIN end) as a loose item and associated
auxillary relays and accessories for the remote end is included in the
scope of supply .
13.4

BOARD 33KV - CEL METERING + EARTING 33KV


33kV EQUIPMENT (INDOOR)

13.5

33/3 kV/ (100 )/3 V/100/3V,Core1:0.5/3P,50VA,Core2:0.5/3P,50VA, Voltage


transformers equipped with two secondary windings

Nos

Three pole operated earthing switch manual operated equipped with a locking coil
in combination with push button

No

TEST CONNECTORS FOR 33kV SWITCHGEAR

Page 17 of 35

1. VT ratings,type and clause mentioned are tentaive


and shall be confirmed after the approval of calculation
by the client and the consultant.
-

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

UNIT

REMARKS

One test connector for each type of protection relays located in 33kV switchgear

LT

14

MV & LV Cable ladder/Tray Accessories as per general technical


specification, scope of works,drawings and technical data sheets.

14.01.01

LV CABLE LADDER (INDOOR) (HOT DIP GALVANISED)

Notes-All of the cable paths, trays and their supports shall be hot-dip
galvanised as per General Technical Specifications,clause 3 page no 9/11 Cable installation and cable connection works REF.: NKTNDB/4FG/0292672/001/00 .

Straight Section sheet steel Material hot dip galvanised , 600mm Wide 20mm
Outside Stiffened Upper Return Flange, Swaged Round Tubular Rungs, Material
Thickness-2mm, Side Rail Height - 175mm, Rung Spacing - 140mm, Length 3660mm Cable ladder having the following widths. (indoor)

600mm Wide Horizontal Tee cable ladder of hot dip galvanised , sheet steel
Material Thickness-2mm, Side rail height - 175mm, 20mm flange, 300mm radius,
Aluminum, Round tubular rung type with the following wide & side heights
(indoor)

Blind End with Screw of hot dip galvanised, nut & flat washer for 600mm Wide&
Side rail height-175mm

Blind End with Screw of hot dip galvanised, nut & flat washer for 450mm Wide&
Side rail height-175mm

31

Standard connector of hot dip galvanised and hardware

31

Expansion Connectors of hot dip galvanised & Hardwares

6m long, Double unistruct channel of hot dip galvanised for cable ladder supports.

14.01.02

16

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

No

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Post base & Hardwares(INDOOR)(HOT DIP GALVANISED)

Double Channel high Post base of hot dip galvanised with two hole fixing plate

26

52

Block color plastic End Cap

Page 18 of 35

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

52

80mm long, Steel Anchor fastener of hot dip galvanised

70

Hold Down Clamp & Hardwares of hot dip galvanised

39

Bonding Jumper of hot dip galvanised

14.01.03

REMARKS

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Notes-All of the cable paths, trays and their supports shall be hot-dip galvanised as
per General Technical Specifications,clause 3 page no 9/11 - Cable installation and
cable connection works REF.: NKT-NDB/4FG/0292672/001/00 .

LV CABLE LADDER (OUTDOOR) (HOT DIP GALVANISED)

Straight Section sheet steel Material hot dip galvanised , 600mm Wide 20mm
Outside Stiffened Upper Return Flange, Swaged Round Tubular Rungs, Material
Thickness-2mm, Side Rail Height - 175mm, Rung Spacing - 140mm, Length 3660mm Cable ladder having the following widths. (outdoor)

600mm Wide Horizontal Tee cable ladder of hot dip galvanised , sheet steel
Material Thickness-2mm, Side rail height - 175mm, 20mm flange, 300mm radius,
Aluminum, Round tubular rung type with the following wide & side heights
(outdoor)

600mm Wide Horizontal cross cable ladder of hot dip galvanised , sheet steel
Material Thickness-2mm, Side rail height - 175mm, 20mm flange, 300mm radius,
Aluminum, Round tubular rung type with the following wide & side heights
(outdoor)

600mm Wide Horizontal elbow cable ladder of hot dip galvanised, sheet steel
Material Thickness-2mm, Side rail height - 175mm, 20mm flange, 300mm radius,
Aluminum, Round tubular rung type with the following wide & side heights
(outdoor)

Blind End with Screw of hot dip galvanised, nut & flat washer for 600mm Wide&
Side rail height-175mm

361

50

20

55

722

Standard connector of hot dip galvanised and hardware

722

Expansion Connectors of hot dip galvanised & Hardwares

6m long, Double unistruct channel of hot dip galvanised for cable tray supports.

14.01.04

UNIT

Post base & Hardwares (HOT DIP GALVANISED)(OUTDOOR)

Page 19 of 35

241

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

Double Channel high Post base of hot dip galvanised with two hole fixing plate

Block color plastic End Cap

80mm long, Steel Anchor fastener of hot dip galvanised

Hold Down Clamp & Hardwares of hot dip galvanised

Bonding Jumper of hot dip galvanised

14.02.01

241

UNIT

Nos

REMARKS
QTY&TYPE arrived are tentative and subject to vary
based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

241

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

963

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

481

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

60

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

PERFORATED TYPE (HOT DIP GALVANISED)-(INDOOR)

450mm Wide, Inside returned flange, Straight section, sheet steel Material
thickness-2mm, Side rail height-100mm, length - 3660mm Cable Tray having the
following widths.(indoor)

450mm Wide Horizontal Tee, sheet steel Material Thickness-2mm, Inside returned
20mm flange, side rail height - 100mm, 300mm radius, Aluminum with the
following wide.(indoor)

Blind End with Screw, nut & flat washer with 900mm Wide, 100mm Height

Expansion Connectors & Hardwares of hot dip galvanised

16

10

Hold Down Clamp & Hardwares of hot dip galvanised

23

Page 20 of 35

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

Bonding Jumper of hot dip galvanised

14.02.02

14

REMARKS

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

PERFORATED TYPE (HOT DIP GALVANISED)-(OUTDOOR)

450mm Wide, Inside returned flange of hot dip galvanised, Straight section, sheet
steel material, Material thickness-2mm, Side rail height-100mm, length - 3660mm
perforated Cable Tray with cover having the following widths(oudoor)

450mm Wide Horizontal Tee with cover of hot dip galvanised, sheet steel
material,Material Thickness-2mm, Inside returned 20mm flange, side rail height 100mm, 300mm radius, Aluminum with the following wide. (oudoor)

Blind End with Screw of hot dip galvanised, nut & flat washer with 900mm Wide,
100mm Height

120

25

28

241

Expansion Connectors & Hardwares of hot dip galvanised

241

Hold Down Clamp & Hardwares of hot dip galvanised

30

Bonding Jumper of hot dip galvanised

14.03

UNIT

33kV Cable supports and accessories in the 33kV Switchgear Basement


Area(of hot dip galvanised)

300 mm long, Double Channel Aluminium Vertical Arm of hot dip galvanised

1500 mm long, Double Channel(Back to Back) Aluminium Horizontal Arm of hot


dip galvanised

Page 21 of 35

40

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

3300 mm long, Double Channel Aluminium Vertical Arm (Swgr End) of hot dip
galvanised

1500 mm long, Double Channel Aluminium Horizontal Arm (Swgr End) of hot dip
galvanised

Trefoil aluminium clamps suitable for 33kV,1C X 300Sq.mm cable(indoor)

25

26

Double Channel 3hole Post Base of hot dip galvanised

50

90 Degree Angle Fittings of hot dip galvanised

50

Adjustable hine Fittings of hot dip galvanised

78

Steel Anchor of hot dip galvanised

Hex. Head Cap Screw / Washer (Flat) of hot dip galvanised

Flat Washer 1/2" of hot dip galvanised

15

17

Nuts and bolts of hot dip galvanised

33kV CABLES including marking, cable and connection as per the


technical specification , technical data sheet and scope of works

Page 22 of 35

UNIT

REMARKS

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

Nos

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

LT

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

LT

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

LT

QTY&TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench
layout/ladder/tray layout, cable sizing calculations by
the client and the consultant.

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

UNIT

REMARKS

Mtr

QTY &TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench layout,
cable sizing calculations by the client and the
consultant.

200

Mtr

QTY &TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench layout,
cable sizing calculations by the client and the
consultant.

33kV Outdoor Termination Kit to suit 1C X 185Sq.mm Cable at 20MVA


Transformer End

Nos

1. 3 nos of outdoor termination kit suitable for each


phase of 1C x 185sqmm conductor/cable

33kV Outdoor Termination Kit to suit 1C X 300Sq.mm Cable at 20MVA


Transformer End

Nos

1. 6 nos of outdoor termination kit suitable for each


phase of 1C x 300sqmm conductor/cable

33kV Indoor Termination Kit to suit 1C X 300Sq.mm Cable at 33kV Switchgear End

Nos

1. 3 nos of outdoor termination kit suitable for each


phase of 1C x 300sqmm conductor/cable

33kV Outdoor Termination Kit to suit 1C X 185Sq.mm Cable Station Auxilary


Transformer End

Nos

1. 3 nos of outdoor termination kit suitable for each


phase of 1C x 185sqmm conductor/cable

33kV Outdoor Termination Kit to suit 1C X 300Sq.mm Cable at Earthing


Transformer

Nos

1. 3 nos of outdoor termination kit suitable for each


phase of 1C x 185sqmm conductor/cable

Nos

QTY &TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench layout,
cable sizing calculations by the client and the
consultant.

Nos

QTY &TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench layout,
cable sizing calculations by the client and the
consultant.

600

Nos

QTY &TYPE arrived are tentative and subject to vary


based on the approval of actual cable routing
drawing,overall equipment layout , cable trench layout,
cable sizing calculations by the client and the
consultant.

Protection cabinet for bay line 225kV(PK41-1)

Nos

Protection cabinet for bay line 225kV(PK41-2)

Nos

Protection cabinet for bay line 225kV(NKT central nord -1)

Nos

Protection cabinet for bay line 225kV(NKT central nord -2)

Nos

33kV,1CX185Sq.mm power cable,CU,XLPE ,CU WIRE ARMOURED,PE OUTER


JACKET, Outer sleeve colour - red

33kV,1CX300Sq.mm power cable,CU,XLPE ,CU WIRE ARMOURED,PE OUTER


JACKET, Outer sleeve colour - red

Trefoil aluminium clamps suitable for 33kV,1C X 300Sq.mm cable(outdoor)

Trefoil aluminium clamps suitable for 33kV,1C X 185Sq.mm cable(outdoor)

PVC conduit 100mm dia for outdoor road crossings

16

LV ELECTRICAL EQUIPMENT

16.01

PROTECTION SYSTEM

95

67

32

Protection cabinet for bay line 225kV(TASIAST)

Nos

Protection cabinet for bay TRANSFORMER 225/33KV

No

Protection cabinet for bay REACTANCE COMPENSATION 225KV

Nos

Page 23 of 35

For TASIAST feeder protection panels , the


distance/protection relays at SIN substation should
match with the existings relays in the opposite end
station(i.e .TASIAST substation).Tasiast substation is
under execution by contractor 'KINROS' as per
particular technical specification ( REF - NKTNDB/4FG/0300291/001/00) page no 10/42 clause no
1.4.3.

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

UNIT

Protection cabinet for bay COUPLAGE 225KV

No

225kV bus bar and breaker failure protection

No

LT

Digital Control System of non redundant type

PACKAGE

SAS server panel

No

SAS communication panel

No

common BCU panel

No

Equipment cabinet for Remote Terminal Unit to SOMELEC

PACKAGE

PACKAGE

REMARKS

TEST CONNECTORS
One test connector for each type of protection relays located in 225kV PANELS
16.02

16.03

16.03.01

16.03.01.01

DCS SYSTEM

AUXILLARY SERVICES AND DISTRIBUTION SYSTEM


Auxiliary services distribution 400/230Vac as per technical
specification,scope of works and technical data sheets

Transformer control panel-1(near to transformer), outdoor , Floor


mounted-400V, 3Ph, 4Wire, CU,400A, 50Hz, CU,25kA

No

The Ratings of MCCB/MCB/DB and the qty of MCCB


are subject to approval of load distribution,approval of
auxillary SLD and auxillary transformer sizing
calculations ,cable sizing calculations by the
client/consultant.

No

The Ratings of MCCB/MCB/DB and the qty of


MCCB/MCB are subject to approval of load
distribution,approval of auxillary SLD ,cable sizing
calculations by the client/consultant.

No

The Ratings of MCCB/MCB/DB and the qty of


MCCB/MCB are subject to approval of load
distribution,approval of auxillary SLD ,cable sizing
calculations by the client/consultant.

1.Incomer- 400V , 400A,4P, MCCB- 1NO


AC main distribution board(Control Building), Indoor, Floor mounted400V, 3Ph, 4Wire, 400A, 50Hz,CU, 25kA as per technical
specification,scope of works and technical data sheets
1.Incomer- 400V 4P 400A,4P, MCCB-1 nos
2.Outgoing feeder-400V, 160A TPN MCCB - 5 nos
3.Outgoing feeder-400V, 125A TPN MCCB - 6 nos

16.03.01.03

4.Outgoing feeder-400V,63A TPN MCCB- 6 nos


5.Outgoing feeder-400V,40A TPN MCCB- 6 nos
6.Outgoing feeder-400V,32A TPN MCCB- 5 nos
7.Outgoing feeder-400V,16A SPN MCB- 12 nos
8.One voltmeter with associated voltmetric switch
9.One ammeter

Power distribution board-1 (control building), Indoor, WALL mounted400V, 3Ph, 4Wire, 125A,CU, 50Hz, 10kA .
1.Incomer- 400V , 125A TPN, MCCB -2 no
16.03.01.04

2.Outgoing feeder- 230V ,20A SPN, MCB-14 no


3.Outgoing feeder- 230V,16A SPN, MCB-8 no
4.Outgoing feeder- 230V, 10A SPN, MCB-5 no

Page 24 of 35

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

UNIT

REMARKS

No

The Ratings of MCCB/MCB/DB and the qty of


MCCB/MCB are subject to approval of load
distribution,approval of auxillary SLD ,cable sizing
calculations by the client/consultant.

No

The Ratings of MCCB/MCB/DB and the qty of


MCCB/MCB are subject to approval of load
distribution,approval of auxillary SLD ,cable sizing
calculations by the client/consultant.

No

The Ratings of MCCB/MCB/DB and the qty of


MCCB/MCB are subject to approval of load
distribution,approval of auxillary SLD ,DG sizing
calculations by the client/consultant.

No

The Ratings of MCCB/MCB/DB and the qty of


MCCB/MCB are subject to approval of load
distribution,approval of auxillary SLD , by the
client/consultant.

PACKAGE

110Vdc,400AH Vented Lead Acid battery banks

Nos

I/P 400VAC,3Ph,O/P current of 100A,110V DC-Battery chargers

Nos

FUSE BOX

Nos

Power distribution board-2 (accomodation building), Indoor,


wallmounted- 400V, 3Ph, 4Wire, 63A,CU, 50Hz, 10kA .
1.Incomer- 400V,63A TPN, MCCB - 1 nos
16.03.01.05 2.Outgoing feeder- 230V, 20A SPN, MCB- 6 nos
3.Outgoing feeder- 230V,16A SPN, MCB- 5 nos
4.Outgoing feeder- 230V, 10A SPN, MCB -9 nos

Control and relay panel distribution board , Indoor, Floor mounted400V, 3Ph, 4Wire, 63A,CU, 50Hz, 10kA .
1. Incomer- 400V ,63A ,TPN, MCCB -1 NOS
16.03.01.06

2.Outgoing feeder- 400V,32A, SPN, MCCB -24 NOS


3.Outgoing feeder- 230V,20A, SPN, MCB - 32NOS
4.Outgoing feeder- 230V,10A, SPN, MCB - 20NOS

16.03.01.07

DG control panel (in DG room), Indoor, floor mounted- 400V, 3Ph,


4Wire, 250A, 50Hz, CU,10kA
1.Incomer- 400V ,250A 4P, MCCB -1 no
Emergency distribution board, Indoor, wall mounted- 400V, 3Ph, 4Wire,
63A, 50Hz,CU, 10kA (control building) as per technical
specification,scope of works and technical data sheets.

1.Incoming feeder-230V,63A TPN, MCCB -1nos


16.03.01.08

2.Outgoing feeder-230V,32A TPN, MCCB -6nos


3. Outgoing feeder-230V,16A SPN, MCB -3nos
4. Outgoing feeder-230V,6A SPN, MCB -3nos
5 Outgoing feeder-230V,16A TPN, MCB -10nos

16.04
16.04.01

Auxiliary services distribution 110Vdc and 48Vdc


110VDC - BATTERY

Page 25 of 35

Battery and charger ratings are subject to appoval of


load profile and battery and charger sizing calculation
by the client and the consultant.
The specification does not specify explosion proof type
and location of fuse box. This is for information and
clarity.

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

UNIT

REMARKS

No

48Vdc,200AH on Vented Lead Acid battery banks

Nos

I/P 400VAC,3Ph,O/P current of 50A,48V DC-Battery chargers

Nos

FUSE BOX

Nos

The specification does not specify explosion proof type


and location of fuse box. This is for information and
clarity.

No

The Ratings of MCCB/MCB/DB and the qty of


MCCB/MCB are subject to approval of auxillary SLD
,cable sizing calculations by the client/consultant.

TELECOM system station and associated substations

PACKAGE

Tele protection panel

No

communication panel

Nos

F.O Patch panel

No

625

Mtrs

F.O Patch cable connectors

LT

OPGW-FO JUNCTION BOX

NOS

Telecommunication equipment( 33kV switchgear) at both end of 33kV cable


feeders is not included in scope of supply as per particular technical specification
( REF - NKT-NDB/4FG/0300291/001/00) page no 38/42 clause no 5.2.1

Telephony system station and associated substations

PACKAGE

125V,DC,250A,CU,25kA,1sec-DC Main distribution board Floor


mounted,Indoor(Main DCDB at Auxiliary room of control building) as
per technical specification,scope of works and technical data sheets
1.Incomer-DP,MCCB,250A - 2 nos
2.Bus section-DP,MCCB,250A- 1 nos

16.04.02

3.Bus section-DP,MCCB,63A- 3 nos


4.Outgoing feeder-32A DP MCCB- 12 nos

The Ratings of MCCB/MCB/DB and the qty of


MCCB/MCB are subject to approval of auxillary SLD
,cable sizing calculations by the client/consultant.

5.Outgoing feeder-25A DP MCB- 11 nos


6.Outgoing feeder-10A DP MCB- 69 nos
7.One ammeter with shunt
8.One voltmeter with four-position switch and with automatic return

16.04.03

48VDC - BATTERY

Battery and charger ratings are subject to appoval of


load profile and battery and charger sizing calculation
by the client and the consultant.

48V,DC,63A,CU,10kA,1sec-DC Main distribution board Floor


mounted,Indoor(Main DCDB at Auxiliary room of control building) as
per technical specification,scope of works and technical data sheets

1.Incomer-DP,MCCB,63A - 2nos
16.04.04

2.Bus section-63A DP MCCB - 1nos


3.Outgoing feeder-10A DP MCB - 15nos
4.One ammeter with shunt
5.One voltmeter with four-position switch and with automatic return

17.01

F.O Patch Chord/cable length

17.02

Page 26 of 35

Length given is tentative and shall vary based on the


cable routing drawing, overall equipment layout and the
telecom architecture and the scheme approvals by the
client/consultant.

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

QUANTITY

UNIT

Telecom system /associates at Tasiast substation is not required as per scope of


work(Which will be taken by Tasiast substation contractor 'KINROS' as per
particular technical specification ( REF - NKT-NDB/4FG/0300291/001/00) page no
10/42 clause no 1.4.3 and and as per clause 5.1.2 of page no 38/42).

18

HVAC (heating, ventilating and air conditioning )

PACKAGE

19

Earthing system

PACKAGE

17.03

19.01

EQUIPMENTS

REMARKS

Earthing conductors,cad weld,Earth rods & accessories

120 Sq.mm bare copper conductor

11950

Mtrs

1.In the case of laying in aggressive soil, the buried


copper conductors are covered with a lead sheath as as
the general technical specifications-Earthing system
and lightning protection system ( REF - NKTNDB/4FG/0292667/001/00) page no 7/11 clause no
4.1.
2. The boq is tentative and subject to vary based on
the soil resistivity and the earthing calculations and the
overall earthing layout(indoor and outdoor) and
equipment earthing layout which is subject to client
/consultant approval.
3.Boq is arrived based on 3.2 metre spacing as per 4A
boq.

120Sq.mm Copper Yellow green PVC insulation

275

Mtr

The boq is tentative and subject to vary based on


overall earthing layout(indoor and outdoor) and
equipment earthing layout which is subject to client
/consultant approval.

95Sq.mm Copper Yellow green PVC insulation

300

Mtr

The boq is tentative and subject to vary based on


overall earthing layout(indoor and outdoor) and
equipment earthing layout which is subject to client
/consultant approval.

50 Sq.mm Copper Yellow green PVC insulation

160

Mtr

The boq is tentative and subject to vary based on


overall earthing layout(indoor and outdoor) and
equipment earthing layout which is subject to client
/consultant approval.

35 Sq.mm Copper Yellow green PVC insulation

175

Mtr

The boq is tentative and subject to vary based on


overall earthing layout(indoor and outdoor) and
equipment earthing layout which is subject to client
/consultant approval.

16 Sq.mm Copper Yellow green PVC insulation ( for cable trays/ladder, wiring
boxes, protection
cabinets, protective circuits of the LV cables)

200

Mtr

The boq is tentative and subject to vary based on


overall earthing layout(indoor and outdoor) and
equipment earthing layout which is subject to client
/consultant approval.

20mm dia Copperweld Earthing Rods in 3 metres length

63

Nos

The boq is tentative and subject to vary based on


overall earthing layout(indoor and outdoor) and
equipment earthing layout which is subject to client
/consultant approval.

CU Flat Earthing distribution strip (40x5) of length 600mm

13

Nos

The boq is tentative and subject to vary based on


overall earthing layout(indoor and outdoor) and
equipment earthing layout which is subject to client
/consultant approval.

Coupling for above grounding rod

32

Nos

The boq is tentative and subject to vary based on


overall earthing layout(indoor and outdoor) and
equipment earthing layout which is subject to client
/consultant approval.

Driving stud for 20mm copper rod

21

Nos

The boq is tentative and subject to vary based on


overall earthing layout(indoor and outdoor) and
equipment earthing layout which is subject to client
/consultant approval.

2112

Nos

The boq is tentative and subject to vary based on


overall earthing layout(indoor and outdoor) and
equipment earthing layout which is subject to client
/consultant approval.

120 main to 120 sqmm Main mat conductor (X' - weld)

Page 27 of 35

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

19.02

EQUIPMENTS

QUANTITY

UNIT

120 main to 120 sqmm Main mat conductor (T' - weld)

194

Nos

The boq is tentative and subject to vary based on


overall earthing layout(indoor and outdoor) and
equipment earthing layout which is subject to client
/consultant approval.

120 main to 120 sqmm Main mat conductor (L' - weld)

15

Nos

The boq is tentative and subject to vary based on


overall earthing layout(indoor and outdoor) and
equipment earthing layout which is subject to client
/consultant approval.

120 main to 95 sqmm branch conductor (T' - weld)

20

Nos

The boq is tentative and subject to vary based on


overall earthing layout(indoor and outdoor) and
equipment earthing layout which is subject to client
/consultant approval.

120 main to 50 sqmm branch conductor (T' - weld)

20

Nos

The boq is tentative and subject to vary based on


overall earthing layout(indoor and outdoor) and
equipment earthing layout which is subject to client
/consultant approval.

CU Flat Earthing distribution strip (40x5) of length 600mm

13

Nos

The boq is tentative and subject to vary based on


overall earthing layout(indoor and outdoor) and
equipment earthing layout which is subject to client
/consultant approval.

725

Nos

The boq is tentative and subject to vary based on


overall earthing layout(indoor and outdoor) and
equipment earthing layout which is subject to client
/consultant approval.

Lightning protection system(Early Streamer Protection)

PACKAGE

Early Streamer Emission Air Terminal (ESEAT). Equipped with a metal rods made
of stainless steel(minimum diameter of 4 cm) minimum of 4 metres in height
attached to the gantries and lightning poles.

NOS

The boq is tentative and subject to vary based on the


Lighting protection calculations and the overall lightning
protection layout which is subject to client /consultant
approval.

135

NOS

The boq is tentative and subject to vary based on the


Lighting protection calculations and the overall lightning
protection layout which is subject to client /consultant
approval.

27

NOS

The boq is tentative and subject to vary based on the


Lighting protection calculations and the overall lightning
protection layout which is subject to client /consultant
approval.

Universal rod-to-tape clamp

NOS

The boq is tentative and subject to vary based on the


Lighting protection calculations and the overall lightning
protection layout which is subject to client /consultant
approval.

Earthing disconnecting link

NOS

The boq is tentative and subject to vary based on the


Lighting protection calculations and the overall lightning
protection layout which is subject to client /consultant
approval.

Lighting (normal and emergency), distribution panels

PACKAGE

Clamps & Connectors

Crimp to 2x120mm.Cable (CONNECTION TYPE-E)

20

Tinned copper tape (75mm)

20mm dia Copperweld Earthing Rods in 3 metres length

21

REMARKS

Page 28 of 35

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

UNIT

REMARKS

21.01

Indoor Lighting Panel-1 (control building), Indoor, wall mounted- 400V,


3Ph, 4W,CU, 16A, 50Hz, 10kA
1. Incomer- 400V,16A TPN, MCB - 1 Nos

No

The Ratings of MCB/DB and the qty of MCB are subject


to approval of load distribution,approval of auxillary
SLD and cable sizing calculations by the
client/consultant.

No

The Ratings of MCCB/MCB/DB and the qty of MCB are


subject to approval of load distribution,approval of
auxillary SLD and cable sizing calculations by the
client/consultant.

No

The Ratings of MCB/DB and the qty of MCB are subject


to approval of load distribution,approval of auxillary
SLD and cable sizing calculations by the
client/consultant.

No

The Ratings of MCCB/MCB/DB and the qty of MCB are


subject to approval of load distribution,approval of
auxillary SLD and cable sizing calculations by the
client/consultant.

Surface / Wall / Pendant Mounted luminaries 2 X 36 W, 230V, AC, 50Hz, IP-21, T5


Fluorescent lamp fixture with high power factor.

60

Nos

The boq/description and type is tentative and may vary


based on the approval of lighting design
calculation/lighting layout (indoor,outdoor,emergency)
which is subject to client/consultant approval.

Surface / Wall / Pendant Mounted luminaries 2 X 26 W, 230V, AC, 50Hz, IP-21, T5


Fluorescent lamp fixture with high power factor.

30

Nos

The boq/description and type is tentative and may vary


based on the approval of lighting design
calculation/lighting layout (indoor,outdoor,emergency)
which is subject to client/consultant approval.

Fully Recess Mounted luminaries 4 X 14 W, 230V, AC, 50Hz, IP-21, T5 Fluorescent


lamp fixture with high Power factor.

25

Nos

The boq/description and type is tentative and may vary


based on the approval of lighting design
calculation/lighting layout (indoor,outdoor,emergency)
which is subject to client/consultant approval.

Surface / Wall / Pendant Mounted luminaries 2 X 36 W, 230V, AC, 50Hz, IP-21, T5


Fluorescent lamp fixture with high Power factor(explosion proof)

Nos

The boq/description and type is tentative and may vary


based on the approval of lighting design
calculation/lighting layout (indoor,outdoor,emergency)
which is subject to client/consultant approval.

Wall / Surface / Pendant / Recess mounted, Indoor, IP21, 1X60W, 110V DC lamp
lighting fixtures
(Note-Charging to be done by AC-230V)

35

Nos

The boq/description and type is tentative and may vary


based on the approval of lighting design
calculation/lighting layout (indoor,outdoor,emergency)
which is subject to client/consultant approval.

Wall / Surface / Pendant / Recess mounted, Indoor, IP21, 1X60W, 110V DC lamp
lighting fixtures (explosion proof-indoor)
(Note-Charging to be done by AC-230V)

Nos

The boq/description and type is tentative and may vary


based on the approval of lighting design
calculation/lighting layout (indoor,outdoor,emergency)
which is subject to client/consultant approval.

2. Outgoing feeder-230V , 10A SPN, MCB - 10 Nos

Outdoor Lighting Panel-1(control building), wall mounted- 400V, 3Ph,


4W,CU, 32A, 50Hz, 10kA .(With photoelectric cell and the switches )
21.02

1. Incomer- 400V, 32A TPN, MCCB - 1 Nos


2.Outgoing feeder-400V,10A TPN, MCB - 22 Nos

Indoor Lighting Panel-2 (accomodation building), Indoor, Floor mounted400V, 3Ph, 4W,CU, 16A, 50Hz, 10kA
21.03

1.Incomer- 400V ,16A TPN, MCB - 1 Nos


2. Outgoing feeder-230V ,10A SPN, MCB - 9 Nos

Outdoor Lighting Panel-2(accomodation building), Outdoor,


wallmounted- 400V, 3Ph, 4W, CU,32A, 50Hz, 10kA . (With photoelectric
cell and the switches )
21.04
1.Incomer- 400V, 32A TPN, MCCB - 2 Nos
2. Outgoing feeder-400V,10A TPN, MCB - 8 Nos
21.05

21.06

Indoor Normal lighting

Indoor emergency lighting (capacity one hour)

Page 29 of 35

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO
21.07

EQUIPMENTS

QUANTITY

UNIT

REMARKS

10

Nos

The boq/description and type is tentative and may vary


based on the approval of lighting design
calculation/lighting layout (indoor,outdoor,emergency)
which is subject to client/consultant approval.

Outdoor, Flood light fixture 250W HPS, 230V, AC, 50HZ - Trunnion mounting

60

Nos

The boq/description and type is tentative and may vary


based on the approval of lighting design
calculation/lighting layout which is subject to
client/consultant approval.

Outdoor, Flood light fixture 70W HPS, 230V, AC, 50HZ - Trunnion mounting

10

Nos

The boq/description and type is tentative and may vary


based on the approval of lighting design
calculation/lighting layout which is subject to
client/consultant approval.

Pole Mounted, IP54, 230V AC, 50HZ, 1X 80W HPS

21

Nos

The boq/description and type is tentative and may vary


based on the approval of lighting design
calculation/lighting layout which is subject to
client/consultant approval.

Surface Mtd, IP54, 230V AC, 50HZ, 1X 150W road-lighting luminaire.

64

Nos

The boq/description and type is tentative and may vary


based on the approval of lighting design
calculation/lighting layout which is subject to
client/consultant approval.

Surface Mtd, IP54, 230V AC, 50HZ, 1X 70W road-lighting luminaire.

20

Nos

The boq/description and type is tentative and may vary


based on the approval of lighting design
calculation/lighting layout which is subject to
client/consultant approval.

Surface / Wall / Pendant Mounted luminaries 2 X 36 W, 230V, AC, 50Hz, IP-21, T5


Fluorescent lamp fixture with high power factor.

15

Nos

The boq/description and type is tentative and may vary


based on the approval of lighting design
calculation/lighting layout which is subject to
client/consultant approval.

8 to 10 m height Lighting Pole

35

Nos

The boq/description and type is tentative and may vary


based on the approval of lighting design
calculation/lighting layout which is subject to
client/consultant approval.

Outdoor emergency lighting (capacity one hour)


Wall / Surface / Pendant / Recess mounted, Indoor, IP21, 1X60W, 110V DC lamp
lighting fixtures
(Note-Charging to be done by AC-230V)

21.08

Outdoor lighting poles and lighting system

10

2m height Lighting Pole

Nos

1.The boq/description and type is tentative and may


vary based on the approval of lighting design
calculation/lighting layout which is subject to
client/consultant approval.
2.Seperate pole for lightning as per 4A boq is not
considered since the same can be covered under
lighting poles.

21.09

Receptacles
400V,160A, 3,TPN,5 PIN HEAVY DUTY SWITCH SOCKET OUTLET IP55
PROTECTION WITH BASS SCREW COVER AND PLUGS (WEATHER PROOF)

230V AC 16A flush mounted duplex indoor receptacle with parallel slot &
grounding u-slot

230V AC 16A Surface mounted duplex indoor receptacle (explosion proof)

Page 30 of 35

Nos

The boq/decription and type is tentative and may vary


based on the approval of Buidling layout which is
subject to client/consultant approval.

28

Nos

The boq/decription and type is tentative and may vary


based on the approval of Buidling layout which is
subject to client/consultant approval.

Nos

The boq/decription and type is tentative and may vary


based on the approval of Buidling layout which is
subject to client/consultant approval.

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

UNIT

REMARKS

16

Nos

The boq/decription and type is tentative and may vary


based on the approval of Buidling layout which is
subject to client/consultant approval.

PACKAGE

230V AC 25A flush mounted duplex indoor receptacle with parallel slot &
grounding u-slot

22

22.01

LV CABLES including marking, cable and connection

NOTES - As per General Technical Specifications Power, control and signalling cables (ref.: NKTNDB/4FG/0292669/001/00) clause 4.3 page 8 of 12,
The cables shall be of the type with PVC insulation, a
protective circuit with a
copper screen (stranded wire) and a PVC outer sleeve.

PVC Sheathed,cable

1.Size ,no of cores, Type of cables and BOQ and


descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.
4C X 4 Sq.mm CU,PVC cable.unarmoured

1510

Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
1.Size ,no of cores, Type of cables and BOQ and
descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.

4C X 4 Sq.mm CU,PVC cable.armoured

8285

Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
1.Size ,no of cores, Type of cables and BOQ and
descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.

4C X 2.5 Sq.mm CU,PVC cable.armoured

225

Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
1.Size ,no of cores, Type of cables and BOQ and
descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.

7C X 2.5 Sq.mm CU,PVCcable. armoured

7855

Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
1.Size ,no of cores, Type of cables and BOQ and
descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.

9C X 2.5 Sq.mm CU,PVC armoured

675

Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.

Page 31 of 35

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

UNIT

REMARKS
1.Size ,no of cores, Type of cables and BOQ and
descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.

12C X 2.5 Sq.mm CU,PVC cable.armoured

5865

Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
1.Size ,no of cores, Type of cables and BOQ and
descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.

19C X 2.5 Sq.mm CU,PVC armoured

3910

Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.
1.Size ,no of cores, Type of cables and BOQ and
descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.

27C X 2.5 Sq.mm CU,PVC armoured

1310

Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.

Cable glands and terminations

22.02

LT

NOTES - As per General Technical Specifications Power, control and signalling cables (REF.: NKTNDB/4FG/0292669/001/00) clause 4.2 page 8 of
12,The LV cables shall have either PVC or XLPE
insulation, with a PVC outer jacket; a
protective conductor shall be provided under the outer
jacket of the cable.

XLPE Sheathed,cable

1.Size ,no of cores, Type of cables and BOQ and


descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.
1C X 95 Sq.mm CU,PVC Un armoured

335

Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.

1.Size ,no of cores, Type of cables and BOQ and


descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.
1C X 150 Sq.mm CU,XLPE armoured

570

Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.

Page 32 of 35

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

UNIT

REMARKS

1.Size ,no of cores, Type of cables and BOQ and


descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.
1C X 120 Sq.mm CU,XLPE armoured

385

Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.

1.Size ,no of cores, Type of cables and BOQ and


descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.
2C X 4 Sq.mm CU,XLPE armoured

3155

Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.

1.Size ,no of cores, Type of cables and BOQ and


descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.
2C X 16 Sq.mm CU,XLPE armoured

650

Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.

1.Size ,no of cores, Type of cables and BOQ and


descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.
2C X 35 Sq.mm CU,XLPE armoured

855

Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.

1.Size ,no of cores, Type of cables and BOQ and


descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.
4C X 120 Sq.mm CU,XLPE armoured

115

Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.

Page 33 of 35

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

EQUIPMENTS

QUANTITY

UNIT

REMARKS

1.Size ,no of cores, Type of cables and BOQ and


descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.
4C X 35 Sq.mm CU,XLPE armoured

1310

Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.

1.Size ,no of cores, Type of cables and BOQ and


descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.
4C X 25 Sq.mm CU,XLPE armoured

210

Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.

1.Size ,no of cores, Type of cables and BOQ and


descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.
4C X 16 Sq.mm CU,XLPE armoured

1575

Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.

1.Size ,no of cores, Type of cables and BOQ and


descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.
4C X 10 Sq.mm CU,XLPE armoured

2555

Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.

1.Size ,no of cores, Type of cables and BOQ and


descriptions may vary based on the overall equipment ,
cable routing drawings,cable tray/ladder routing
drawings, cable sizing calculation, schematic drawings,
which is subject to approval of client/consultant.
4C X 6 Sq.mm CU,XLPE armoured

220

Mtr
2.As per specification the type of cable is not
mentioned whether copper or aluminium however the
same is mentioned as copper in the BOQ(for MV,LV
power and control cables) which is subject to client and
consultant approval.

4 sq.mm. cu. wire PVC insulated (of various colours)

3245

Mtr

Size , Type of wires and BOQ and descriptions may


vary based on the buiding layout/lighting and small
power layouts which is subject to client/consultant.

2.5 sq.mm. cu. wire PVC insulated (of various colours)

1500

Mtr

Size , Type of wires and BOQ and descriptions may


vary based on the buiding layout/lighting and small
power layouts which is subject to client/consultant.

Page 34 of 35

BOQ FOR ELECTRICAL (PRELIMINARY/TENTATIVE BOQ) REV 0 DATED 07.05.2014


225/33kV SIN - SUBSTATION
NO

23

EQUIPMENTS

QUANTITY

36 Core Fiber optic cable

450

UNIT

Mtr

REMARKS

1. Length Will vary base based on the equipment


layout,actual cable routing drawings and cable
tray/ladder routing drawings which is subject to
client/consultant approval.
2. No of optical fibres is subject to client/consultant
approval

24

DIESEL GENERATOR-100kVA (indoor) WITH ALL ITS ACCESSORIES

No

25

125 Vdc to 230Vac INVERTER - 8KVA( including future feeders )

No

NOTES

Ratings mentioned are tentaive and shall vary based


on the DG sizing calculation which is subject to
approval of client/consultant.

Ratings mentioned are tentaive and shall vary based


on the inverter sizing calculation which is subject to
approval of client/consultant.

1. The boq/descriptions, types mentioned under sl.no (12.1 to 12.4,12.5.1 to 12.5.2, 13.1 to 13.5, 14.01.01 to 14.01.04 , 14.02.01 to 14.02.02, 14.03 , 15 , 16.03.01.01
to 16.03.01.08 , 16.04.01 to 16.04.04, 17.01 to 17.03 , 19.01 to 19.02 , 20 , 21.01 to 21.09 and 22.01 to 22.02) of this BOQ are tentative only and not for ordering
purpose. Actaul quantity shall be confirmed during detailed engineering which is subject to approval of client/consultant only.

*********************X************************